Bulletin 20-18 / March 2011 M1218 Air Handler FEATURES AND CONTROLS The following table shows a comparison of the various features. Applications The Unico System is a complete indoor comfort system that includes an indoor fan coil unit and small duct system. The fan coil unit and duct system were designed to operate together to provide the proper airflow in every installation. The conditioned air is supplied through a series of two-inch diameter ducts as a stream of air that entrains and mixes with the room air. This process of aspiration produces a more even temperature distribution in the room than a conventional system. The Unico M1218 Fan Coil unit is a single packaged unit. The cooling and heating coils are contained within the same cabinet. The unit can be mounted in a verticalupflow or horizontal-flow configuration. The coils can be combined as a heating-only, cooling-only, or heating and cooling fan coil unit. For cooling, the M1218 is designed for R-410A refrigerant (both A/C and Heat Pump) or a chilled water coil. For heating, the M1218 offers an optional hot water, or you may use the installed heat pump coil or chilled water coil (using hot water), or you may use an electric heater (WON 0502 or WON 0752). The M1218 is designed to deliver up to 350 CFM (0.17 m3/s) of air with a static pressure of 1.5 inches of water (373 Pa). The minimum airflow for refrigerant systems is 200 CFM per nominal ton (27 L/s per nominal kW) Cabinet Construction The cabinet is fully insulated with closed cell insulation. There is no exposed fiberglass inside the cabinet. The cabinet is constructed of 22 gauge (0.7-mm) galvanized steel with removable access panels on both sides for ease of service. See Dimension drawing. INT ERTEK CM US C LISTED CERTIFIED TO UL STD 1995 CONFORMS TO CAN/CSA STD C22.2 NO. 236 Control Box Configuration Balanced wheels Direct drive motor Shaft key connection Recessed control panel Control voltage transformer Screw terminal connections Heat pump AFS bypass Boiler relay Number of modes of operation Adjustable low airflow mode Efficient ventilation mode Adjustable restrictor plate Point-to-point wiring Electric heater fan interlock Electric heater stage 3 lockout protection Chilled water relay Air cycle feature EAC, HRV, or ERV relay Potable water circulation Humidifier compatibility UniChiller Leader/Follower control Soft-start and Soft-stop Constant airflow Low airflow indicator Preset airflow settings Laptop configurable Laptop troubleshooting Optimized for zone damper systems Optimized for efficiency and sound STD ACB ECx ** 2 2 6 ** with separate relay included in cooling module Balanced wheels – All blower wheels are individually balanced. Direct drive motor – The wheel is mounted directly to the motor shaft to improve drive efficiency and lower costs. Shaft key – The wheel is attached to the motor shaft using a square keyway which is more secure than a simple set screws. Recessed control panel – The control panel is recessed in the cabinet on the connection side. Knockouts are available for incoming power. All control panels include the following features: Control voltage transformer – a 50VA 24-volt transformer which provides control voltage power to the thermostat, electric heaters, and other optional equipment. 81037 © Copyright 2011 Unico, Inc. Bulletin 20-18 — Page 2 Screw terminal connections – terminal blocks with large screws and wire washers to securely connect the control wires. as part of a domestic water system to prevent the formation of stagnant water. Heat pump AFS bypass – removes the anti-frost switch (AFS) from the circuit during heat pump heating mode which eliminates nuisance shutdowns during defrost mode. Humidifier compatibility (ACB and EC) – The control board includes the ability to connect a humidistat and a humidifier so that the humidistat turns on the humidifier when needed. The user may choose whether the fan with humidifier operates at high or low HEAT airflow setting. Boiler relay (ACB, EC) – The ACB and SCB includes a separate dry-contact relay to turn on the boiler, boiler pump, or hot water coil valve. (The STD control box includes room for a relay to be added.) UniChiller Leader/Follower control (ACB and EC) – The control allows one air handler to be set the UniChiller mode of operation as the ‘Leader’ with all other air handlers dependent (‘Follower’). Modes of operation – Both the STD and ACB controls allow for high and for low airflow modes. The EC control has 6 modes (FAN-ONLY, LOW-COOL, HIGH-COOL, LOW-HEAT, HIGH-HEAT, and EMERGENCY HEAT). The STD control allows the user to adjust the low airflow amount but is not very efficient. The EC control allows adjustability for every mode maintaining high efficiency. The ACB cannot be adjusted but provides high efficiency ventilation. Soft-start and soft-stop (ACB and EC) – For quieter operation, the unit will slowly ramp the motor from stop to full speed, and vice versa. Adjustable restrictor plate (STD, ACB models only) – The patented restrictor plate provides a low cost solution to finely adjust the airflow using a single or two-speed motor. The movable restrictor plate is accessible from the exterior of the front of the unit even with the duct installed. Point-to-point wiring (ACB and EC) – The control boards have separate terminals for the thermostat, electric heater, outdoor condenser, and other options for easy wiring and troubleshooting. Electric heater stage 3 lockout (ACB and EC) – The control board includes a lockout feature to prevent the third stage of the electric heater from turning on if the heat pump is also on. This prevents nuisance shutdowns from overheating the electric heater. This feature is available with the STD control box by using an outside thermostat. Chiller relay (ACB and EC )– The control box includes a separate dry-contact relay (ColdW) to turn on a chiller or zone pump. Air cycle (ACB and EC) – The control board includes a separate switch to provide periodic cycling of the fan to reduce the chance for water to collect in the ducts if located in a cold space and not used, or to provide periodic fresh air if connected to a fresh air source. EAC, ERV, or HRV (ACB and EC) – For the optimum in indoor equality, the control board includes a dry-contact relay to turn on an electronic air cleaner, energy recovery ventilator, or heat recovery ventilator any time the fan is on. Potable water circulation (ACB and EC) – For improved health safety, the control provides a switch selectable feature to turn on the boiler pump periodically if installed © Copyright 2011 Unico, Inc. Constant airflow (EC only) – The EC control will deliver the airflow requested without any user adjustments to the duct system, or requiring the user to measure the amperage. Low airflow indicator (EC only) – The S.M.A.R.T. control board (SCB) includes an indicator light that informs the user that the desired airflow is not being met, usually caused by a restrictive duct system or too few outlets. Pre-set air flow rate (EC only) – The SCB is preprogrammed for two different air flow rates for HIGHCOOL that can be selected with a board mounted switch. Each of the six different modes are a fixed percentage of this airflow. Laptop adjustable (EC only) – The airflow for each mode of operation is adjustable to any value between the blower minimum and maximum using the ECMconfig software (available for download at www.unicosystem.com) and an ordinary USB cable. Laptop troubleshooting (EC only) – The ECMconfig software will also provide the user with feedback indicating the actual airflow, motor speed, communications between the boards and the motor, and the state of various inputs and outputs. Optimized for zoning with hydronic systems (EC only) – The ECMconfig software provides an additional feature that allows the user to specify the maximum motor speed so that the motor does not over speed when zone dampers are closed. This prevents the need for bypass loops and pressure switch controls and reduces noise at the outlets caused by the blower trying to maintain a constant airflow with fewer outlets. Setting a maximum airflow to approximate constant static pressure should not be used with a single speed condensing unit. Refer to the Unico Tech Bulletin on zoning for more information. Optimized for efficiency and sound (EC only) – The EC control will use the lowest motor speed to achieve the required airflow, which minimizes sound and maximizes electrical efficiency. Bulletin 20-18 — Page 3 All dimensions in inches (mm) Blower Capacity Data – 1 ph / 230V / 60 Hz Motor Speed Static Pressure, inches of water (Pa) 1.0 (248) 2-Spd Standard 3 1.25 (310) 3 1.5 (372) 3 1.75 (435) 3 2.0 (496) 3 CFM (m /s ) Amps CFM (m /s ) Amps CFM (m /s ) Amps CFM (m /s ) Amps CFM (m /s ) Amps High 450 (0.21) 1.82 420 (0.20) 1.73 385 (0.18) 1.65 345 (0.16) 1.56 300 (0.14) 1.44 Med. 400 (0.19) 1.55 372 (0.18) 1.46 340 (0.16) 1.36 300 (0.14) 1.24 226 (0.11) 1.05 Low 350 (0.17) 1.41 325 (0.15) 1.32 295 (0.14) 1.22 245 (0.12) 1.06 — — High 465 (0.22) 1.59 441 (0.21) 1.45 398 (0.19) 1.35 352 (0.17) 1.28 274 (0.13) 1.19 Low EC Low-speed airflow is half of rated high speed airflow at 1.0 amp with static pressure less than 0.5 inches of water (125 Pa) The EC Motor adjusts RPM to maintain a desired airflow. Refer to page 8 for the performance map. Hot Water Coil Performance Entering Water Temperature °F GPM (L/s) 2 (0.13) 120 (48.9) 4 (0.25) 6 (0.38) 2 (0.13) 130 (54.4) 4 (0.25) 6 (0.38) 2 (0.13) 140 (60) 4 (0.25) 6 (0.38) 2 (0.13) 150 (65.5) 4 (0.25) 6 (0.38) 2 (0.13) 160 (71.1) 4 (0.25) 6 (0.38) 2 (0.13) 170 (76.7) 4 (0.25) 6 (0.38) Minimum Number of Outlets © Copyright 2011 Unico, Inc. °C 3 Water Flow rate Airflow, SCFM (m /s) 200 (0.09) Capacity MBH (KW) 9.9 (2.87) 10.5 (3.05) 10.6 (3.07) 11.9 (3.45) 12.6 (3.65) 12.8 (3.71) 14.0 (4.06) 14.7 (4.26) 14.9 (4.32) 16.0 (4.79) 16.9 (4.98) 17.1 (5.02) 18.1 (5.25) 19.0 (5.51) 19.2 (5.57) 20.1 (5.83) 21.1 (6.12) 21.4 (6.21) 6 300 (0.14) Capacity MBH (KW) 12.9 (3.74) 14.3 (4.15) 14.8 (4.29) 15.6 (4.52) 17.3 (5.02) 17.8 (5.16) 18.3 (5.31) 20.2 (5.86) 20.8 (6.03) 21.0 (6.50) 23.2 (7.05) 23.9 (7.22) 23.7 (6.87) 26.1 (7.57) 26.9 (7.80) 26.4 (7.66) 29.1 (8.44) 29.9 (8.67) 9 400 (0.19) Capacity MBH (KW) 15.1 (4.38) 17.4 (5.05) 18.2 (5.28) 18.2 (5.28) 20.9 (6.06) 21.9 (6.35) 21.4 (6.21) 24.5 (7.11) 25.7 (7.45) 24.6 (7.75) 28.1 (8.75) 29.4 (9.10) 27.8 (8.06) 31.7 (9.19) 33.2 (9.63) 31.0 (8.99) 35.4 (10.27) 36.9 (10.70) 12 WPD ft. water (KPa) 0.8 (2.39) 3.2 (9.57) 7.0 (20.93) 0.8 (2.39) 3.2 (9.57) 6.9 (20.63) 0.8 (2.39) 3.1 (9.27) 6.9 (20.63) 0.8 (2.39) 3.1 (9.27) 6.8 (20.33) 0.8 (2.39) 3.1 (9.27) 6.8 (20.33) 0.8 (2.39) 3.1 (9.27) 6.7 (20.03) Bulletin 20-18 — Page 4 Chilled Water Coil Performance (Cooling Mode) Entering Water Temperature 3 Water Flowrate Airflow, SCFM (m /s) 200 (0.09) 300 (0.14) Capacity Capacity °F °C GPM (L/s) MBH (KW) SHR MBH (KW) 2 (0.13) 11.1 (3.25) 0.62 14.1 (4.13) 4 (0.25) 11.9 (3.48) 0.61 15.8 (4.63) 40 (4.4) 6 (0.38) 12.5 (3.66) 0.60 17.2 (5.04) 2 (0.13) 8.6 (2.52) 0.66 10.7 (3.14) 4 (0.25) 10.1 (2.96) 0.63 13.3 (3.90) 45 (7.2) 6 (0.38) 10.6 (3.11) 0.62 14.5 (4.25) 2 (0.13) 6.9 (2.02) 0.72 8.7 (2.55) 4 (0.25) 8.1 (2.37) 0.68 10.7 (3.14) 50 (10.0) 6 (0.38) 8.5 (2.49) 0.67 11.6 (3.40) 2 (0.13) 5.3 (1.55) 0.83 6.9 (2.02) 4 (0.25) 6.0 (1.75) 0.77 8.0 (2.34) 55 (12.8) 6 (0.38) 6.3 (1.84) 0.76 8.6 (2.52) Minimum Number of Outlets 6 9 *Entering Air Temperature 80°F (26.7°C) dry bulb / 67°F (19.4°C) wet bulb Entering Water Temperature SHR 0.67 0.64 0.62 0.75 0.68 0.65 0.82 0.74 0.71 0.92 0.85 0.82 WPD ft. water (KPa) 1.2 (3.60) 4.6 (13.80) 9.9 (29.70) 1.1 (3.30) 4.5 (13.50) 9.9 (29.70) 1.1 (3.30) 4.5 (13.50) 9.8 (29.40) 1.1 (3.30) 4.5 (13.50) 9.7 (29.10) SHR 0.72 0.70 0.68 0.82 0.76 0.73 0.92 0.85 0.82 1.00 1.00 1.00 WPD ft. water (KPa) 1.2 (3.60) 4.6 (13.80) 9.9 (29.70) 1.1 (3.30) 4.5 (13.50) 9.9 (29.70) 1.1 (3.30) 4.5 (13.50) 9.8 (29.40) 1.1 (3.30) 4.5 (13.50) 9.8 (29.40) 3 Water Flowrate Airflow, SCFM (m /s) 200 (0.09) 300 (0.14) Capacity Capacity °F °C GPM (L/s) MBH (KW) SHR MBH (KW) 2 (0.13) 9.1 (2.66) 0.67 11.7 (3.42) 4 (0.25) 9.7 (2.84) 0.66 12.9 (3.77) 40 (4.4) 6 (0.38) 10.1 (2.95) 0.65 14.0 (4.09) 2 (0.13) 6.8 (1.99) 0.74 8.6 (2.52) 4 (0.25) 7.9 (2.37) 0.70 10.5 (3.07) 45 (7.2) 6 (0.38) 8.2 (2.46) 0.69 11.3 (3.30) 2 (0.13) 5.2 (1.56) 0.83 6.8 (2.00) 4 (0.25) 5.9 (1.73) 0.78 8.0 (2.34) 50 (10.0) 6 (0.38) 6.2 (1.82) 0.77 8.5 (2.49) 2 (0.13) 3.7 (1.09) 1.00 5.0 (1.47) 4 (0.25) 4.0 (1.18) 0.96 5.6 (1.65) 55 (12.8) 6 (0.38) 4.1 (1.21) 0.95 5.8 (1.71) Minimum Number of Outlets 6 9 *Entering Air Temperature 75°F (23.9°C) dry bulb / 63°F (17.2°C) wet bulb © Copyright 2011 Unico, Inc. SHR 0.64 0.62 0.61 0.71 0.65 0.64 0.78 0.71 0.69 0.88 0.81 0.79 400 (0.19) Capacity MBH (KW) 16.0 (4.68) 18.7 (5.47) 20.9 (6.11) 12.2 (3.58) 15.7 (4.61) 17.5 (5.14) 10.1 (2.96) 12.7 (3.72) 14.0 (4.09) 8.2 (2.40) 9.7 (2.84) 10.5 (3.07) 12 SHR 0.70 0.68 0.66 0.79 0.73 0.71 0.88 0.82 0.79 1.00 1.00 0.97 400 (0.19) Capacity MBH (KW) 13.5 (3.95) 15.3 (4.48) 17.0 (4.98) 10.0 (2.93) 12.5 (3.66) 13.7 (4.01) 8.1 (2.37) 9.6 (2.81) 10.4 (3.04) 5.9 (1.73) 7.0 (2.05) 7.3 (2.14) 12 Bulletin 20-18 — Page 5 Chilled Water Coil Performance (Heating Mode) Entering Water Temperature °F (L/s) 200 (0.09) Capacity MBH 300 (0.14) Capacity 400 (0.19) Capacity MBH (KW) MBH 2 (0.13) 4.9 (1.44) 4 (0.25) 4.9 (1.44) 6 (0.38) 4.9 (1.44) 2 (0.13) 7.9 (2.30) 4 (0.25) 7.9 (2.30) 110 (43) 6 (0.38) 7.9 (2.30) 2 (0.13) 9.8 (2.85) 4 (0.25) 9.8 (2.85) 120 (49) 6 (0.38) 9.8 (2.85) 2 (0.13) 13.8 (3.99) 4 (0.25) 13.8 (3.99) 140 (60) 6 (0.38) 13.8 (3.99) 2 (0.13) 17.7 (5.14) 4 (0.25) 17.7 (5.14) 160 (71) 6 (0.38) 17.7 (5.14) 2 (0.13) 21.8 (6.38) 4 (0.25) 21.8 (6.38) 180 (82) 6 (0.38) 21.8 (6.38) Minimum Number of Outlets 6 *Entering Air Temperature 70°F (21°C) dry bulb 6.7 7.2 7.3 10.9 11.6 11.7 13.7 14.5 14.6 19.4 20.4 20.5 25.1 26.3 26.4 30.8 32.2 32.3 (1.97) (2.12) (2.14) (3.20) (3.39) (3.41) (4.01) (4.21) (4.23) (5.68) (5.92) (5.94) (7.35) (7.63) (7.65) (9.02) (9.34) (9.37) 8.0 9.1 9.3 13.1 14.7 14.9 16.6 18.4 18.7 23.5 25.9 26.4 30.4 33.4 34.0 37.4 40.8 41.6 (35) GPM Airflow, SCFM (m /s) (KW) 95 °C 3 Water Flowrate 9 (KW) (2.35) (2.67) (2.73) (3.84) (4.30) (4.36) (4.86) (5.34) (5.41) (6.88) (7.51) (7.73) (8.90) (9.70) (9.87) (10.86) (11.85) (12.08) 12 WPD ft. water 1.1 4.3 9.3 1.1 4.2 9.2 1.1 4.2 9.1 1.1 4.1 8.9 1.1 4.0 8.7 1.1 3.9 8.6 WARNING – To prevent injury from high temperatures, do not install floor outlets when operating with water above 160°F. © Copyright 2011 Unico, Inc. (KPa) (3.28) (12.84) (27.75) (3.28) (12.43) (27.45) (3.28) (12.43) (27.15) (3.28) (12.19) (26.55) (3.28) (11.98) (25.95) (3.28) (11.60) (25.65) Bulletin 20-18 — Page 6 Engineering Specifications Unico Part No. Construction Dimensions, inch (mm): Shipping weight, lb (kg): Cabinet Type: Insulation: Drain pan: Drain pan connection: Standard Return Duct ID, in (mm): Standard Plenum ID, in (mm): 12 H x 20 W x 38 L (305H x 508W x 965L) 92 (42) Galvanized 1 inch (25 mm) closed cell vinyl nitrile Stainless Steel 1/2 inch FPT 12 (305) 7.0 (178) Electrical Type: PSC (STD & ACB) EC (SCB) Fan Relay: Transformer: 1 ph - 60/50 Hz - 208/230V 1 ph - 60/50 Hz - 100/120V 1 ph - 60/50 Hz - 208/230V Snap acting with inherent time-delay 50 VA, 230/208V-24V A00175-G10 A00175-G07 A00056-G02 A00057-G02 1/3 (0.25) ½ (0.37) A00331-001 Standard A00974-001 Two-speed A01426-002 Motor Size, hp (kW): PSC EC (variable speed) Motor Speed, RPM PSC EC (variable speed) FLA: RLA: Bearing Type: 1700/1550/1350 1800/VAR 1.9 (PSC), 5.6 (EC@120V), 3.2 (EC@230V) Refer to Amperage Chart Permanently Lubricated Ball Blower Wheel 3 Airflow, CFM (m /s): Static Pressure**, in. wc (Pa) Type: Nom. Diameter, inch (cm): Width, inch (cm): See table See table SISW Forward Curved 9.5 (24) 1.5 (3.8) A00137-003 Refrigerant Coil (AC or HP option) Nominal Capacity, tons (kW): 3 Rated Airflow, CFM (m /s): 3 Min. Airflow, CFM/ton (m /s•kW): Refrigerant Type: Face Area, ft² (m²): Number of Rows: Number of Circuits: Fin Density, fins/in. (fins/cm): Fin Type and pattern, in. (mm): Tube Diameter, in (mm): Tube Type: Expansion Device: Liquid Line Connection OD, in. (mm): Suction Connection OD, in. (mm) : 1 to 1.5 (3.5 to 5) 400 (0.189) 200 (0.027) R407C, R410A 1.167 (0.108) 6 3 15 (6) Corrugated, 1 x 0.625 (25.40 x 15.88) 3/8 (9.53) Rifled TXV with Bleed Port and Check Valve 3/8 (9.53) 5/8 (15.88) Chilled Water Coil (CW option) Fluid Type 2 2 Face Area, ft (m ): Number of Rows: Number of Circuits: Fin Density, fins/in. (fins/cm): Fin Type and pattern, in. (mm): Tube Diameter, in (mm): Connection OD SWT, in (mm): Water or Glycol-Water Solution 1.167 (0.108) 6 6 15 (6) Corrugated, 1 x 0.625 (25.40 x 15.88) 3/8 (9.53) 5/8 (15.87) Hot Water Coil (HW option) Fluid Type Face Area, ft² (m²) Number of Rows Number of Circuits Fin Density, fins/in. (fins/cm): Fin Type and pattern, in. (mm): Tube Diameter, in (mm): Connection OD SWT, in (mm): Water or Glycol-Water Solution 1.0 (0.093) 4 6 10 (4) Raised Lance, 1 x 0.866 (25.40 x 22.00) 3/8 (9.53) 5/8 (15.87) A00326-001 A00366-002 (R410A) A00397-001 HW-1218 ** Static pressure across unit without hot water coil, using 6 inch ID plenum. Motor speed factory default is medium. Static pressure will be greater © Copyright 2011 Unico, Inc. when using 7 inch ID plenum. Bulletin 20-18 — Page 7 Blower Capacity Data (PSC motors) Wheel: FC950-200D Housing: 950M Motor: 1/3 HP, 1700 RPM (Dayton Model 9DM89) Equip: M1218+AC Supply: Metal duct, 7" dia., 5 feet to tee, then horseshoe configuration Return: UPC-104-1218 (12" flex) connected to UPC-01-1218 (14 x 20" filter) with two 90° bends Temperature: 66.2°F dry bulb L/s 50 100 150 L/s 200 0 1700 1700 1600 1600 1500 1500 RPM RPM 0 Wheel: FC950-200D Housing: 950M Motor: 1/3 HP, 1700 RPM (Dayton Model 9DM89) Equip: M1218+AC Supply: Metal duct, 7" dia., 5 feet to tee, then horseshoe configuration Return: UPC-104-1218 (12" flex) connected to UPC-01-1218 (14 x 20" filter) with two 90° bends Temperature: 66.2°F dry bulb M1218 60Hz High Speed 1400 50 100 M1218 60Hz Medium Speed 150 200 1400 1300 400 V 8 230 20 1300 400 V 250 V 230 V V 250 300 Watts Watts 300 200 200 208V 100 2.0 100 2.0 V 208 230V 8V 20 Amps Amps 1.5 1.0 1.0 0.5 0.5 500 2.0 1.5 300 Pa 400 1.0 300 1.0 0 50 100 150 200 250 300 350 400 Airflow, CFM 50 100 500 0 0 50 100 150 200 250 300 350 400 Airflow, CFM 0 1600 1600 1500 1500 RPM 1700 1400 1400 1300 400 1300 50 300 500 M1218+CB 60 Hz 208-250V L/s 200 1700 450 R0301 _ Catalog Graph3 1/15/2003 Tested by: J. Riley Approved by: C. Messmer Wheel: Revcor BC950-150S Housing: Revcor 950M Motor: 1/3 HP, 1625 RPM, Dayton A19844 Equip: M1218 + AC Supply: 7" sheet metal duct to 9" sheet metal, straight to 1 tee, horse shoe Return: 12" with filter across the duct opening (no grille) Temperature: 68.9F, 32.4% RH M1218 60Hz Low Speed 150 100 0.0 R0301 _ Catalog Graph1 1/15/2003 Tested by: J. Riley Approved by: C. Messmer Wheel: FC950-200D Housing: 950M Motor: 1/3 HP, 1700 RPM (Dayton Model 9DM89) Equip: M1218+AC Supply: Metal duct, 7" dia., 5 feet to tee, then horseshoe configuration Return: UPC-104-1218 (12" flex) connected to UPC-01-1218 (14 x 20" filter) with two 90° bends L/s Temperature: 66.2°F dry bulb 0 450 200 0.5 0 0.0 400 1.5 0V 25 0V 23 0V 25 100 500 8V V 08 0V 2 23 0.5 200 600 Pa 2.5 20 Static Pressure, in. wc 2.0 600 Static Pressure, in. wc 2.5 RPM V 230 V 250 V 250 1.5 100 150 200 High Speed Watts Watts 300 200 200 100 Low Speed 230V 250V 208V 100 2.0 0 2.0 8V 20 V 230 V 250 1.5 1.0 1.0 0.5 Low Speed 0.5 2.5 600 1.5 300 1.0 200 0.5 100 100 150 200 250 300 Airflow, CFM © Copyright 2011 Unico, Inc. 350 0V 50 400 0V 25 V 0 23 8 20 0.0 450 0 500 R0301 _ Catalog Graph2 1/15/2003 Tested by: J. Riley Approved by: C. Messmer Pa 400 Static Pressure, in. wc 500 2.0 600 High Speed 2.0 500 400 1.5 300 1.0 200 Low Speed 0.5 100 0.0 0 0 50 100 150 200 250 300 Airflow, CFM 350 400 450 500 0337 Graph7 01/15/2004 Tested by: J. Riley Approved by: C. Messmer Pa 2.5 Static Pressure, in. wc High Speed Amps Amps 1.5 Bulletin 20-18 — Page 8 Blower Capacity Data (EC motor) 0.02 0.04 0.06 0.08 0.10 0.16 0.18 0.22 0.24 Default Settings A: 300 CFM, 1.2" , 165 W B: 400 CFM, 1.2" , 240 W 2.8 2.6 W Max RPM 1800 2.2 0.70 0.65 0.55 0.50 0 25 2.0 W 1600 0.45 0 15 1.8 0.26 0.60 0 20 2.4 W 1.6 0.40 0W 30 Static Pressure (IN WC) 0.20 1.4 1400 10 0 0.35 W A 1.2 B 0.30 1200 1.0 0.8 Static Pressure (kPa) 0.00 U1218L-1EC1,1EC2 3 m /s 0.12 0.14 0.25 0.20 1000 0.6 0.15 50 W 800 0.4 600 0.2 0.10 25 W 0.05 400 0.0 0 50 100 150 200 250 300 350 400 450 Flow Rate (CFM) R1014- Operating Envelope M1218EC Rev. AR * Shaded Area Represents the Operating Range Transmission Loss for Common Construction, dB ACOUSTICAL DATA Frequency, Hz Sound is always present in our lives and is important to comfort. Understanding how sound is defined is essential to understanding how to design a proper Unico System. Sound is defined as a physical disturbance in pressure that is detectable by the human ear. Sound is usually presented as Sound Pressure Level (SPL) in decibels (dB), but can also be presented as Sound Power Level (SWL). Sound pressure is what you hear so it is the only value that is important to the occupant. However, determining the value is difficult because it is dependent on the surroundings and distance from the sound source. For instance, a carpeted room is much quieter than a room with wood floors. The data shown in this catalog was measured in a large room with hard surfaces for the walls and floor. It is considered to be the worst case (i.e. loudest) situation. The sound level in the occupied space will always be considerably less than this, depending on where the unit is located. To determine the actual sound level, subtract the TL for the barrier from the sound data of the unit. The table below shows typical TL values for common construction configurations. Subtract these values from the Unico air handler data. © Copyright 2011 Unico, Inc. 1k 2k 4k R Sheet Metal, 24 GA 125 250 500 13 17 20 27 34 39 18 Ceiling Tile, mineral fiber 13 21 27 31 35 40 20 Gypsum Frame wall 12 23 31 38 42 37 20 Gypsum Frame wall, insul. 15 30 32 43 46 38 23 Wood Floor, uninsulated 22 28 37 43 46 43 25 Wood Floor, insulated 29 40 51 57 60 58 26 Concrete Block, 190-mm 38 41 43 50 55 61 26 Concrete, 100-mm (4 in.) 41 41 45 52 56 64 26 Ref: Handbook of Acoustical Measurements and Noise Control, 1998 R = Overall Loss for typical Blower Module (based on MB4260H-50HZ) M1218 90 50 Hz 60 Hz 80 Sound Pressure Level, dB re 20 Pa For the Unico System, it is also important to consider sound transmission losses through ceilings and walls. The blower is never placed in the occupied room so the sound is always less than the published value. This reduction in sound level depends on the construction of the ceiling or wall. For instance, a ceiling structure made of gypsum board with insulation above it will have a much greater sound transmission loss (TL) than a dropped ceiling without insulation. 0.00 550 500 300 CFM (142 L/s) 70 60 NC-60 NC-55 50 NC-50 NC-45 40 NC-40 NC-35 30 NC-30 Measured 3 ft. (1 m) from unit (side opposite control box) 21 ft. x 35 ft. lab (school classroom). Tested 9/12/2002 and 2/26/2004 20 10 31.5 63 125 250 500 1k NC-25 2k Octave Band Center Frequency, Hz 4k 8k
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertising