DG408KIT Keypad - Access Control

DG408KIT Keypad - Access Control
DG408KIT Keypad
MAIN FEATURES:
- Power supply: from 11 to 30 V ac/dc
- Current drain: 4 mA at 12 V.
- 1 relay: resistive load: 10A/30V dc. It’s not allowed to apply to relay’s contacts voltages over 30
V dc or 24 V ac. On the contrary, please link an external relay.
- Contact of relay: permanent or impulsive.
- “Dead man” function
- Maximum number of codes: 60
- State memory of the relay.
- Output for LED on/off
- Output for programme mode LED
- Output for Tamper alarm function (30 sec.)
- Possibility to enter program mode directly from keypad.
- Maximum distance between keypad and control-box: 300 mt.
Simplified instruction manual for DIGITEN – MICROTEN keypads use only
• Press and hold down the push-button CLEAR for 6 sec. on the control-box to make a total erasing
of the memory. During this time the red LED flashes quickly and, at the end, it flashes slowly.
Release the push-button CLEAR.
• Enter the first code that will be the MASTER code and wait for 5 sec. Without pressing any other
push-button on the keypad. At the end the LED flashes for 1 sec.
• Enter the other codes that must have the same number of digits of the Master code.
• To exit programme mode enter a code already stored.
NOTE:
• Master code does not operate the relay. It is useful only to enter programme mode directly
via keypad.
• Master code decides how many digits must have all the other codes. If Master code has 4 digits,
all the other codes must be composed by 4 digits.
• If it happens to press a wrong push-button on the keypad, wait for 5 sec. without pressing any
other push-button. At the and, the red LED will switch off to indicate it is possible to enter the
correct code.
• It is possible to store codes whose length is from 1 to 8 digits maximum.
• Codes that start with more than three zeros are refused (ex.: 000057)
RELAY’S TIME SETTING
Shut down the power supply to the control-box.
Press the push-button CLEAR for the duration of relay’s contact.
Press and hold down CLEAR push-button and, in the same time, give power supply to the controller. Hold
st
down the push-button and count the flashes of the red LED on the control-box, considering that: 1 flash =
bistable
nd
2
flash = dead man function (*)
rd
3 flash = 250 ms (minimum contact duration)
th
4 flash = 1 second
th
5 flash = 2 seconds and so on until a maximum time of 27 seconds. Release
the push button when the desired duration is gained.
(*) Dead man function = the relay stays attracted as long as the last digit of the code is pressed.
STORING ADDITIONAL CODES
In any time is always possible to add other codes into the memory of the control-box via Master code, directly from
the keypad.
• Enter Master code: the relay does not operate, the red LED flashes and the control-box enter in programme mode.
• Enter the new codes you want to store with the same number of digits of the Master code.
• To exit programme mode enter a code already stored.
ADDRESSED CODES ERASING
In any time it is always possible to erase a code from the memory of the control-box, via Master code
directly from the keypad.
•
Enter Master code: the relay does not operate, the red LED flashes and the control-box enter in
programme mode.
•
Enter five zeros followed by the number the corresponds to the location’s code in the memory.
th
For example if the code you want to erase is 1234 and it is the 4 code you have stored, operate as
follow: enter Master code, then enter 000004.
•
Wait for 5 sec. without pressing any other push-button on the keypad. After that short time the
red LED flashes quickly and then flashes slowly.
•
It is possible to store a new code with same digits of the Master code, in the empty location of
the code you have just erased.
•
To exit programme mode enter a code already stored.
th
Anyway, the control-box will exit programme mode automatically when the 60 code is stored (full
memory) or when you shut down the power supply.
th
TAMPER alarm output – Violet wire. It activates (closes to negative) at the 4
sec.) at tampering or after 8 sec. of continuous transmission .
To reset Tamper alarm, enter a valid code or wait for 30 sec.
attempt (during a period of 30
Green LED of keypad is free for
the user:
Green wire: connect to + 12 V cc
Black wire: connect to negative
CLEAR push-button
DIGITEN
Keypad
RELAY
Pos. 12 to 30 V ac/dc power supply
Black wire
Grey wire : N.O.
Violet wire: tamper alarm
Black wire: negative power supply
Yellow wire: (+) LED on/off
Blue wire: COM.
White wire: data
Brown wire: N.C.
White wire
Green wire: (+) LED progr.
Warranty
The product is warranted against defects in material and workmanship while used in normal service for a period
of 1 year from the date of sale to the original client. The Guardall policy is one of continual development and
improvement, therefore Guardall reserves the right to change specifications without notice
GUARDALL © All rights reserved.
WWW.GUARDALLLOCKS.COM.AU
Head Office: Guardall Security,
19-21 Belmont Avenue, Belmont WA 6104
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising