wago-i/o-system - WAGO Corporation
Application Note
WAGO-I/O-SYSTEM
Using library
“WagoLibMSSQL_03.lib”
in CoDeSys 2.3 for interface to
Microsoft SQL Server 200x
a302510, English
Version: 1.0.0
2
Impressum
© 2012 by WAGO Kontakttechnik GmbH & Co. KG
All rights reserved.
WAGO Kontakttechnik GmbH & Co. KG
Hansastraße 27
D-32423 Minden
Phone:
Fax:
+49 (0) 571/8 87 – 0
+49 (0) 571/8 87 – 1 69
E-Mail:
info@wago.com
Web:
http://www.wago.com
Technical Support
Phone:
Fax:
+49 (0) 571/8 87 – 7 77
+49 (0) 571/8 87 – 87 77
E-Mail:
tcba@wago.com
Every conceivable measure has been taken to ensure the accuracy and
completeness of this documentation. However, as errors can never be fully
excluded, we always appreciate any information or suggestions for improving the
documentation.
We wish to point out that the software and hardware terms as well as the
trademarks of companies used and/or mentioned in the present manual are
generally protected by trademark or patent.
a302510e
Table of Contents
3
Table of Contents
1
Important Notes ........................................................................................... 4
1.1
Legal Principles......................................................................................... 4
1.1.1
Subject to Changes ............................................................................... 4
1.1.2
Copyright.............................................................................................. 4
1.1.3
Personnel Qualification ........................................................................ 4
1.1.4
Intended Use......................................................................................... 4
1.2
Scope of Validity....................................................................................... 5
1.3
Number Notation....................................................................................... 5
1.4
Font Conventions ...................................................................................... 5
a302510e
2
2.1
Description.................................................................................................... 6
Components............................................................................................... 6
3
3.1
3.2
3.3
3.4
3.5
Setup database.............................................................................................. 7
Enable TCP/IP........................................................................................... 7
Enable “SQL Server Authentication” ....................................................... 9
Enable remote connection ....................................................................... 12
Enable or create database account ‘sa’.................................................... 14
Create database ‘testdb’ .......................................................................... 15
4
WagoLibMSSQL03_Example01.pro ....................................................... 17
4
1
Important Notes
Important Notes
To ensure quick installation and start-up of the units, we strongly recommend that
the following information and explanations are carefully read and adhered to.
1.1
Legal Principles
1.1.1
Subject to Changes
WAGO Kontakttechnik GmbH & Co. KG reserves the right to provide for any
alterations or modifications that serve to increase the efficiency of technical
progress. WAGO Kontakttechnik GmbH & Co. KG owns all rights arising from
the granting of patents or from the legal protection of utility patents. Third-party
products are always mentioned without any reference to patent rights. Thus, the
existence of such rights cannot be excluded.
1.1.2
Copyright
This Manual, including all figures and illustrations, is copyright-protected. Any
further use of this Manual by third parties that violate pertinent copyright
provisions is prohibited. Reproduction, translation, electronic and phototechnical
filing/archiving (e.g., photocopying) as well as any amendments require the
written consent of WAGO Kontakttechnik GmbH & Co. KG, Minden, Germany.
Non-observance will involve the right to assert damage claims.
1.1.3
Personnel Qualification
The use of the product detailed in this document is exclusively geared to
specialists having qualifications in PLC programming, electrical specialists or
persons instructed by electrical specialists who are also familiar with the valid
standards. WAGO Kontakttechnik GmbH & Co. KG declines any liability
resulting from improper action and damage to WAGO products and third party
products due to non-observance of the information contained in this document.
1.1.4
Intended Use
For each individual application, the components are supplied from the factory
with a dedicated hardware and software configuration. Modifications are only
admitted within the framework of the possibilities documented in this document.
All other changes to the hardware and/or software and the non-conforming use of
the components entail the exclusion of liability on part of WAGO Kontakttechnik
GmbH & Co. KG.
Please direct any requirements pertaining to a modified and/or new hardware or
software configuration directly to WAGO Kontakttechnik GmbH & Co. KG.
a302510e
Important Notes
1.2
5
Scope of Validity
This application note is based on the stated hardware and software of the specific
manufacturer as well as the associated documentation. This application note is
therefore only valid for the described installation.
New hardware and software versions may need to be handled differently.
Please note the detailed description in the specific manuals.
1.3
Number Notation
Table 1: Number Notation
Number code
Decimal
Hexadecimal
Binary
1.4
Example
100
0x64
'100'
'0110.0100'
Note
Normal notation
C notation
In quotation marks, nibble separated with
dots (.)
Font Conventions
Table 2: Font Conventions
Font type
italic
Menu
>
Input
“Value”
[Button]
[Key]
a302510e
Indicates
Names of paths and data files are marked in italic-type.
e.g.: C:\Programme\WAGO-I/O-CHECK
Menu items are marked in bold letters.
e.g.: Save
A greater-than sign between two names means the selection of a
menu item from a menu.
e.g.: File > New
Designation of input or optional fields are marked in bold letters,
e.g.: Start of measurement range
Input or selective values are marked in inverted commas.
e.g.: Enter the value “4 mA” under Start of measurement range.
Pushbuttons in dialog boxes are marked with bold letters in square
brackets.
e.g.: [Input]
Keys are marked with bold letters in square brackets.
e.g.: [F5]
6
2
Description
Description
Library “WagoLibMSSQL_03.lib” provide function blocks for accessing
Microsoft databases for executing SQL-Statements.
The “WagoLibMSSQL_03.lib” library will work with any WAGO Ethernet
controller and is based on the SysLibSockets.lib system library. It is expected that
the person using this library has a solid base knowledge of CoDeSys and the IEC
61131-3 standard.
The configuration of Microsoft SQL Server takes a little time, for this application
we used ‘Microsoft SQL Server Management Studio Express’ with SQL Server
Configuration Manager – both freely available from the Microsoft website.
This application note covers those steps as well as some of the more common
errors that could occur from an incorrect set-up as well as an example of how to
use the library in an application.
2.1
Components
Table 3: Components
Supplier
WAGO
WAGO
Pieces Name
1
Programmable Fieldbus Controller
1
End Module
WAGO
Microsoft
Microsoft
Microsoft
Microsoft
1
1
1
1
1
Item No.
750-8xx
750-600
WAGO-I/O-PRO CAA
759-333
SQL Server 2005(EXPRESS)
SQL Server 2008(EXPRESS)
SQL Server Management Studio Express’
SQL Server Configuration Manager
Trademarks: All terms mentioned in this document that are known to be
trademarks or service marks have been appropriately capitalized.
Use of a term in this document should not be regarded as affecting the validity of
any trademark or service mark. Microsoft is a registered trademark of Microsoft
Corporation. SQL Server is a trademark of Microsoft Corporation.
a302510e
Setup database
3
7
Setup database
Follow the online guide on Microsoft’s website to download and install
‘Microsoft SQL Server Management Studio Express Edition’ and all other
relevant software (Microsoft Core XML Services (MSXML) 6.0 and Microsoft
.NET Framework 2.0.). These are available on the Microsoft web site.
3.1
Enable TCP/IP
After installation TCP/IP driver is disabled by default and have to be enabled
manually.
Enable TCP/IP access to database by selecting
Start>Programs>Microsoft SQL Server 2005> Configuration Tools> SQL Server
Configuration Manager.
In the configuration manager expand SQL Server 2005 Network Configuration on
the left of the window and then select Protocols for SQLEXPRESS
Check minimum system specification on Microsoft’s website for the SQL Server
package. This has been tested with SQL Express 2005 and 2008. For more
information on SQL Server components beyond this application note, please
consult the Microsoft web site.
a302510e
8
Setup database
If TCP/IP isn’t enabled – right click on it and select Enable
Double click on TCP/IP and expand register card “IPAll”
Edit the TCP Port to the TDS default port 1433.
The port number is also used as input parameter of the MSSQL_Login function
block and can be changed to meet your IT requirements.
a302510e
Setup database
3.2
Enable “SQL Server Authentication”
SQL Server provides two different authentication methods:
- “Windows-Authentication” (Enabled by default)
- “SQL Server Authentication”(Disabled by default).
Libraries function block “MSSQL_Login” utilizes “SQL Server Authentication”,
where database user and password are input parameters who must match with the
one stored inside the database self.
Open Microsoft SQL Server Management Studio Express.
Select Database Engine, and Windows Authentication as shown in the screenshot
below.
For Server name: select <Browse for more…>.
In the new window, select the Network Servers tab and wait a few seconds while
it retrieves data.
Eventually you will see the Database Engine displayed only, expand this and
select the SQLEXPRESS Server.
a302510e
9
10
Setup database
Click OK to connect to the Server.
Now in the object explorer section, right click on the server and select Properties
from the drop down menu.
Choose the Security page and in the Server authentication section select SQL
Server and Authentication mode
After clicking OK you will be told that you need to restart the SQL Server.
a302510e
Setup database
You can do this in the object explorer section, right click on the server as before
but this time select Restart from the menu.
Wait for the server to restart, current state are displayed with green or red icon.
a302510e
11
12
3.3
Setup database
Enable remote connection
Open the SQL Server Service Area Configuration.
The following dialog should be displayed
Select Surface Area Configuration for Services and Connections
Select Remote Connections and then on the right choose 'Local and remote
connections' and press button “Apply”.
a302510e
Setup database
The final bit to check here is in the SQL Server Browser.
Select Service and check that Startup type: is set to Automatic.
a302510e
13
14
3.4
Setup database
Enable or create database account ‘sa’
In Microsoft SQL Server Management Studio Express, go to the object explorer
and expand the Security folder then the Logins folder.
If ‘sa’ doesn’t exist here, right click on the Logins folder and select New Login…
If it already exists then double click on it.
Create the login name sa if it isn’t already there.
Set the password to wago00 (2 zeros) which is the password used in the CoDeSys
example project.
You are free to create other user with more or less access rights, just update login
creditals in example project.
a302510e
Setup database
3.5
15
Create database ‘testdb’
In Microsoft SQL Server Management Studio Express, go to the object explorer
and right click the Databases folder.
Select New Database and enter “testdb” as the Database name.
Refresh
a302510e
the object explorer then open the newly created testdb folder.
16
Setup database
In here right click on the Tables folder and choose New Table… Following steps
1 to 3 in the screenshot below
After saving this new table the SQL set-up should now be complete.
Alternative you can execute attached SQL-Script “Create_aTable.sql” in
Microsoft SQL Server Management Studio Express, to create the table “aTable in
one step.
“Menu-> File -> Open -> File ...” or press [Crtl + O] will show File open dialog.
Browse to location where “Create_aTable.sql” stored and open it.
Run SQL-CREATE-Statement with “Menu -> Query -> Execute”.
Microsoft SQL Server Management Studio also useful to take a look into current
content of a table, just a right click on the table of interest open the background
menu. Select “Open Table” will show table data with the opportunity to modify it.
You can also use function block “MSSQL_Execute” to create databases and
tables from your CoDeSys application, because SQL-CREATE-Statements are
nothing else then SQL-Statements who do not return result sets, like INSERT,
UPDATE, DELETE, DROP, ALTER and so on.
a302510e
WagoLibMSSQL03_Example01.pro
4
17
WagoLibMSSQL03_Example01.pro
Copy library file “WagoLibMSSQL_03.lib” into folder ‘CoDeSys
V2.3\Targets\WAGO\Libraries\Application\’ first.
The start of this program demonstrates how to connect to a database and then add
values to a table named ‘aTable’ in the ‘testdb’ database.
Below is an example of what the MSSQL_Login function block should look like
in your application.
Function block MSSQL_Login establish the connection to your server.
Be sure to match the parameters here to those on your server.
To run this change the “xConnect” variable to TRUE.
Verify function blocks output params “diError“, “sStatus” and “xConnected” that
the connection is established.
Don’t forget to Logout after work is done, otherwise you will waste performance
and memory on server machine. Also you can not be shure that a TCP/IP
connection is working for days and weeks.
To run this change the “xDisonnect” variable to TRUE.
a302510e
18
WagoLibMSSQL03_Example01.pro
The next thing we will do is inserting some data into the database.
There for we need a SQL INSERT statement.
What we will do is hard code a few values, these will likely be variables in your
application. GETDATE() calls a database function who returns servers local time.
Its recommended to build and test your SQL-Statement in the SQL Management
Studio prior to coding it to ensure proper syntax.
INSERT INTO aTable
(aLongDT, aBool, aDint, aReal, aNVarChar)
VALUES
(GETDATE(), 1, 12345, 1.73, 'Hello world')
Because the apostrophe [’] character in CoDeSys used as STRING-BEGIN and
STRING-END identifier, each occurrence within the SQL-Statement have to be
“escaped” by character [§].
So that final CoDeSys-SQL-Statement looks like below:
sSql := 'INSERT INTO aTable
(aLongDT, aBool, aDint, aReal, aNVarChar)
VALUES
GETDATE(), 1, 12345, 1.73, $'Hello world$')’;
Take time to find the additional and the escaped apostrophe [’].
To run this, change the “xExec1” variable to TRUE. The “xExec1” variable will
reset itself upon completion.
Again, check “diError” and “sStatus” to make sure the command executed.
If you received no errors, this will have inserted a record into your database
a302510e
WagoLibMSSQL03_Example01.pro
19
Next step is to retrieve data from the database.
First we need a SQL-SELECT-Statement, this example will get all data sets from
table “aTable”.
SELECT * from aTable
Next, the asSqlStatement2 needs to be populated with our query.
asSqlStatement2[0] := ‘SELECT * from aTable’;
asSqlStatement2[1] := ‘’; (* END OF SQL-Statement*)
After the statement is populated,
Getting the results from the database from CoDeSys requires a few things more in
your application.
In the example application we have created two user defined data types, one
labelled “RowData” and the other “TableData”, where “RowData” descripes all
columns of the table as in IEC-Datatypes.
“TableData” will be filled in the Convert2IEC action of PLC_PRG and hold the
query data.
To run the query, set “xQuery2” variable to TRUE. The “xQuery2” variable will
reset itself upon completion.
This will send the SQL command to the database and the status will come back at
‘Successful executed’ and list the number of rows that it returned.
Now the Convert2IEC action is run, and this will break apart the binary data from
the query into meaningful records.
The resulting data set is pictured above. For the example, I edited a couple of the
records in the MSSQL Server tool to show they are different
a302510e
20
WagoLibMSSQL03_Example01.pro
It is important to understand that the WagoLibMSSQL_03 has no knowledge
about the structure and dataypes of a query result set.
There are helper functions written to get the different data types from the MS
format and convert them to IEC format (CoDeSys.)
So after some error checking the Convert2IEC action comes to converting field 1,
and executes the MSSQL_GetDATETIME.
If the database you are connected to varies, the changes to this routine happen
here where the data is broken up.
The routine can be followed with the comments to see where columns 2, 3, 4 and
5 are also converted to their respective data types.
a302510e
Serie
Artikelnummer Artikelbezeichnung
[eof]
a302510e
21
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880
D-32385 Minden
Hansastraße 27
D-32423 Minden
Phone:
+49/5 71/8 87 – 0
Fax:
+49/5 71/8 87 – 1 69
E-Mail:
info@wago.com
Internet:
http://www.wago.com