DSP Multipower Convertible Series
Inform Uninterruptible Power Systems
DSP Multipower Convertible Series
On-Line “Double Conversion” Technology
1 Phase in / 1 Phase out 5kVA to 10kVA,
3 Phase in / 1 Phase out 10kVA to 20 kVA
(Tower & Rack Convertible)
On-line ‘double conversion’ technology
Real Digital Signal Processor ( DSP ) Controller
Parallel redundant operation up to 4 units
Input Power Factor Correction PFC
High output power factor ( PF : 0.9 )
Low total harmonic distortion (THD) level
Convertible display helps to use both for tower and rack applications
Transformerless Design
Availability to configure as 50/60Hz Frequency Converter from LCD Panel
High Performance with the PWM Sinewave Topology
Cold Start Function
Intelligent Battery Management System extends the life time of batteries
Overload, Overheat & Short Circuit Protections
User Friendly Multi-Functional LED/LCD Display Panel
Energy Saving Mode ( ECOMODE )
Smart Fan Speed Regulation with temperature controlled
RS232 Communication Port & Management Software
Internal SNMP, DRY contact, RS485 card options
(Ups Looking Battery Cabinet)
DSP Multipower Convertible Series Technical Specifications
MODEL
Power (kVA)
Power (kW)
INPUT
Phase Configuration
Nominal Voltage
Minimum Voltage (at Half load)
Minimum Voltage (at Full load)
Maximum Voltage
Frequency
Power Factor
OUTPUT
Power Factor
Phase Configuration
Nominal Voltage
Wave Form
Total Harmonic Distortion at 100% linear load
at 100% non-linear load
Frequency
Frequency Tolerance(free running)
Frequency Synchronized Range
Static Voltage Regulation (0%-100% load)
Crest Factor
Transfer Time
DSPMP-1105
5
4,5
DSPMP-1106
6
5,4
1Ph + N + PE (Hardwire)
220VAC/230VAC/240VAC
160VAC
180VAC
280VAC
DSPMP-3110
10
9
DSPMP-3115
15
13,5
0.95
0,9
1Ph + N + PE (Hardwire)
220VAC / 230VAC / 240VAC
Pure Sine Wave
<3%
<5%
50Hz or 60Hz (adjustable)
±0,1 %
±1Hz; ±3Hz (selectable)
<1%
3
0sec
Up to 10min. @100%~120%
Up to 1min. @120%~150%
Transfer to bypass @ >150%
up to 91%
≥97%
External Socket Box (2 pcs SCHUKO, 4 pcs IEC C13 Outlets) Optional
up to 90%
Maintenance-free lead acid batteries
4-6h up to 90%
Voltage
240VDC
Quantity per string
Internal batteries
Built in max. Charge Current
Cold Start
DISPLAY
LED + LCD Display
N/A
1.6A
up to 93%
192VDC for 16 pcs
240VDC for 20 pcs
(20 pcs 12V Batteries) or
(16 pcs 12V Batteries)**
4A
Present
Line Mode, Backup Mode, ECO Mode, Bypass Supply, Battery Low, Battery Bad/Disconnect, Overload and
Transferring with Interruption & UPS Fault
Input Voltage, Input Frequency, Output Voltage, Output Current, Output Frequency, Load Percentage, Battery Voltage & Inner Temperature.
Upon Power-on, Front Panel Setting & Software Control, 24-hour routine checking
Line Failure, Battery Low, Transfer to Bypass, System Fault Conditions
Bypass transfer time is calculated by simulating a temperature related model of a fuse
Acts as the ideal current source during the short circuit time
Against excessive (heat,voltage,current) intense battery discharge
Standard RS232 port and optional RS485, Internal SNMP, Dry Contact Cards
Standard
<50 dB
25kg
55kg
440x88x680
440x176x680
0 ˚C.... + 40 ˚C
20 - 25 ˚C
up to 95% ( non-condensing )
<60 dB
IP 20
26kg
440x132x680
-
28kg
36 kg
440x220x720
-
EN62040-1-1 (safety); EN62040-2 (EMC);EN62040-3(performance); EN60950-1
LCD display
Self Diagnostics
Audible and Visual Alarms
PROTECTION
Overload Protection
Short Circuit Protection
Other Protection
COMMUNICATION
Interface (Communication ports)
Monitoring and Management Software
ENVIRONMENT
Operating Temperature
Proposed Temp. to extend battery life
Humidity
Audible Noise at 1 m
Protection Class
PHYSICAL SPECIFICATIONS (tower position)
Net Weight ( power module)
Net Weight (with internal batteries)
Dimensions(mm) (HxWxD)-power module
Dimensions(mm) (HxWxD)- w/battery vers.
STANDARDS
Standards
ACCESORIES
20 pcs 12V Batteries
20 pcs 12V 4.5Ah (internal battery version only)
DSPMP-3120
20
18
3Ph + N + PE (Hardwire)
380VAC/400VAC/415VAC
277VAC
312VAC
485VAC
45-65 Hz
0.99
Overload
Total Efficiency
Greenmode efficiency
Outlets
BATTERY
Type
Recharge Time
DSPMP-1110
10
9
L
E
INT
RTIFICAT
I
ON
NA
CE
RNAT
IO
Internal&External SNMP, Dry Contact Board, External Manual Bypass, Rail Kit, External Battery Connection Cable,
Optional
External Socket Box, External Additional Charging Board
** Availability to use 16pcs 12V batteries per string if load is less than 85%