850033855 1U Dist Shelf J2013001 QSG r04 DRAFT outlined step

850033855 1U Dist Shelf J2013001 QSG r04 DRAFT outlined step
GE
Critical Power
Quick Start Guide
1U Stackable Distribution Shelf - 19 in Rack Mount
J2013001 - multiple models - See SPS, CP, or NE Brochure for models.
Supplementary Distribution Shelves
Primary Distribution Shelf
Rectifier Shelves
Battery
Connection
Options
SPS System Example
Distribution shelves may be bused together as shown above in SPS, CP, and NE systems or used as stand-alone remote distribution (cabled
to a power system).
Primary distribution shelves include battery connections. Some models also include battery contactors.
Install the primary distribution shelf immediately above the primary SPS, CP, or NE rectifier shelf (with controller).
Communication cables and interconnecting hardware are included.
Refer to SPS, CP, or NE-S Power System Brochure for details and accessories.
Tools required:
Torque wrench (0-65 in-lb or 0-10Nm)
Screw Drivers (#1 Phillips)
Sockets - 5/16”, 7/16”
Wire cutters and strippers
Cable crimpers
Step 1 - Mount Shelf
1. Reposition mounting ears as required - 4 screws each.
Torque to 25 in-lb (2.8Nm) - Phillips screwdriver.
2. Position the Initial Panel immediately above the rectifier shelf with Controller.
Position Supplementary Panels immediately above another Panel.
3. Install Inter-Shelf brackets between adjacent shelves (optional).
Torque to 25 in-lb (2.8Nm) - Phillips screwdriver.
4. Attach shelf to the frame using a minimum of four screws (two on each side) 12-24 (provided).
Torque to 35 in-lb (4Nm) - 5/16” socket.
Mounting Ears
2 Adjacent
Shelves
Inter-Shelf Bracket
Step 2 - Ground Chassis
Notes: Lug landing is M5 on 5/8” centers (lug not provided)
10 AWG (6mm2) recommended.
Some applications may rely on frame mounting screws for shelf ground omitting the
shelf ground cable
Torque to 35 in-lb (4Nm ) - 5/16” (8 mm) socket.
Frame Ground
(right sides)
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
1
Step 3 - Connect System DC Reference (CO) Ground
Make one connection to the power system (CP, NE, SPS, etc.).
No connection to a stand-alone, remote distribution shelf.
Connections are on the rear under the RETURN cover.
Attach lug adapter to the unused RETURN bus landings of the top or bottom Shelf
(850036871 lug adapter is supplied with primary distribution shelves).
Lug landing - 1/4” holes on 5/8” centers (hardware provided, lug not provided)
Torque all hardware to 65 in-lb (7.3 Nm) - 7/16” socket.
Lug Adapter
Step 4 - Connect Shelf DC
RETURN bus
Connections
covers shown
Connections are on the rear under covers.
Bus Connection - to an adjacent shelf
Install inter-shelf buses joining -48V and RETURN bus
connections of adjacent shelves.
Torque to 65 in-lb (7.3 Nm)
Dual Lug
Landings
(stand-alone
Shelf)
Cable Connection - Stand-alone Shelf
CAUTION: Verify battery voltage and polarity with a voltmeter
before proceeding.
Lug Landings - 2 x 1/4” on 5/8” center, 0.7” (18mm) max. tongue
width.
Connect cables with suitable lugs to -48V and RETURN.
Torque to 65 in-lb (7.3 Nm)
2 Adjacent
shelves
Inter-shelf bus
-48V bus Connections
covers removed
Step 5 - Connect Communication Wires
Connectors are on the rear of the shelf.
1. Connect alarm cable between Primary Distribution
Shelf and adjacent Primary Rectifier Shelf (with
controller) (if present) - cable provided.
2. Connect alarm cables between all Distribution
Shelves.
Supplemental
Distribution Shelves
Alarm Cable
Shelf to Shelf
Primary
Distribution Shelf
Primary
Rectifier Shelf
(with Controller)
SPS System
2
Alarm Cable
Primary Distribution Shelf
to
Primary Rectifier Shelf
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
NE or CP System
Step 6 - Connect Batteries - skip if not present
Battery connections are labeled “-48Vdc BATT” and “POS RTN”.
Battery connections are either on the rear or front.
-48V Lug Landings
Return Lug Landings
Only front battery connections have breakers.
CAUTION:
·
·
Verify battery voltage and polarity with a voltmeter before proceeding.
Front Connections only:
Verify that breaker is OFF or not installed.
1. Remove Cover
2. Connect cables with suitable lugs to -48Vdc BATT and POS RTN landings.
3. Torque to 65 in-lb (7.3 Nm) - 7/16” socket
4. Replace cover.
Rear Battery Lug Landings
(front figure below)
Step 7 - Connect Bullet Circuit Breaker Loads - skip if not present
Load connections are labeled “-48Vdc LOAD” and “POS RTN”.
Load Breakers have Black handles.
Lug Landings - Circuit Bullet Breaker Loads and Battery
2 Circuit Block
Battery or Load
3 Circuit Block
Load only
1/4”
#10
0.7” (18 mm)
0.44” (11.2 mm)
Torque
65 in-lb (7.3 Nm)
30 in-lb (3.4 Nm)
Socket
7/16”
5/16”
CAUTION: Verify that breaker is OFF or not installed
1. Remove Cover
2. Connect wires with suitable lugs to -48Vdc LOAD and
POS RTN landings.
3. Torque per table
4. Replace Cover.
Lug Holes - on 5/8” centers
Tongue Width max.
Cover Screws
-48V Lug Landings
Return Lug Landings
2-Circuit Blocks - Battery or Load
Cover Screws
-48V Lug Landings
Return Lug Landings
3-Circuit Blocks - Load only
Bullet Breaker Connections
(ID Label and Breaker landing covers not shown)
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
1
3
Step 8 - Connect Snapak Circuit Breaker Loads - skip if not present
1. Verify that breaker is OFF or not installed.
2. Remove detachable terminal block
3. Insert load and load return wires
Strip 0.4 in (10 mm)
8 AWG (6 mm2) max.
4. Torque to 6.5 in-lb (0.75 Nm).
5. Pull wires to verify.
6. Insert detachable terminal block fully.
Wire Entry
V- V+
Load Return
Screw
-48V Load
Detachable
Terminal Block
Snapak Breaker Connections
Step 9 - Connect GMT Style Fuse Loads - skip if not present
Connections for Load GMT Fuses to GMT terminal blocks identified as
“-48VDC” and “RTNS” on labels above each row of terminals blocks.
Tie Bar
Wire Size: 24-12AWG
Strip Length: 0.35” (9mm)
1. Verify that fuse is not installed.
2. Strip wires
3. Insert wires into terminal blocks labeled -48VDC and associated RTNS.
4. Tighten screw - 4 in-lb (0.45 Nm).
5. Pull wire to verify.
6. Reposition the Tie Bar to the bottom of the panel if desired - 2 screws.
7. Secure wires to Tie Bar.
Insert Wire
Screw
Step 10 - Label Connections
1. Mark each connected circuit identification on the ID label.
2. Snap the ID Label onto the Tie Bar.
ID Label Examples
4
2
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
Step 11 - Install Breakers and Fuses
Install breakers and fuses into positions as specified in Site Engineering Instructions.
Bullet Breakers
CAUTION: 1. Install breakers oriented as shown
Orientation is different for Left and Right breakers.
2. Install proper breaker type in Battery and Load positions.
Battery Breakers (Yellow handle) in Battery Position. (Right positions only)
Load Breakers (Black handle) in Load Positions. (Right and Left positions)
1. Remove Retention Cover (2 screws)
2. Verify that each Breaker is OFF.
3. Insert each Breaker fully into its position — oriented as shown below.
4. Remove cover knockouts for installed positions.
5. Replace Cover (2 thumb screws)
6. Turn each Breaker ON
Load Breaker Positions
Battery or Load
Breaker Positions
Breaker Guard Orientation
Left Positions
Breaker Retention Covers
Breaker Guard Orientation
Right Positions
Snapak Breakers
1. Remove Cover (2 thumb screws)
2. Verify that each Breaker is OFF.
3. Insert each Breaker fully into its position
— oriented with ON position at top.
4. Remove cover knockouts for installed positions.
5. Replace Cover (2 thumb screws)
6. Turn each Breaker ON
GMT Style Fuses
1. Insert each GMT style fuse fully into its position
- oriented as shown.
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
1
5
Step 12 - Controller Shunt and Contactor Settings - if battery connections are present
Details in Pulsar Edge Controller Family Product Manual.
Shunt size and contactor option label is on the side of the Battery Lug Landing assembly.
Verify settings as specified in Site Engineering Instructions.
Verify Battery Shunt Settings:
A. Controller Display - Follow the menu path; Menu > Configuration > Shunt Monitors > Built In - edit as necessary.
B. Web Pages or EasyView2 - Select the Settings Tab > Shunts > Plant Shunt - edit as necessary.
Verify Disconnect Contactor Settings - if disconnect contactor is present:
A. Controller Display - Follow the menu path; Menu > Configuration > Contactor Interfaces > Built In - type “LVBD” or “LVLD”;
and Menu > Configuration > Disconnects > LVBD or LVBD 1—3 - edit as necessary
B. Web Pages or EasyView2 - Select the Settings Tab > Contactors > DCNC1 - type “LVBD”; Select Edit button, edit settings as necessary.
Shunt Size and
Disconnect Contactor option
label
Reference Documents
These documents are available at www.gecriticalpower.com.
Document Title
CC848815341 Pulsar Edge Controller Family Product Manual
Infinity S Power System (NE-S) Brochure and Ordering Guide
Slimline Power System (SPS) Brochure and Ordering Guide
Cabinet Power System (CP) Brochure and Ordering Guide
6
2
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
Safety Statements
 Do not install this equipment over combustible surfaces.
 Rules and Regulations - Follow all national and local rules and regulations when making field connections.
 Compression Connectors
 U. S. or Canada installations - use Listed/Certified compression connectors to terminate Listed/Certified field-wire conductors.
 All installations - apply the appropriate connector to the correct size conductor as specified by the connector manufacturer, using only
the connector manufacturer’s recommended or approved tooling for that connector.
 Electrical Connection Securing: Torque to the values specified on labels or in the product documentation.
 Cable Dress - dress to avoid damage to the conductors and undue stress on the connectors.
 Circuit Breakers and Fuses
 Use only those specified in the equipment ordering guide.
 Size as required by the National Electric Code (NEC) and/or local codes.
Safety Tested Limits - Refer to the equipment ratings to assure current does not exceed:
Continuous Load (List 1) - 60% of protector rating
Maximum Load (List 2 - typically end of discharge) - 80% of protector rating.
 GMT Style Fuses - Use only fuses provided with safety caps.
 Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
 Insulation rating: 90°C minimum; 105°C (minimum) if internal to enclosed equipment cabinets.
 Size AC field-wired conductors with 75°C ampacity (NEC) equal to or greater than their panel board circuit breaker rating.
 AC and DC input disconnect/protection - Provide accessible devices to remove input power in an emergency.
 Alarm Signals - Provide external current limiting protection. Rating 60V, 0.5A unless otherwise noted.
 Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground
bus. In huts, vaults, and central offices connect to the system bonding network.
Precautions
 Install, service, and operate equipment only by professional, skilled and qualified personnel who have the necessary knowledge and
practical experience with electrical equipment and who understand the hazards that can arise when working on this type of equipment.
 Disconnect batteries from outputs and/or follow safety procedures while working on equipment. Batteries may be connected in parallel
with the output of the rectifiers. Turning off the rectifiers will not necessarily remove power from the bus.
 Do not disconnect permanent bonding connections unless all power inputs are disconnected.
 Verify that equipment is properly safety earth grounded before connecting power. High leakage currents may be possible.
 Exercise care and follow all safety warnings and practices when servicing this equipment. Hazardous energy and voltages are present in
the unit and on the interface cables that can shock or cause serious injury. When equipped with ringer modules, hazardous voltages will
be present on the ringer output connectors.
 Use the following precautions in addition to proper job training and safety procedures:
 Use only properly insulated tools.
 Remove all metallic objects (key chains, glasses, rings, watches, or other jewelry).
 Follow Lock Out Tag Out (LOTO) procedures: customer specified, site specific, or general as appropriate.
Disconnect all power input before servicing the equipment. Check for multiple power inputs.
 Wear safety glasses.
 Follow Personal Protective Equipment requirements: customer specified, site specific, or general as appropriate.
 Test circuits before touching.
 Be aware of potential hazards before servicing equipment.
 Identify exposed hazardous electrical potentials on connectors, wiring, etc.
 Avoid contacting circuits when removing or replacing covers;.
 Use a personal ESD strap when accessing or removing electronic components.
 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and
cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease
with distance.
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
Document 850033855 r04 2015 August
1
7
Notes
2
8
1U Distribution Shelf - 19 in Rack Mount - Quick Start Guide
GE ● 601 Shiloh Rd. ● Plano, TX 75074 ● 1- 888 546-3243
www.gecriticalpower.com