Compressed Air Monitoring according to ISO SANS 7396

Compressed Air Monitoring according to ISO SANS 7396
Dew point
Compressed Air
Monitoring
according to
ISO/ SANS 7396-1
for Hospitals,
Laboratories and
Pharmaceutical Industries
www.cs-instruments.co.za
1
Dew point
Dew point set DS 400
Special features:
• 3.5“ graphic display - easy operation with
touch screen
according to ISO/ SANS 7396-1
• Dew point monitoring with alarm function ( ml/m³ / ppm)
• Optional pressure compensation
• 2 alarm contacts (230 VAC, 3 A) pre- and
main alarm freely adjustable
• NEW: An alarm delay can be set for
each alarm relay
Dew point set DS 400
• 4...20 mA analogue output
consisting of:
• Option: Ethernet and RS 485 interface
(Modbus protocol)
- Option alarm unit (buzzer and continuous red light)
- Chart recorder DS 400
• System ready for plug-in: Everything
completely wired
-USB interface
• Option: Webserver
- Standard
measuring
chamber
Option: Integrated data logger
• Recording of the dew point progression
of up to 100 million measuring values
- Dew point
sensor
FA 410
- 2nd sensor input for dew
point or consumption sensor
- Optional: Ethernet- and
RS 485 interface
Pressure
sensor
• CS Soft Basic for evaluation in graphic
and table form. Read-out of the data
either via USB stick or via Ethernet
www.cs-instruments.
Technical data DS 400
Dimensions:
118 x 115 x 98 mm
IP 54 (wall housing)
92 x 92 x 75 mm
(panel mounting)
Inputs:
2 digital inputs for FA
410 resp. VA 400/420
Interface:
USB
Power supply:
100...240 VAC, 50-60
Hz
Accuracy:
please see FA 410
Alarm outputs:
2 relays, (pot.-free)
Description
Order No.
Options:
Dew point set DS 400 for adsorption dryers (-80...+20 °Ctd)
0601 0410
Data logger:
Virtual channels for dew point monitoring in ppm with the option of actual pressure measurement for pressure fluctuation compensation.
Z500 4007
Alarm unit mounted at wall housing
Z500 0003
100 million measuring
values start/stop time,
measuring rate freely
adjustable
Alarm unit for external mounting with 5 m cable
Z500 0004
2 additional sensor inputs:
for connection of
pressure sensors,
temperature sensors,
clamp-on ammeters,
third-party sensors
with 4...20 mA 0 to 10
V, Pt 100, Pt 1000
Options
2
Standard pressure sensor CS 16 from 0…16 bar
0694 1886
Connection cable 5 m
0553 0108
Integrated data logger for 100 million measured values
Z500 4002
Integrated Ethernet and RS 485 interface
Z500 4004
Technical data FA 410
Integrated webserver
Z500 4005
Measuring range:
2 additional sensor inputs for analogue sensors (pressure sensor, temperature
sensor and so on)
Z500 4001
-80...20 °Ctd resp.
-20...50 °Ctd
Accuracy:
± 1 °C at 20...-20 °Ctd
± 2 °C at -20...-50 °Ctd
± 3 °C at -50...-80 °Ctd
Pressure range:
-1...50 bar, special
version up to 350 bar
CS Soft Basic - data evaluation in graphic and table form - reading out of the
measured data via USB or Ethernet
0554 7040
Precision calibration at -40 °Ctd or +3 °Ctd including ISO certificate
0699 3396
Dew point
Additional compressed air quality
parameters according to ISO 8573-1
Residual oil content measurement - OIL check
The residual oil content sensor OIL check measures the vaporous residual oil content in the compressed air. By means of a sample taking a
representative part volume flow is taken from the compressed air and led to the OIL check.
Due to the continuous measurement threshold value exceeding will be recognized immediately and remedial actions initiated.
Description
Order No.
OIL-Check residual oil content measurement for vaporous residual oil content (DN 20-DN 40), 3-16 bar,
measuring range <0.01...5.000 mg/m³, including sampling probe (DN 20-DN 40), inspection certificate,
4...20 mA analogue output. Please order measuring section for sampling separately.
0699 0060
OIl-Check measuring section for sampling (DN 20, 3/4“, 16 bar, stainless steel, outer diameter 26.9 mm,
outer thread R 3/4“)
4000 2001
Ball valve G 3/8“ incl. connection fittings for installation between sampling probe and OIL-Check, cleaned
oil- and grease-free
3300 0004
Connection plug for 4...20 mA analogue output
3300 0005
Connection cable 5 m
0553 0108
DS 400 chart recorder with graphic display and touch screen operation
0500 4000 A
Option: Integrated data logger for 100 million measured values
Z500 4002
Option: Integrated Ethernet and RS 485 interface
Z500 4004
CS Soft Basic - data evaluation in graphic and table form - reading out of the measured data via USB or
Ethernet
0554 7040
OIL-Check versions for different pipe diameters:
OIL-Check - residual oil content measurement for vaporous residual oil content (DN 50 - DN 80), 3-16 bar, meas.range <0.01...5.000 mg/m³ including
sampling probe (DN 50 - DN 80), inspection certificate, 4...20 mA analogue output. Please order meas. section for sampling separately.
0699 0061
OIL-Check - residual oil content measurement for vaporous residual oil content (>DN 80), 3-16 bar, meas.range <0.01...5.000 mg/m³, incl. sampling
probe (customer-specific length), insp. certificate, 4...20 mA analogue output. Please order meas. section for sampling separately.
0699 0062
OIL-Check measuring section for sampling (DN 25, 1“), 16 bar, stainless steel, outer diameter 33.7 mm, R 1“
4000 2002
OIL-Check measuring section for sampling (DN 32, 1 1/4“), 16 bar, stainless steel, outer diameter 42.4 mm, R 1 1/4“
4000 2003
OIL-Check measuring section for sampling (DN 40, 1 1/2“), 16 bar, stainless steel, outer diameter 48.3 mm, R 1 1/2“
4000 2004
OIL-Check measuring section for sampling (DN 50, 2“), 16 bar, stainless steel, outer diameter 60.3 mm, R 2“
4000 2005
OIL-Check measuring section for sampling (DN 65, 2 1/2“), 16 bar, stainless steel, outer diameter 76.1 mm, R 2 1/2“
4000 2006
OIL-Check measuring section for sampling (DN 80, 3“), 16 bar, stainless steel, outer diameter 88.9 mm, R 3“
4000 2007
Stainless steel pipe 6x1 mm for horizontal installation, length max. 1000 mm including connection fittings
4000 2008
Particle counter PC 400
The highly precise optical particle counter PC 400 measures particles from a size of 0.1 µm and is therefore suitable
for monitoring of the compressed air quality class 1 (ISO 8573). The correct function the filtration elements mounted
in the compressed air is monitored and possible filter perforations are recognized immediately. The compressed air
flow through the particle counter is automatically supervised.
Description
Order No.
PC 400 particle counter up to 0.1 µm for compressed air and gases incl.
pressure reducer
0699 0040
Connection cable 5 m
0553 0108
DS 400 chart recorder with graphic display and touch screen operation
0500 4000 D
Option: Integrated data logger for 100 million measured values
Z500 4002
Option: Integrated Ethernet and RS 485 interface
Z500 4004
CS Soft Basic - data evaluation in graphic and table form - reading out of the measured data via USB or Ethernet
0554 7040
Alternative version to PC 400 up to 0.1 µm:
PC 400 particle counter up to 0.3 µm for compressed air and gases
incl. pressure reducer
0699 0041
www.cs-instruments.co.za
3
Dew point
CS Instruments [Pty] LTD
142 Briza Road
Table View
Cape Town, 7441
South Africa
Phone/ fax: +27 21 557 5618
Fax local: 086 695 5877
Cell: +27 76 942 6677
Email: info@cs-instruments.co.za
www.cs-instruments.co.za
4
www.cs-instruments.co.za
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising