NELSON ALT-CMD Continuity Monitor Device Installation instructions
Below you will find brief information for Continuity Monitor Device ALT-CMD. The Continuity Monitor Device ALT-CMD is used to monitor bus continuity on a parallel type heater cable. After the heater cable is installed on the pipe, connect the ALT-CMD to the opposite end of the power connection kit.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
9
NELSON™ HEAT TRACING SYSTEMS INSTALLATION ALT-CMD CONTINUITY MONITOR DEVICE INSTRUCTIONS DESCRIPTION KIT CONTENTS The ALT-CMD continuity monitor device is used to monitor bus continuity on a parallel type heater cable. After the heater cable is installed on the pipe, connect the ALT-CMD to the opposite end of the power connection kit. 1 1 1 1 1 2 CMD Device Conduit Locknut Sealing Grommet Stand-off Label Wire Nuts 1 1 1 1 2 Power Termination Box Adapter Gasket Tube of Silicone Pipe Clamps Silicone CMD Device Box Cover Gasket Power Termination Conduit Locknut Label Gasket Box Adapter Sealing Grommet J-Grommet - Overjacket Product B-Grommet - Base Product U-Grommet - non-standard construction Stand-off *Heater Cable (see warning below) *Fiberglass Tape *ITEMS NOT INCLUDED IN KIT Pipe Clamps Note: This detail shows Braided “CB” Products only. For Overjacket “J” or “JT” Products see diagram on sheet 8. ! WARNING: Article 427-22 of the National Electrical Code requires that all heaters shall have metal coverings and be provided with branch circuit ground-fault protection. P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com GA-2075 Rev.1 Sheet 1 of 9 September 2005 NELSON™ HEAT TRACING SYSTEMS INSTALLATION ALT-CMD CONTINUITY MONITOR DEVICE INSTRUCTIONS STAND-OFF POSITIONING Section View A A (recommend installing at the 4 or 8 o'clock positions.) ! WARNING: Do not place pipe clamps over the heater cable. 8 o'clock 4 o'clock Pipe Clamps 254mm (10") A A Fiberglass Tape Stand-off Fiberglass Tape Stand-off (not included in kit) (not included in kit) Sealing Grommet Box Adapter Power Termination n o p Mark pipe where stand-off will be mounted. Push heater cable through bottom opening of stand-off. Slide the sealing grommet over the heater cable and position inside stand-off opening: for Braided “CB” Products: See “Grommet Installation for Braided “CB” Products”, sheet 3. for Overjacket “J” or “JT” Products Proceed with step 4 below. q r s t Apply silicone around the heater cable on top of the sealing grommet and fill any voids in sealing grommet. Slide the box adapter over the heater cable and tighten securely to stand-off. Prepare heater cable for power termination: for Braided “CB” Products, see sheet 3. for Overjacket “J” or “JT” Products, see sheet 4. Terminate heater cable, see sheet 7. P.O. BOX 726 GA-2075 Rev. 1 Sheet 2 of 9 September 2005 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com NELSON™ HEAT TRACING SYSTEMS INSTALLATION ALT-CMD CONTINUITY MONITOR DEVICE INSTRUCTIONS SEALING GROMMET INSTALLATION FOR BRAIDED “CB” PRODUCTS 13mm (.5") n o Slide braid back, allowing at least 13mm (.5”) of heater cable exposed. Cut and remove 13mm (.5”) of heater cable. p q r Slide braid back over heater cable and twist excess braid into a pigtail. Slide the sealing grommet over the heater cable and position inside stand-off opening. Continue with step 4 on sheet 2. BRAIDED “CB” PRODUCTS q 127mm (5') n o p Secure cable braid with fiberglass tape. Slide braid back 127mm (5”) to create a bulge. At the bulge, separate the braid to make an opening. P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 While bending the heater cable, work it through the braid opening. 114mm (4.5") cut off excess braid r s t Proceed to “LT, CLT & HLT Products”, sheet 5 FAX 918-641-7336 Pull the braid tight. Cut off excess braid. www.nelsonheaters.com GA-2075 Rev.1 Sheet 3 of 9 September 2005 NELSON™ HEAT TRACING SYSTEMS ALT-CMD CONTINUITY MONITOR DEVICE INSTALLATION INSTRUCTIONS OVERJACKET “J or “JT” PRODUCTS ! WARNING: DO NOT CUT BRAID 127mm (5") n o Lightly cut around cable overjacket 127mm (5") from the end. Bend cable to break the overjacket. Lightly cut overjacket up the center between first cut mark and the cable end. Bend cable to break the overjacket. r s p At the bulge, separate the braid to make an opening. While bending the heater cable, work it through the braid opening. Remove overjacket from heater cable. 114mm (4.5") cut off excess braid q Move braid back toward the overjacket, creating a bulge. P.O. BOX 726 GA-2075 Rev. 1 Sheet 4 of 9 September 2005 TULSA, OK 74101 TEL 918-627-5530 t u v Pull the braid tight. Cut off excess braid. Proceed to “LT, CLT & HLT Products”, sheet 5. FAX 918-641-7336 www.nelsonheaters.com NELSON™ HEAT TRACING SYSTEMS ALT-CMD CONTINUITY MONITOR DEVICE INSTALLATION INSTRUCTIONS FOR ALL NELSON LT, CLT & HLT PRODUCTS (See sheet 6 for an alternate stripping method for HLT products.) 102mm (4") n o Lightly cut around cable outer jacket 102mm (4") from the end. Bend cable to break outer jacket. Lightly cut the outer jacket up the center between the first cut mark & the cable end. Bend cable to break outer jacket. p Remove the jacket from the heater cable. ! r Starting at the end, pull each bus wire away from the core material. Remove exposed core material. s t u Cut 6mm (0.25") off the end of each bus wire. Proceed to “Power Termination”, sheet 7. WARNING: DO NOT CUT BUS WIRES q Shave the core material from the outside of each bus wire. P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com GA-2075 Rev.1 Sheet 5 of 9 September 2005 NELSON™ HEAT TRACING SYSTEMS ALT-CMD CONTINUITY MONITOR DEVICE INSTALLATION INSTRUCTIONS HLT PRODUCTS ALTERNATE STRIPPING METHOD 102mm (4") n Lightly cut around cable outer jacket 102mm (4") o p r from the end. Bend cable to break outer jacket. Lightly cut the outer jacket up the center between the first cut mark & the cable end. Bend cable to break outer jacket. s Remove the exposed core material. Remove the jacket from the heater cable. t q Starting at the end, in the same plane as the cable, pull each bus wire away from the core material. Make a cut inside each bus wire. P.O. BOX 726 GA-2075 Rev. 1 Sheet 6 of 9 September 2005 TULSA, OK 74101 TEL 918-627-5530 Remove the remaining core material off the outside of each bus wire. Cut 6mm (0.25") off the end of each bus wire. u v Proceed to “Power Termination”, sheet 7. FAX 918-641-7336 www.nelsonheaters.com NELSON™ HEAT TRACING SYSTEMS ALT-CMD CONTINUITY MONITOR DEVICE INSTALLATION INSTRUCTIONS POWER TERMINATION ! WARNING: Bus wires must not touch or cross while inserting into power termination. 13mm (.5") apply silicone here p q n o Push power termination to overlap jacket. r The silicone will set up in about 30 minutes with a complete cure after 24 hours. Proceed to “Electrical Connection”, sheet 8. FAX 918-641-7336 Insert bus wires into power termination. Squeeze power termination opening and fill with silicone. P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 www.nelsonheaters.com GA-2075 Rev.1 Sheet 7 of 9 September 2005 NELSON™ HEAT TRACING SYSTEMS INSTALLATION ALT-CMD CONTINUITY MONITOR DEVICE INSTRUCTIONS CMD DEVICE CONNECTION Wire Nut Power Termination Conduit Locknut Box Adapter Note: This detail shows Overjacket “J” or “JT” Products only. For Braided “CB” Products see diagram on sheet 1. n o p q r s Place gasket onto the box adapter. Position the CMD device onto the box adapter and secure it with the conduit locknut. Connect heater bus wires together with the CMD lead wires using the wire nuts. (See diagram above.) Make sure all wires are placed inside the CMD device. Place the box cover and box cover gasket onto the CMD device. See sheet 9 for “CMD Cable Connections to CM-1 and CM-2/1”. P.O. BOX 726 GA-2075 Rev. 1 Sheet 8 of 9 September 2005 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com NELSON™ HEAT TRACING SYSTEMS INSTALLATION ALT-CMD CONTINUITY MONITOR DEVICE INSTRUCTIONS CMD CABLE CONNECTIONS TO CM-1 & CM-2/1 PNL PNL Branches are monitored by current flow on process applications. CMD CMD Long side branch Short side branch (under 254mm (10")) PNL CM-1 CMD JB CMD JB (Typ.) Wire & conduit to series connect segments. JB CMD CMD Long side branch will not work Branch / Tee Piping (single circuit, multiple cable segments) PNL PNL CMD CMD CM-1, CM-2/1 Heater Connection Kit Pipe Heater Cable Field Wiring CMD CMD CMD will not work Grouped Segments (several separate cables through single monitor point) Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's website at www.nelsonheaters.com. P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com GA-2075 Rev.1 Sheet 9 of 9 September 2005
advertisement
Key Features
- Monitors bus continuity
- Connects to power connection kit
- Parallel type heater cable
- Stand-off positioning
- Grommet installation
- Power termination
- Electrical connection
Frequently Answers and Questions
What is the purpose of the ALT-CMD Continuity Monitor Device?
The ALT-CMD Continuity Monitor Device monitors bus continuity on a parallel type heater cable. It helps ensure that the heater cable is properly installed and functioning.
How do I connect the ALT-CMD to the heater cable?
After the heater cable is installed on the pipe, connect the ALT-CMD to the opposite end of the power connection kit. The instructions provided in the document will guide you through the process.
What safety precautions should be taken when installing the ALT-CMD?
The document provides several safety warnings, including not placing pipe clamps over the heater cable, and ensuring that bus wires do not touch or cross while inserting into the power termination. It's crucial to follow all instructions carefully for safe installation.