AIR CONDITIONER
Cassette type
DESIGN & TECHNICAL DATA
SINGLE
INDOOR
AUA30LBLU
AUA36LBLU
OUTDOOR
AOA30LBTL AOA30LFTL
AOA36LBTL AOA36LFTL
1. INDOOR UNIT
CASSETTE TYPE :
AUA30LBLU
AUA36LBLU
D2D_AU034E/03
2010.01.18
CONTENTS
1. INDOOR UNIT
1. FEATURE.................................................................................................................. 01 - 01
2. REMOTE CONTROLLER............................................................................. 01 - 04
3. SPECIFICATIONS. ............................................................................................. 01 - 06
4. DIMENSIONS......................................................................................................... 01 - 07
5. WIRING DIAGRAMS........................................................................................ 01 - 09
6. CAPACITY TABLE............................................................................................. 01 - 10
6-1.
COOLING CAPACITY....................................................................................... 01 - 10
6-2.
HEATING CAPACITY. .......................................................................................01 - 11
7. FAN PERFORMANCE..................................................................................... 01 - 12
7-1.
AIR VELOCITY DISTRIBUTION..................................................................... 01 - 12
7-2.
AIR FLOW. ......................................................................................................... 01 - 17
7-3.
FRESH AIR......................................................................................................... 01 - 19
7-4.
DUCT CONNECTION. ...................................................................................... 01 - 20
8. OPERATION NOISE......................................................................................... 01 - 22
8-1.
NOISE LEVEL CURVE..................................................................................... 01 - 22
8-2.
SOUND LEVEL CHECK POINT...................................................................... 01 - 23
9. ELECTRIC CHARACTERISTICS........................................................... 01 - 24
10.SAFETY DEVICES............................................................................................. 01 - 25
11.EXTERNAL INPUT & OUTPUT. .............................................................. 01 - 26
11-1. EXTERNAL INPUT............................................................................................ 01 - 26
11-2. EXTERNAL OUTPUT. ...................................................................................... 01 - 27
12.FUNCTION SETTING. ..................................................................................... 01 - 29
12-1. INDOOR UNIT.................................................................................................... 01 - 29
12-2. WIRED REMOTE CONTROLLER.................................................................. 01 - 30
13.OPTIONAL PARTS............................................................................................ 01 - 33
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
111FEATURE
MODEL
„„
INDOOR UNIT
OUTDOOR UNIT
AOA30LBTL
AOA30LFTL
AOA36LBTL
AUA36LBLU
AOA36LFTL
AUA30LBLU
FEATURES
„„
Energy saving
zz
••All DC design
••Heat exchange efficiency increased and larger air flow by adoption of new type turbo fan
Advancement in comfort
zz
••Quiet operation was realized by adoption of new type turbo fan
••Improvement of air stream
Adoption of high efficiency turbo fan
High efficiency achieved by equaling the performance of the wing and air passing the heat
exchanger
500mm
Quiet
Wind
velocity
Fast
Heat exchanger
< Motor side >
No airflow
separation
3-dimensional wing
Slow
: Spin direction
: Airflow direction
Improvement of the flap
Making space between the ceiling, the air flows far wide and ceiling does not get dirty.
Front part
Bottom view
Ceiling
Rear part
Round Flap
Much less temperature irregularity
happens by spreading airflow widely
- (01 - 01) -
[m]
3
Side view
1.5
120
7
5
3
3
5
7
[m]
Airflow range of 2m / s
Improvement of installation & maintenance
zz
••Adjustment of nut is possible after installation
Mounting position of body can be fine adjusted after Decoration panel mounting.
Grille corner
Adjustment
can be done just taking
off the corner part
Simplification of drain water check
zz
High lift drain pump
zz
Ceiling panel
Drain and contamination check are possible
without removing the decoration panel.
850mm
DRAIN CAP
Easy installation
zz
Easy setting by wired
remote controller
DRAIN COVER
Can be easily checked by removing the drain
cover.
- (01 - 02) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Wide & powerful airflow
The wind is widely delivered by a high efficiency fan and round flap.
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
FUNCTION SETTING
„„
Outlet direction selection
zz
••Performs operation matched to the number of outlets when 4 directions are unnecessary and
outlets are blocked when the ceiling cassette is installed in a corner, etc.
4-way direction
3-way direction
4-way direction mode: S
et when there are 4 outlets
(shipped state).
3-way direction mode: Set when there are 3 outlets.
Ceiling switching function
zz
Also delivers air to high ceilings by selecting the mode and raising the air flow according to the
height of the ceiling.
High ceiling (Mode 2)
Low ceiling (Mode 1)
Standard ceiling (Standard)
*1
4.2m
3.2m
2.7m
*1 : AU*A30L is 3.6m
Standard ...Operates at normal air flow.
Mode 1 ...Air flow becomes smaller than normal.
Mode 2 ...Air flow becomes greater than normal.
Filter sign
zz
The indoor unit has sign to inform the user that it is time to clean the filter
Cooling room temperature correction
zz
Heating room temperature correction
zz
Auto restart
zz
The units restart automatically when the current was returned even when there was a power
interruption during operation.
Room temperature sensor switching
zz
Switches from room temperature judgment by room temperature sensor attached to indoor
unit body to room temperature judgment by room temperature sensor attached to wired remote
controller.
Economy operation
zz
The power consumption can be reduced.
Powerful mode ...Standard
Soft mode ...Performs operation which reduces the power consumption
- (01 - 03) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
222REMOTE CONTROLLER
WIRED REMOTE CONTROLLER
FEATURES
„„
¾¾Various timer setup (ON / OFF / WEEKLY) are possible.
¾¾Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
¾¾When setting up a timer, operation mode and a temperature
setup can be changed.
¾¾When a failure occurs,the error code is displayed. (Maximum of 16)
¾¾Error indication.(A maximum of 16 error histories are memorizable.)
¾¾Up to 16 indoor units can be simultaneously controlled.
¾¾Economy operation are possible.
¾¾Easy installation with a slim shape with no bulge in the back.
¾¾The room temperature can be controlled by being detected the
temperature accurately with built-in thermo sensor.
Simple function setting
zz
Setting of the air conditioner selection function is performed by remote controller.
High performance and compact size
zz
Three functions are combined in
one unit.
Wired
remote
controller
Built-in timers
zz
+
+
Weekly
timer
Setback
timer
Weekly timer
Setback timer
Possible to set ON/OFF time to operate twice each day
of the week.
Possible to set temperature for two time spans and
for each day of the week.
Easy-to-understand time bar display
SU MO TU WE TH FR SA
SU MO TU WE TH FR SA
SU MO TU WE TH FR SA
7
3 6 9 12 15 18 21
7
3 6 9 12 15 18 21
3 6 9 12 15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
Screen
after setup
28°C
24°C
0
3
6
9
12
15
18
21
0
Time
At "Weekly timer" + "Set back timer" setup
24°C
28°C
24°C
24°C
0
Easy-to-understand operation
zz
3
6
9
3
6
9
12
15
18
21
Time
28°C
12
15
18
21
Time
Simple installation
zz
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
Timer
area
Operation
area
[Variable timer control]
The operation/display sections are zoned
according to time and operation, enabling
variable programming to match application.
- (01 - 04) -
European
switch box
JIS box
15
1
3
4
2
6
7
8
9
13
12
10
5
11
14
Display panel
19 20 18
16
START/STOP button
2
Set temperature button
3
Master control button
4
Fan control button
5
Economy button
6
Timer mode (CLOCK ADJUST) button
7
Day (DAY OFF) button
8
Set back button
9
Set time button
Selects the setting temperature.
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
Turns the economy efficient mode on and off.
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY
TIMER). Set the current time.
Temporarily cancels of one day timer.
Pressed to select the set back timer.
Pressed to set time.
10 17
11
Delete button
The schedule of a weekly timer is deleted.
Set button
Sets the date, hour, minute and on-off time.
12 Vertical airflow direction and swing button
13 Horizontal airflow direction and swing button
14 Filter button
15 Operation lamp
16 Timer and clock display
[ Unit : mm ]
17 Operation mode display
17
18 Fan speed display
19 Operation lock display
20 Temperature display
21 Function display
21
DIMENSION
„„
Pressed to start and stop operation.
120
Push for two seconds to change the swing mode.
Push for two seconds to change the swing mode.
Lights during operation and when the timer is on.
Defrost display
Thermo sensor display
Economy display
Vertical swing display
Horizontal swing display
Filter display
Functions will be different due to type of indoor unit.
For details, please see operation manual.
Front View
SPECIFICATION
„„
SIZE
(H x W x D mm)
120 x 120 x 17
WEIGHT
(g)
160
CABLE LENGTH
(m)
10
POWER
(V)
12
- (01 - 05) -
CASSETTE TYPE
AUA30-36L
1
120
CASSETTE TYPE
AUA30-36L
FUNCTIONS
„„
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
333SPECIFICATIONS
CASSETTE MODEL
Type
INVERTER HEATPUMP
Indoor unit
Model name
AUA30LBLU
Outdoor unit
AOA30LBTL
AUA36LBLU
AOA30LFTL
Power source
198-264V~ 50Hz
European energy label
Rated
Cooling
Min.-Max.
Capacity
Rated
Heating
Min.-Max.
Cooling
Input power
Heating
Cooling
Current
Heating
Cooling
A
Heating
A
A
A
kW
8.50
10.00
BTU/h
29000
34100
kW
2.80 - 10.00
2.80 - 11.20
BTU/h
9500 - 34100
9500 - 38200
kW
10.00
11.20
BTU/h
34100
38200
kW
2.70 - 11.20
2.70 - 12.70
BTU/h
9200 - 38200
9200 - 43300
Rated
2.65
3.11
3.12
Max.
3.88
4.56
4.22
kW
Rated
2.77
3.02
Max.
3.88
4.56
Rated
11.6
*Max.
17.0
A
Rated
Cooling
COP
Heating
kW/kW
20.0
3.21
3.71
3.5(7.4)
High
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
1150
1600
1800
Med
1400
1400
Low
1270
1270
Quiet
1150
High
Heating
17.0
3.21
3.61
l/h (pints/h)
Airflow
rate
3
m /h
1150
Type × Q'ty
Turbo Fan × 1
Motor output
W
Cooling
Sound pressure level
Heating
80
40
43
Med
38
38
Low
36
36
Quiet
32
32
40
43
dB(A)
Med
38
38
Low
36
36
Quiet
Dimensions (H × W × D)
80
High
High
mm
32
32
252 × 2030 × 26.6
252 × 2093 × 26.6
252 × 2030 × 26.6
252 × 2093 × 26.6
Fin pitch
Heat exchanger type
Rows x Stages
Pipe type
Fin type
1.2
1.2
2 × 12
2 × 12
Copper
Copper
Aluminium
Aluminium
Material
Enclosure (Panel)
Gross
NET
Weight
Gross
Connection pipe
HIPS
WHITE
Approximate colour of MUNSELL N 9.25/
Colour
NET
Size
Unit
Panel
Unit
288 × 842 × 842
50 × 950 × 950
mm
360 × 960 × 985
Panel
115 × 1020 × 1000
Unit
26(58)
Panel
5.5(12)
Unit
kg(lb.)
32(71)
Panel
Liquid
Gas
8.5(19)
mm
Method
Ø 9.52
(Ø 3 / 8 in.)
Ø 9.52
Ø15.88
(Ø 5 / 8 in.)
Ø15.88
Flare
Cooling
Operation range
Heating
(Ø 3 / 8 in.)
(Ø 5 / 8 in.)
Flare
°C
18 to 32
18 to 32
%RH
80 or less
80 or less
°C
16 to 30
Remote controller type
Drain pipe
18.5
13.3
2.5(5.3)
Moisture removal
Cooling
13.7
20.0
12.2
*Max.
EER
Dimensions
( H×W×D)
AOA36LFTL
230V~ 50Hz
Available voltage range
Fan
AOA36LBTL
16 to 30
WIRED
Material
Size
PVC (VP25)
mm
Outer diameter : 32.0 / Inner diameter : 25.0
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
The maximum current and the maximum input value are the maximum values when operated within the operation range(temperature)
*The maximum current is the total current of indoor unit and outdoor unit.
- (01 - 06) -
CASSETTE TYPE
AUA30-36L
MODEL:: AUA30L, AUA36L
„„
Ceiling opening and hanging bolt pitch
zz
(Unit : mm)
950 mm(Panel frame)
860 - 910 mm(Ceiling opening)
20 - 45 mm
50 mm
130 mm
200 mm
Refrigerant piping and drain piping positions
zz
278 mm
60 mm
140 mm
180 mm
358 mm
200 mm
Drain pipe
(Connect the attached drain hose)
Airflow split-flow duct and fresh air inlet positions
zz
100 mm
100 mm
Airflow split-flow duct connecting port
Refrigerant pipe
83 mm
83 mm
Cut out
185 mm
90 mm
Airflow split-flow duct connecting port
Airflow split-flow duct connecting port
Drain pipe
352 mm
2.5 mm hole
10
Detailed diagram of branched duct connecting port
(4 sides)
250 mm
88 mm
Burling hole pitch
70 mm
Cut out
Fresh air inlet position
185 mm
Airflow split-flow duct connecting port
Fresh air inlet position
- (01 - 07) -
4
2.5 mm hole
298 mm
288 mm
40 mm
50 - 100 mm
20 - 45 mm
10 mm
950 mm(Panel frame)
840 mm(Body frame)
80 mm
130 mm
699 mm(Hanging bolt pitch)
140 - 145 mm
20 - 45 mm
840 mm(Body frame)
795 mm(Hanging bolt pitch)
860 - 910 mm(Ceiling opening)
20 - 45 mm
130 mm
CASSETTE TYPE
AUA30-36L
444DIMENSIONS
3,000 or more
Ceiling mode “Low”
: 2.7 m
Ceiling mode “Standard” : 3.2 m
Ceiling mode “High”
: 3.6 m (30 model)
4.2 m (36 model)
1,000 or more
Strong and durable ceiling
1,500
or more
Obstruction
Floor
3-way directions setting
zz
(Unit : mm)
100 or more
To set “3-way directions”, the air outlet shutter plate (UTR-YDZC) sold separately must be installed
and “outlet-direction” switched to “3-way” by remote controller.
- (01 - 08) -
CASSETTE TYPE
AUA30-36L
(Unit : mm)
2,500 or more
CASSETTE TYPE
AUA30-36L
INSTALLATION PLACE
„„
MODEL:: AUA30L, AUA36L
„„
- (01 - 09) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
555WIRING DIAGRAMS
CASSETTE TYPE
AUA30-36L
This table is created using the maximum capacity.
MODEL:: AUA30L
„„
AFR
26.7
Indoor temperature
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
-15
8.67
6.58
1.20
9.66
6.62
1.22
9.99
7.20
1.22
10.65
7.22
1.24
10.98
7.80
1.24
11.64
7.77
1.25
12.29 8.27
-10
8.52
6.38
1.64
9.49
6.42
1.66
9.81
6.98
1.67
10.46
7.00
1.69
10.79
7.56
1.70
11.43
7.53
1.71
12.08 8.02
1.73
0
8.12
6.26
2.11
9.04
6.30
2.15
9.35
6.85
2.16
9.97
6.87
2.18
10.28
7.42
2.19
10.89
7.39
2.21
11.51
7.87
2.23
2.26
Outdoor temperature
°CDB
TC
SHC
PI
1.27
5
7.99
6.11
2.14
8.90
6.14
2.17
9.21
6.68
2.19
9.81
6.70
2.21
10.12
7.23
2.22
10.72
7.21
2.24
11.33
7.68
10
7.96
6.19
2.19
8.87
6.23
2.23
9.17
6.77
2.24
9.77
6.79
2.26 10.07
7.34
2.27 10.68
7.31
2.29
11.28
7.78
2.32
15
8.63
6.48
2.41
9.62
6.52
2.45
9.94
7.09
2.46 10.60
7.11
2.49 10.93
7.68
2.50
11.58
7.65
2.53 12.24
8.14
2.55
7.07
3.01
20
9.82
7.03
2.97 10.94
25
9.48
6.89
3.31
11.31
7.69
3.03 12.06
7.71
3.06 12.43 8.33
3.08
13.18
8.30
3.11
13.92 8.84
3.14
10.56 6.93
3.36 10.92
7.53
3.38
11.64
7.56
3.41
12.00
8.16
3.43
12.72
8.13
3.46 13.44 8.66
3.50
30
8.81
6.70
35
7.90
6.12
3.34
9.81
6.74
3.39
10.15
7.32
3.41
10.81
7.35
3.44
11.15
7.93
3.46
11.82
7.90
3.50 12.49
8.42
3.53
3.35
8.80
6.16
3.40
9.10
6.69
3.42
9.70
6.71
3.45 10.00
7.25
3.47
10.60
7.22
3.51
11.20
7.69
3.54
40
6.16
5.13
2.94
6.86
5.16
2.99
7.09
5.61
3.01
7.56
5.63
3.04
7.80
6.08
3.05
8.26
6.05
3.08
8.73
6.45
3.11
46
5.44
4.92
2.91
6.06
4.95
2.96
6.27
5.39
2.97
6.68
5.40
3.00
6.89
5.83
3.02
7.30
5.81
3.05
7.71
6.19
3.08
MODEL:: AUA36L
„„
AFR
30.0
Indoor temperature
Outdoor temperature
CASSETTE TYPE
AUA30-36L
666CAPACITY TABLE
66666COOLING CAPACITY
°CDB
18
21
23
25
27
29
32
°CWB
12
15
16
18
19
21
23
°CDB
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
TC
SHC
PI
-15
9.33
7.37
1.29
10.39
7.41
1.31
10.74
8.06
1.32
11.45
8.08
1.33
11.80
8.73
1.34
12.51
8.70
1.35
13.22 9.26
-10
9.22
7.23
1.69
10.27
7.27
1.71
10.62
7.90
1.72
11.32
7.93
1.74
11.67
8.56
1.75
12.37 8.53
1.77
13.07
9.08
1.78
0
8.77
7.13
2.18
9.77
7.17
2.22
10.10
7.80
2.23
10.77
7.82
2.25
11.10
8.45
2.26
11.77
2.29 12.44 8.96
2.31
2.38
8.41
TC
SHC
5
8.69
6.98
2.25
9.68
7.02
2.28
10.01
7.64
2.29 10.67
7.66
2.32
11.00
8.27
2.33
11.66
8.24
2.35 12.32
10
8.62
7.06
2.25
9.60
7.10
2.29
9.93
7.72
2.30 10.58
7.75
2.32
10.91
8.37
2.34
11.56
8.33
2.36 12.22 8.88
2.38
15
9.17
7.17
2.42
10.21
7.22
2.46 10.56
7.85
2.47
11.25
7.87
2.50
11.60
8.50
2.51
12.30
8.47
2.54 13.00
9.02
2.56
20
10.70
7.92
2.99
11.92
7.97
3.03 12.33 8.66
3.05
13.14
8.69
3.08 13.54 9.39
3.10
14.36 9.35
3.13
9.96
3.16
25
10.64 8.02
3.32
11.86
8.06
3.38 12.26
8.77
3.39
13.07
8.79
3.43
13.47
3.45 14.28 9.46
3.48 15.09 10.08
3.51
30
10.24
7.76
4.05
11.40
7.81
4.11
11.79
8.49
4.13
12.57
8.51
4.17
12.96
9.19
4.19
13.73
9.16
4.24
9.75
4.28
35
8.85
6.78
4.03
9.86
6.82
4.10
10.19
7.42
4.12
10.86
7.44
4.16
11.20
8.04
4.18
11.87
8.01
4.22 12.54 8.53
4.26
40
6.80
5.96
3.09
7.58
6.00
3.14
7.84
6.52
3.16
8.35
6.54
3.19
8.61
7.07
3.20
9.13
7.04
3.24
9.65
7.50
3.27
46
6.11
5.84
2.96
6.81
5.87
3.01
7.04
6.39
3.02
7.50
6.41
3.05
7.74
6.92
3.07
8.20
6.89
3.10
8.67
7.34
3.13
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
SHC : Sensible Heat capacity (kW)
PI : Power Input (kW)
- (01 - 10) -
9.50
15.17
14.51
8.78
PI
1.36
CASSETTE TYPE
AUA30-36L
This table is created using the maximum capacity.
MODEL:: AUA30L
„„
AFR
26.7
Indoor temperature
Outdoor temperature
°CDB
16
°CDB
°CWB
TC
-15
-16
8.34
-10
-11
8.79
18
PI
20
TC
PI
TC
3.37
8.14
3.44
7.94
3.38
8.58
3.45
8.37
22
PI
24
TC
PI
TC
PI
3.51
7.75
3.58
7.55
3.65
3.52
8.16
3.59
7.95
3.66
-5
-7
9.55
3.41
9.32
3.48
9.09
3.55
8.86
3.62
8.64
3.69
0
-2
10.12
3.37
9.88
3.44
9.64
3.51
9.40
3.58
9.16
3.65
5
3
11.23
3.35
10.96
3.42
10.69
3.49
10.43
3.56
10.16
3.62
7
6
11.76
3.33
11.48
3.40
11.20
3.47
10.92
3.54
10.64
3.61
10
8
12.12
3.30
11.83
3.37
11.54
3.44
11.25
3.51
10.96
3.57
15
10
10.86
2.52
10.60
2.57
10.34
2.62
10.09
2.67
9.83
2.71
20
15
10.87
2.23
10.61
2.28
10.35
2.33
10.09
2.37
9.83
2.41
24
18
11.31
2.25
11.04
2.30
10.78
2.34
10.51
2.39
10.24
2.43
MODEL:: AUA36L
„„
AFR
30.0
Indoor temperature
°CDB
Outdoor temperature
CASSETTE TYPE
AUA30-36L
66666HEATING CAPACITY
16
18
20
22
24
°CDB
°CWB
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
-15
-16
9.63
3.92
9.40
4.00
9.17
4.08
8.94
4.17
8.71
4.25
-10
-11
9.70
3.96
9.47
4.04
9.24
4.13
9.01
4.21
8.77
4.29
-5
-7
10.69
4.07
10.43
4.16
10.18
4.24
9.92
4.33
9.67
4.41
0
-2
12.54
3.99
12.24
4.08
11.94
4.16
11.64
4.24
11.34
4.33
5
3
13.18
3.81
12.87
3.89
12.55
3.97
12.24
4.05
11.92
4.13
7
6
13.34
3.36
13.02
3.43
12.70
3.50
12.38
3.57
12.07
3.64
10
8
13.74
3.19
13.42
3.26
13.09
3.33
12.76
3.39
12.43
3.46
15
10
12.26
2.55
11.97
2.60
11.67
2.65
11.38
2.71
11.09
2.75
20
15
12.28
2.26
11.99
2.31
11.69
2.36
11.40
2.40
11.11
2.44
24
18
12.80
2.28
12.49
2.32
12.19
2.37
11.88
2.42
11.58
2.46
AFR : Air flow rate (m3/min)
TC : Total capacity (kW)
PI : Power Input (kW)
- (01 - 11) -
Note:
Condition
Fan speed : High
Operation mode : FAN
MODEL:: AUA30L
„„
Ceiling mode : Standard
4-way air outlet
zz
5
(m)
Unit : m/s
4
3
2
1
0
1
2
3
4
5
3.2
TOP VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
3.2
SIDE VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Downward
10
9
8
7
6
5
4
3
2
1
0
1
2
- (01 - 12) -
3
4
5
6
7
8
9
10
(m)
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
777FAN PERFORMANCE
77777 AIR VELOCITY DISTRIBUTION
7777777 STANDARD MODE
Condition
Fan speed : High
Operation mode : FAN
MODEL:: AUA36L
„„
Ceiling mode : Standard
4-way air outlet
zz
5
(m)
Unit : m/s
4
3
2
1
0
1
2
3
4
5
3.2
TOP VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
3.2
SIDE VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Downward
10
9
8
7
6
5
4
3
2
1
0
1
2
- (01 - 13) -
3
4
5
6
7
8
9
10
(m)
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Note:
Condition
Fan speed : High
Operation mode : FAN
MODEL:: AUA30L
„„
Ceiling mode : Standard
3-way air outlet
zz
5
(m)
Unit : m/s
4
3
2
1
0
1
2
3
4
5
3.2
TOP VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
3.2
SIDE VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Downward
10
9
8
7
6
5
4
3
2
1
0
1
2
- (01 - 14) -
3
4
5
6
7
8
9
10
(m)
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Note:
Condition
Fan speed : High
Operation mode : FAN
MODEL:: AUA36L
„„
Ceiling mode : Standard
3-way air outlet
zz
5
(m)
Unit : m/s
4
3
2
1
0
1
2
3
4
5
3.2
TOP VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
3.2
SIDE VIEW
VERTICAL LOUVER
: Upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
(m)
8
9
10
(m)
Unit : m/s
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Downward
10
9
8
7
6
5
4
3
2
1
0
1
2
- (01 - 15) -
3
4
5
6
7
8
9
10
(m)
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Note:
Condition
7777777SPECIAL UPWARD MODE
Fan speed : High
Operation mode : FAN
MODEL:: AUA30L
„„
Ceiling mode : Standard
4-way air outlet
zz
3.2
(m)
Unit : m/s
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Special upward
10
9
8
7
6
5
4
3
2
1
0
1
2
3
4
5
6
7
8
9
10
(m)
MODEL:: AUA36L
„„
4-way air outlet
zz
3.2
Unit : m/s
(m)
2
1
0
SIDE VIEW
VERTICAL LOUVER
: Special upward
10
9
8
7
6
5
4
3
2
1
0
1
2
- (01 - 16) -
3
4
5
6
7
8
9
10
(m)
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Note:
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
77777AIR FLOW
7777777 4-WAY OUTLET
MODEL:: AUA30L
„„
Cooling / Heating
zz
Fan speed
Number of
rotations
(r.p.m)
HIGH
570
MED
510
LOW
470
QUIET
420
Airflow
m3/h
1600
l/s
444
CFM
942
3
m /h
1400
l/s
389
CFM
824
m3/h
1270
l/s
353
CFM
747
m3/h
1150
l/s
319
CFM
677
MODEL:: AUA36L
„„
Cooling / Heating
zz
Fan speed
HIGH
MED
LOW
QUIET
Number of
rotations
(r.p.m)
640
510
470
420
Airflow
m3/h
1800
l/s
500
CFM
1059
m3/h
1400
l/s
389
CFM
824
3
m /h
1270
l/s
353
CFM
747
3
m /h
1150
l/s
319
CFM
677
- (01 - 17) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
77777773-WAY OUTLET
MODEL:: AUA30L
„„
Cooling / Heating
zz
Fan speed
Airflow
Number of
rotations
(r.p.m)
HIGH
610
MED
550
LOW
510
QUIET
460
*Max.
*Min.
m3/h
1550
1350
l/s
431
375
CFM
912
794
3
m /h
1350
1200
l/s
375
333
CFM
794
706
m3/h
1250
1100
l/s
347
306
CFM
736
647
m3/h
1100
950
l/s
306
264
CFM
647
559
MODEL:: AUA36L
„„
Cooling / Heating
zz
Fan speed
HIGH
MED
LOW
QUIET
Airflow
Number of
rotations
(r.p.m)
680
550
510
460
*Max.
*Min.
m3/h
1700
1550
l/s
472
431
CFM
1000
912
3
m /h
1350
1200
l/s
375
333
CFM
794
706
3
m /h
1250
1100
l/s
347
306
CFM
736
647
m3/h
1100
950
l/s
306
264
CFM
647
559
*Air flow can be changed according to the direction in which the outlet is blocked.
- (01 - 18) -
CASSETTE TYPE
AUA30-36L
MODEL:: AUA30L, AUA36L
„„
10
98
8
6
49
4
2
0
Duct static pressure (mmAq)
Air flow volume - Static pressure of Fresh air intake characteristic
zz
Duct static pressure (Pa)
0
0.1
0.2
0.3
0.4
3
0.5
0.6
0
0.7
Duct
(Inside Dia. ø70mm)
Duct Fan
Static pressure required
to take in fresh air
Air flow (m /min)
Installation
zz
70 mm
Drain pipe
62 mm
Refrigerant pipe
4
2.5 mm hole
62 mm
250 mm
185 mm
CASSETTE TYPE
AUA30-36L
77777FRESH AIR
View (A)
Fresh air inlet position
Fresh air inlet position (A)
Flexible duct *2
Duct flange *2
Flexible duct *2
Fan *2
Fresh air inlet position
Insulation *1
*1 : In case of fresh air intake, please remove the insulation.
*2 : Locally procured parts
- (01 - 19) -
L
CASSETTE TYPE
AUA30-36L
AUA30L
98
10
9
8
Fan speed High
7
6
49
5
Fan speed
Qutiet
4
3
L=10m
0
0
2
4
6
8
3
10
L=5m
2
L=1m
1
12
14
0
Air flow (m /min)
AUA36L
98
10
Fan speed High
9
8
7
6
49
5
Fan speed
Quiet
4
3
0
L=10m
2
L=5m
1
L=1m
0
2
4
6
8
3
Air flow (m /min)
- (01 - 20) -
Duct static pressure (mmAq)
Duct
(Inside Dia. 350mm×100mm)
Duct static pressure (Pa)
Outlet air
zz
Duct static pressure (mmAq)
MODEL:: AUA30L, AUA36L
„„
Duct static pressure (Pa)
CASSETTE TYPE
AUA30-36L
77777DUCT CONNECTION
10
12
14
0
the air outlet duct at up to two locations among the four duct
zConnect
z
connection locations. (Do not connect ducts at three or more locations.)
A
D
B
C
pattern when a branch duct is installed
zBlow-off
z
Bi-directional branching, main unit bi-directional branching
Branch
Close
Branch
Close
Close
Branch
Close
Branch
the location where the duct is to be connected is decided,
zOnce
z
always be sure to close the outlets in the same direction.
DUCT (Locally procured parts)
Close the outlet here.
*Use only after closing the outlet of the cassette on the
side on which the duct is used, using the “Air outlet
shutter plate (UTR-YDZC)”.
- (01 - 21) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
PRECAUTIONS WHILE CONNECTING AIR OUTLET DUCT
„„
Ceiling mode : Standard
Air outlet : 4-way air outlet
Heating
zz
80
80
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
HIGH
NC-40
NC-35
30
NC-30
NC-25
QUIET
20
NC-20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Cooling
zz
NC-65
60
NC-60
NC-55
50
NC-50
HIGH
40
NC-45
NC-40
NC-35
30
NC-30
NC-25
QUIET
20
NC-20
NC-15
NC-15
10
0
63
CASSETTE TYPE
AUA30-36L
Condition
MODEL:: AUA30L
„„
10
125
250
500
1,000
2,000
4,000
0
63
8,000
125
Octave band center frequency,Hz
250
500
1,000
2,000
4,000
8,000
Octave band center frequency,Hz
MODEL:: AUA36L
„„
Heating
zz
Cooling
zz
80
80
70
70
NC-65
60
NC-60
NC-55
50
NC-50
HIGH
40
NC-45
NC-40
NC-35
30
NC-30
NC-25
QUIET
20
NC-20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band sound pressure level, dB:(0dB=0.0002µbar)
CASSETTE TYPE
AUA30-36L
888OPERATION NOISE
88888NOISE LEVEL CURVE
NC-65
60
NC-60
NC-55
50
NC-50
HIGH
40
NC-40
NC-35
30
NC-30
NC-25
QUIET
20
NC-20
NC-15
NC-15
10
0
63
NC-45
10
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency,Hz
0
63
125
250
500
1,000
2,000
Octave band center frequency,Hz
- (01 - 22) -
4,000
8,000
Microphone
1.5m
Microphone
CENTER
- (01 - 23) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
88888SOUND LEVEL CHECK POINT
Model Name
Power Supply
AUA30L
Voltage
V
230V ~
Frequency
Hz
50Hz
A
0.7
Max Operating Current (Indoor unit)
Wiring Spec.
(Indoor unit to outdoor unit)
AUA36L
Circuit breaker
A
Connection Cable
mm
Limited wiring length
- (01 - 24) -
m
0.8
2
1.5-2.5
51
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
999ELECTRIC CHARACTERISTICS
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
1111 SAFETY DEVICES
Model
Protection form
AUA30L
AUA36L
Circuit protection
Current fuse (PCB)
3.15A 250V
Fan motor protection
Thermal protection
program
110±15°C OFF
105±15°C ON
- (01 - 25) -
Connector
INPUT
OUTPUT
CN102
Control input
(Operation/Stop)
—
CN103
—
Operation status output
CN6
—
Fresh air control output
REMARKS
See external
input/output settings for
details.
111111 EXTERNAL INPUT
CONTROL INPUT (Operation/Stop)
„„
The air conditioner can be remotely operated by means of the following on-site work.
Operation is started at the following contents by adding the contact input of a commercial ON/OFF switch to a
connector on the external control PC board and turning it ON.
Operation mode
Set temperature
Air flow mode
Up-down air direction (swing)
Left-right air direction (swing)
Initial starting after power turned on
Auto changeover
24°C
AUTO
Standard air direction (swing OFF)
Standard air direction (swing OFF)
Circuit diagram example
zz
Indoor
control PC board
Connected unit
Connector
1
Ex.) Switch
3
*10 m
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
Contact capacity : 12VDC or more, 15mA or more.
Please use the non-polar relays and switches.
Input signal
Indoor unit
ON
OFF
Operation
Stop
Parts (Optional)
zz
Model name
UTY-XWZX
Wire (External input)
- (01 - 26) -
Starting other than at the left
Mode at previous operation
Temperature at previous operation
Mode at previous operation
Air direction at previous operation
Air direction at previous operation
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
1111 EXTERNAL INPUT & OUTPUT
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
111111 EXTERNAL OUTPUT
OPERATION STATUS OUTPUT
„„
An air conditioner operation status signal can be output.
Circuit diagram example
zz
Indoor
control PC board
Connector
1
Connected unit
24V DC
Ex.)Relay unit
Ex.)Display
Relay
power
supply
V
2
*10 m
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
Indoor unit
Output signal
Operation
Stop
ON
OFF
Parts (Optional)
zz
Model name
UTY-XWZX
Wire (External output)
- (01 - 27) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
FRESH AIR CONTROL OUTPUT
„„
A signal linked to air conditioner indoor fan ON can be output.
* However, signal becomes OFF during cold air prevention control operation.
Circuit diagram example
zz
Indoor
control PC board
Connected unit
Ex.) Fan
Ex.) Relay unit
12 V Connector
Relay
power
supply
1
on/off
2
*10 m
Signal
Field supply
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Rated 12VDC, 50mA or less.
Indoor fan
Operation
Output signal
Stop
ON
OFF
Parts (Optional)
zz
Model name
UTD-ECS5A
Wire (Fresh air output)
*The wire (fresh air output) for connecting the fresh air intake kit (optional parts) is attached to the fresh air intake kit
and, therefore, does not have to be purchased separately.
- (01 - 28) -
CASSETTE TYPE
AUA30-36L
INDOOR UNIT
1
2
DIP SW
3
Forbidden
4
JM1
Jumper Wire
JM2
JM3
Remote control unit signal code
Fan delay setting
SWITCH POSITION
„„
MAIN PCB
JM1
JM2
Indoor unit Printed circuit board
JM3
CASSETTE TYPE
AUA30-36L
1111 FUNCTION SETTING
111111 INDOOR UNIT
JUMPER WIRE SETTING
„„
Remote control unit signal code
Indoor unit setting
( Factory setting)
Jumper wire
JM 1
JM 2
Remote control unit
signal code
Connect
Connect
A
Disconnect
Connect
B
Connect
Disconnect
C
Disconnect
Disconnect
D
- (01 - 29) -

DIP SW
1
Can not be used. (Do not change)
2
Dual remote controller setting
3
Can not be used. (Do not change)
4
Can not be used. (Do not change)
5
Can not be used. (Do not change)
6
Memory backup setting
SWITCH POSITION
„„
Front case (back side)
OFF
ON
1
2
3
4
5
6
ON
Do not use this
DIP Switch
DIP Switch
DIP SWITCH SETTING
„„
1. Dual remote controller setting
Set the remote controller DIP switch No.2 according to the following table.
( Factory setting)
Number
of remote
controller
Master unit
Slave unit
DIP-SW No.2
DIP-SW No.2
 1 (Normal)
OFF
―
2 (Dual)
OFF
ON
2. Memory backup setting
Set to ON to use batteries for the memory backup. If batteries are not used, all of the settings
stored in memory will be deleted if there is a power failure.
( Factory setting)

DIP-SW
No.6
Memory backup
OFF
Invalidity
ON
Validity
- (01 - 30) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
111111 WIRED REMOTE CONTROLLER
•Confirm whether the wiring work for outdoor unit has been
finished.
)(
) to select the setting
The display flashes as shown to the right during setting value
selection.
•Confirm whether the ccover for electric control box on the
outdoor unit is close.
1. Turning on the power
(5)Press the TIMER SET button to confirm the setting. Press the
TIMER SET button for a few seconds until the setting value
stops flashing.
(1)Check the remote controller wiring and DIP switch settings.
(2)Install the front case.
When installing the front case, connect the connector to the
front case.
If the setting value display changes or if “- -” is displayed when
the flashing stops, the setting value has not been set correctly.
(An invalid setting value may have been selected for the indoor
unit.)
(3)Check the indoor and outdoor unit wiring and circuit board
switch settings, and then turn on the indoor and outdoor
units. After " " has flashed on the set temperature display for
several seconds, the clock display will appear in the center of
the remote controller display.
SU MO TU WE TH FR SA
The clock display will appear in the center of the remote
controller display.
Setting value
SU MO TU WE TH FR SA
2. Function setting
•This procedure changes to the function settings used to control
the indoor unit according to the installation conditions. Incorrect
settings can cause the indoor unit malfunction.
•After the power is turned on, perform the “FUNCTION SETTING”
according to the installation conditions using the remote
controller.
•The settings may be selected between the following two:
Function Number or Setting Value.
•Settings will not be changed if invalid numbers or setting values
are selected.
(6)Repeat steps 2 to 5 to perform additional settings. Press
the set temperature buttons ( ) ( ) and fan control button
simultaneously again for more than 5 seconds to cancel the
function setting mode. In addition, the function setting mode
will be automatically canceled after 1 minute if no operation is
performed.
(7)After completing the FUNCTION SETTING, be sure to turn off
the power and turn it on again.
Setting the Ceiling Height
•Select the setting values in the table below according to the
height of the ceiling. (The unit is factory-set to “00”.)
Setting Description [m] Function Number
Setting Value
Standard
Operation Method
00
(3.2m)
(1)Press the set temperature buttons ( ) ( ) and fan control
button simultaneously for more than 5 seconds to enter the
function setting mode.
Low ceiling
20
(2.7m)
01
High ceiling
02
(4.2m)
The ceiling height values are for the 4-way outlet.
Do not change this setting in the 3-way outlet mode.
SU MO TU WE TH FR SA
Setting the vertical direction adjusting scope
(2)Press the SET BACK button to select the indoor unit number.
SET BACK
•To prevent from draft, we recommend using “upward mode”. (The
unit is factory-set to “00”.)
Setting Description
Standard
Function Number
Setting Value
00
23
Upward
01
SU MO TU WE TH FR SA
Ceiling
Unit number of INDOOR UNIT
(3)Press the set time buttons to select the function number.
Standard
UP
Upward
SU MO TU WE TH FR SA
Swing range
Outlet cross section
Function number
- (01 - 31) -
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
(4)Press the set temperature buttons (
value.
! CAUTION
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Setting the Outlet Directions
Setting record
•Select the setting values in the table below for using a 3-way
outlet. (The unit is factory-set to “00”.)
•Record any changes to the settings in the following table.
Setting Description
Function Number
4-way
22
3-way
Setting
Setting Value
00
Vertical direction adjusting
scope
01
Outlet directions
Setting the Filter Sign
Filter sign
•The indoor unit has a sign to inform the user that it is time to
clean the filter.
Cooler room temperature
correction
•Select the time setting for the filter sign display interval in the
table below according to the amount of dust or debris in the
room. (The unit is factory-set to “00”.)
Heater room temperature
correction
•If you do not wish the filter sign to be displayed, select the setting
value for “No indication”.
Setting Description
Setting Value
Ceiling height
Function Number
Standard
Setting Value
Long interval
(4,400 hours)
11
Short interval
3. Setting the room temperature detection
location
01
02
(1,250 hours)
No indication
Indoor room temperature
sensor switching function
After completing the FUNCTION SETTING, be sure to turn off the
power and turn it on again.
00
(2,500 hours)
Auto restart
The detection location of the room temperature can be selected
from the following two examples. Choose the detection location
that is best for the installation location.
03
Setting the Cooler Room Temperature Correction
A. Indoor unit setting (factory setting)
•Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be selected
as shown in the table below. (The unit is factory-set to “00”.)
The room temperature is detected by the indoor unit temperature
sensor.
Setting Description
Function Number
Standard
30
Lower control
Setting Value
(1)When the THERMO SENSOR button is pressed, the lock
display flashes because the function is locked at the factory.
00
A
01
Indoor unit
Setting the Heater Room Temperature Correction
•Depending on the installed environment, the room temperature
sensor may require a correction. The settings may be changed
as shown in the table below. (The unit is factoryset to “00”.)
Setting Description
Function Numbe
Standard
Setting Value
B. Indoor unit/remote controller setting (room
temperature sensor selection)
00
Lower control
31
Slightly warmer control
Warmer control
01
The temperature sensor of the indoor unit or the remote controller
can be used to detect the room temperature.
02
(1)Enable the room temperature sensor selection in FUNCTION
SETTING, which will be described later.
03
(2)Press the THERMO SENSOR button for 5 seconds or more to
select the temperature sensor of the indoor unit or the remote
controller.
Setting Other Functions
•The following settings are also possible, depending on the
operating conditions. (The unit is factory-set to “00”.)
Auto Restart
Setting Description
Yes
No
B
Function Number
40
Setting Value
Indoor unit
00
01
Indoor Room Temperature Sensor Switching Function
(Wired remote controller only)
Setting Description
No
Yes
Function Number
42
Setting Value
NOTE
00
01
•If setting value is “00”, room temperature is controlled by the
indoor unit temperature sensor.
•If setting value is “01”, room temperature is controlled by either
indoor unit temperature sensor or remote control unit sensor.
If the function to change the temperature sensor is used as
shown in examples A (other than example B), be sure to lock the
detection location.
If the function is locked, the lock display
will flash when the
THERMO SENSOR button is pressed.
- (01 - 32) -
Exterior
(x1)
(x2)
(x1)
(x2)
Parts name
Model No.
Air outlet
shutter plate
UTR-YDZC
Air outlet shutter plate is
installed at the air outlet when
3-way direction is performed.
Wide panel
UTG-AGYA-W
Wide panel hides the gap
between the ceiling hole and
the Decoration panel.
Panel spacer
UTG-BGYA-W
Installation in a space of 256mm
or greater is possible by using
panel spacer when the height
behind the ceiling is low.
(Normal behind the ceiling
installation height is 298mm.)
IR Receiver kit
UTY-LRHA1
Unit control is performed by
wireless remote controller
Wired remote
controller
UTB-UD
Unit control is performed by
wired remote controller
Insulation kit
for high humidity
UTZ-KXGA
Install when the under roof
condition is expected to be the
humidity of over 80% and the
temperature of over 30 °C
External
connect kit
UTY-XWZX
Use to connect with various
peripheral devices and air
conditioner PC board.
UTD-ECS5A
Use to connect with various
peripheral devices and air
conditioner PC board.
(Set of 6)
External
control set
- (01 - 33) -
Summary
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
1111 OPTIONAL PARTS
Parts name
Fresh air intake
kit
- (01 - 34) -
Model No.
Summary
UTZ-VXGA
It can be taken in fresh air of
up to 10% of “high” air volume
of the indoor unit by attaching
Fresh Air Intake Kit to cassette
type indoor unit.
CASSETTE TYPE
AUA30-36L
CASSETTE TYPE
AUA30-36L
Exterior
2. OUTDOOR UNIT
SINGLE TYPE :
AOA30LBTL
AOA30LFTL
AOA36LBTL
AOA36LFTL
D2D_AO022E/02
2010.01.18
CONTENTS
2. OUTDOOR UNIT
1. SPECIFICATIONS. ............................................................................................. 02 - 01
2. DIMENSIONS......................................................................................................... 02 - 03
3. REFRIGERANT CIRCUIT............................................................................. 02 - 04
4. WIRING DIAGRAMS........................................................................................ 02 - 06
5. CAPACITY COMPENSATION RATE FOR PIPE LENGTH AND
HEIGHT DEFFERENCE................................................................................. 02 - 09
6. ADDITIONAL CHARGE CALCULATION..........................................02 - 11
7. AIR FLOW................................................................................................................. 02 - 12
8. OPERATION NOISE......................................................................................... 02 - 14
8-1.
NOISE LEVEL CURVE..................................................................................... 02 - 14
8-2.
SOUND LEVEL CHECK POINT...................................................................... 02 - 15
9. ELECTRIC CHARACTERISTICS........................................................... 02 - 16
10.SAFETY DEVICES............................................................................................. 02 - 17
111SPECIFICATIONS
Type
INVERTER HEATPUMP
Model name
AOA30LBTL
Available voltage range
198-264V ~ 50Hz
Starting current
Fan
AOA36LBTL
230V ~ 50Hz
A
Airflow
rate
Cooling
m3/h
Heating
15.0
15.0
3600
4000
3800
Type × Q'ty
Motor output
Sound pressure level
W
Cooling
dB(A)
Heating
Dimensions (H × W × D)
Fin pitch
Heat exchanger type
3800
Propeller × 1
mm
103
103
53
54
55
55
798 × 900 × 36.4
798 × 900 × 36.4
Rows x Stages
1.30
1.30
2 × 38
2 × 38
Pipe type
Copper
Fin type
Compressor
Aluminium
Type × Q'ty
Motor output
Twin Rotary × 1
W
1700
Type
Refrigerant
Charge
Refrigerant oil
R410A
g
2100
Type
PVE
Material
Enclosure
Dimensions
( H×W×D)
Weight
Net
830 × 900 × 330
mm
Gross
Net
970 × 1050 × 445
62 ( 136 )
kg (lb.)
Gross
Liquid
Gas
70 ( 154 )
Ø 9.52 (Ø 3/8 in.)
mm
Ø 15.88 (Ø 5/8 in.)
Method
Flare
Max. length
Max. height difference
Operation range
BEIGE
Approximate colour of MUNSELL 10YR 7.5/1.0
Colour
Size
Connection
pipe
Steel sheet
Cooling
Heating
m
50(chargeless:20)
50(chargeless:20)
30
30
˚C
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
- (02 - 01) -
-15 to 46
-15 to 24
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
Power source
Type
INVERTER HEATPUMP
Model name
AOA30LFTL
Available voltage range
198-264V ~ 50Hz
Starting current
Fan
AOA36LFTL
230V ~ 50Hz
A
Airflow
rate
Cooling
m3/h
Heating
15.0
15.0
3600
3800
3600
Type × Q'ty
Motor output
Sound pressure level
W
Cooling
dB(A)
Heating
Dimensions (H × W × D)
Fin pitch
Heat exchanger type
3800
Propeller × 1
mm
100
100
53
54
55
55
798 × 900 × 36.4
798 × 900 × 36.4
Rows x Stages
1.30
1.30
2 × 38
2 × 38
Pipe type
Copper
Fin type
Compressor
Type × Q'ty
Motor output
Charge
Refrigerant oil
Enclosure
Weight
2100
R410A
g
2100
Type
POE (RB68)
Material
Steel sheet
Net
BEIGE
Approximate colour of MUNSELL 10YR 7.5/1.0
830 × 900 × 330
mm
Gross
Net
970 × 1050 × 445
61 (135)
kg (lb.)
Gross
Liquid
Gas
68 (150)
Ø 9.52 (Ø 3/8 in.)
mm
Ø 15.88 (Ø 5/8 in.)
Method
Flare
Max. length
Max. height difference
Operation range
W
Colour
Size
Connection
pipe
Twin Rotary × 1
Type
Refrigerant
Dimensions
( H×W×D)
Aluminium
Cooling
Heating
m
50(chargeless:20)
50(chargeless:20)
30
30
˚C
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
- (02 - 02) -
-15 to 46
-15 to 24
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
Power source
222DIMENSIONS
(Unit : mm)
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LB, AOA36LB, AOA30LF, AOA36LF
„„
Top view
77
31
330
12
9
21
830
900
400
Front view
Side view
650
99
603
196
370
Air flow
147
Bottom view
170
INSTALLATION PLACE
„„
When there are obstacles at the back,
side(s), and top.
When there are obstacles at the back,
side with the installation of more than
one unit.
600 mm or more
When there are obstacles at the back
or front sides.
m
0 more
10 r m
o
m
0 m re
60 r mo
o
1
or 00 m
m m
or
e
25
(Se0 m
rvi m o
ce r m
sp or
ac e
e)
m
0 m re
30 r mo
o
- (02 - 03) -
2
or 50 m
mo m
re
2
or 50 m
mo m
re
m
0 m re
30 r mo
o
333REFRIGERANT CIRCUIT
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LB, AOA36LB
„„
- (02 - 04) -
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LF, AOA36LF
„„
- (02 - 05) -
444WIRING DIAGRAMS
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LB, AO36LB
„„
- (02 - 06) -
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LF
„„
- (02 - 07) -
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA36LF
„„
- (02 - 08) -
555CAPACITY COMPENSATION RATE FOR PIPE LENGTH
AND HEIGHT DEFFERENCE
MODEL:: AOA30LB, AOA30LF
„„
Pipe length (m)
COOLING
1
Indoor unit is upper
than outdoor unit
5
7.5
10
20
30
40
50
30
-
-
-
-
0.908
0.894
0.876
20
-
-
-
0.935
0.923
0.909
0.891
10
-
-
0.968
0.951
0.938
0.924
0.906
7.5
-
0.982
0.972
0.954
0.942
0.928
0.909
5
0.992
0.986
0.976
0.958
0.946
0.932
0.913
0
1.000
0.994
0.983
0.966
0.954
0.939
0.920
-5
1.000
0.994
0.983
0.966
0.954
0.939
0.920
-7.5
-
0.994
0.983
0.966
0.954
0.939
0.920
-10
-
-
0.983
0.966
0.954
0.939
0.920
Height
difference H
(m)
2
Indoor unit is under
than outdoor unit
-20
-
-
-
0.966
0.954
0.939
0.920
-30
-
-
-
-
0.954
0.939
0.920
Pipe length (m)
HEATING
1
Indoor unit is upper
than outdoor unit
5
7.5
10
20
30
40
50
30
-
-
-
-
0.931
0.914
0.899
20
-
-
-
0.954
0.931
0.914
0.899
10
-
-
0.990
0.954
0.931
0.914
0.899
7.5
-
0.991
0.990
0.954
0.931
0.914
0.899
5
1.000
0.991
0.990
0.954
0.931
0.914
0.899
0
1.000
0.991
0.990
0.954
0.931
0.914
0.899
-5
0.995
0.986
0.986
0.949
0.926
0.909
0.895
-7.5
-
0.983
0.983
0.946
0.924
0.907
0.892
-10
-
-
0.981
0.944
0.921
0.904
0.890
-20
-
-
-
0.935
0.912
0.895
0.881
-30
-
-
-
-
0.903
0.886
0.872
Height
difference H
(m)
2
Indoor unit is under
than outdoor unit
Height difference H
Outdoor unit
Indoor unit
H
H
Outdoor unit
Indoor unit
Connection pipe
Connection pipe
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
- (02 - 09) -
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
This table is created using the maximum capacity.
MODEL:: AOA36LB, AOA36LF
„„
Pipe length (m)
COOLING
1
Indoor unit is upper
than outdoor unit
5
7.5
10
20
30
40
50
30
-
-
-
-
0.908
0.894
0.876
20
-
-
-
0.935
0.923
0.909
0.891
10
-
-
0.968
0.951
0.938
0.924
0.906
7.5
-
0.982
0.972
0.954
0.942
0.928
0.909
5
0.992
0.986
0.976
0.958
0.946
0.932
0.913
0
1.000
0.994
0.983
0.966
0.954
0.939
0.920
-5
1.000
0.994
0.983
0.966
0.954
0.939
0.920
-7.5
-
0.994
0.983
0.966
0.954
0.939
0.920
-10
-
-
0.983
0.966
0.954
0.939
0.920
Height
difference H
(m)
2
Indoor unit is under
than outdoor unit
-20
-
-
-
0.966
0.954
0.939
0.920
-30
-
-
-
-
0.954
0.939
0.920
Pipe length (m)
HEATING
1
Indoor unit is upper
than outdoor unit
5
7.5
10
20
30
40
50
30
-
-
-
-
0.931
0.914
0.899
20
-
-
-
0.954
0.931
0.914
0.899
10
-
-
0.990
0.954
0.931
0.914
0.899
7.5
-
0.991
0.990
0.954
0.931
0.914
0.899
5
1.000
0.991
0.990
0.954
0.931
0.914
0.899
0
1.000
0.991
0.990
0.954
0.931
0.914
0.899
-5
0.995
0.986
0.986
0.949
0.926
0.909
0.895
-7.5
-
0.983
0.983
0.946
0.924
0.907
0.892
-10
-
-
0.981
0.944
0.921
0.904
0.890
-20
-
-
-
0.935
0.912
0.895
0.881
-30
-
-
-
-
0.903
0.886
0.872
Height
difference H
(m)
2
Indoor unit is under
than outdoor unit
Height difference H
Outdoor unit
Indoor unit
H
H
Outdoor unit
Indoor unit
Connection pipe
Connection pipe
1 Indoor unit is upper than outdoor unit.
2 Indoor unit is under than outdoor unit.
- (02 - 10) -
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
This table is created using the maximum capacity.
666ADDITIONAL CHARGE CALCULATION
MODEL:: AOA30LB, AOA36LB, AOA30LF, AOA36LF
„„
Refrigerant amount
R410A
g
2100
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
Refrigerant type
REFRIGERANT CHARGE
zz
Pipe length
m
~ 20
30
40
50
Additional charge
g
0 (Chargeless)
+400
+800
+1200
- (02 - 11) -
40g/m
777AIR FLOW
MODEL:: AOA30LB
„„
Number of
rotations
(r.p.m)
850
Air flow
m3/h
3600
l/s
1000
CFM
2119
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
COOLING
zz
HEATING
zz
Number of
rotations
(r.p.m)
900
Air flow
m3/h
3800
l/s
1056
CFM
2236
MODEL:: AOA36LB
„„
COOLING
zz
Number of
rotations
(r.p.m)
950
Air flow
m3/h
4000
l/s
1111
CFM
2354
HEATING
zz
Number of
rotations
(r.p.m)
900
Air flow
m3/h
3800
l/s
1056
CFM
2236
- (02 - 12) -
MODEL:: AOA30LF
„„
Number of
rotations
(r.p.m)
850
Air flow
m3/h
3600
l/s
1000
CFM
2119
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
COOLING
zz
HEATING
zz
Number of
rotations
(r.p.m)
900
Air flow
m3/h
3600
l/s
1000
CFM
2119
MODEL:: AOA36LF
„„
COOLING
zz
Number of
rotations
(r.p.m)
950
Air flow
m3/h
3800
l/s
1056
CFM
2236
HEATING
zz
Number of
rotations
(r.p.m)
900
Air flow
m3/h
3800
l/s
1056
CFM
2236
- (02 - 13) -
888OPERATION NOISE
88888NOISE LEVEL CURVE
HEATING
zz
80
80
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band sound pressure level, dB:(0dB=0.0002µbar)
OUTDOOR UNIT
AOA30-36L
COOLING
zz
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
NC-15
NC-15
10
0
63
10
125
250
500
1,000
2,000
4,000
0
63
8,000
125
250
Octave band center frequency,Hz
500
1,000
2,000
4,000
8,000
Octave band center frequency,Hz
MODEL:: AOA36LB, AOA36LF
„„
HEATING
zz
80
80
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
Octave band sound pressure level, dB:(0dB=0.0002µbar)
COOLING
zz
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
NC-20
NC-15
10
0
63
NC-15
10
125
250
500
1,000
2,000
4,000
8,000
Octave band center frequency,Hz
0
63
125
250
500
1,000
2,000
Octave band center frequency,Hz
- (02 - 14) -
4,000
8,000
OUTDOOR UNIT
AOA30-36L
MODEL:: AOA30LB, AOA30LF
„„
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
88888SOUND LEVEL CHECK POINT
- (02 - 15) -
999ELECTRIC CHARACTERISTICS
OUTDOOR UNIT
AOA30-36L
Power supply
AOA36LB
AOA36LF
Voltage
V
230 ~
Frequency
Hz
50
*1) Max. operating current
A
Starting current
A
15.0
A
30
mm2
5.3 - 6.0
Main fuse (Circuit breaker)
current
*2) Wiring spec.
Power cable
*3)Limited wiring length
m
17.0
20.0
21
*1) T
he maximum current is the total current of indoor unit and outdoor unit.
*2) W
iring spec.
Selected sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*3) L
imited wiring length :
This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
- (02 - 16) -
18
OUTDOOR UNIT
AOA30-36L
AOA30LB
AOA30LF
Model name
1111 SAFETY DEVICES
Model
Circuit protection
AOA30LB
AOA30LF
AOA36LB
AOA36LF
Current fuse (NEAR THE TERMINAL)
25A 250V
Current fuse (FILTER PRINTED CIRCUIT BOARD)
10A 250V
Current fuse (MAIN PRINTED CIRCUIT BOARD)
Fan motor protection
Thermal protection program
High Pressure Protection
Pressure Switch
3.15A 250V
OFF : 140±20°C
ON : 110±20°C
OFF : 4.2±0.1MPa
ON : 3.2±0.15MPa
Thermal protection program (COMPRESSOR TEMP.)
Compressor protection
Thermal protection program (DISCHARGE TEMP.)
- (02 - 17) -
OFF : 120°C
ON : 80°C
OFF : 110°C
ON : After 7 minutes
OUTDOOR UNIT
AOA30-36L
OUTDOOR UNIT
AOA30-36L
Protection form
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project