sinus penta keypad rs485

sinus penta keypad rs485
• 15P0102Q2 •
SINUS PENTA
KEYPAD CONNECTED TO
NETWORK RS485
USERS MANUAL
Upd. 08/06/04
R. 00
English
• This manual is integrant and essential to the product. Carefully read the instructions contained herein as
they provide important hints for use and maintenance safety.
• This device is to be used only for the purposes it has been designed to. Other uses should be considered
improper and dangerous. The manufacturer is not responsible for possible damages caused by improper,
erroneous and irrational uses.
• Elettronica Santerno is responsible for the device in its original setting.
• Any changes to the structure or operating cycle of the device must be performed or authorized by the
Engineering Department of Elettronica Santerno.
• Elettronica Santerno assumes no responsibility for the consequences resulting by the use of non original
spare-parts.
• Elettronica Santerno reserves the right to make any technical changes to this manual and to the device
without prior notice. If printing errors or similar are detected, the corrections will be included in the new
releases of the manual.
• Elettronica Santerno is responsible for the information contained in the original version of the Italian
manual.
• The information contained herein is the property of Elettronica Santerno and cannot be reproduced.
Elettronica Santerno enforces its rights on the drawings and catalogues according to the law.
Elettronica Santerno S.p.A.
Via G. Di Vittorio, 3 - 40020 Casalfiumanese (Bo) Italy
Tel. +39 0542 668611 - Fax +39 0542 668622
After-sales Service Tel. +39 0542 668610 - Fax +39 0542 668623
Sales Department Tel. +39 0542 668611 - Fax +39 0542 668600
15P0097P2
USERS MANUAL
SINUS Penta
Keypad Remoting Kit for RS485
GENERAL FEATURES
The keypad remoting kit is used to connect a standard SINUS PENTA keypad to one or multiple inverters
manufactured by Elettronica Santerno via an RS485 link using protocol MODBUS RTU. The keypad can then
communicate with one device at a time and will become the network master, thus avoiding communicating
with any other master devices (e.g. PLCs).
The keypad automatically detects which device it is connected to. If multiple devices are connected, you can
select the device to be used from a selection list.
The devices connected to the same network must have different addresses,
NOTE
otherwise no communication is possible.
2/7
SINUS Penta
Keypad Remoting Kit for RS485
15P0097P2
USERS MANUAL
CONTENTS
GENERAL FEATURES...................................................................................................................................2
CONTENTS................................................................................................................................................3
1 Kit Component Parts................................................................................................................................4
1.1 Applicability .....................................................................................................................................4
2 Connecting the Keypad............................................................................................................................5
2.1 Communications Protocol .................................................................................................................6
3 CONNECTION .......................................................................................................................................7
3/7
15P0097P2
USERS MANUAL
SINUS Penta
Keypad Remoting Kit for RS485
1 K IT C OMPONENT P ARTS
The kit covered in this manual includes the following component parts:
N.1 Interface converter provided with 1 plug RJ45 on one side, and with a 9-pole, female sub-d connector on
the other side.
N.1 220 VAC – 9 VAC feeder for standard SINUS PENTA keypad
1.1 Applicability
The keypad remoting kit can be applied to the following devices manufactured by Elettronica Santerno:
“Sinus PENTA” industrial inverters
“Sunway T” solar inverters (starting from products manufactured in 2004)
“Sunway Bach” solar battery chargers
“ALADIN M/T” hybrid inverters
4/7
SINUS Penta
Keypad Remoting Kit for RS485
2 C ONNECTING
THE
15P0097P2
USERS MANUAL
K EYPAD
Inverter-side connection: use 9-pole, male D connector. To gain access to the D connector, just remove the
cover on top of the inverter (size S05..S15), or remove the cover from the inverter bottom, located next to the
control terminals (size ≥ S20). For more details on D connector, see Sunway T’s Installation Manual. If
multiple inverters are connected to the same network, use a connector having the same features as the
connector installed on the inverter.
The connector pins are detailed in the table below.
PIN
1–3
2–4
5
6
7–8
9
FUNCTION
(TX/RX A) Differential input/output A (bidirectional) according to standard RS485. Positive polarity with
respect to pins 2 – 4 for one MARK.
(TX/RX B) Differential input/output B (bidirectional) according to standard RS485. Negative polarity
with respect to pins 1 – 3 for one MARK.
(GND) Control board zero volt
(VTEST) Test supply input – do not connect
Not connected
+5 V, max. 100mA power supply
NOTE
The metal frame of the connector is connected to the ground. Connect the
braiding of the twisted pair data cable to the metal frame of the female
connector to be connected to the inverter.
Connector RJ 45 must be connected to the keypad:
PIN
4
6
1-2-3
5-7-8
FUNCTION
(TX/RX A) Differential input/output A (bidirectional) according to standard RS485. Positive polarity with
respect to pin 6 for one MARK.
(TX/RX B) Differential input/output B (bidirectional) according to standard RS485. Negative polarity
with respect to pin 4 for one MARK.
(GND) keypad zero volt.
+5 V, max. 100mA power supply
5/7
SINUS Penta
Keypad Remoting Kit for RS485
15P0097P2
USERS MANUAL
2.1 Communications Protocol
Standard MODBUS RTU protocol is used for communications.
Set the following values for the inverter/keypad; please refer to the Programming Manual of the inverter being
used for the setup of the relevant parameters:
Setting values to the inverter
Baud rate:
Data format:
Start bit:
Parity:
Stop bit:
Protocol:
Device address:
Electrical standard:
Inverter response delay:
End of message timeout:
38.400 bps
8 bits
1
NO
2
MODBUS RTU
set between 1 and 247 to avoid conflicts (default address is 1)
RS485
5 ms
2 ms
Setting values to the keypad
Device address:
set between 0 to 247 (default address is 1)
In order to scan the connected inverters, set the device address to 0 for the keypad. The keypad can
communicate with one device at a time, based on the address that has been set up.
CAUTION
6/7
If different parameter values are set, communication errors between the
inverter and the keypad may occur.
SINUS Penta
Keypad Remoting Kit for RS485
15P0097P2
USERS MANUAL
3 CONNECTION
Remove voltage from the inverter. Then proceed as follows:
Disconnect the keypad installed on the inverter (if any)
Please refer to the Installation Manual of the inverter being used.
Connect the cable to the interface converter and the keypad
Connect connector DB9 to the inverter or to network RS485. The inverter side with telephone connector RJ45
must be already connected to the keypad.
Check that communication is correct
Turn on one of the inverters connected to the network. The keypad shows POWER ON. To scan the inverters
connected to the network, set the device address on the keypad to 0 (please refer to the Programming Manual
of the inverter being used). The list of the connected devices appears on the keypad display. Select the device
to be used to start communicating with the keypad, using all functionalities offered by the connected device.
Please refer to the Users Manual of the device being used for the operation of the keypad connected to the
device.
Segregate the keypad power supply using the feeder
Connect the feeder output to the proper plug and set the toggle to ON.
7/7