EasyLine XLP Fuse Switch Disconnector 1-2-3

EasyLine XLP Fuse Switch Disconnector 1-2-3
Protection and Connection
EasyLine XLP
Fuse Switch Disconnector 1-2-3-4 pole
Contents
Introduction
1
Overview 1 and 2-pole
2
Overview 3-pole
3
Overview 4-pole
4
Electronic Fuse Monitoring
5
Busbar Adapters
6
Cable clamps & bolts
7
Technical Data
8
Ordering information
9
Dimension drawings
10
11
12
13
14
15
16
17
18
Fuse Switch Disconnectors
1, 2, 3 and 4 pole solutions, 100A - 630A
1
The EasyLine family fulfils the highest requirements for modern switch fuses with a
total safety concept. The fuse switches are tested according to the EN/IEC 60947-3
standard, meeting all the requirements for isolation, current making, performance and
safety.
Selectivity
The melting curves and current limiting diagrams for NH fuse
links are given in the EN/IEC 60269-2 standard. The standardised
fuse characteristics and high degree of current limitation ensure
a simple and effective co-ordination with fuse links and other
devices. Selecting the right fuse type for your installation is very
simple and can be done without complicated calculations or
tools.
Fuses provide selective coordination. When a fault occurs,
only the fuse nearest a fault trips without upstream fuses being
affected.
When more power is needed in an installation, more feeders can
be added without changing the present structure or any new
selectivity calculations. Fuse links will assure selectivity in the
installation by 1,6:1 difference in the rated current.
Reduction of downtime and lower maintenance cost
Fuse links withstand high short circuit levels. After fuse operation,
only the fuse link needs to be replaced and the rest of the network
remains functional. The fuses can be replaced easily and quickly,
decreasing the plant downtime and maintenance cost.
High performance and reliability
Fuses have very high limiting capability, clearing faults rapidly at
different voltage and short circuit levels.
As the fuse link body is filled with quartz sand, there will be no
emission of gases or arcs when a short circuit occurs. This
again leads to less stress on the network and a higher degree
of personal safety.
XLP 1-,2-,3- and 4-pole solutions
1
1SEC312011B0202 | ABB Catalogue
Fuse Switch Disconnectors
1, 2, 3 and 4 pole solutions, 100A - 630A
•
•
•
•
•
•
•
All units are applicable for AC Voltage, and the 1-pole and
2-pole range are also rated for DC voltage.
Compact XLP000
Typetested according to IEC60947-3
Fullfills BGV A2
Easy to recycle / EN14001 standards
Quick-make operation device
V-0 plastic materials
•
The 3-pole range from size 00 to size 3 (160A - 630A) are
1
also designed to be used in distribution systems by use of
a busbar adapter for easy installation.
Easy cable connections
• All the XLP cable terminals can be delivered with integrated
bolts for cable lugs or with integrated bridge clamps (BC) for
easy direct cable connection.
Safe installation and operation
• Sturdy design
• Integrated IP20 cable termination
• IP30 degree of protection from the front
• Voltage measuring from the front
Easy to install
• Wide range of cable terminals and snap-on accessories
• Compact, add-on Electronic Fuse Monitoring (EFM)
• Busbar adapters available for 40mm, and 60mm distance
in-between centre of the phases for each busbar systems.
All variants of poles available in the different sizes
•
NH00/160A, NH1/250A, NH2/400A and NH3/630A.
•
The XLP 1-pole and 2-pole: Rated operational votage:
220-440VDC / -690VAC
•
The XLP 4-pole: Rated operational votage: 500VAC
ABB Catalogue | 1SEC312011B0202
2
Overview
XLP 1 and 2-pole
2
Features
• Rated operational voltage: 220VDC / -690VAC
• Rated operational current: 160 - 630A
• Micro auxillary switches, 1 or 2 pcs per pole
• Single cable shroud per phase
• Cable clamps
• Front frames
• Padlocking
• Sealing facility
Application
•
UPS: Uninterruptible Power Supply, used for the power
supply for computer/servers, storage devices, communication network systems, industry control systems, etc.
•
Telecom Power Supplies.
•
General protection in smaller distribution panels using
1-pole or 2-pole configurations AC or DC.
XLP, 1 pole
XLP, 2 pole
3
1SEC312011B0202 | EasyLine
Overview
3-pole, XLP000
Features
•
Compact design for NH 00 compact fuses up to 100 A (width = 21mm)
•
Modern integrated cable clamps for 1,5 - 35 mm² cables
•
Integrated cable shrouds IP 20
•
Snap on for DIN rail mounting (accessory)
•
Front frames for 1 - 3 apparatus (accessory)
•
Micro auxiliary switches, 1or 2 pcs (accessory)
•
Sealing facility
3
Sealing facility
DIN rail mounting
Voltage measurement
3-pole, XLP000
Integrated cable clamps
for 1,5 - 35 mm² cables
Front frames for
1-3 apparatuses
EasyLine | 1SEC312011B0202
4
Overview
3-pole, XLP00
•
•
•
•
•
•
Electronic fuse monitoring (EFM)
Micro auxilliary switches, 1 or 2 pcs
Auxilliary switches, 1 NO or 1 NC acc. to IEC 60947-5-1
Cable shrouds
Front frames for 1 - 3 apparatus
Wide range of cable terminal clamps (See page 13 and 14)
•
•
•
•
Kit for double DIN rail mounting
Adapter for 40 and 60 mm busbar distance
Padlocking facility
Sealing facility
3
Padlocking and
Sealing facilities
Electronic fuse monitoring
showing detail for remote
signaling
Micro auxiliary switch on the sides.
Auxiliary switch NO or NC in the front
Cable shrouds
5
1SEC312011B0202 | EasyLine
Overview
3-pole, XLP1, XLP2 and XLP3
•
•
•
•
•
•
•
•
•
Electronic fuse monitoring (EFM)
Micro auxilliary switches, 1 or 2 pcs
Auxilliary switches, 1 NO or 1 NC acc. to IEC 60947-5-1
Cable shrouds
Front frames
Wide range of cable terminal clamps (See page 13 and 14)
Adapter for 40mm (only XLP1) and 60mm busbar distance
Padlocking facility
Sealing facility
3
EasyLine | 1SEC312011B0202
6
Overview 4-pole
4-pole, XLP1, XLP2 and XLP3
XLP 4-pole
• Rated operational voltage: 550VAC
• Rated operational current: 160 - 630A
• Micro auxillary switches, 1 or 2 pcs per pole
• Single cable shroud per phase
• Cable clamps
• Front frames
• Padlocking
• Sealing facility
4
7
1SEC312011B0202 | EasyLine
Application
• General fuse protection in 4-pole power supply networks
with switching neutral.
•
Secondary power generators from public networks
Electronic Fuse Monitoring
3-pole
1SEB000018
The Electronic Fuse Monitoring (EFM) is a fuse blown indication device.
The EFM unit has an integrated potentional free relay (1NO, 1NC) for
remote signal/alarm. It will be automatically reset after the blown fuse
has been replaced and the green LED turns on again.
The matrix below show all possible cases of indication
Fuse status
Relay contacts
NO contact 13, 14
Green
NC contact 11, 12
Red
1. Closed
Open
Fuses OK
X
Fuses BLOWN
Closed
Open
Closed
5
X
X
X
2. Open
Fuses OK
X
X
Fuses BLOWN
X
X
Power supply to the EFM unit from phase L2 and L3
The fuse monitor is connected to the gripping lugs of the fuses.
NOTE : • NH fuses with insulated gripping lugs can not be used.
• The EFM unit requires that the supply side of the XLP
should be on top of the switch.
Technical data:
Min. operation voltage
290V -10%
Max. operation voltage
690V +10%
Operation temp. range
-25/+80C
Operation time
< 2 sec.
Power consumption
< 3VA
Uimp. over a blown fuse
12,3kV
Uimp. between phases
9,8kV
Uimp. between main circuit / relay contacts
9,8kV
Dielectric test voltage input/output
3,5kV / 50Hz / 1 minute
Electrostatic Discharge
EN 61000-4-2 +- 4kV
Electrical Fast Transient
EN 61000-4-4 +- 4kV
Conducted Fast Transient
EN 61000-4-6 10Vrms/150kHz-80MHz
Recommended cable size
AWG 22-12/0,2-2,5mm2
EMC tested
Yes
Relay:
Nominal current
8A
Max. switching voltage
240VAC, 24VDC
EasyLine | 1SEC312011B0202
8
Busbar Adapters
60mm for XLP00, XLP1, XLP2 and XLP3
6
60mm busbar system
Designed for 60 mm busbar distance
XLP00 and XLP1 use busbar Cu/Al 5 or 10mm x 10-30mm.
3 pieces of distance shoes for 5 mm busbars are included
with the adapter.
For XLP2 and XLP3 use busbar Cu/Al 5-10mm x 10-30mm.
The adapters are available for cable connection above (A) or
cable connection below (B).
Distribution system for standard Busbars type SF-60
The busbar system type SF-60 is designed to take busbars
of different cross sections, and it is type tested to VDE-0660,
section 50 and IEC 439-1.
9
1SEC312011B0202 | EasyLine
The SF-60 Busbar system features
Busbar width
10 - 30 mm
Busbar thickness
5 or 10 mm
Centre distance between busbars
60 mm
Cable connection supply module
Electrical data
690V / 440A
Cable connections
Al/Cu 35 - 120mm²
Dimension (W x H x D)
81 x 200 x 84 mm
Busbar Adapters
40mm for XLP00 and XLP1
40mm busbar system
Cu 12 x 5mm or 12 x 10mm.
Adapter 95 mm depth to busbars: A 40/95
40 mm Busbar system for Striebel & John switchboards
Specially designed for the Striebel & John Busbar system 250A and
360A.
Cu 12x5 or 12x10 mm.
Adapter 75 mm depth to busbars, cable connection below: A 40/75
Adapter 120 mm depth to busbars, cable connection below: A 40/120
1SEB000017
6
EasyLine | 1SEC312011B0202
10
Cable clamps & bolts
Conductor cross section min-max
Type of
clamp/bolt
Busbars
height/weight
(mm2)
Conductor
flexible
(mm2)
Rm/Sm
(mm2)
Re/Se
(mm2)
Torque
(Nm) 1)
Order code
1,5 -25
1,5 - 35
1,5 - 35
3,2
Incl. in the switch
Bridge clamp (BC)
1,5 - 35
1,5 - 50
1,5 - 50
3,5
1SEP407733R0001
Triple clamp (TC)
1,0 - 10
1,0 - 10
1,0 - 10
3,5
1SEP407787R0001
1,5 - 16
1,5 - 16
1,5 - 16
3,5
1SEP407732R0001
10
1SEP407811R0001
10
NHP 400940R0006
10
1SEP407733R0002
10
1SEP407732R0002
10
NHP 403631R0002
16
NHP 403625R0001
XLP000
Cage clamp (CC)
XLP00
Single prism clamp
(SPC)
Feeding clamp (FC)
for XLP00 - 6BC
7
Bolt M8x16 DIN933
25 - 50
25 - 70
25 - 70
25 - 70
25 - 95
25 - 95
20 x 4
Bolt M8x16 DIN933
Cable lug DIN46234
10 - 95
10 - 95
10 - 95
Bolt M8x16 DIN933
Cable lug DIN46235
16 - 70
16 - 70
16 - 70
16 - 70
16 - 95
16 - 95
16 - 70
16 - 95
16 - 95
XLP1
Bridge clamp (BC)
19 x 10
Single prism clamp
(SPC)
95 - 150
Doube prism clamp
(DPC)
95 - 150
2)
95 - 150
2x70 - 2x95
2x70 - 2x150
2x70 - 2x150
Bolt M10x20 DIN933
Cable lug DIN46234
10 - 240
10 - 240
10 - 240
Bolt M10x20 DIN933
Cable lug DIN46234
16 - 240
16 - 240
16 - 240
Bolt M10x20 DIN933
40 x 10
1) For correct Torque (Nm) values, study the installation description delivered with the devices
2) The Sm (sector shaped stranded) 150mm² have to be round formed before inserted in the Prism clamp
11
1SEC312011B0202 | EasyLine
Cable clamps & bolts
Conductor cross section min-max
Type of
clamp/bolt
Busbars
height/weight
(mm2)
Conductor
flexible
(mm2)
Rm/Sm
(mm2)
Re/Se
(mm2)
14 x 26
16-70 (M8x25)
300 (M8x40)
16-50 (M8x25)
185-300 (M8x40)
16-50 (M8x25)
185-300 (M8x40)
70 - 240
50 - 185
50 - 185
95 - 240
70 - 240
95 - 240
Torque
(Nm) 1)
Order code
14
1SEP407953R0001
14
1SEP407954R0001
22
1SEP407956R0001
XLP2 and 3
Bridge clamp
(BC)
Single prism clamp
(SPC)
Double Prism clamp
(DPC)
Bolt M12x30 DIN933
25 - 95
35 - 70
50- 70
2x35 - 2x120
2x35 - 2x150
2x35 - 2x50
2x50 - 2x185
7
50 x 12
25
Bolt M12x30 DIN933
Cable lug DIN46234
10 - 240
10 - 240
10 - 240
Bolt M12x30 DIN933
Cable lug DIN46235
16 - 300
16 - 300
16 - 300
NHP 403626R0001
1) For correct Torque (Nm) values, study the installation description delivered with the devices
Type tested according to standard: EN IEC 60947-1 and DIN VDE 0295.
Explanations:
Flexible:Multi stranded
Re:
Round solid
Se:
Sector shaped solid
Rm:
Round stranded
Sm:
Sector shaped stranded
EasyLine | 1SEC312011B0202
12
Technical Data
1-pole
XLP00
XLP2
XLP3
(V)
-
500
690
-
500
690
-
500
690
-
500
690
Rated operational voltage Ue DC
(V)
220
-
-
220
-
-
220
-
-
220
-
-
Rated operational current Ie
(A)
160
160
125
250
250
200
400
400
315
630
630
500
Thermal current with fuse-link Ith
(A)
Utilization category
160
160
160
250
250
250
400
400
-
630
630
-
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
Rated insulation voltage Ui
(V)
1000
1000
1000
1000
Rated impulse withstand voltage Uimp
(kV)
8
8
8
8
Rated conditional short circuit current
(kArms)
50
50
50
50
Rated frequency
(Hz)
50 - 60
50 - 60
50 - 60
50 - 60
Power loss (Ith) without fuselink, per phase
(W)
3,5
7,5
13
24
200
200
200
200
Electrical durability
Mechanical durability
Degree of protection from the front
according to IEC60529
1400
1400
800
800
Open
IP20
IP20
IP20
IP20
Closed
IP30
IP30
IP30
IP30
XLP00
XLP1
XLP2
XLP3
2-pole
8
XLP1
Rated operational voltage Ue AC
Rated operational voltage Ue AC
(V)
-
500
690
-
500
690
-
500
690
-
500
690
Rated operational voltage Ue DC
(V)
220
-
-
440
-
-
440
-
-
440
-
-
Rated operational current Ie
(A)
160
160
125
250
250
200
400
400
315
630
630
500
Thermal current with fuse-link Ith
(A)
160
160
160
250
250
250
400
400
-
630
630
-
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
DC22B
AC22B
AC21B
Utilization category
Rated insulation voltage Ui
(V)
1000
1000
1000
1000
Rated impulse withstand voltage Uimp
(kV)
8
8
8
8
Rated conditional short circuit current
(kArms)
50
50
50
50
Rated frequency
(Hz)
50 - 60
50 - 60
50 - 60
50 - 60
Power loss (Ith) without fuselink, per phase
(W)
3,5
7,5
13
24
Electrical durability
200
200
200
200
Mechanical durability
1400
1400
800
800
Open
IP20
IP20
IP20
IP20
Closed
IP30
IP30
IP30
IP30
Degree of protection from the front
according to IEC60529
13
1SEC312011B0202 | EasyLine
Technical Data
3-pole
XLP000
000
For NH fuse links acc. to IEC60269-2-1
XLP00
XLP1
XLP2
XLP3
00
1
2
3
max width = 21mm
Rated operational voltage Ue AC
(V)
400
500
690
400
500
690
500
80
100
50
125
160
125
250
690
500
200
400
690
500
315
630
690
Rated operational current Ie AC
(A)
Thermal current with fuse link Ith
(A)
100
160
250
400
630
Rated insulation voltage Ui
(V)
690
1000
1000
1000
1000
Rated impulse withstand voltage Uimp
(kV)
6
8
8
8
8
Rated conditional short circuit current
(kArms)
Rated making and breaking capacity
50
AC23B
AC22B
50
AC21B
AC23B
AC22B
50
AC21B
AC22B
500
50
AC21B
AC22B
50
AC21B
AC22B
AC21B
Rated frequency
(Hz)
50 - 60
50- 60
50 - 60
50 - 60
50 - 60
Power loss at Ith without fuse link/per phase
(W)
1,4W
3,5W
7,5W
13W
24W
Max allowed poweloss in the Fuse per phase
(W)
7,5W
12W
23W
30W
48W
Electrical durability
300
200
200
200
200
Mechanical durability
1700
1400
1400
800
800
Open
IP20
IP20
IP20
IP20
IP20
Closed
IP30
IP30
IP30
IP30
IP30
Degree of protection from the front acc. to
IEC60529
4-pole
XLP00
XLP1
XLP2
XLP3
Rated operational voltage Ue AC
500
500
500
500
Rated operational current Ie
160
250
400
630
Thermal current with fuse-link Ith
160
250
400
630
Utilization category
AC22B
AC22B
AC22B
AC22B
Rated insulation voltage Ui
(V)
1000
1000
1000
1000
Rated impulse withstand voltage Uimp
(kV)
8
8
8
8
Rated conditional short circuit current
(kArms)
50
50
50
50
Rated frequency
(Hz)
50 - 60
50 - 60
50 - 60
50 - 60
Power loss (Ith) without fuselink, per phase
(W)
3,5
7,5
13
24
Electrical durability
200
200
200
200
Mechanical durability
1400
1400
800
800
Open
IP20
IP20
IP20
IP20
Closed
IP30
IP30
IP30
IP30
Degree of protection from the front
according to IEC60529
EasyLine | 1SEC312011B0202
8
14
Ordering information
XLP 3-pole
Type
Item Description
Order code
Weight
(Kg)
0,46
XLP000
XLP000
XLP000-6CC
100A, incl. 6 Cage Clamps
1SEP201428R0001
XLP000-6CC in carton
100A, incl. 6 Cage Clamps in carton
1SEP201428R0002
XUP000-6CC
100A, Fuse Base, incl. 6 Cage Clamps
1SEP201432R0001
0,34
XLP00
160A without clamps or bolts
1SEP101890R0001
0,55
XLP00-6BC
160A, incl. 6 Bridge Clamps
1SEP101890R0002
0,63
XLP00-6BC-3M8
160A, incl. 6 Bridge Clamps and 3 x M8x16mm bolts
1SEP101890R8002
0,65
XLP00-6M8
160A, incl. 6 x M8x16mm bolts
1SEP101890R0004
0,63
XLP00-EFM-6BC
160A, incl. Electronic Fuse Monitoring and
6 Bridge Clamps
1SEP101890R0012
0,68
XLP00-MNS adapter-3BC
160A, incl. MNS adapter and 3 Bridge Clamps
1SEP101890R0402
0,88
XLP00-MNS adapter-EFM-3BC
160A, incl. MNS adapter, EFM and 3 Bridge Clamps
1SEP101890R0412
1,1
XLP00-A60/60-B-3BC-below
160A, incl. A60/60 adapter and 3 Bridge Clamps,
cable below
1SEP101916R0001
0,95
XLP00-A60/60-B-below
160A, incl. A60/60 adapter and cable below, without clamps or
bolts
1SEP101916R0002
0,95
XLP00-A60/60-A-3BC-above
160A, incl. A60/60 adapter and 3 Bridge Clamps,
cable above
1SEP101917R0001
0,95
XLP00-A40/95-B-3BC-below
160A, incl. A40/95 adapter and 3 Bridge Clamps,
cable below
1SEP101889R0002
1,1
XLP00-A40/75-B-3BC-below
160A, incl. A40/75 adapter and 3 Bridge Clamps,
cable below
1SEP101898R0002
1
XLP00-A40/75-B-3M8-below
160A, incl. A40/75 adapter and 3 x M8 bolts,
cable below
1SEP101898R0004
1
XLP00-A40/120-B-3BC-below
160A, incl. A40/120 adapter and 3 Bridge Clamps,
cable below
1SEP101899R0002
1,2
XLP00-A40/120-B-3M8-below
160A, incl. A40/120 adapter and 3 x M8x16mm bolts,
cable below
1SEP101899R0004
1,2
XLP00-A40/120-A-3BC-above
160A, incl. A40/120 adapter and 3 Bridge Clamps,
cable above
1SEP101899R0102
1,2
XLP00-A40/120-A-3M8-above
160A, incl. A40/120 adapter and 3 x M8 bolts,
cable above
1SEP101899R0104
1,2
XLP1
250A without clamps or bolts
1SEP101891R0001
1,6
XLP1-6BC
250A, incl. 6 Bridge Clamps
1SEP101891R0002
1,8
XLP1-6M10
250A, incl. 6 x M10 bolts
1SEP101891R0004
1,8
XLP1-EFM-6BC
250A, incl. Electronic Fuse Monitoring and
6 Bridge Clamps
1SEP101891R0012
1,97
XLP00
XLP00
9
XLP1
XLP1
15
1SEC312011B0202 | EasyLine
Ordering information
XLP 3-pole
Order code
Weight
(Kg)
250A, incl. A60/85 adapter and 3 Bridge Clamps,
cable below
1SEP101918R0001
2,47
XLP1-A60/85-A-3BC-above
250A, incl. A60/85 adapter and 3 Bridge Clamps,
cable above
1SEP101919R0001
2,47
XLP1-A40/120-A-3BC-above
250A, incl. A40/120 adapter and 3 Bridge Clamps,
cable above
1SEP101912R0002
2,8
XLP1-A40/120-A-3M10-above
250A, incl. A40/120 adapter and 3xM10x20mm bolts,
cable above
1SEP101912R0004
2,75
XUP1
250A Fuse Base without clamps or bolts
1SEP101895R0001
1,1
XUP1-6BC
250A, Fuse Base incl. 6 Bridge Clamps
1SEP101895R0002
1,3
XLP2
400A without clamps or bolts
1SEP101892R0001
2,5
XLP2-6BC
400A, incl. 6 Bridge Clamps
1SEP101892R0002
3,02
XLP2-EFM-6BC
400A, incl. Electronic Fuse Monitoring and 6 Bridge Clamps
1SEP101892R0012
3,2
XLP2-A60/120-A-above
400A, incl. A60/120 adapter, cable above without clamps or
bolts
1SEP102285R0001
4,9
XLP2-A60/120-B-below
400A, incl. A60/120 adapter, cable below without clamps or
bolts
1SEP102286R0001
4,9
XUP2
400A, Fuse Base without clamps or bolts
1SEP101974R0001
XLP3
630A without clamps or bolts
1SEP101975R0001
3,7
XLP3-6BC
630A, incl. 6 Bridge Clamps
1SEP101975R0002
4,25
XLP3-EFM-6BC
630A, incl. Electronic Fuse Monitoring and
6 Bridge Clamps
1SEP101975R0012
4,4
XLP3-A60/120-A-above
630A, incl. A60/120 adapter, cable above without clamps or
bolts
1SEP102287R0001
7,4
XLP3-A60/120-B-below
630A, incl. A60/120 adapter, cable below without clamps or
bolts
1SEP102288R0001
7,4
Type
Item Description
XLP1-A60/85-B-3BC-below
XLP1
XLP2
XLP2
XLP3
XLP3
EasyLine | 1SEC312011B0202
9
16
Ordering information
XLP 1- and 2-pole
Type
Item Description
Order code
Weight
(Kg)
1-pole
XLP_-1P
XLP00-1P
160A without clamps or bolts
1SEP600113R0001
0,24
XLP00-1P-2BC
160A, incl. 2 Bridge Clamps
1SEP600113R0002
0,28
XLP00-1P-2M8
160A, incl. 2 x M8 bolts
1SEP600113R0003
0,26
XLP1-1P
250A without clamps or bolts
1SEP600116R0001
0,70
XLP1-1P-2BC
250A, incl. 2 Bridge Clamps
1SEP600116R0002
0,82
XLP1-1P-M10
250A, incl. M10 bolts
1SEP600116R0003
0,76
XLP2-1P
400A without clamps or bolts
1SEP600122R0001
1,06
XLP2-1P-2BC
400A, incl. 2 Bridge Clamps
1SEP600122R0002
1,25
XLP3-1P
630A without clamps or bolts
1SEP600126R0001
1,87
XLP3-1P-2BC
630A, incl. 2 Bridge Clamps
1SEP600126R0002
2,20
XLP00-2P
160A without clamps or bolts
1SEP600114R0001
0,53
XLP00-2P-4BC
160A, incl. 4 Bridge Clamps
1SEP600114R0002
0,61
XLP00-2P-4M8
160A, incl. 4 x M8 bolts
1SEP600114R0003
0,57
XLP1-2P
250A without clamps or bolts
1SEP600117R0001
1,63
XLP1-2P-4BC
250A, incl. 4 Bridge Clamps
1SEP600117R0002
1,87
XLP1-2P-4M10
250A, incl. 4 x M10 x 20 bolts
1SEP600117R0003
1,75
XLP2-2P
400A without clamps or bolts
1SEP600123R0001
2,32
XLP2-2P-4BC
400A, incl. 4 Bridge Clamps
1SEP600123R0002
2,7
XLP3-2P
630A without clamps or bolts
1SEP600127R0001
3,95
XLP3-2P-4BC
630A, incl. 4 Bridge Clamps
1SEP600127R0002
4,5
2-pole
XLP_-2P
9
17
1SEC312011B0202 | EasyLine
Ordering information
XLP 4-pole
Type
Item Description
Order code
Weight
(Kg)
4-pole
XLP00-4P
160A without clamps or bolts
1SEP600115R0001
0,83
XLP00-4P-8BC
160A, incl. 8 Bridge Clamps
1SEP600115R0002
0,99
XLP00-4P-8M8
160A, incl. 8 x M8 bolts
1SEP600115R0003
0,91
XLP1-4P
250A without clamps or bolts
1SEP600119R0001
2,50
XLP1-4P-8BC
250A, incl. 8 Bridge Clamps
1SEP600119R0002
2,98
XLP1-4P-8M10
250A, incl. 8 x M10 x 20 bolts
1SEP600119R0003
2,74
XLP2-4P
400A without clamps or bolts
1SEP600124R0001
3,87
XLP2-4P-8BC
400A, incl. 8 Bridge Clamps
1SEP600124R0002
4,5
XLP3-4P
630A without clamps or bolts
1SEP600128R0001
6,47
XLP3-4P-8BC
630A, incl. 8 Bridge Clamps
1SEP600128R0002
7,5
XLP_-4P
9
EasyLine | 1SEC312011B0202
18
Ordering tables
Accessories
Common accessories
Type
1
2
Weight
(Kg)
1
Micro auxilliary switch (not for XLP000)
1SEP407742R0001
0,01
2
Auxiliary switch NC
1SEP407742R0002
0,02
Auxiliary switch NO
1SEP407742R0003
0,02
3
Padlock device
1SEP407786R0001
0,005
4
XLP00 Bolt (M8) w/washer, kit including 3 x Bolts M8x16 mm with washer
NHP 400940R0006
0,04
XLP1 Bolt (M10) w/washer, kit including 3 x Bolts M10x20 mm with washer
NHP 403625R0001
0,09
XLP2/3 Bolt (M12) w/washer, kit including 3 x Bolts M12x30 mm with washer
NHP 403626R0001
0,18
XLP1 Double Prisme Clamp, for cable 2 x 70 - 150mm²
NHP 403631R0002
0,15
Order code
Weight
(Kg)
XLP000 Front cover ( spare part )
1SEP304222R0001
0,12
XLP000 Micro auxiliary switch
1SEP408738R0001
0,01
XLP000 DIN rail snap on kit - Qty. 1 pc
1SEP407740R0001
0,006
XLP000 DIN rail snap on kit - Qty. 10 pc
1SEP407740R0010
0,6
XLP000 Frontframe for 1 XLP000
1SEP407741R0001
0,02
XLP000 Frontframe for 2 XLP000
1SEP407741R0002
0,025
XLP000 Frontframe for 3 XLP000
1SEP407741R0003
0,03
3
5
4
Order code
Accessories XLP000 - 3-pole
5
Type
6
6
7
7
Accessories XLP00 - 3-pole
9
Order code
Weight
(Kg)
XLP00 Front cover ( spare part )
1SEP101873R0001
0,17
XLP00 A60/60 Adapter above, for 60 mm busbar distance, 5 or 10 mm, cable above
1SEP101910R0001
0,38
XLP00 A60/60 Adapter below, for 60 mm busbar distance, 5 or 10 mm, cable below
1SEP101915R0001
0,38
XLP00 A40/75 Adapter above/below, for 40 mm busbarsystem Striebel & John, cable
above or below
1SEP101909R0001
XLP00 A40/120 Adapter above/below, for 40 mm busbarsystem Striebel & John, cable
above or below
1SEP101909R0002
Type
8
9
XLP00 Front cover with EFM (Electronic Fuse Monitoring)
1SEP101873R0007
9
XLP00 Front fixing bracket with front frame
1SEP201534R0001
7
XLP00 Frontframe for 1 XLP00
1SEP407792R0001
0,02
XLP00 Frontframe for 2 XLP00
1SEP407792R0002
0,03
XLP00 Frontframe for 3 XLP00
1SEP407792R0003
0,04
XLP00 ABB-INS Frontframe for 1 XLP00
1SEP407792R0004
0,02
XLP00 ABB-INS Frontframe for 2 XLP00
1SEP407792R0005
0,03
XLP00 Cable shroud
1SEP407793R0001
0,03
XLP00 Snap for double DIN rail
1SEP407897R0001
0,24
10
XLP00 Bridge Clamp ( 3-BC ), for cable 1,5 - 50mm²
1SEP407733R0001
0,04
11
XLP00 Triple Clamp ( 3-TC ), for cable 1,0 - 10mm²
1SEP407787R0001
0,15
12
XLP00 Single Pris.Clamp ( 3-SPC ), for cable 1,5 - 70mm²
1SEP407732R0001
0,09
13
XLP00 Feeding Clamp ( 3-FC ), for cable 25 - 95 mm²
1SEP407811R0001
0,29
10
11
8
12
13
19
1SEC312011B0202 | EasyLine
0,09
Ordering tables
Accessories
Order code
Weight
(Kg)
XLP1 Front cover (spare part)
1SEP101883R0001
0,5
XLP1 A60/85 Adapter above, 60mm busbar distance, 5 or 10mm cable, above
1SEP201451R0001
0,74
XLP1 A60/85 Adapter below, 60mm busbar distance, 5 or 10mm cable, below
1SEP201456R0001
0,74
Type
Accessories XLP1 - 3-pole
14
15
XLP1 Front cover with EFM (Electronic Fuse Monitoring)
1SEP101883R0007
0,37
14
XLP1 Frontframe for 1 XLP1
1SEP407815R0001
0,04
15
XLP1 Frontframe for 2 XLP1
1SEP407815R0002
0,06
16
XLP1 Cable shroud
1SEP407793R0002
0,1
17
XLP1 Bridge Clamp (3-BC), for cable 16 - 95mm²
1SEP407733R0002
0,11
18
XLP1 Single Prisme Clamp (3-SPC) , for cable 16-185mm²
1SEP407732R0002
0,17
Accessories XLP2/3 - 3-pole
16
17
19
XLP2 Front cover ( spare part )
1SEP101982R0001
0,65
14
XLP2 Frontframe for 1 XLP2
1SEP407951R0001
0,04
15
XLP2 Frontframe for 2 XLP2
1SEP407951R0002
0,06
XLP2 Front cover with EFM (Electronic Fuse Monitoring)
1SEP101982R0007
0,25
XLP3 Front cover ( spare part )
1SEP101984R0001
0,9
XLP3 Frontframe for 1 XLP3
1SEP407955R0001
0,055
XLP3 Front cover with EFM (Electronic Fuse Monitoring)
1SEP101984R0007
0,35
16
XLP2/3 Cable shroud
1SEP407952R0001
0,18
17
XLP2/3 Bridge Clamp (3-BC), for cable 35 - 300mm²
1SEP407953R0001
0,26
18
XLP2/3 Single Pris. Clamp (3-SPC), for cable 25 - 240mm²
1SEP407954R0001
0,5
19
XLP2/3 Double Pris. Clamp (3-DPC), for cable 2 x 35 - 150mm² (sm)
1SEP407956R0001
0,36
Busbar carrier 3-pole, for busbar 5-10 x 10-30mm
GHV 240849R0001
0,17
Cable connection supply module,
for busbar 5-10 x 10-30mm or cable 35 - 120mm²
GHV 240849R0034
0,62
18
SF-60 Busbar system
20
9
20
EasyLine | 1SEC312011B0202
20
Ordering tables
Accessories XLP 1-, 2- and 4-pole
Order code
Weight
(Kg)
XLP00-1P Cable Shroud For 1- and 2-Pole and N at the 4-Pole
1SEP618708R0001
0,02
XLP1-1P Cable Shroud For 1- and 2-Pole and N at the 4-Pole
1SEP618709R0001
0,07
XLP2/3-1P Cable Shroud For 1- and 2-Pole and N at the 4-Pole
1SEP618710R0001
0,13
XLP00 Triple Clamp (1-TC) 1,0-10mm2
1SEP407787R0010
0,08
XLP00 Single Pris.Clamp (1-SPC) 1,5-70mm2
1SEP407732R0010
0,05
XLP1 Single Pris.Clamp (1-SPC) 16-185mm2
1SEP407732R0011
0,09
XLP23 Sing.Pris.Clamp (1-SPC) 25-240mm2
1SEP407954R0010
0,25
XLP23 Dou.Pris.Clamp (1-DPC) 35-185mm2
1SEP407956R0010
0,35
XLP00 1P Front Frame f/1 Apparatus
1SEP407792R0011
0,01
XLP00 1P Front Fr. f/2 1P, f/1 2P Apparatus
1SEP407792R0012
0,02
XLP00 4P Front Frame f/1 Apparatus
1SEP407792R0041
0,02
XLP00 4P Front Frame f/2 Apparatus
1SEP407792R0042
0,04
XLP00 4P Front Frame f/3 Apparatus
1SEP407792R0043
0,05
XLP1 1P Front Frame f/1 Apparatus
1SEP407815R0011
0,03
XLP1 1P Front Fr. f/2 1P, f/1 2P Apparatus
1SEP407815R0012
0,04
XLP1 4P Front Frame f/1 Apparatus
1SEP407815R0041
0,05
XLP1 4P Front Frame f/2 Apparatus
1SEP407815R0042
0,07
XLP2 1P Front Frame f/1 Apparatus
1SEP407951R0011
0,28
XLP2 1P Front Fr. f/2 1P, f/1 2P Apparatus
1SEP407951R0012
0,32
XLP2 4P Front Frame f/1 Apparatus
1SEP407951R0041
0,48
XLP3 1P Front Frame f/1 Apparatus
1SEP407955R0011
0,04
XLP3 2P Front Frame f/1 Apparatus
1SEP407955R0021
0,05
XLP3 4P Front Frame f/1 Apparatus
1SEP407955R0041
0,07
Type
9
21
1SEC312011B0202 | EasyLine
Dimensional drawings
XLP000
XLP000
1SEB000001
10
EasyLine | 1SEC312011B0202
22
Dimensional drawings
XLP00 and XLP1
XLP00
1SEB000307
XLP1
10
1SEB000308
1SEB000311
23
1SEC312011B0202 | EasyLine
Dimensional drawings
XLP2 and XLP3
XLP2
1SEB000309
XLP3
10
EasyLine | 1SEC312011B0202
24
Dimensional drawings
Busbar Adapters XLP00
1SEB000006
XLP00 – A40/75
1SEB000117
XLP00 – A40/95
XLP00 – A40/120
5-10
25
1SEC312011B0202 | EasyLine
1SEB000007
105
1SEB000007
23
33
93
60
209
202
74
60
126
(103)
44
59
14
9
135
16
XLP00 – A60/60
10-30
1SEB000005
10
Dimensional drawings
Busbar Adapters XLP1
XLP1 – A60/85
30
5-10
27
1SEB000010
69
60
265
60
45
158
(134 )
84
50
10-30
220
185
XLP1 – A40/120
30
124
40
40
265
112
146
10
118
1SEB000019
196
167
48
13
220
185
EasyLine | 1SEC312011B0202
26
Dimensional drawings
Busbar Adapters XLP2 and XLP3
XLP2 – A60/120
59
24
210
10-30
289
84
60
118
197
(167)
60
49
5-10
XLP3 – A60/120
7,9
111,3
10-30
5-10
106,3
60,0
337,6
60,0
122,5
(176)
205,8
53,3
249,0
10
XLP3 A60/120 Below
XLP3 A60/120 Above
27
1SEC312011B0202 | EasyLine
5-10
10-30
60,0
125,4
60,0
348,7
(176)
122,1
204,8
53,7
90,2
2,0
11,1
249,0
Dimensional drawings
Front frames
XLP00
XLP1
Double 406
Single
220
176
5
176
5
2
4
5
9
1,5
4
13,5
17,5
1SEB000011
39
86
222,5
62
5,5
265
1SEB000013
1SEB000012
XLP000
28
158
158
185
10
371
XLP2
8,5
2,5
61
1,5
XLP3
20
99
5,5
211
246
1SEB000015
17,5
1SEB000014
43,75
2
4,5
182,5
21,25
287
244,5
62
3
EasyLine | 1SEC312011B0202
28
ABB AS
Low Voltage Products
P.O.Box 100, Sentrum
N-3701 Skien, Norway
http://new.abb.com/low-voltage
Note: We reserve the right to make technical changes or
modify the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars shall
prevail. ABB AS does not accept any responsibility whatsoever
for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents – in whole or in parts –
is forbidden without prior written consent of ABB AS.
Copyright © 2016 ABB
All rights reserved
© Copyright ABB. 1SEC312011B0202 - 2016.02
Contact us
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising