a Project to an HMI with a USB Flash

a Project to an HMI with a USB Flash
T E C H N I C A L
Maple Model(s)
HMI5000 Series
(EZware-5000)
HMI5000P Series
(EZwarePlus)
N O T E
PLC or Controller
N/A
Title: Download a Project to an HMI with a USB Flash Drive
or SD Card
Summary
This technical note describes how to download an EZware project to an HMI5000 Series with a USB
flash drive or SD card.
Solution
To download a project from a USB flash drive or SD card:
1. Open the project in EZware-5000 (or EZwarePlus) and compile the project (Tools >
Compile).
2. Select “Build Data for USB Disk or CF Card Download” from the Tools menu.
3. In the “USB Disk/CF Card/SD Card Data” dialog box, under “Select the folder to save
download data:” use the Browse button to select the location to save the project. Click Build.
When the process is complete the message “Creating successful!" appears. Click OK and
click Exit.
4. A folder named mt8000 will be created on the root (main) directory of the USB flash drive
or SD card.
5. Remove the flash drive from your computer and connect it to the HMI. When a flash drive is
inserted into the HMI5000 Series, the following dialog is displayed:
Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com
0907-5087
Page 1 of 4
Rev. 01, 06/10/2013
.
Download
Upload
Restart Project and Exit
Cancel
Time Remaining
Transfer data from the flash drive to the HMI.
Transfer data from the HMI to the flash drive.
Close the dialog and restart the HMI.
Close the dialog without transferring.
The dialog will automatically close after 10 seconds if no
selection is made; shows the time remaining.
Note: The Download/Upload dialog box can be disabled. If it does not pop up when the USB flash
drive or SD card is installed, open the System Settings in the HMI and enable it on the Miscellaneous
tab.
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: support@maplesystems.com • www.maplesystems.com
0907-5087
Page 2 of 4
Rev. 01, 06/10/2013
When Download is selected, a dialog box appears requesting the Download password and what data
to download. The default password is 111111.
Enter the Download password.
When checked, the HMI checks the specified folder for project data,
Download Project Files
and transfers it if it exists.
When checked, the HMI checks the specified folder for history data,
Download History Files and transfers it if it exists (includes data log files, event log files, and
recipe files).
When checked, clears all history files in the HMI (includes data log
Clear History Files
files, event log files, and recipe files).
Password
If a USB flash drive is being used to download the project, select the folder under the usbdisk folder
(disk_a_1) and then click OK. If an SD card is being used, select the folder under the pccard folder
(SD_MMCO_1). If the project is in a folder on the USB drive or SD card, select the folder just above
the mt8000 folder.
Maple Systems Inc., 808 134th Street SW, Suite 120, Everett, WA 98204-7333 – www.maplesystems.com
0907-xxxx
Page 3 of 4
Rev. 01, 06/10/2013
.
Note: Do not select the mt8000 folder, but the folder just above the mt8000 folder.
USB flash drive
SD card
Click OK to download the project from the USB drive or SD card to the HMI. When the download is
complete, the HMI automatically reboots and runs the project.
Note: The storage device can be left with the HMI as a backup should the project need to be
downloaded to the HMI again.
Phone: 425/745-3229 • Fax: 425/745-3429 • Email: support@maplesystems.com • www.maplesystems.com
0907-5087
Page 4 of 4
Rev. 01, 06/10/2013