nSP5 2P - Acuity Brands

nSP5 2P - Acuity Brands
nSP5 2P
SECONDARY PACK 2-POLE
5 AMPS @ 120/277/347 VAC
SPECIFICATIONS
The nLight nSP5 2P Series secondary
OPTIONS
relay pack switches two lighting loads up to
LOW TEMP/HIGH HUMIDITY (LT)
5A. The relay pack’s two RJ 45 connectors
• Sensor is corrosion resistant to
make control wiring with standard CAT-5
moisture
• Operates down to -40º F/C
cabling easy and clean. For simplifying
installation, secondary packs have an
elongated chase nipple that allows them to be attached either directly through a
1/2” knockout into a junction box, or inside an adjacent box for meeting specific
local code requirements in ceiling plenums.
FEATURES
Communicates w/ nLight Network
Remotely Configurable/Upgradeable
Push-Button Programmable
Reversible Relay Logic
Self-Contained Relay Switches
Line Voltage Load
Green LED Indicator
Extended Chase Nipple
RELAY OPERATION
PHYSICAL SPECS
SIZE (not including ½” chase nipple) 3.38” H x 2.53” W x 1.83” D
(8.59 cm x 6.43 cm x 4.65 cm)
WEIGHT 6 oz
MOUNTING ½” knockout COLOR White
NETWORK CONNECTION
2 RJ-45 ports
Power for the nSP5 2P pack is provided via the CAT-5 connection and not taken
off the line. Therefore the two internal latching relays function as dry contacts for
switching up to 5A loads.
NLIGHT OPERATION
The device is nLight-enabled, meaning it is powered and has the ability to
communicate over an nLight network. Typically, it is daisy-chain wired, using
CAT-5 cabling, with other nLight-enabled power packs, sensors and/or WallPods
in an nLight control zone. Left alone, the zone will assume default operation and
can be programmed via its’ devices’ push-buttons. Once linked to a Gateway,
directly or via a Bridge, the zone becomes capable of remote status monitoring
and control via SensorView software.
ELECTRICAL SPECS
SWITCHING LOAD / POLE:
800 W @ 120 VAC
1200 W @ 277 VAC
1500 W @ 347 VAC
MOTOR LOAD: 1/4 HP
WIRES 18 AWG (4)
All switches and sensors can be configured to communicate on one of sixteen
channels. Devices with relays, such as the nSP5 2P, can then be configured
to follow any of these channels via their own channel settings. By default, both
relays are configured to follow all occupancy and photocell information on
Channel 1. Relay 1 will also follow switch commands arriving on Channel 1,
while relay 2 will follow switch commands on Channel 2. Using SensorView,
however, these channel tracking settings can be edited for each pole individually.
This is critical when an nSP5 2P is in a zone with a sensor that sends information
on two different channels simultaneously.
ENVIRONMENTAL SPECS
OPERATING TEMP
14º to 160º F (-10º to 71º C)
STORAGE TEMP
-14º to 160º F (-26º to 71º C)
RELATIVE HUMIDITY
20 to 90% non-condensing
OTHER
UL and CUL Listed
Plenum Rated
Title 24 Compliant
5 Year Warranty
Made in the U.S.A.
ORDERING INFO
nSP5 2P [TEMP/HUMIDITY]
OPTIONS
TEMP/HUMIDITY
Blank = Standard
LT = Low Temp
Revised 12.03.10 © 2010 Sensor Switch
WIRING (DO NOT WIRE HOT)
Device power is provided via the CAT-5 connection and not taken off the line. Therefore the internal latching relays
function as dry contacts. CAT-5 cables can be wired using either T568A or T568B pin/pair assignments.
H
N
H
CAT-5
LOAD 1
N
nSP5 2P
BLK
BLU
BLK
BLU
LOAD 2
OPERATIONAL SETTINGS
Several operational settings for the nSP5 2P are available:
Override (On/Off/Normal)
Start to High (Enable/Disable)
Occupancy Tracking (Enable/Disable)
LED (Override On/Override Off/Normal)
Photocell Tracking (Enable/Disable)
Follow Photocell Mode (Enabled +, Enabled +/-, Disabled)
Switch Tracking (Enable/Disable)
Occupancy Tracking Channel (1-16)
Special Modes:
Manual On to Auto Off (Semi-Auto), Auto to (Timed) Override On,
Manual to (Timed) Override On, Manual On to Full Auto, Predictive Off
Photocell Tracking Channel (1-16)
Button Mode (Enable/Disable)
Invert Relay Logic (Enable/Disable)
Switch Tracking Channel (1-16)
INSTALLATION
• Mount to any junction box through a ½”
knockout (note: chase nipple is long enough to
accomodate mounting inside an adjacent box
if necessary for local code requirements)
• Connect Class 1 wires to line voltage feed and
load
• Connect Class 2 dimming output wires to
ballast dimming inputs
• Interconnect unit (via RJ-45 ports) with other
nLight devices in lighting zone using CAT-5
cables
• Once power is received via CAT-5 connection,
all devices in zone will automatically begin
functioning together according to each device’s
defaults
BUTTON
RJ-45 PORTS
LED
WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a
period of 60 months. Sensor Switch, Inc., upon prompt notice of such defect, will, at its option, provide a Returned Material
Authorization number and repair or replace returned product.
LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied
warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall
Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.
TN-609-01
900 Northrop Road, Wallingford, CT 06492 • 1.800.PASSIVE • FX 203.269.9621 • www.sensorswitch.com