CONVENTIONAL FIRE CONTROL PANEL 2 / 4-20 Zones

CONVENTIONAL FIRE CONTROL PANEL 2 / 4-20 Zones
CONVENTIONAL
FIRE CONTROL PANEL
2 / 4-20 Zones
GENERAL DESCRIPTION
The SmartLine020 conventional fire-detection
control panel series offers a 2 zone nonexpandable model and a 4 zone expandable
model expandable to 20 zones by means of
SmarLine/8Z 8-zone expansion boards.
The extreme compactness and ease of
programming and operation makes this
control panel ideal for small applications,
where fast installation and programming are
among the most important aspects of the
application.
SmartLine020 provides housing for a
SmartLetLoose/ONE fire extinction board.
This board is EN12094-1 approved, and
offers a complete range of functions for fire
extinguishing system management.
The SmartLine020 control panel has 2
supervised outputs for alarm and fault
signaling (the efficiency of these outputs is
monitored continuously).
The control panel provides 1 terminal per
zone configurable as: open-collector output,
supervised output, supervised input, gas
detector input with 4-20mA interface, gas
detector input with open-collector output
interface. This flexibility notably increases
the
application
panorama
of
the
SmartLine020.
System information is provided through the
graphic display and LEDs on the control
panel. The SmartLine020 manages an RS485
BUS which supports 4 remote - control
Repeater
panels
(Model:
SmartLetUSee/LCD).
INIM Electronics
Repeater panels replicate all the fire alarm
system data and allow users to access and
control the system in accordance with their
authorized access level. Programming the
system from the control panel is
straightforward and trouble-free thanks to the
easy-to-follow instructions on the display,
The system can also be programmed using
SmartLeague software application (free
downloadable from web site).
MAIN FEATURES
• EN54 Approved
• EN12094-1 Approved (Fire extinction)
• SmartLine 020-2 : 2 Zones not expandable
• SmartLine 020-4 : 4 Zones expandable to 20
•
Manages
SmartLetLoose/ONE
Fire
Extinction board (EN12094-1 Approved)
• Supports 4 remote-control Repeater panels
• 1 supervised alarm output (NAC)
• 1 output for communicator/dialler activation
• 1 dry-contact alarm output
• 1 dry-contact fault output
• 1 power supply output
• 1 resettable power supply output
• 1 terminal per zone configurable as: opencollector
output,
supervised
output,
supervised input, gas detector input with 420mA interface, gas detector input with opencollector output interface.
• Battery shutdown relay for deep discharge
conditions
• Backlit graphic display for easy
management of Installer/User interface
• Navigation keys for easy access to menu
options
• Fast keys (Silence, Reset, Evacuate,
Investigate)
• Beeper (provides audible signals)
• RS232 connector for uploading /
downloading data
SMART LINE 020
• Programming software (free dowlodable
from web site)
• Easy system programming from the control
panel
• Access key for Level 2 functions (EN54
compliant)
• On-board connector for Thermal probe
(accessory item).
• Battery efficiency test
• Extensive application of SMD reflux
technology for higher reliability
• Metal box
ORDERING CODES
SMARTLINE 020 -2
SMARTLINE 020 -4
SMARTLINE/8Z
SMARTLETUSEE/LCD
SMARTLETLOOSE/ONE
PROBE TH
non-expandable 2 zone
conventional control panel
I/O terminal Board
For each line is also available an I/O terminal
board which can be configured as:
Open collector Programmable Output
Supervised programmable Input:
conventional control panel
with
4 zone expandable to 20
8 zone expansion board
Remote-control Repeater
panel
Fire Extinction board (1
channel)
Thermal probe. This device
protects the battery against
overheating and consequent
permanent damage.
4-20 mA gas detectors input
FRONT PANEL
Call point Line separated from detectors line
OUTPUTS
LINES:
For each line is available a couple of terminal
board for detectors and call ponts connection,
Control panel is able to understand if the
alarm is from a detector or a call point.
INIM Electronics
SMART LINE 020
Dialler Output:
Supervised output for external alarm dialler ,
approved as E output according to EN54
standards.
Closes to GND when active.
RS485 BUS for repeaters connection (4):
Allows to connect up to 4 repeater
SmartLetUSee/LCD. Wiring by means of a 4
pole shilded twisted cable.
24V power output
Supply 24V for external device feed,
protected by a 0,9 A self restorable fuse.
24R Output
Supply 24 V (0,9 A) for external devices feed,
is switched off for 10 seconds during panel
reset. Suitable for beam detector powering.
This output can also be configured as always
ON , switched OFF in case of alarm of one or
more zones (suitable for door holder magnet).
Programmable Relay
A full programmable dry contact output is
available on the panel board.
TECHNICAL SPECIFICATIONS
Fault output:
Panel board is equipped with a dry contact
output activated in case of fault.
Alarm Output:
Supervised output for Sounders / beacon
connection, protected by a 0,9 A self
restorable fuse.
INIM Electronics
PARAMETER
Operating voltage
Consumption
MAX
current
for
external loads
Batteries
Operating temperature
Dimensions
Weight
(without
batteries)
SMART LINE 020
VALUE
230 Vac 50/60 Hz
0,5 A
0,8 A
2 x 7Ah 12V
-5° .. +40°
325x325x80 mm
2,8 Kg
INIM ELECTRONICS s.r.l.
DISTRIBUTOR:
Via Fosso Antico – Loc. Centobuchi
63033 MONTEPRANDONE
(AP) ITALY
Tel. +39 0735 705007
Fax +39 0735 704912
www.inim.biz
INIM Electronics
SMART LINE 020