SiteManager xx29, xx39 and xx49 - Working with I/O ports

SiteManager xx29, xx39 and xx49 - Working with I/O ports
SiteManager™ xx29, xx39 and xx49
Working with I/O Ports
This document describes how to operate the I/O ports of the SiteManager.
This document is supplementary to the “SiteManager Initial Contact” leaflets
and the SiteManager product data sheets. These publications can be found on
the Secomea web site.
This guide is applicable to SiteManager firmware version 5.9 (15123) or newer.
Version 3.1, March 20, 2015
Page 1 of 13
Table of Contents
Introduction
3
1.
About GND, 0V GND and Shield
3
2.
Digital Input Ports (ALL SiteManager models)
4
2.1.
Electrical information
4
2.2.
Digital Input ports default functionality
4
2.3.
Low-side Output switching equipment example
4
2.4.
High-side Output switching equipment example
5
2.5.
Changing Input 1 default functionality
5
2.6.
Defining Input port Alerts
6
3.
Digital Output Ports
7
3.1.
Digital Output ports - Electrical information
7
3.2.
Low-side Input switching equipment example.
8
3.3.
High-side Input switching equipment example.
9
4.
Relay Output Port (isolated)
10
4.1.
Relay output ports - Electrical information
10
4.2.
Low-side Input switching equipment example.
10
4.3.
High-side Input switching equipment example
10
5.
Output ports default functionality
11
5.1.
Manual toggling of Output port state
12
Notices
SiteManager xx29, xx39 and xx49 - Working with I/O ports
13
Page 2 of 13
Introduction
SiteManagers are equipped with 2 x input- and 2 x output ports that can be
used to extend the primary functionality of the SiteManager.
The Input ports can be used to trigger alerts sent as Email or SMS messages from the GateManager, or trigger an SMS sent from SiteManager itself
(SMS alerts are only applicable to xx39 models with integrated 3G modems).
Additionally an Input port can be used to control when remote access is possible.
The Output ports can be used to trigger a signal to e.g. a PLC or HMI, based
on manually toggling of a button in the SiteManager GUI. Additionally an
Output port can signal when remote access is made via the SiteManager, or
simply when the SiteManager is connected to the GateManager.
1.
About GND, 0V GND and Shield
On the SiteManager the power should be applied between GND and +V as
shown.
Models: 10xx, 14xx, 32xx, 34xx
Models: 11xx, 33xx
Voltage 12-48V
Voltage: 12-24V
On some industrial equipment, you will find that power should be supplied
between terminals marked -V or 0V and +V, and where -V/0V, GND and
Shield may have different potentials. The specifications for a USB port is that
GND and Shield should have the same potential, and since the SiteManager
has a USB port, the GND and Shield is per design short circuited internally.
It is also intentional that there are no separate -V/0V pins on the
SiteManager, since the presence of the USB port would make it extremely
difficult to protect the power regulation circuitry in the SiteManager, should
you by accident apply voltage between -V/0V and GND.
This would typically not be an issue even in cases where GND and Shield
are wired separately.
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 3 of 13
2.
Digital Input Ports (ALL SiteManager models)
IMPORTANT: Examples in the following are only for illustration of the functionality. Always consult the specifications of the equipment you intend to
connect.
2.1. Electrical information
Input port toggling on the SiteManager would typically be controlled by a
mechanical switch or a relay connected to the GND and Input terminals. The
Input port is when not connected in “Open state” (inactive) that corresponds
to a connected mechanical switch is turned OFF. An input toggles to “Close
state” (ON) when pulled from 2.34 V or above to 0.16 V or below.
The behavior for input voltages between 0.16 V and 2.34 V is undefined.
In the SiteManager there is an internal 10 Kohm pull-up resistor to 3.3 V, so
an unconnected input port is in the “OFF” state.
2.2. Digital Input ports default functionality
Input port 1 is default assigned to toggle GateManager Access. By connecting a simple on/off switch you can control when remote service should be allowed (see also section 2.5 Changing Input 1 default functionality)
Input port 2 is not associated with anything as default.
2.3. Low-side Output switching equipment example
When a digital input port of the SiteManager is connected to equipment that
has “low-side switching” conductor connections on the output, you can use
the SiteManager input ports directly without any external components (such
as pull up resistors or relays).
A typical use is the following, where a mechanical single pole switch is connected between Input 1 and GND.
+24V
SM
+V
In1
GND
0V
This exploits the default use of Input 1, which is to control the remote access. Short circuit of Input 1 and GND will by default disable the
GateManager connection.
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 4 of 13
2.4. High-side Output switching equipment example
When an input port of the SiteManager is connected to equipment that has
“high-side switching” connections on the output, you must apply a circuitry to
pull the output towards zero.
The following example uses a 24V relay, which subsequently assumes the
output of the equipment to support 24V operation (the coil voltage).
SM
+24V
(24V high-side switching)
+V
24V
In1
Output
24V relay
GND
0V
0V
2.5. Changing Input 1 default functionality
As mentioned previously, Input 1 by default controls remote access.
In the SiteManager menu System > I/O you can determine if the default action is enabled, which is the case in this screen shot:
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 5 of 13
If you want to use Input 1 for another purpose, you can disable the current
action. Enter the menu GateManager > General and press the [More>>]
button. The control of the "Input 1 Action" will be shown, and you can define
it to trigger and alert instead.
2.6. Defining Input port Alerts
Alerts resulting from triggering Input ports can be sent locally from a
SiteManager as SMS (xx39 models only), or via the GateManager as Email
or SMS (all models).
Refer to the separate guide “SiteManager Working with SMS and Email
Alerts” available in the support section on the Secomea web site.
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 6 of 13
3.
Digital Output Ports
NOTE: This section applies to:
Output port 1 and 2 for models 10xx, 14xx, 32xx, 34xx
Output port 2 only for Models 11xx and 33xx
3.1. Digital Output ports - Electrical information
The digital output ports are of the “open drain” kind, which means that (just
like a switch) no voltage is output by the port itself, but must be controlled
from a circuitry supplied by an external source (max 24V) or from the Vout
(5V) pin.
Do NOT apply voltage (e.g. 24V) directly to a SiteManager Digital Output port, as this could permanently damage the port.
In the “OFF” (inactive) state, the impedance is min 24 Mohm; in the “ON”
(active) state, the impedance is max 0.5 ohm.
Maximum sink current is 0.2A, which means the Output port is protected by
0.2A fuses mounted in extension to the FET transistors of the Output ports;
but it is still very important to dimension the external circuitry to not overload
the ports. At 24V you should therefore apply pull-up resistors at minimum
24V/0.2A = 120 ohm (24V*0.2A = 4.8W), but it is recommended to not exceed 3W, meaning a pull-up resistor of 220 ohm is recommended. These
pull-up resistors must be applied externally, unless you are using a relay
which has high enough impedance.
A 12V or 24V relay can be applied to an output port directly if the relay is
supplied with the corresponding working voltage (12V or 24V respectively)
and with a "trigger current" at max 0,2A. (A larger relay would require more
current, and subsequently would require an additional "assisting" relay for
the SiteManager output ports to trigger it)
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 7 of 13
3.2. Low-side Input switching equipment example.
When a digital output port of the SiteManager is connected to equipment
that has “low-side switching” conductor connections on the input, you can
use the SiteManager’s digital output ports directly without any external components (such as pull up resistors or relays).
SM
+24V
( low-side switching)
+V
24V
Vout
Input
Digital Out
GND
0V
0V
With a “trigger current” of 0,2A, the digital ports of the SiteManager should
also be powerful enough to pull a relay directly (even an electromechanical
one).
You could also choose to control e.g. a 24V LED light tower up to 4.8 Watts:
SM
+24V
+V
Vout
Max 0.2A
Digital Out
GND
0V
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 8 of 13
3.3. High-side Input switching equipment example.
When a digital output port of the SiteManager is connected to equipment
that has “high-side switching” conductor connections on the input, you must
apply additional circuitry to pull the output towards +.
Be careful about just applying a resistor to pull the output high, as the effect
and resistor value must be calculated based on the power consumption and
switching voltage level of the attached equipment.
A safer setup will be to use a Relay.
The following example uses a 5V relay, which means you can use the Vout
of the SiteManager to pull the output high.
SM
+24V
(24V high-side switching)
24V
+V
Vout
5V relay
Digital Out
Input
0V
GND
0V
In the following example a 24V relay is used, which means an external
source must keep the level high.
SM
+24V
(24V high-side switching)
24V
+V
Vout
24V relay
Digtial Out
GND
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Input
0V
Page 9 of 13
4.
Relay Output Port (isolated)
NOTE: This section applies to:
Output port 1 for Models 11xx and 33xx only
4.1. Relay output ports - Electrical information
The Relay Output1 is a “dual pin” port where both pins are isolated when
OFF and short-circuited when ON.
Maximum sink current is 0.5 A. Maximum Voltage is 24V.
4.2. Low-side Input switching equipment example
SM 11xx/33xx
+V
(Low-side switching)
+V
Out1b
Input
0V
Out1a
0V
4.3. High-side Input switching equipment example
SM 11xx/33xx
+V
Out1b
(High-side switching)
+V
Max 24V
Input
Out1a
0V
0V
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 10 of 13
By default Output 1 is configured to go ON when Output port 1 is by default
configured to go active when e.g. a LinkManager is connected, and can be
used to turn on a signal that notifies the users that the device is being serviced. The signal could be a LED light tower up to 12 Watts.
SM 11xx/33xx
+24V
Out1b
Max 24V, 0.5A
Out1a
0V
5.
Output ports default functionality
Output port 1 is by default set to go active when connecting to the
SiteManager or its Agents, using LinkManager, LinkManager Mobile or the
“Go To Device” buttons from GateManager. The purpose is to signal, e.g. by
turning on an external warning light, to the local service people that the machine is currently being serviced remotely.
Output port 2 is by default set to NO predefined action, but it can be configured to the same values as Output 1. I.e. if you want to use a digital Output
port 2 on a SiteManager 11xx or 33xx model to signal remote service, and
use the isolated Output ports 1a/1b for other purposes, you can change this
under GateManager > General > [More>>].
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 11 of 13
When an Output port function is selected for an Output port under
GateManager Settings, the active state will be displayed as follows under
System > I/O.
5.1. Manual toggling of Output port state
Both Output ports can be manually set ON or OFF via the toggle button in
the SiteManager web GUI under System > I/O.
Note that an Output that is triggered ON by a value defined under
GateManager Settings as mentioned above cannot be forced OFF.
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 12 of 13
Notices
Publication and Copyright
© Copyright Secomea A/S 2011-2015. All rights reserved. You may download and print a copy for your own use. As a high-level administrator, you
may use whatever you like from contents of this document to create your
own instructions for deploying our products. Otherwise, no part of this document may be copied or reproduced in any way, without the written consent of
Secomea A/S. We would appreciate getting a copy of the material you produce in order to make our own material better and – if you give us permission – to inspire other users.
Trademarks
GateManager™, SiteManager™ and LinkManager™ are trademarks of
Secomea A/S. Other trademarks are the property of their respective owners.
Disclaimer
Secomea A/S reserves the right to make changes to this publication and to
the products described herein without notice. The publication of this document does not represent a commitment on the part of Secomea A/S. Considerable effort has been made to ensure that this publication is free of
inaccuracies and omissions but we cannot guarantee that there are none.
The following paragraph does not apply to any country or state where such
provisions are inconsistent with local law:
SECOMEA A/S PROVIDES THIS PUBLICATION "AS IS" WITHOUT
WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING,
BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE
SECOMEA A/S SHALL NOT BE LIABLE FOR ANY DIRECT, INDIRECT,
INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGE ALLEGED IN
CONNECTION WITH THE FURNISHING OR USE OF THIS INFORMATION.
Secomea A/S
Denmark
CVR No. DK 31 36 60 38
Tel.: +45 88 70 86 50
Fax: +45 88 70 80 60
E-mail: sales@secomea.com
www.secomea.com
SiteManager xx29, xx39 and xx49 - Working with I/O ports
Page 13 of 13