Specifications Benefits and Features C13 Generator Set Electric

Specifications Benefits and Features C13 Generator Set Electric
C13 Generator Set
Electric Power
Caterpillar is leading the power generation marketplace with
Power Solutions engineered to deliver unmatched flexibility,
expandability, reliability, and cost-effectiveness.
Specifications
Generator Set Specifications
Minimum Rating
320 ekW
Maximum Rating
400 ekW
Voltage
380 to 415 Volts
Frequency
60 Hz
Speed
1800 RPM
Generator Set Configurations
Emissions/Fuel Strategy
Low Fuel Consumption, EU Stage IIIA Nonroad Emission
Standards, China Nonroad III Emission Standards
Engine Specifications
Engine Model
C13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Displacement
12.5 L
762.8 in³
Bore
130 mm
5.12 in
Stroke
157 mm
6.18 in
Compression Ratio
16.3:1
Aspiration
Air to Air Aftercooled
Governor Type
Adem™A4
Fuel System
MEUI
Benefits and Features
Cat Diesel Engine
Reliable, rugged, durable design
Field-proven in thousands of applications worldwide
Four-stroke-cycle diesel engine combines consistent performance and excellent fuel economy with minimum
weight
Generator
SS-8254230-1000029524-001
MSS-EPG-1000029524-004.pdf
SS Page 1 of 7
© 2017 Caterpillar All Rights Reserved
Page: M-1 of M-4
C13 Generator Set
Electric Power
Matched to the performance and output characteristics of Cat engines
Industry leading mechanical and electrical design
Industry leading motor starting capabilities
High Efficiency
Cat EMCP Control Panel
The EMCP controller features the reliability and durability you have come to expect from your Cat equipment.
EMCP4 is a scalable control platform designed to ensure reliable generator set operation, providing extensive
information about power output and engine operation. EMCP4 systems can be further customized to meet your
needs through programming and expansion modules.
Design Criteria
The generator set accepts 100% rated load in one step per NFPA 110 and meets ISO 8528-5 transient
response.
Single-Source Supplier
Fully prototype tested with certified torsional vibration analysis available
World Wide Product Support
Cat dealers provide extensive post-sale support including maintenance and repair agreements. Cat dealers have
RYHUGHDOHUEUDQFKVWRUHVRSHUDWLQJLQFRXQWULHV7KH&DWHUSLOODU6ವ2ವ6യSURJUDPFRVWHIIHFWLYHO\
detects internal engine component condition, even the presence of unwanted fluids and combustion by-products
Standard Equipment
Packaged Generator Set
• Disposable Air filter
• Service indicator
• Radiator package mounted
• Coolant level sight gauge
• Low coolant level sensor
• Coolant drain line with valve
• Fan and belt guards
• Cat Extended Life Coolant
• Dry exhaust manifold
• Stainless steel flex fittings
• Exhaust flange outlet
• Integral narrow single wall fuel tank base
• Primary fuel filter with integral water separator
• Secondary fuel filters
• Fuel priming pump
• Engine fuel transfer pump
• Fuel cooler integral with cooling system
• Flexible fuel lines
• Class H insulation
SS-8254230-1000029524-001
MSS-EPG-1000029524-004.pdf
SS Page 2 of 7
© 2017 Caterpillar All Rights Reserved
Page: M-2 of M-4
C13 Generator Set
Electric Power
• Self excited (SE)
• Class H temperature rise
• IP23 protection
• R450 voltage regulator with single phase sensing and load adjustment module
• Power Center houses EMCP controller and power/control terminations (rear mounted)
• Circuit breaker, IEC compliant, 3-4 pole (100% Rated)
• Segregated low voltage wiring termination panel
• Bottom cable entry
• EMCP 4.1 (Rear-mounted in Power Center)
• Integral Narrow 8hr tank base
• Linear vibration isolation
• 24 volt starting motor
• 24 volt, 45 amp charging alternator
• Batteries with rack and cables
• Paint - Caterpillar Yellow except rails and radiators gloss black (Powder Coated)
• Flywheel housing - SAE No.1/2
Optional Equipment
Packaged Generator Set Options: Note some options are not available in all regions
• Canister type Air Filter:
Single element
Dual element
• Radiator duct flange
• Stone Guard
• Low coolant temperature alarm
• Industrial, Residential, Critical Mufflers
• Manifold and turbocharger guards
• Elbows and flange kits
• Fuel level switch
• Manual fuel transfer pump
• Oversize generators
• Permanent magnet excitation (PMG)
• Internal excited (IE)
• Cat digital voltage regulator (Cat DVR) with kVAR/PF
• Anti-condensation space heaters
• Coastal Insulation Protection (CIP)
• Reactive droop
• Three phase sensing
SS-8254230-1000029524-001
MSS-EPG-1000029524-004.pdf
SS Page 3 of 7
© 2017 Caterpillar All Rights Reserved
Page: M-3 of M-4
C13 Generator Set
Electric Power
• C.B. Shunt trips
• C.B. Auxiliary contacts
• EMCP 4.2
• Oil temperature sensor
• Manual sump pump
• Narrow skid base
• Integral Dual Wall 8hr tank base (Available only with enclosed units)
• Jacket water heater
• Battery disconnect switch
• Battery charger - 5 amp
• EU Certificate of Conformance
• Sound attenuated protective enclosure with integral lifting frame
• High Ambient enclosure with integral lifting frame
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their
respective logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well
as corporate and product identity used herein, are trademarks of Caterpillar and may not be used
without permission.
SS-8254230-1000029524-001
MSS-EPG-1000029524-004.pdf
SS Page 4 of 7
© 2017 Caterpillar All Rights Reserved
Page: M-4 of M-4
ELECTRIC POWER - Technical Spec Sheet
STANDARD
C13 ACERT
400 ekW/ 500 kVA/ 60 Hz/ 1800 rpm/ 480 V/ 0.8 Power Factor
Fuel Strategy: LOW FUEL CONSUMPTION
Rating Type: STANDBY
C13 ACERT
400 ekW/ 500 kVA
60 Hz/ 1800 rpm/ 480 V
Image shown may not reflect actual configuration
Metric
English
Package Performance
Genset Power Rating with Fan @ 0.8 Power Factor
400 ekW
Genset Power Rating
500 kVA
Aftercooler (Separate Circuit)
N/A
N/A
100% Load with Fan
107.7 L/hr
28.4 gal/hr
75% Load with Fan
80.9 L/hr
21.4 gal/hr
50% Load with Fan
56.5 L/hr
14.9 gal/hr
25% Load with Fan
33.7 L/hr
8.9 gal/hr
14.2 L
3.8 gal
27.2 m³/min
960.0 cfm
50 ° C
122 ° F
577.4 ° C
1071.2 ° F
82.5 m³/min
2911.4 cfm
10.0 kPa
40.0 in. water
Fuel Consumption
Cooling System¹
Engine Coolant Capacity
Inlet Air
Combustion Air Inlet Flow Rate
Max. Allowable Combustion Air Inlet Temp
Exhaust System
Exhaust Stack Gas Temperature
Exhaust Gas Flow Rate
Exhaust System Backpressure (Maximum Allowable)
SS-8254230-1000029524-001
TSS-EM0423-04-GS-EPG-8254230.pdf
© 2016 Caterpillar All Rights Reserved
SS Page 5 of 7
Page 1 of 3
ELECTRIC POWER - Technical Spec Sheet
STANDARD
C13 ACERT
400 ekW/ 500 kVA/ 60 Hz/ 1800 rpm/ 480 V/ 0.8 Power Factor
Fuel Strategy: LOW FUEL CONSUMPTION
Rating Type: STANDBY
Heat Rejection
Heat Rejection to Jacket Water
158 kW
8981 Btu/min
Heat Rejection to Exhaust (Total)
386 kW
21950 Btu/min
Heat Rejection to Aftercooler
70 kW
3997 Btu/min
Heat Rejection to Atmosphere from Engine
72 kW
4122 Btu/min
Heat Rejection to Atmosphere from Generator
29 kW
1661 Btu/min
Alternator²
Motor Starting Capability @ 30% Voltage Dip
880 skVA
Current
601 amps
Frame Size
LC6114B
Excitation
SE
Temperature Rise
150 ° C
Emissions (Nominal)³
NOx
2396.2 mg/Nm³
4.9 g/hp-hr
CO
630.8 mg/Nm³
1.3 g/hp-hr
HC
5.7 mg/Nm³
0.0 g/hp-hr
PM
N/A
N/A
DEFINITIONS AND CONDITIONS
1.
For ambient and altitude capabilities consult your Cat dealer. Air flow restriction (system) is added to existing
restriction from factory.
2.
UL 2200 Listed packages may have oversized generators with a different temperature rise and motor starting
characteristics. Generator temperature rise is based on a 40° C ambient per NEMA MG1-32.
3.
Emissions data measurement procedures are consistent with those described in EPA CFR 40 Part 89, Subpart D &
E and ISO8178-1 for measuring HC, CO, PM, NOx. Data shown is based on steady state operating conditions of
77° F, 28.42 in HG and number 2 diesel fuel with 35° API and LHV of 18,390 btu/lb. The nominal emissions data
shown is subject to instrumentation, measurement, facility and engine to engine variations. Emissions data is based
on 100% load and thus cannot be used to compare to EPA regulations which use values based on a weighted cycle.
SS-8254230-1000029524-001
TSS-EM0423-04-GS-EPG-8254230.pdf
© 2016 Caterpillar All Rights Reserved
SS Page 6 of 7
Page 2 of 3
ELECTRIC POWER - Technical Spec Sheet
STANDARD
C13 ACERT
400 ekW/ 500 kVA/ 60 Hz/ 1800 rpm/ 480 V/ 0.8 Power Factor
Fuel Strategy: LOW FUEL CONSUMPTION
Rating Type: STANDBY
Applicable Codes and Standards:
AS1359, CSA C22.2 No100-04, UL142,UL489, UL869, UL2200,
NFPA37, NFPA70, NFPA99, NFPA110, IBC, IEC60034-1, ISO3046, ISO8528,
NEMA MG1-22,NEMA MG1-33, 2006/95/EC, 2006/42/EC, 2004/108/EC.
Note: Codes may not be available in all model configurations. Please consult your local Cat Dealer representative for
availability.
STANDBY:Output available with varying load for the duration of the interruption of the normal source power. Average
power output is 70% of the standby power rating. Typical operation is 200 hours per year, with maximum expected usage
of 500 hours per year.
Ratings are based on SAE J1349 standard conditions. These ratings also apply at ISO3046 standard conditions
Fuel Rates are based on fuel oil of 35º API [16º C (60º F)] gravity having an LHV of 42 780 kJ/kg (18,390 Btu/lb) when
used at 29º C (85º F) and weighing 838.9 g/liter (7.001 lbs/U.S. gal.). Additional ratings may be available for specific
customer requirements, contact your Cat representative for details. For information regarding Low Sulfur fuel and
Biodiesel capability, please consult your Cat dealer.
www.Cat-ElectricPower.com
Performance No.: EM0423-04
Feature Code: C13DE12
Generator Arrangement: 3969606
Date: 12/26/2016
The International System of Units (SI) is used in this publication. CAT, CATERPILLAR, their respective
logos, ADEM, EUI, S•O•S, "Caterpillar Yellow" and the "Power Edge" trade dress, as well as corporate
and product identity used herein, are trademarks of Caterpillar and may not be used without permission.
Source Country: U.K.
SS-8254230-1000029524-001
TSS-EM0423-04-GS-EPG-8254230.pdf
© 2016 Caterpillar All Rights Reserved
SS Page 7 of 7
Page 3 of 3