iQ Star LYRA chilled beam cassette

iQ Star LYRA chilled beam cassette
iQ Star LYRA chilled beam cassette
iQ Star LYRA chilled beam cassette
Key features
Ventilation
Heating and cooling
Compact chilled beam
Adjustable induction
Flow pattern control
Integrated control
The LYRA chilled beam cassette is a compact chilled beam for ventilation,
cooling and heating. It provides comfort with low air velocities in the room by
mixing the supply air with the ambient air. LYRA diffuses air in 4 directions.
This gives a high cooling effect. It is available with comfort control - Fläkt
Woods adjustable induction-and flow pattern control. These two features give
high flexibility. LYRA is equipped with Coanda Safety Control. This function
is necessary if a low air flow setting is used, to guarantee an optimal indoor
climate. LYRA can also be supplied with integrated control to offer a plug and
play system.
Quick Selection
Specifications
Compact chilled beams for
installation flush into false ceiling or
suspended from soffit
2 or 4 pipes coil for cooling or
cooling and heating
Equipped with comfort control:
adjustable induction which enables
1 to 4 diffusion directions which
enables 1 to 4 diffusion directions’
with ‘for each side enabling
asymmetric throw
Flow pattern control to adjust the
diffusion angle in each side
Available in two lengths, 600 mm
and 1200 mm
Low noise level
Integrated control for a simple
installation
Product code example
The diagram shows the approximate cooling power Ptot in W with water
flow qw=0.05 l/s, temperature difference between room air and supply air
Δt=10 °C . Temperature difference between mean water temperature and
room temperature, Δt=8 °C . Total air pressure drop 70 Pa .
Fläkt Woods
9327 GB 2016.06.10
1 (13)
Cassette chilled beam
IQCB-060-12-1-01-0
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Product version and function
The LYRA chilled beam cassette is designed for
installation in false ceilings, and its dimensions fit a 600
mm false ceiling module.
This regards both its length and height, which means that
the product must be installed completely flush with the
ceiling. If the LYRA chilled beam cassette is equipped
with the accessory IQAZ-33, it can be freely suspended
from the ceiling.
The LYRA chilled beam cassette is equipped with comfort
control and has control equipment as an accessory. This
combination provides high flexibility for dimensioning
the indoor climate. The air flow can be adjusted with
levers (comfort control) by changing the number of
open nozzles in the air duct. This is easily done during
commissioning. The adjustable nozzles offer a choice of
air distribution options (1-way, 2-way, 3-way and 4-way).
This easy adjustment of air distribution and capacity
makes it easy to adapt the system to changing conditions.
On delivery, the standard beam has the maximum
number of nozzles open as default (nozzle 3). The LYRA
chilled beam cassette is equipped with Coanda Safety
Control (CSC). It can be varied between high effect mode
(front in lowest position) and normal effect mode (front in
highest position). CSC should be used with low air flows
to ensure that the air stream adheres to the ceiling. High
effect mode is obtained when the front is in the lowest
position. This mode should not be used below 50 Pa.
To achieve optimal air distribution into the room, and
full flexibility, tool free air flow adjustment is available
for each side. Levers located at each side enables fast
and simple air flow adjustment without the need for
additional tools.
From shut off position, low, medium and high setting
are available with 3 nozzle positions, boost setting with
4 nozzle positions and fixed boost setting fixed to 1
position.
Fixed boost setting requires no nozzle adjustment and
offers higher airflows at quieter noise levels.
Tool free nozzle settings for LYRA - low, medium and
high airflow.
Material and surface finish
The casing mainly consists of galvanized steel sheet. The
front panel has a white powder-coated finish. Standard
colour RAL 9010, equivalent to NCS 0502-Y, gloss level 30.
Tool free nozzle settings for LYRA - boost airflow.
Coil in copper with connector Øy = 15 mm and
aluminium fins. Max. working pressure 1.6 MPa.
Instructions
Instructions for installation, adjustment and maintenance
are delivered with each product. Instructions can also be
accessed via ExSelAir.
Technical data and dimensions
For full dimension data, use Fläkt Woods product
selection program ExSelAir.
Airflow with different nozzle settings.
For further information, contact our nearest sales office.
Web address, ExSelAir http://exselair.flaktwoods.com/
Comfort control
LYRA is available with 5 different air flow settings: low,
medium, high, boost and fixed boost.
Air flow in l/s at 70 Pa
Low airflow
Medium airflow
High airflow
Boost airflow, Ø125, with CC
Boost airflow, Ø160, with CC
Fixed boost flow, Ø125
Fixed boost airflow, Ø160
Fläkt Woods
9327 GB 2016.06.10
60 x 60
4 - 12
6 - 17
8 - 22
25 - 39
39
-
60 x 120
8 - 21
11 - 29
14 - 35
38 - 52
52 - 67
61
2 (13)
Flow Pattern Control - FPC
The FPC (Flow Pattern Control) is a function that
makes LYRA highly flexible. It is the FPC function
combined with comfort control that gives LYRA its
unique characteristics. Fläkt Wood's FPC function allows
the air flow to be directed at different angles. It is very
easy to adjust and change the air flow direction.
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
45°
15°
30°
1-2-3
15°
To adjust the front panel, pull or push it so that it snaps
into position.
45°
30°
1-2-3
The image below shows an installation where air
direction is set to 30 ° in two directions and the airflow is
set with comfort controls to the same nozzle on each side
of a size 120. This installation options provide an efficient
and comfortable air throughout the room.
The image below shows an installation where a high
airflow is needed. Comfort control is still set to the same
nozzle at each side, but the flaps set to 30 ° in the direction
of two neighboring beams.
Freely suspended
LYRA can be adapted for freely suspended installation.
This is done by ordering the accessory IQAZ-33, which
consists of a casing and a front plate adapter. This
accessory is fitted on the cassette while the cassette is
suspended from the ceiling.
In the freely suspended version, the air outlet is specially
designed to direct the air flow slightly upwards. This
reduces the air velocity in the occupied zone and ensures
that air from the room mixes with the chilled air before it
reaches the occupied zone.
Coanda Safety Control (CSC), Freely
suspended
Directing the air upwards also creates the Coanda effect
without needing to rely on nearby surfaces.
Coanda Safety Control (CSC)
Coanda Safety Control (CSC) is a function that maintains
the Coanda effect (adhesion of the air to the ceiling) while
simultaneously ensuring the highest possible cooling
power. This is done by adjusting the position of the front
panel.
At low flows and pressures, it may be necessary to adjust
the front panel to its highest position to keep the coanda
effect.
At high flows and pressure, the Coanda effect is easily
maintained, so the front panel can be set in its lowest
position, which increases the cooling and heating power
by approximately 5-10%.
Fläkt Woods
9327 GB 2016.06.10
3 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
A duct enclosure for concealing water pipes and air ducts
to the cassette unit is also available as an accessory with
three ranges of size:
• 30 to 50 cm
• 50 to 90 cm
• 90 to 170 cm
Suspension of the chilled beam
Installation with fastening bracket QFAZ-18
A suspension bracket facilitates the suspension of chilled
beams from the ceiling. Two brackets are used for each
beam. The brackets can be ordered in advance or along
with the chilled beam. The suspension brackets can be
fitted directly to the ceiling or onto channel support bars.
The chilled beam is simply attached by pressing it against
the bracket until it clicks into place. No tools are needed.
After this, the chilled beam can be adjusted lengthwise
by sliding the bracket along the beam's fastening points.
To adjust it sideways, slide the threaded bars along the
grooves in the bracket.
Installation of chilled beam with wire QFAZ-23-01-01
The chilled beam cassette can also be suspended with
wires. In this case, the beam's height is easily adjusted
with a stepless fastening device. This type of installation is
suitable for metal or concrete ceilings. Alternately, a wire
can simply be wound round a bar in the ceiling. A special
concrete fastener for concrete ceilings is included in every
kit.
With the lock system it is easy to adjust the height
installation of the chilled beam.
Fläkt Woods
9327 GB 2016.06.10
4 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Integrated control
LYRA is available with integrated control by ordering the
accessory STRZ-75. The room controller can be positioned
in three different locations depending on the desired level
of accessibility.
Actuators and valves are fixed on LYRA in factory. It
is delivered with push–on connections. A very simple
operation allows the installer to connect it with no risk
of leakage. The valves are factory wired. Lyra integrated
control offers Modbus or Bacnet communication as
standard.
In option
• Condensation sensor mounted and wired
• Specific connection unit dedicated to IPSUM
From the room controller, it is possible to make the
commissioning, increase and decrease temperature and
display main information (see STRA-14 catalogue for
detailed information)
Room controller on side
The room controller is factory mounted on the short side
of LYRA and wired. This configuration uses an external
temperature sensor installed below the coil. Temperature
and condensation (in option) sensor are factory wired.
Loose delivered room controller
The room controller is loose delivered. This configuration
used the temperature sensor built into the room
controller. A 5m cable is pre-wired to the room controller.
On site, installer needs to connect this cable to the
connection unit placed on the side of LYRA.
Condensation sensor (in option) is factory wired.
Room controller on front plate
The room controller is factory mounted on the front
plate of LYRA and wired. This configuration uses
the temperature sensor built into the room controller.
Condensation sensor (in option) is factory wired.
The controller has 2 postions to be always flush with the
front plate (when coanda safety control function is used).
Fläkt Woods
9327 GB 2016.06.10
5 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Table 6: LYRA-120 – low airflow, Ø125, Water flow 0.05 l/
s, Pressure drop water ∆p = 9 kPa
Performance
Cooling
Table 1: LYRA-060 – low airflow, Ø125, Water flow 0.05 l/
s, Pressure drop water ∆p = 5 kPa
Nozzle Pressure
1
2
3
1
2
3
[Pa] 70
70
70
100
100
100
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
[l/s] 6
8
10
4.1 168 208 248
7.8 272 332 391
12.5 380 457 534
5.3 211 260 309
9.5 329 400 472
14.9 455 547 639
Q
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A) 119 159 199 <20
179 238 298 <20
230 307 384 <20
147 196 245 <20
215 286 358 <20
276 368 460 <20
Table 2: LYRA-060 – medium airflow, Ø125, Water flow
0.05 l/s, Pressure drop water ∆p = 5 kPa
Nozzle Pressure
1
2
3
1
2
3
[Pa] 70
70
70
100
100
100
Q
[l/s] 5.9
10.8
17.4
7.3
12.9
20.7
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
210 256 302
343 414 485
477 567 656
256 313 369
408 493 577
561 665 770
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A) 139 185 231 <20
213 284 355 <20
269 358 448 <20
169 225 281 <20
254 338 423 <20
313 417 521 <20
Table 3: LYRA-060 – high airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 5 kPa
Nozzle Pressure
1
2
3
1
2
3
[Pa]
70
70
70
100
100
100
Q
[l/s] 8.2
14.2
22.1
10.2
16.9
26.3
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
262 316 371
417 499 582
548 642 736
321 387 454
493 590 687
649 760 871
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A)
164 218 273 <20
247 329 411 <20
283 377 471 <20
199 265 331 <20
290 387 484 <20
333 444 555 22
Table 4: LYRA-060 – boost airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 5 kPa
Nozzle Pressure
1
2
3
4
1
2
3
4
[Pa]
70
70
70
70
100
100
100
100
Q
[l/s] 25.2
30.3
34.5
39.4
30.1
36.1
41
46.7
Ptot [W]
Pcoil [W]
dT
dT
dT
dT
dT
dT
LA10
[°C] [°C] [°C] [°C] [°C] [°C]
6
8
10
6
8
10 dB(A)
499 564 630 196.5 262 327 25
613 697 780 250 333 416 26
704 801 898 290 387 484 28
781 884 986 308 411 514 30
593 670 747 232 309 386 31
736 837 938 303 404 505 32
844 961 1078 352 469 586 34
949 1078 1208 388 518 647 36
Q
[Pa] 70
100
[l/s] 39
46
Fläkt Woods
dT
[°C]
6
783
921
Ptot [W]
dT
dT
[°C]
[°C]
8
10
889 994
1043 1166
dT
[°C]
6
317
367
9327 GB 2016.06.10
1
2
3
1
2
3
[Pa] 70
70
70
100
100
100
Pcoil [W]
dT
dT
LA10
[°C]
[°C]
8
10 dB(A) 422 528
28
489 611
34
6 (13)
Q
[l/s] 8.2
14.0
20.9
10.0
16.8
24.9
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
282 409 438
439 629 670
587 834 879
348 499 537
530 757 808
699 993 1046
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A) 233 311 389 <20
346 461 576 <20
437 583 729 <20
284 379 474 <20
416 555 694 <20
521 694 868 <20
Table 7: LYRA-120 – medium airflow, Ø125, Water flow
0.05 l/s, Pressure drop water ∆p = 9 kPa
Nozzle Pressure
1
2
3
1
2
3
[Pa] 70
70
70
100
100
100
Q
[l/s] 10.9
19.3
28.7
13.2
23.0
34.2
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
330 477 503
540 779 813
711 1014 1046
401 576 610
649 935 979
838 1196 1231
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A) 260 346 433 <20
410 547 684 <20
503 670 838 <20
314 418 523 <20
494 659 824 <20
590 786 983 23
Table 8: LYRA-120 – high airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 9 kPa
Nozzle Pressure
1
2
3
1
2
3
[Pa] 70
70
70
100
100
100
Q
[l/s] 14.4
24.1
35.3
17.4
28.8
42.1
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
417 598 630
647 925 965
826 1172 1200
509 724 766
766 1097 1142
972 1380 1409
Pcoil [W]
dT
dT
dT
LA10
[°C] [°C] [°C]
6
8
10 dB(A) 319 425 531 <20
477 636 795 <20
561 748 935 22
386 515 644 <20
563 751 939 <20
656 875 1094 28
Table 9: LYRA-120 – boost airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 9 kPa
Nozzle Pressure
1
2
3
4
1
2
3
4
[Pa]
70
70
70
70
100
100
100
100
Q
[l/s] 38
43.1
47.2
51.7
45.3
51.3
56.2
61.5
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
815 935 1055
967 1117 1267
1073 1242 1411
1154 1332 1510
990 1139 1287
1171 1357 1542
1300 1509 1718
1405 1628 1850
Pcoil [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
359 479 598
450 600 750
507 676 845
534 712 890
446 595 744
556 741 926
656 835 1044
667 890 1112
LA10
dB(A)
27
31
33
35
33
36
38
40
Table 10: LYRA-120 – boost airflow, Ø160, Water flow
0.05 l/s, Pressure drop water ∆p = 9 kPa
Nozzle Pressure
Table 5: LYRA-060 – Fixed boost airflow, Ø125, Water
flow 0.05 l/s, Pressure drop water ∆p = 5 kPa
Pressure
Nozzle Pressure
1
2
3
4
1
2
3
4
[Pa]
70
70
70
70
100
100
100
100
Q
[l/s] 52.4
57.4
61.9
67.5
62.5
68.4
73.7
80.4
Ptot [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
1015 1144 1272
1157 1314 1470
1258 1430 1601
1334 1509 1683
1229 1389 1548
1398 1591 1783
1547 1767 1988
1699 1944 2188
Pcoil [W]
dT
dT
dT
[°C] [°C] [°C]
6
8
10
386 515 644
468 625 781
515 687 859
524 699 874
479 639 799
577 770 962
662 883 1103
734 979 1224
LA10
dB(A)
34
35
35
37
39
40
41
41
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Table 11: LYRA 120 - Fixed boost airflow, Ø160,
Waterflow 0.05 l/s, Pressure drop water ∆p = 9 kPa
Pressure
Q
[Pa]
70
100
[l/s]
60.6
72.1
dT
[°C]
6
614
701
Ptot [W]
dT
dT
[°C]
[°C]
8
10
1546 1024
1799 2033
dT
[°C]
6
614
701
Table 17: LYRA-120 – low airflow, Water flow 0.05 l/s,
Pressure drop water ∆p = 10 kPa
Pcoil [W]
dT
dT
LA10
[°C]
[°C]
8
10 dB(A) 819 1024 28
934 1168 34
Heating
Table 12: LYRA-060 – low airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 6 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s]
4.1
7.8
12.5
5.3
9.5
14.9
dT [°C]
10
147
201
247
174
233
284
Pcoil [W]
dT [°C]
dT [°C]
15
20
221
294
302
402
371
494
261
348
350
466
426
568
LA10
dB(A)
<20
<20
<20
<20
<20
<20
Table 13: LYRA-060 – medium airflow, Ø125, Water flow
0.05 l/s, Pressure drop water ∆p = 6 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s]
5.9
10.7
17.2
7.3
12.8
20.5
dT [°C]
10
169
234
278
199
266
312
Pcoil [W]
dT [°C]
dT [°C]
15
20
254
338
351
468
417
556
299
398
399
532
468
624
LA10
dB(A)
<20
<20
<20
<20
<20
<20
Table 14: LYRA-060 – high airflow, Ø125, Water flow 0.05
l/s, Pressure drop water ∆p = 6 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s]
8.4
14.1
22.1
10.2
16.9
26.3
Pcoil [W]
dT [°C]
dT [°C]
dT [°C]
10
15
20
191
287
382
262
393
524
299
449
598
222
333
444
300
450
600
439
659
878
LA10
dB(A)
<20
<20
<20
<20
<20
22
Table 15: LYRA-060 – boost airflow, Ø125, Water flow
0.05 l/s, Pressure drop water ∆p = 6 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
4
70
1
100
2
100
3
100
4
100
Q
[l/s]
25.2
30.3
34.5
39.4
30.1
36.1
41
46.7
dT [°C]
10
209
263
297
313
244
303
339
367
Pcoil [W]
dT [°C]
dT [°C]
15
20
314
419
395
527
445
593
470
627
366
488
454
605
508
677
550
733
LA10
dB(A)
25
26
28
30
31
32
34
36
Table 16: LYRA 060 - Fixed boost airflow, Ø125, Water
flow 0.05 l/s, Pressure drop water ∆p = 6 kPa
Pressure
[Pa] 70
100
Fläkt Woods
Q
[l/s] 38.9
46.2
dT [°C]
10
346
384
Pcoil [W]
dT [°C]
15
519
576
9327 GB 2016.06.10
dT [°C]
20
692
768
Nozzle Pressure
[Pa] 1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s] 8.2
14.0
20.9
10.0
17.8
24.9
dT [°C]
10
292
401
490
342
461
572
Pcoil [W]
dT [°C]
dT [°C]
15
20
438
584
602
802
735
980
513
684
692
922
858
1144
LA10
dB(A) <20
<20
<20
<20
<20
<20
Table 18: LYRA-120 – medium airflow, Water flow 0.05 l/
s, Pressure drop water ∆p = 10 kPa
Nozzle Pressure
[Pa] 1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s] 10.9
19.3
28.7
13.2
23.0
34.2
dT [°C]
10
331
468
570
385
541
646
Pcoil [W]
dT [°C]
dT [°C]
15
20
497
662
702
936
855
1140
578
770
812
1082
969
1292
LA10
dB(A) <20
<20
<20
<20
<20
23
Table 19: LYRA-120 – high airflow, Water flow 0.05 l/s,
Pressure drop water ∆p = 10 kPa
Nozzle Pressure
[Pa] 1
70
2
70
3
70
1
100
2
100
3
100
Q
[l/s] 14.4
24.1
35.3
17.4
28.8
42.1
dT [°C]
10
394
530
621
460
621
714
Pcoil [W]
dT [°C]
dT [°C]
15
20
591
788
795
1060
932
1242
690
920
932
1242
1071
1428
LA10
dB(A) <20
<20
22
<20
<20
28
Table 20: LYRA-120 – boost airflow, Ø125, Water flow
0.05 l/s, Pressure drop water ∆p = 10 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
4
70
1
100
2
100
3
100
4
100
Q
[l/s]
38
43.1
47.2
51.7
45.3
51.3
56.2
61.5
dT [°C]
10
461
534
588
610
548
633
679
649
Pcoil [W]
dT [°C]
dT [°C]
15
20
691
921
801
1068
883
1177
915
1220
822
1096
950
1267
1018
1357
974
1299
LA10
dB(A)
27
31
33
35
33
36
38
40
Table 21: LYRA-120 – boost airflow, Ø160, Water flow
0.05 l/s, Pressure drop water ∆p = 10 kPa
Nozzle Pressure
[Pa]
1
70
2
70
3
70
4
70
1
100
2
100
3
100
4
100
Q
[l/s]
52.4
57.4
61.9
67.5
62.5
68.4
73.7
80.4
dT [°C]
10
463
539
569
531
563
661
739
829
Pcoil [W]
dT [°C]
dT [°C]
15
20
694
925
809
1079
854
1139
796
1061
845
1127
991
1321
1108
1477
1243
1657
LA10
dB(A)
34
35
35
37
39
40
41
41
LA10
dB(A) 28
34
7 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Table 22: LYRA 120 - Fixed boost airflow, Ø160 ,
Waterflow 0.05 l/s, Pressure drop water dp = 10 kPa
Pressure
[Pa]
70
100
Fläkt Woods
Q
[l/s]
60.6
72.1
dT [°C]
10
641
727
Pcoil [W]
dT [°C]
15
962
1091
9327 GB 2016.06.10
dT [°C]
20
1282
1454
LA10
dB(A)
28
34
8 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Criteria for reading cooling power tables
The cooling power of the supply air is based on the supply air being 10 °C cooler than the ambient air. The indicated
power for water are based on the CSC (Coanda Safety Control) function in high capacity setup mode. The effects for
other water flows are indicated in Fläkt Woods's product selection program. Contact our nearest sales office for further
information. The tables on this page are based on tests performed according to EN 15116. The method is used to compare
different chilled beams under equivalent conditions, and does not permit any difference in temperature between the
supply air to the beam's coil and the air 1.1 m above the floor. At low air flows, the CSC function should be set to its
highest position (Normal capacity setup) for optimal air flow characteristics.
Sound effect level
Size
60
120
Tol +/-
63
4
4
6
125
-6
-3
3
Correction Koct dB Octave band, mid-frequency, Hz
250
500
1000
-2
-1
1
-3
-1
1
2
2
2
2000
-3
-3
2
4000
-10
-10
2
8000
-16
-17
3
The sound effect levels for different octave bands are based on computing the sound pressure level LA10, dB(A)
specified in Fläkt Woods's product selection program and the octave band corrections Koct in the table using the
following formula: L A10 = LW + Koct The correction Koct is the average value for the application area for the LYRA chilled
beam cassette.
Sound attenuation
The average sound attenuation ΔL of the LYRA chilled beam cassette from duct to room includes damping the
connecting duct's opening when the product is installed on the ceiling.
Size
60
120
Tol +/-
63
19
19
6
125
7
7
3
Correction Kok dB Octave band, mid-frequency, Hz
250
500
1000
6
8
4
6
7
9
2
2
2
2000
10
11
2
4000
12
13
2
8000
4
5
3
Correction of cooling capacity for other water flow than 0,05 l/s
Pressure drop Δp – water cooling
40
BIQC
30
20
120
60
B-0
IQC
10
Dpw , kpa
5
4
3
2
1
0,02
0,03
0,04
0,05
0,06
0,07
0,08
0,09
0,1
qw , l/s
Ptot = cooling power air + coil
Pcoil = cooling power coil
Fläkt Woods
9327 GB 2016.06.10
9 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Dimensions and weights
LYRA-060
Delivery weight:
Operating weight:
16 kg
17 kg (incl. cooling water)
18 kg (incl. cooling and heating water)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
LYRA-060 Freely suspended
Delivery weight:
Operating weight:
Fläkt Woods
18 kg
19 kg (incl. cooling water)
20 kg (incl. cooling and heating water)
9327 GB 2016.06.10
10 (13)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Dimensions and weights
LYRA-120
Delivery weight:
Operating weight:
29 kg
31 kg (incl. cooling water)
32 kg (incl. cooling and heating water)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
LYRA-120 Freely suspended
Delivery weight:
Operating weight:
Fläkt Woods
31 kg
33 kg (incl. cooling water)
34 kg (incl. cooling and heating water)
9327 GB 2016.06.10
11 (13)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Dimensions and weights
LYRA-060 low-built
Delivery weight:
Operating weight:
14 kg
15 kg (incl. cooling water)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
25 kg
26 kg (incl. cooling water)
= Cooling water in
= Cooling water out
= Heating water in
= Heating water out
LYRA-120 low-built
Delivery weight:
Operating weight:
Fläkt Woods
9327 GB 2016.06.10
12 (13)
Specifications are subject of alteration without further notice.
iQ Star LYRA chilled beam cassette
Product code
Cassette chilled beam
IQCB-aaa-bb-c-dd-e
Nominal length (aaa)
060 = 60 cm
120 = 120 cm
Accessories
Casing freely suspended
(only for bb=12 in IQCB)
IQAZ-33-bbb-c-ddd
Size (bbb)
060 = 60 cm
120 = 120 cm
Connections (bb)
Execution (c)
1 = Cooling, Ø125
2 = Cooling and heating, Ø 125
3 = Cooling, Ø160 (only aaa = 120)
4 = Cooling and heating, Ø160 (only aaa = 120)
12 = Water to the left of air
72 = Low-built
14 = Water to the right of air
74 = Low-built
16 = 2 spigots (alternative
connection)
76 = Low-built
Water near air connections
Duct enclosure (ddd)
000 = without
050 = 30-50 cm
090 = 50-90 cm
170 = 90-170 cm
Coil(c)
1 = Cooling
2 = Cooling and heating (only bb = 12, 14, 16)
Gripple (suspension
QFAZ-23-01-01
system with wire)
Complete set for one chilled beam cassette
4 wires, 4 concrete fasteners
Comfort Control (dd)
02 = Low airflow, with CC, Ø125, FPC
04 = Medium airflow, With CC, Ø125, FPC
06 = High airflow, With CC, Ø125, FPC
14 = Fixed boost airflow, Without CC, Ø125, FPC
(only aaa = 060, bb = 12, 14, 16)
16 = Fixed boost airflow, Without CC, Ø160, FPC
(only aaa = 120, bb = 12, 14, 16)
18 = Boost airflow, With CC, Ø125, FPC
20 = Boost airflow, With CC, Ø160, FPC
(only aaa = 120, bb = 12, 14, 16)
Fastening bracket
Set of two, for one chilled
beam cassette
Suspension rods M8
Set of two, length 500 mm
Two sets QFAZ-12 per
cassette
QFAZ-18-7-1
QFAZ-12
Purging nipple
IQAZ-32-15-0
Integrated control
Suspension alternatives (e)
0 = For installation in false ceiling
1 = For exposed installation (only bb = 12, 14, 16)
STRZ-75-bb-cc-d-e
bb - Location Room controler
01 = Loose delivered Room Controler
02 = Room controler mounted on shortside
03 = Room controler in frontplate
cc - Sensors, valves and actuators
01 = Cooling valve
02 = Cooling valve with condensate sensor
03 = Cooling valve and heating valve
04 = Cooling valve, heating valve and condensate sensor
d - Connection
1 = Connection terminal
2 = Connection unit - IPSUM
e - Chilled beam
1 = LYRA 060
2 = LYRA 120
Fläkt Woods
9327 GB 2016.06.10
13 (13)
Specifications are subject of alteration without further notice.