DLP SERIES
DLP
DLP240
DLP180
DLP120
DLP100
DLP75
3
DLP-PU
Y
E
A
R
S
warranty
医 療
信
信
信
Single Output 75W - 240W
計 測
F A
半導体
F A
F A
医 療
その他
■ Features
■ Model naming method
DLP 75−24−1/ □
● DIN Rail mounting
● 半導体
Alarm (ALM) LED indicator
Red LED lit in overload or output shorted conditions
● Wide range of operating ambient temperatures
Operation with full load in -10℃ to +50℃
DLP75/100/120/180 -- Load: 60% at +60℃
半導体
DLP240 -- Load: 60% at +70℃
● Long hold-up time
100/230Vin: 20/30 ms
● DLP-PU
Diode boxes (2 units/maximum load 20A) for
backup and parallel operation in DLP series
Each power supply operation status is indicated by
LED, and signals are emitted (relay contact output).
Blank: Block terminal
EJ: European terminal
Single phase input
Nominal output voltage
Output power
Series name
DLP−PU/ EJ
European terminal
Series name
■ Applications
計 測
F A
■ Conformity to RoHS Directive
半導体
This means that, in conformity with EU Directive 2002/95/
EC, lead, cadmium, mercury, hexavalent chromium, and
specific bromine-based flame retardants, PBB and PBDE,
have not been used, except for exempted applications.
■ Product Line up
医 療
計 測
75W
Output
F AVoltage
半導体
Output Current
Model
24V
医 療
計 測
F A
3.1A
DLP75
100W
120W
180W
240W
Output Current
Model
Output Current
Model
Output Current
Model
Output Current
Model
4.1A
DLP100
5A
DLP120
7.5A
DLP180
10A
DLP240
半導体
・All specifications are subject to change without notice.
A-23
DLP75
DLP75 Specifications
ITEMS/UNITS
Input
DLP
Output
MODEL
Voltage Range
(*2)
Frequency
(*2) Hz
DLP75-24-1
V
AC85 - 132 / 170 - 265 (Auto selectable)
47 - 63
Efficiency (100/230VAC)(typ) (*1) %
82 / 83
Current (100/230VAC)(typ) (*1)
A
1.7 / 0.8
Inrush Current (100/230VAC)(typ) (*3)
A
20 / 45, Ta=25℃, cold start
Leakage Current
(*9) mA
Nominal Voltage
VDC
Less than 0.75
24
Maximum Current
A
3.1
Maximum Power
W
74.4
Maximum Line Regulation (*4)(*5) mV
120
Maximum Load Regulation (*4)(*6) mV
192
Temperature Coefficient
Less than 0.05%/℃
Maximum Ripple & Noise (0≤Ta≤60℃) (*4) mVp-p
Maximum Ripple & Noise (ー10≤Ta<0℃) (*4) mVp-p
360
Hold-up Time (100/230VAC) (*1) ms
20 /30
Voltage Adjustable Range
Over Current Protection (*7)
Function
240
VDC
21.6 - 28
A
>3.3
Over Voltage Protection (*8) VDC
30.0 - 35.0
Parallel Operation
-
Series Operation
Possible
- 10 to + 60
Operating Temperature (*10) ℃
Storage Temperature
Operating Humidity
Convection: -10 to +50 (100%); 60 (60%)
℃
- 30 to +85
%RH
30 - 90 (No dewdrop)
%RH
Environment Storage Humidity
10 - 95 (No dewdrop)
At no operating and with DIN RAIL,
Vibration
10~55Hz (sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
Shock (In package)
Less than 196m/s²
Cooling
Isolation
Convection cooling
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
Withstand Voltage
Output - FG : 500VAC (100mA) for 1min.
Isolation Resistance
More than 100MΩ at Ta=25℃ and 70%RH, Output - FG : 500VDC
Approved by UL60950-1, CSA C22.2 No.60950, EN60950-1, UL508 UL1310,
Safety Standards
CSA C22.2 No.14-M95, EN50178 CATEGORY III (Primary) Built to meet DENAN.
Standards PFHC
EMI
Built to meet IEC61000-3-2
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Immunity
Mechanical
Weight (typ)
Size (W x H x D)
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
g
470
mm
50 x 97 x 110 (Refer to outline drawing)
(*1) At 100/230VAC and maximum output power, Ta=25℃ .
(*2) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-120VAC/200-240VAC,
50/60Hz on name plate.
(*7) Foldback type O.C.P with automatic recovery.
Avoid to operate at overload or dead short for more than 30 seconds.
(*8) OVP circuit will shutdown output, manual reset. (Re Power on)
(*3) Not applicable for the in-rush current to Noise Filter for less than
0.2ms.
(*9) Measured by each measuring method of UL, CSA, EN and DENAN
(at 60Hz).
(*4) Please refer to Fig A for measurement of line & load regulation
and output ripple voltage. (Measure with JEITA RC-9131 probe.)
(*10) At standard mounting method, Fig B.
- Load(%) is percent of maximum output load (Item2 and 3), do not
exceed derating in both maximum output current and power.
- For standard mounting, refer to derating curve.
(*5) 85-132VAC/170-265VAC, constant load.
(*6) No load - full load (maximum power), constant input voltage.
●Recommended EMC Filter
z
A-24
RSEN-2003
Please refer to "TDK-Lambda
EMC Filters" catalog.
・All specifications are subject to change without notice.
DLP75
Outline Drawing
【DLP75】
(Block Terminal)
DIN RAIL REMOVE
DIN RAIL REMOVE
PUSHING BUTTON
PUSHING BUTTON
OUTPUT TERMINAL
OUTPUT TERMINAL
TERMINAL COVER
TERMINAL COVER
VOLTAGE ADJUSTMENT
VOLTAGE ADJUSTMENT
DC ON INDICATIOR
DC ON INDICATIOR
(GREEN LED)
(GREEN LED)
ALM INDICATIOR
ALM INDICATIOR
(RED LED)
(RED LED)
NOTES :
A : M3 EMBOSSED TAPPED & COUNTERSUNK HOLES (3) ARE FOR CUSTOMER
CHASSIS MOUNTING. SCREWS MUST
NOT PROTRUDE INTO POWER SUPPLY BY MORE THAN 4mm.
B : RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
C : RECOMMENDED SCREW TORQUE =
1.27N・m
NAME PLATE
NAME PLATE
DLP
TERMINAL COVER
TERMINAL COVER
SEE NOTE A
SEE NOTE A
INPUT TERMINAL
INPUT TERMINAL
DIN RAIL REMOVE HOLE
DIN RAIL REMOVE HOLE
(unit : mm)
【DLP75/EJ】
(European Terminal)
DIN RAIL REMOVE
DIN RAIL REMOVE
PUSHING BUTTON
PUSHING BUTTON
OUTPUT TERMINAL
OUTPUT TERMINAL
VOLTAGE ADJUSTMENT
VOLTAGE ADJUSTMENT
NOTES :
A : M3 EMBOSSED TAPPED & COUNTERSUNK HOLES (3) ARE FOR CUSTOMER
CHASSIS MOUNTING. SCREWS MUST
NOT PROTRUDE INTO POWER SUPPLY BY MORE THAN 4mm.
B : RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
WIRE STRIP LENGTH = 6-7mm
C : RECOMMENDED SCREW TORQUE =
0.49N・m
DC ON INDICATIOR
DC ON INDICATIOR
(GREEN LED)
(GREEN LED)
ALM INDICATIOR
ALM INDICATIOR
(RED LED)
(RED LED)
NAME PLATE
NAME PLATE
SEE NOTE A
SEE NOTE A
INPUT TERMINAL
INPUT TERMINAL
DIN RAIL REMOVE HOLE
DIN RAIL REMOVE HOLE
(unit : mm)
Output Derating
端子カバー
端子カバー
出力電圧可変ボリューム
出力電圧可変ボリューム
出力表示用LED
出力表示用LED
(緑色LED)
(緑色LED)
アラーム用LED
アラーム用LED
(赤色LED)
(赤色LED)
LOAD (%)
100
80
Output connector
Rail
60
40
20
0
-10 0
10
20
30
40
50
60
端子カバー
端子カバー
Ta (℃)
Input connector
STANDARD MOUNTING
3-M3取付用
(挿入長4mm以下)
3-M3取付用
(挿入長4mm以下)
100
負荷
80
60
(%) 40
20
0
-10 0
10
・All specifications are subject to change without notice.
20
30
40
周囲温度 (℃)
50
60 出力電圧可変ボリューム
出力電圧可変ボリューム
出力表示用LED
出力表示用LED
(緑色LED)
(緑色LED)
A-25
DLP100
DLP100 Specifications
ITEMS/UNITS
Voltage Range
DLP
MODEL
(*2)
(*2)
Frequency
Efficiency (100/230VAC)(typ)(*1)
Input
Current (100/230VAC)(typ)(*1)
Inrush Current (100/230VAC)(typ)(*3)
(*9)
Leakage Current
Nominal Voltage
Maximum Current
Maximum Power
Maximum Line Regulation(*4)(*5)
Maximum Load Regulation(*4)(*6)
Output
Temperature Coefficient
DLP100-24-1
V
Hz
%
A
A
mA
VDC
A
W
mV
mV
AC85-132 / 170-265 (Auto selectable)
47-63
83
2.5 / 1.1
20 / 45, Ta=25°C, cold start
Less than 0.75
24
4.1
98.4
120
192
Less than 0.05%/°C
240
360
20 / 30
21.6-28
4.330.0-35.0
Possible
mVp-p
mVp-p
Hold-up Time (100/230VAC)(*1) ms
VDC
Voltage Adjustable Range
Over Current Protection (*7) A
Over Voltage Protection (*8) VDC
Function
Parallel Operation
Series Operation
Maximum Ripple & Noise (0<Ta<60°C)(*4)
Maximum Ripple & Noise (-10<Ta<0°C)(*4)
- 10 to + 60
Operating Temperature (*10) °C
Storage Temperature
Operating Humidity
Environment Storage Humidity
Convection: -10 to +50 (100%); 60 (70%)
- 30 to +85
30 - 90 (No dewdrop)
10 - 95 (No dewdrop)
°C
%RH
%RH
At no operating and with DIN RAIL,
Vibration
10-55Hz (Sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
Shock (In package)
Cooling
Isolation
Less than 196m/s²
Convection cooling
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
Withstand Voltage
Output - FG : 500VAC (100mA) for 1min.
More than 100MΩ at Ta=25°C and 70%RH, Output - FG : 500VDC
Approved by UL60950-1, CSA C22.2 No.60950, EN60950-1, UL508, UL1310,
Isolation Resistance
Safety Standards
Standards PFHC
EMI
Immunity
Weight (typ)
Mechanical
Size (W x H x D)
g
mm
CSA C22.2 No.14, EN50178 CATEGORY III (Primary). Built to meet DENAN.
Built to meet IEC61000-3-2
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
540
60 x 97 x 110 (Refer to outline drawing)
(*1) At 100/230VAC and maximum output power, Ta=25°C.
(*2) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-120VAC/200-240VAC,
50/60Hz on name plate.
(*8) OVP circuit will shutdown output, manual reset. (Re Power on)
(*3) Not applicable for the in-rush current to Noise Filter for less than
0.2ms.
(*9) Measured by each measuring method of UL, CSA, EN and DENAN
(at 60Hz).
(*4) Please refer to Fig A for measurement of line & load regulation and
output ripple voltage. (Measure with JEITA RC-9131 probe.)
(*10) At standard mounting method, Fig B.
- Load(%) is percent of maximum output load (Item2 and 3), do not
exceed derating in both maximum output current and power.
- For standard mounting, refer to derating curve.
(*5) 85-132VAC/170-265VAC, constant load.
(*6) No load - Full load (maximum power), constant input voltage.
z
A-26
(*7) Constant current limit with automatic recovery.
Avoid to operate at overload or dead short for more than 30 seconds.
●Recommended EMC Filter
RSEN-2006
Please refer to "TDK-Lambda
EMC Filters" catalog.
・All specifications are subject to change without notice.
DLP100
3-M3取付用
(挿入長4mm以下)
Outline Drawing
3-M3取付用
(挿入長4mm以下)
【DLP100】
(Block Terminal)
DIN RAIL REMOVE
PUSHING BUTTON
TERMINAL COVER
DIN RAIL REMOVE
PUSHING BUTTON
OUTPUT TERMINAL
VOLTAGE ADJUSTMENT
TERMINAL COVER
DC ON INDICATIOR
VOLTAGE
ADJUSTMENT
(GREEN
LED)
ALM INDICATIOR
DC ON INDICATIOR
(RED LED)
(GREEN LED)
ALM INDICATIOR
(RED LED)
NAME PLATE
OUTPUT TERMINAL
NOTES :
A : M3 EMBOSSED TAPPED & COUNTERSUNK HOLES (3) ARE FOR
CUSTOMER CHASSIS MOUNTING.
SCREWS MUST NOT PROTRUDE
INTO POWER SUPPLY BY MORE
THAN 4mm.
B : RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
C : RECOMMENDED SCREW TORQUE =
1.27N・m
NAME PLATE
TERMINAL COVER
DLP
TERMINAL COVER
SEE NOTE A
INPUT TERMINAL
DIN RAIL REMOVE HOLE
INPUT TERMINAL
SEE NOTE A
(unit : mm)
DIN RAIL REMOVE HOLE
【DLP100/EJ】
(European Terminal)
DIN RAIL REMOVE
PUSHING BUTTON
DIN RAIL REMOVE
PUSHING BUTTON
OUTPUT TERMINAL
VOLTAGE ADJUSTMENT
DC ON INDICATOR
VOLTAGE
ADJUSTMENT
(GREEN
LED)
ALM INDICATOR
DC ON INDICATOR
(RED LED)
(GREEN LED)
ALM INDICATOR
LED)
NAME(RED
PLATE
OUTPUT TERMINAL
NOTES :
A : M3 EMBOSSED TAPPED & COUNTERSUNK HOLES (3) ARE FOR
CUSTOMER CHASSIS MOUNTING.
SCREWS MUST NOT PROTRUDE
INTO POWER SUPPLY BY MORE
THAN 4mm.
B : RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
WIRE STRIP LENGTH = 6-7mm
C : RECOMMENDED SCREW TORQUE =
0.49N・m
NAME PLATE
SEE NOTE A
100
INPUT TERMINAL
DIN RAIL REMOVE HOLE
SEE NOTE A
80
負荷
INPUT TERMINAL
DIN RAIL REMOVE HOLE
60
(unit : mm)
(%) 40
20
0
-10 0
10
20
30
Output Derating
40
50
周囲温度 (℃)
60
端子カバー
出力電圧可変ボリューム
端子カバー
出力表示用LED
出力電圧可変ボリューム
(緑色LED)
アラーム用LED
出力表示用LED
(赤色LED)
(緑色LED)
アラーム用LED
(赤色LED)
OUTPUT DERATING CURVE
100
Output terminal
Rail
LOAD (%)
80
60
40
端子カバー
20
0
-10 0
10
20
30
40
50
60
Input terminal
STANDARD MOUNTING
端子カバー
Ta (℃)
3-M3取付用
(挿入長4mm以下)
3-M3取付用
(挿入長4mm以下)
100
負荷
80
60
・All specifications are subject to change without
notice.
(%) 40
20
出力電圧可変ボリューム
出力表示用LED
出力電圧可変ボリューム
(緑色LED)
アラーム用LED
出力表示用LED
A-27
DLP120
DLP120 Specifications
ITEMS/UNITS
Input
DLP
Output
MODEL
Voltage Range
(*2)
Frequency
(*2) Hz
DLP120-24-1
V
AC85-132 / 170 - 265 (Auto selectable)
47 - 63
Efficiency (100/230VAC)(typ) (*1) %
83 / 85
Current (100/230VAC)(typ) (*1)
A
2.9 / 1.3
Inrush Current (100/230VAC)(typ) (*3)
A
20 / 45, Ta=25℃, cold start
Leakage Current
(*9) mA
Nominal Voltage
VDC
Less than 0.75
24
Maximum Current
A
5
Maximum Power
W
120
Maximum Line Regulation(*4)(*5) mV
120
Maximum Load Regulation(*4)(*6) mV
192
Temperature Coefficient
Less than 0.05%/℃
Maximum Ripple & Noise (0<Ta<60℃)(*4)
mVp-p
240
Maximum Ripple & Noise (-10<Ta<0℃)(*4)
mVp-p
360
Hold-up Time (100/230VAC)(*1) ms
Voltage Adjustable Range
VDC
Over Current Protection (*7)
Function
20 / 30
21.6 - 28
A
>5.3
Over Voltage Protection (*8) VDC
30.0 - 35.0
Parallel Operation
-
Series Operation
Possible
- 10 to + 60
Convection: -10 to +50 (100%); 60 (60%)
Operating Temperature (*10) ℃
℃
- 30 to +85
%RH
30 - 90 (No dewdrop)
%RH
10 - 95 (No dewdrop)
Storage Temperature
Operating Humidity
Environment Storage Humidity
At no operating and with DIN RAIL,
10-55Hz (sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
Vibration
Isolation
Shock (In package)
Less than 196m/s²
Cooling
Convection cooling
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
Output - FG : 500VAC (100mA) for 1min.
Withstand Voltage
Isolation Resistance
More than 100MΩ at Ta=25℃ and 70%RH, Output - FG : 500VDC
Approved by UL60950-1, CSA C22.2 No.60950, EN60950-1, UL508,
CSA C22.2 No.14-M95, EN50178 CATEGORY III (Primary). Built to meet DENAN.
Safety Standards
Standards PFHC
Built to meet IEC61000-3-2
EMI
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Immunity
Mechanical
Weight (typ)
Size (W x H x D)
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
g
540
mm
60x97x110 (Refer to Outline Drawing)
(*1) At 100/230VAC and maximum output power, Ta=25℃ .
(*2) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-120VAC/200-240VAC,
50/60Hz on name plate.
(*8) OVP circuit will shutdown output, manual reset. (Re Power on)
(*3) Not applicable for the in-rush current to Noise Filter for less than
0.2ms.
(*9) Measured by each measuring method of UL, CSA, EN and DENAN
(at 60Hz).
(*4) Please refer to Fig A for measurement of line & load regulation
and output ripple voltage. (Measure with JEITA RC-9131 probe.)
(*10) At standard mounting method, Fig B.
- Load(%) is percent of maximum output load (Item2 and 3), do not
exceed derating in both maximum output current and power.
- For standard mounting, refer to derating curve.
(*5) 85-132VAC/170-265VAC, constant load.
(*6) No load - full load (maximum power), constant input voltage.
z
A-28
(*7) Constant current limit with automatic recovery.
Avoid to operate at overload or dead short for more than 30seconds.
●Recommended EMC Filter
RSEN-2006
Please refer to "TDK-Lambda
EMC Filters" catalog.
・All specifications are subject to change without notice.
DLP120
3-M3取付用
(挿入長4mm以下)
Outline Drawing
3-M3取付用
(挿入長4mm以下)
【DLP120】
(Block Terminal)
DIN RAIL REMOVE
PUSHING BUTTON
OUTPUT TERMINAL
TERMINAL COVER
VOLTAGE ADJUSTMENT
DIN RAIL REMOVE
PUSHING BUTTON
OUTPUT TERMINAL
DC ON INDICATIOR
(GREEN
LED)
TERMINAL
COVER
ALM INDICATIOR
VOLTAGE(RED
ADJUSTMENT
LED)
DLP
NOTES:
DC ON INDICATIOR
(GREEN LED)
ALM
INDICATIOR
NAME
PLATE
(RED LED)
A: M3 EMBOSSED TAPPED &
COUNTERSUNK HOLES (3)
ARE FOR CUSTOMER CHASSIS MOUNTING. SCREWS
NAME PLATE
TERMINAL COVER
MUST NOT PROTRUDE INTO
POWER SUPPLY BY MORE
THAN 4mm.
B: RECOMMENDED WIRE = SOL-
TERMINAL COVER
INPUT TERMINAL
SEE NOTE A
ID AND STRANDED
AWG12-20 (0.5-3.5mm2)
DIN RAIL REMOVE HOLE
C: RECOMMENDED SCREW
TORQUE = 1.27N・m
INPUT TERMINAL
SEE NOTE A
(unit : mm)
DIN RAIL REMOVE HOLE
RAIL REMOVE
【DLP120/EJ】
(DIN
European
Terminal)
PUSHING BUTTON
DIN RAIL REMOVE
80 BUTTON
PUSHING
負荷
DC ON INDICATIOR
(GREEN LED)
ALM INDICATIOR
(RED
LED)
VOLTAGE
ADJUSTMENT
60
(%) 40
OUTPUT TERMINAL
DC ON INDICATIOR
(GREEN LED)
ALM INDICATIOR
NAME PLATE
(RED LED)
20
0
OUTPUT TERMINAL
VOLTAGE ADJUSTMENT
100
-10 0
10
20
30
40
50
NOTES:
A: M3 EMBOSSED TAPPED &
COUNTERSUNK HOLES (3)
60
周囲温度 (℃)
ARE FOR CUSTOMER CHASSIS MOUNTING. SCREWS
NAME PLATE
MUST NOT PROTRUDE INTO
POWER SUPPLY BY MORE
THAN 4mm.
100
SEE NOTE A
B: RECOMMENDED WIRE = SOL-
INPUT TERMINAL
DIN RAIL REMOVE HOLE
負荷
80
60
SEE NOTE A
(%) 40
ID AND STRANDED
AWG12-20 (0.5-3.5mm2)
WIRE STRIP LENGTH =
INPUT TERMINAL
DIN RAIL REMOVE HOLE
6-7mm
C: RECOMMENDED SCREW
20
0
TORQUE = 0.49N・m
-10 0
10
20
30
40
50
(unit : mm)
60
周囲温度 (℃)
Output Derating
OUTPUT DERATING CURVE
Output terminal
100
Rail
LOAD (%)
80
60
40
20
0
Input terminal
-10 0
10
20
30
40
50
60
40
50
60
TA (℃)
STANDARD MOUNTING
100
負荷
80
60
(%) 40
20
A-29
・All specifications are subject to change without notice.
0
-10 0
10
20
30
DLP180
DLP180 Specifications
ITEMS/UNITS
MODEL
Voltage Range
(*2)
Frequency
(*2) Hz
Power Factor (typ)
(*1)
DLP180-24-1
V
AC85 - 265 or DC120 - 370
47-63
0.99 / 0.95
Input Efficiency (100/230VAC)(typ) (*1) %
DLP
Output
84 / 87
Current (100/230VAC)(typ) (*1)
A
2.3 / 1.0
Inrush Current (100/230VAC)(typ) (*3)
A
20 / 45, Ta=25℃, cold start
Leakage Current
(*9) mA
Nominal Voltage
VDC
Less than 0.75
24
Maximum Current
A
7.5
Maximum Power
W
180
Maximum Line Regulation (*4)(*5) mV
120
Maximum Load Regulation (*4)(*6) mV
192
Temperature Coefficient
Less than 0.05%/℃
Maximum Ripple & Noise (0<Ta<60℃) (*4)
mVp-p
240
Maximum Ripple & Noise (-10<Ta<0℃) (*4)
mVp-p
360
Hold-up Time (100/230VAC) (*1) ms
Voltage Adjustable Range
Over Current Protection (*7)
Function
20 / 30
VDC
21.6 - 28
A
>7.9
Over Voltage Protection (*8) VDC
30.0 - 35.0
Parallel Operation
-
Series Operation
Possible
- 10 to + 60
Operating Temperature (*10) ℃
Storage Temperature
Operating Humidity
Environment Storage Humidity
Convection: -10 to +50 (100%); 60 (60%)
℃
- 30 to +85
%RH
30 - 90 (No dewdrop)
%RH
10 - 95 (No dewdrop)
At no operating and with DIN RAIL,
Vibration
Isolation
10~55Hz (sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
Shock (In package)
Less than 196m/s²
Cooling
Convection cooling
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
Withstand Voltage
Output - FG : 500VAC (100mA) for 1min.
Isolation Resistance
More than 100MΩ at Ta=25℃ and 70%RH, Output - FG : 500VDC
Approved by UL60950-1,CSA C22.2 No.60950, EN60950-1, UL508,
Safety Standards
CSA C22.2 No14-M95, EN50178 CATEGORY III (Primary), Built to meet DENAN
Standards PFHC
Built to meet IEC61000-3-2
EMI
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Immunity
Mechanical
Weight (typ)
Size (W x H x D)
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
g
780
mm
80 x 97 x 110 (Refer to outline drawing)
(*1) At 100/230VAC and maximum output power, Ta=25℃ .
(*2) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-240VAC, 50/60Hz on
name plate.
(*3) Not applicable for the in-rush current to Noise Filter for less than
0.2ms.
(*4) Please refer to Fig A for measurement of line & load regulation
and output ripple voltage. (Measure with JEITA RC-9131 probe.)
(*5) 85-265VAC, constant load.
(*6) No load - full load (maximum power), constant input voltage.
Avoid to operate at overload or dead short for more than 30 seconds.
(*8) OVP circuit will shutdown output, manual reset. (Re power on.)
(*9) Measured by each measuring method of UL, CSA, EN and DENAN
(at 60Hz).
(*10) At standard mounting method, Fig B.
- Load(%) is percent of maximum output load (Item2 and 3), do not
exceed derating in both maximum output current and power.
- For standard mounting, refer to derating curve.
●Recommended EMC Filter
(*7) Constant current limit with automatic recovery.
z
A-30
RSEN-2006
Please refer to "TDK-Lambda
EMC Filters" catalog.
・All specifications are subject to change without notice.
DLP180
Outline Drawing
【DLP180】
(Block Terminal)
VOLTAGE ADJUSTMENT
DIN RAIL REMOVE
PUSHING BUTTON
DC ON INDICATOR
(GREEN LED)
VOLTAGE
ADJUSTMENT
ALM INDICATOR
DIN RAIL REMOVE
PUSHING BUTTON
(RED LED)
DC ON INDICATOR
(GREEN LED)
OUTPUT TERMINAL
NOTES:
A: M3 EMBOSSED TAPPED HOLES(6) ARE FOR
CUSTOMER CHASSIS MOUNTING. SCREWS
MUST NOT PROTRUDE INTO POWER SUPPLY BY MORE THAN 4mm.
B: RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
C: RECOMMENDED SCREW TORQUE = 1.27N・
m
OUTPUT TERMINAL
ALM INDICATOR
(RED LED)
NAME PLATE
DLP
NAME PLATE
LOAD (%)
100
SEE NOTE A
80
60
40
TERMINAL
COVER
20
0
SEE NOTE A
-10 0
10
20
INPUT
TERMINAL
DIN RAIL
REMOVE HOLE
30 TERMINAL
40 50 60INPUT
TERMINAL
Ta (℃)
COVER
(unit : mm)
DIN RAIL
REMOVE HOLE
【DLP180/EJ】
(European Terminal)
VOLTAGE ADJUSTMENT
DIN RAIL REMOVE
100
PUSHING BUTTON
DC ON INDICATOR
(GREEN LED)
LOAD (%)
80
DIN RAIL REMOVE
PUSHING BUTTON
60
VOLTAGE
ADJUSTMENT
ALM INDICATOR
40
ALM INDICATOR
(RED LED)
20
0
NOTES:
A: M3 EMBOSSED TAPPED HOLES(6) ARE FOR
CUSTOMER CHASSIS MOUNTING. SCREWS
MUST NOT PROTRUDE INTO POWER SUPPLY BY MORE THAN 4mm.
B: RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
C: RECOMMENDED SCREW TORQUE = 1.27
N・m
(RED
DC ONLED)
INDICATOR
(GREEN LED)
-10 0
10
20
30
40
50
NAME PLATE
60
Ta (℃)
NAME PLATE
SEE NOTE A100
INPUT
TERMINAL
LOAD (%)
80
SEE NOTE A
DIN RAIL
REMOVE HOLE
INPUT
TERMINAL
60
40
DIN RAIL
REMOVE HOLE
0
-10 0
10
20
30
Ta (℃)
40
50
出力表示用LED
(緑色LED)
60
アラーム用LED
出力電圧可変ボリューム
(赤色LED)
出力表示用LED
(緑色LED)
アラーム用LED
(赤色LED)
端子カバー
Output Derating
OUTPUT DERATING CURVE
100
LOAD (%)
(unit : mm)
出力電圧可変ボリューム
20
端子カバー
Output connector
Rail
80
60
40
Input connector
20
0
STANDARD MOUNTING
-10 0
10
20
30
40
50
60
Ta (℃)
3-M3取付用(対称面共)
(挿入長4mm以下)
端子カバー
3-M3取付用(対称面共)
(挿入長4mm以下)
端子カバー
100
負荷
80
60
(%) 40
・All specifications are subject to change20
without notice.
0
85∼170VAC
170∼265VAC
出力電圧可変ボリューム
出力表示用LED
(緑色LED)
アラーム用LED
出力電圧可変ボリューム
(赤色LED)
出力表示用LED
(緑色LED)
アラーム用LED
A-31
DLP240
DLP240 Specifications
ITEMS/UNITS
MODEL
Voltage Range
(*2)
Frequency
(*2) Hz
Power Factor (typ)
(*1)
DLP240-24-1
V
AC85 - 265 or DC120 - 370
47-63
0.99 / 0.95
Input Efficiency (100/230VAC)(typ) (*1) %
DLP
Output
82 / 86
Current (100/230VAC)(typ) (*1)
A
3.0 / 1.3
Inrush Current (100/230VAC)(typ) (*3)
A
20 / 45, Ta=25℃, cold start
Leakage Current
(*9) mA
Nominal Voltage
VDC
Less than 0.75
24
Maximum Current
A
10
Maximum Power
W
240
Maximum Line Regulation (*4)(*5) mV
120
Maximum Load Regulation (*4)(*6) mV
192
Temperature Coefficient
Less than 0.05%/℃
Maximum Ripple & Noise (0≤Ta≤60℃) (*4)
mVp-p
240
Maximum Ripple & Noise (-10≤Ta<0℃) (*4)
mVp-p
360
Hold-up Time (100/230VAC) (*1) ms
Function
20 / 30
VDC
21.6 - 28
Over Current Protection (*7)
A
>10.5
Over Voltage Protection (*8)
V
30.0 - 35.0
Voltage Adjustable Range
Parallel Operation
-
Series Operation
Possible
Operating Temperature (*10) ℃
Storage Temperature
Operating Humidity
Environment Storage Humidity
85VAC - 170VAC : -10 to +60, Convection: -10 to +50 (100%); 60 (60%)
170VAC - 265VAC : -10 to +70, Convection: -10 to +55 (100%); 70 (60%)
℃
- 30 to +85
%RH
30 - 90 (No dewdrop)
%RH
10 - 95 (No dewdrop)
At no operating and with DIN RAIL
Vibration
10~55Hz (sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
Shock (In package)
Less than 196m/s²
Cooling
Isolation
Convection cooling
Input - Output : 3.0kVAC, Input - FG : 2.0kVAC (20mA) for 1min
Withstand Voltage
Output - FG : 500VAC (100mA) for 1min.
Isolation Resistance
More than 100MΩ at Ta=25℃ and 70%RH, Output - FG : 500VDC
Approved by UL60950-1, CSA C22.2 No.60950, EN60950-1, UL508,
Safety Standards
CSA C22.2 No.14-M95, EN50178 CATEGORY III (Primary), Built to meet DENAN
Standards PFHC
Built to meet IEC61000-3-2
EMI
Built to meet VCCI-B, FCC-ClassB, EN55011/EN55022-B
Immunity
Mechanical
Weight (typ)
Size (W x H x D)
Built to meet IEC61000-6-2 (IEC61000-4-2,-3,-4,-5,-6,-8,-11)
g
1000
mm
120 x 97 x 110 (Refer to outline drawing)
(*1) At 100/230VAC and maximum output power, Ta=25℃ .
(*2) For cases where conformance to various safety specs (UL, CSA,
EN) are required, to be described as 100-240VAC, 50/60Hz on
name plate.
(*8) OVP circuit will shutdown output, manual reset. (Re power on.)
(*3) Not applicable for the in-rush current to Noise Filter for less than
0.2ms.
(*9) Measured by each measuring method of UL, CSA, EN and DENAN
(at 60Hz).
(*4) Please refer to Fig A for measurement of line & load regulation
and output ripple voltage. (Measure with JEITA RC-9131 probe.)
(*10) At standard mounting method, Fig B.
- Load(%) is percent of maximum output load (Item2 and 3), do not
exceed derating in both maximum output current and power.
- For standard mounting, refer to derating curve.
(*5) 85-265VAC, constant load.
(*6) No load - full load (maximum power), constant input voltage.
z
A-32
(*7) Constant current limit with automatic recovery.
Avoid to operate at overload or dead short for more than 30 seconds.
●Recommended EMC Filter
RSEN-2006
Please refer to "TDK-Lambda
EMC Filters" catalog.
・All specifications are subject to change without notice.
DLP240
3-M3取付用(対称面共)
(挿入長4mm以下)
Outline Drawing
【DLP240】
(Block Terminal)
100
負荷
80
60
VOLTAGE ADJUSTMENT
DIN RAIL REMOVE PUSHING BUTTON
(%) 40
DC ON INDICATOR
(GREEN LED)
ALM INDICATOR
(RED LED)
20
0
-10 0
10 20
DIN RAIL REMOVE PUSHING BUTTON
30
OUTPUT TERMINAL
40VOLTAGE
50 60ADJUSTMENT
ON INDICATOR
周囲温度 (℃)DC
(GREEN LED)
ALM INDICATOR
(RED LED)
DLP
OUTPUT TERMINAL
NAME PLATE
100
負荷
80
NAME PLATE
60
(%) 40
SEE NOTE A
TERMINAL COVER
20
0
-10 0
10
20
30
40
50
INPUT TERMINAL
60
周囲温度 (℃)
DIN RAIL REMOVE HOLE
TERMINAL COVER
SEE NOTE A
NOTES:
A: M3 EMBOSSED TAPPED HOLES(6) ARE
FOR CUSTOMER CHASSIS MOUNTING.
SCREWS MUST NOT PROTRUDE INTO
POWER SUPPLY BY MORE THAN 4mm.
B: RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
C: RECOMMENDED SCREW TORQUE
= 1.27N・m
(unit : mm)
INPUT TERMINAL
VOLTAGE ADJUSTMENT
DIN RAIL REMOVE PUSHING BUTTON
【DLP240/EJ】
(European Terminal)
DC ON INDICATOR
(GREEN LED)
ALM INDICATOR
(RED LED)
100
DIN RAIL REMOVE PUSHING BUTTON
80
OUTPUT TERMINAL
DIN RAIL REMOVE HOLE
VOLTAGE ADJUSTMENT
負荷
DC ON INDICATOR
(GREEN LED)
60
OUTPUT TERMINAL
ALM INDICATOR
(RED LED)
NAME PLATE
(%) 40
20
0
-10 0
10
20
30
40
50
60
NAME PLATE
周囲温度 (℃)
SEE NOTE A
INPUT TERMINAL
100
負荷
80
SEE NOTE A
DIN RAIL REMOVE HOLE
60
INPUT TERMINAL
(%) 40
20
0
DIN RAIL REMOVE HOLE
-10 0
10
20
30
40
50
NOTES:
A: M3 EMBOSSED TAPPED & COUNTERSUNK HOLES(6) ARE FOR CUSTOMER
CHASSIS MOUNTING. SCREWS MUST
NOT PROTRUDE INTO POWER SUPPLY
BY MORE THAN 4mm.
B: RECOMMENDED WIRE = SOLID AND
STRANDED AWG12-20 (0.5-3.5mm2)
WIRE STRIP LENGTH = 6-7mm
C: RECOMMENDED SCREW TORQUE
= 0.49N・m
(unit : mm)
60
周囲温度 (℃)
Output Derating
OUTPUT DERATING CURVE
100
LOAD (%)
80
Rail
85-170VAC
170-265VAC
60
40
Input connector
20
0
Output connector
-10
0
10
20
30
40
50
60
70
STANDARD MOUNTING
Ta (℃)
・All specifications are subject to change without notice.
A-33
DLP-PU SERIES
DLP-PU Specifications
ITEMS/UNITS
DLP
MODEL
Nominal Voltage
Voltage Range
Input
Efficiency (typ)
(*1)
Current (nominal)
Output Maximum Current
Over Current Protection
Over Voltage Protection
Input Voltage Monitor Indicator
Input Voltage Monitor Alarm
Low Input Voltage Alarm Level(*3)
Function High Input Voltage Alarm Level(*4)
Input Number
Voltage Drop (typ)
(*2)
Maximum Reverse Output Voltage
DLP-PU/EJ
V
V
%
A
A
A
VDC
DC24
DC21-28
97
20 (A, B total)
20
None
None
A,B Individual Monitor Green LED
Relay Contact (at nominal input voltage: Contact + to OK)
Less than low level or more than high level:
19.2V±1%
30V±5%
Contact + to F (Discontact + to OK)
2 (A, B)
DC0.5
DC35
Maximum : 28VDC , 1A; 120VAC, 0.5A
V
V
Relay Contacts Ratings
Minimum : DC 1mA (5mA or more recommended)
- 10 to +70
Operating Temperature (*5) ℃
Storage Temperature
Operating Humidity
Environment Storage Humidity
Convection: -10 to +60 (100%); 70 (60%)
-30 to +85
30-90 (No dewdrop)
10-95 (No dewdrop)
At no operating and with DIN rail,
℃
%RH
%RH
Vibration
10-55Hz (sweep for 1min) 9.8m/s² constant, X, Y, Z each 1hour
196m/s² (20G)
Convection cooling
Input,Output - FG; Input, Output - Relay Contact; Relay Contact-FG:
Shock
Cooling
Withstand Voltage
500VAC (100mA) for 1min.
Input,Output -FG; Input,Output - Relay Contact; Relay Contact-FG:
Isolation
Isolation Resistance
Safety Standards
EMI
Weight (typ)
Mechanical
Size (W x H x D)
More than 10MΩ at Ta=25℃ and 70%RH at 500VDC
Approved by UL60950-1, UL508, CSA C22.2 No.14-M95, CATEGORY I
No specify
470
100
50 x 97 x 110 (Refer to outline drawing)
Standards
g
mm
(*1) Nominal input voltage, nominal input curent, Ta = 25℃.
Signal connector
80
LOAD (%)
(*2) Differential voltage between input and output.
60
(*3) On the condition of increasing input voltage, hysiteresis is about 0.7V.
Rail
(*4) On the condition of decreasing input voltage, hysiteresis is about 0.7V.
(*5) At standard mounting method, Fig A.
- Load(%) is percent of maximum output current.
- For standard mounting, refer to derating curve.
40
20
0
-10
0
10
20
30
40
Ta (℃)
50
60
70
Input/output connector
Fig.A
Output Derating
100
Signal connector
LOAD (%)
80
60
Rail
40
20
0
-10
A-34
0
10
20
30
40
Ta (℃)
50
60
70
Input/output connector
Fig.A
・All specifications are subject to change without notice.
DLP-PU SERIES
Outline Drawing
DLP
NOTES
A: M3 EMBOSSED TAPPED & COUNTERSUNK HOLES (3)
ARE FOR CUSTOMER CHASSIS MOUNTING.
SCREWS MUST NOT PROTRUDE INTO POWER SUPPLY
BY MORE THAN 4mm.
B: RECOMMENDED WIRE = SOLID AND STRANDED
AWG12-20 (0.5-3.5mm2)
WIRE STRIP LENGTH = 7mm
C: RECOMMENDED SCREW TORQUE = 0.49N·m
Basic Connection
■ Dual Input Mode
Power
supply
#1.
+
+
−
−
DLPSeries
Power
Power
supply
supply
#2.
#1.
Power
supply
#2.
+
+
+
−
+
−
−
−
+
+
−
−
+
Power +
−
■supply
Single
−
Power
supply
A+
B+
+V
+V
−V
+
+
−
−
A+
B+
+V
+V
−V
A+
B+
+V
+V
−V
OK
+
F
OK
+
F
Input channel A
monitor device
Input channel B
monitor device
+
Input channel A
monitor
+DCdevice
+
BUS
Input −
channel
B
monitor device
OK
F
OK
F
OK
+
F
OK
Input channel A
monitor device
+DC
Input Mode+
Input channel B
−BUS
monitor device
OK
Input channel A
monitor
device
+DC
A+
B+
+V
+V
−V
F
+
F
OK
+
F
BUS
Input −
channel
B
monitor device
+DC
−BUS
・All specifications are subject to change without notice.
A-35
DLP, DLP-PU SERIES
DLP Series Block Diagram
Rectifier & Filter
Switching
Rectifier & Filter
Circuit mode
DLP75 : Self-oscillating flyback topology
DLP100,120 : Single-ended forward topology
Switching frequency
DLP75 : 60kHz-400kHz
DLP100,120 : 140kHz(fixed)
PCB material : Glass composite(CEM-3)
−V
OCP
Alarm
OVP
Output Sensing
Rectifier & Filter
Rectifier & Filter
PFHC Control
Circuit
+V
Output
24VDC
−V
A
OCP
Control Circuit
A
Control Circuit
FG
Inrush Current
Limit Circuit
Input
85-265VAC
N
Output
24VDC
Fuse
Line Filter
L
+V
A
A
Control Circuit
FG
Switching
DLP
Input Auto Select
N
Line Filter
Input
85-132VAC/
170-265VAC
Inrush Current
Limit Circuit
Fuse
L
Alarm
OVP
Output
Sensing
Circuit mode and switching frequency
Switching circuit : Single-ended forward topology(DLP180:110kHz - fixed, DLP240:95kHz - fixed)
PFHC control circuit : Active filter(DLP180:75kHz - fixed、DLP240:70kHz - fixed)
PCB material : Glass composite
(CEM-3)
DLP-PU Series Block Diagram
A+
+V
B+
+V
LED
+
A
F
OK
+
B
LED
−V
A-36
F
OK
・All specifications are subject to change without notice.
DLP SERIES
DLP Series Instruction Manual
BEFORE USING THE POWER SUPPLY UNIT
Pay attention to all warnings and cautions before using the unit.
Incorrect usage could lead to an electric shock, damage to the
unit or a fire hazard.
・Warning Symbols
CAUTION
・DO NOT MODIFY, DISASSEMBLE THE POWER SUPPLY.
・HOT SURFACE.
・READ INSTRUCTION MANUAL BEFORE CONNECTING TO MAINS.
・ELECTRIC SHOCK HAZARDOUS ON THE CONNECTOR SECTION.
NOTICE :
(1)Installing/Storage Environment
1. Store the product with ambient temperature –30 to
+85℃, and relative humidity 10 to 95% (no dewdrop).
2. Never operate the unit under over current or shorted
conditions for 30 seconds or more and out of input voltage range in specification which could result in damage
or insulation failure or smoking or burning.
3. Confirm connections to input/output terminals are correct as indicated in the instruction manual.
4. Use the product where the relative humidity is 30 to
90% (no dewdrop).
5. Avoid places where the product is subjected to direct
sun light.
6. Avoid penetration of metal chips when processing
mounting holes.
7. Avoid places where the products is subjected to penetration of liquid, foreign substance or corrosive gas.
8. Avoid places subject to shock or vibration.
A device such as a contact breaker may be a vibration
source. Set the power supply as far as possible from
possible sources of shock or vibration.
9. If the power supply is used in an area with excessive
electronic noise, be sure to separate the power supply
as far as possible from the noise sources.
10.Don’t use the product in the environment with strong
electromagnetic field, corrosive gas and conductive
substance.
Precautions in Using the product:
When the product is used under the circumstance or environment below, ensure adherence to limitations of the ratings and
functions.
Also take countermeasures for safety precautions such as failsafe installations.
1.Under the circumstances or environment which are not described in the instruction manual.
2.For nuclear power control, railway, aircraft, vehicle, incinerator, medical equipment, entertainment equipment, safety device etc…
3.For applications where death or serious property damage is
possible and extensive safety precautions are required.
4.Terminal block covers are necessary to be used when connecting the input and output wire.
5.Don’t recommend using input power source with large inductance, which may cause power supply operate unstablely.
6.DLP180 and DLP240 are capable of providing hazardous
energy output (240VA), the end equipment manufacturer
must provide protection to service personal against inadvertent contact with output terminals.
These terminals must not be user accessible.
DLP
Note : CE MARKING
CE Marking, when applied to a product covered by this handbook, indicates compliance with the low voltage directive
(73/23/EEC) as modified by the CE Marking Directive (93/68/
EEC) which complies with EN60950.
1. Terminal Explanation
1Terminal Explanation
1-1.1 DLP75
1-1.2 DLP75/EJ
・All specifications are subject to change without notice.
1-1.3 DLP75/C2
① +V:
+Output terminal
② - V:
- Output terminal
③ V.ADJ: Output voltage adjust trimmer
The output voltage rises when a
trimmer is turned clockwise.
④ L:
AC Input terminal
Live line (fuse in line)
⑤ N:
AC Input terminal
Neutral line
⑥ FG:
Input terminal FG
Safety earth (frame ground)
Connect to safety ground of apparatus or equipment.
A-37
DLP SERIES
1-1.4 DLP75/C2EJ
1-2.1 DLP120
1-2.2 DLP120/EJ
1-2.4 DLP100/EJ
1-2.5 DLP100/C2
1-2.6 DLP100/C2EJ
1-3.1 DLP180
1-3.2 DLP180/EJ
1-4.1 DLP240
1-4.2 DLP240/EJ
1-2.3 DLP100
DLP
①+V:
+Output terminal
②- V:
- Output terminal
③V.ADJ: Output voltage adjust trimmer
The output voltage rises when a trimmer is turned
clockwise.
AC Input terminal
④L:
Live line (fuse in line)
A-38
⑤N: AC Input terminal
Neutral line
⑥FG: Input terminal FG
Safety earth (Frame Ground)
Connect to safety ground of apparatus or equipment.
・All specifications are subject to change without notice.
DLP SERIES
2Terminal Connecting Method
Pay attention to the input wiring. If it is connected to
●The output load line and input line shall be separated
wrong terminal, the power supply will be damaged.
and twisted to improve noise sensitivity.
●When connecting or removing input and output wire, do
not apply stress to PCB.
●Input must be off when making connections.
●Connect FG terminal of input connector and mountable
FG to ground terminal of the equipment.
2-1.1 DLP75
2-1.2 DLP75/EJ
2-1.3 DLP75/C2
2-1.4 DLP75/C2EJ
2-2.1 DLP120
DLP
2-2.2 DLP120/EJ
+V
V.ADJ
2-2.3 DLP100
2-2.4 DLP100/EJ
2-2.5 DLP100/C2
2-2.6 DLP100/C2EJ
-V
H
DC ON
ALM
IND.CONT.EQ.
45JB
L
N
2-3.1 DLP180
2-3.2 DLP180/EJ
・All specifications are subject to change without notice.
2-4.1 DLP240
2-4.3 DLP240/EJ
A-39
DLP SERIES
2. Explanation of Functions and Precautions
DLP
1Input Voltage Range
6Output Ripple & Noise
Input voltage range is single phase 85-132VAC/170-
The standard specification for maximum ripple value is
265VAC (47-63Hz) (DLP75, DLP100, DLP120 series)
or 85-265VAC (DLP180, DLP240 series). Input voltage
which is out of specification may cause unit damage.
For cases where conformance to various safety specs
(UL,CSA,EN) are required, input voltage range will be 100
-120VAC/200-240VAC (50/60Hz) (DLP75, DLP100,
DLP120 series) or 100-240VAC (50/60Hz) (DLP180,
DLP240 series). Do not switch input voltage from 85132VAC directly to 170-265VAC, as may cause power
supply damaged (DLP75,DLP100, DLP120 series).
measured according to measurement circuit specified
by JEITA-RC9131. When load lines are longer, ripple
becomes larger. In this case, electrolytic capacitor, film
capacitor, etc. might be necessary to use across the load
terminal. The output ripple cannot be measured accurately
if the probe ground lead of oscilloscope is too long.
2Output Voltage Range
Except/C2 models (output voltage are fixed at 23.7624.24V), V.ADJ trimmer is for output voltage adjustment
within the range of specifications (21.6-28V). To turn the
trimmer clockwise, the output voltage will be increased.
Note over voltage protection (OVP) function may trigger if
the output voltage is increased excessively.
3Inrush Current
This series has used Power Thermistor to protect the
circuit from Inrush Current. Please carefully select input
switch and fuse in cases of the high temperature and reinput the power.
4Over Voltage Protection (OVP)
The OVP function (inverter shut down method, manual
reset type) is provided. OVP function operates within the
range of OVP specification (30-35V, except DLP75/C2
models are ranging from 26-30V). When OVP triggers, the
output will be shut down. The input shall be removed for a
few minutes, and then re-input for recovery of the output.
OVP setting is fixed and not to be adjusted externally.
5Over Current Protection (OCP)
Output Voltage (V)
Constant current limiting (except DLP75 series, which
characterized as fold back), automatic recovery. OCP
function operates when the output current exceeds OCP
specification. The output will be automatically recovered
when the overload condition is cancelled. Do not operate
overload or dead short conditions for more than 30 seconds, which could result in damage. DLP75 series models
are not recommended for constant current load application.
L
Load
+V
C2 C3
P.S.
INPUT
N
−V
FG
1.5m 50Ω Cable
R
C1 Oscilloscope
Bandwidth : 100MHz
150mm
R:
C1
C2
C3
50Ω
: 4700pF Film Capacitor
: 100μF Electrolytic Capacitor
: 0.1μF Film Capacitor
7Series Operation
For series operation, either method (A) or (B) is possible.
Power Supply +
Output Terminal −
+
Load
−
Power Supply +
Output Terminal −
Power Supply +
Output Terminal −
+
Power Supply +
Output Terminal −
+
Method(A)
Load
−
Load
−
Method(B)
8Parallel Operation
(A)To increase the output current is not possible.
Power Supply
Output
Terminal
Load
Output
Terminal
(A)To use as Back-up Power Supply
1. Set power supply output voltage higher by the forward voltage drop (VF) of diode
2.Adjust the output voltage of each power supply to
be the same.
3.Use within the specifications for output voltage and
output power.
Power Supply
Output +
Terminal
−
+
Output +
Terminal
−
Load
−
9Isolation Test
V
A
100
Load (%)
Isolation resistance between output and FG (Chassis) shall
be more than 100MΩ at 500VDC. For safety operation,
voltage setting of DC isolation tester must be done before
the test. Ensure that it is fully discharged after the test.
: Power supply load characteristics
: Load characteristics
(lamp, motor, and constant current load, etc.)
The unit might stop starting up at A point when a lamp, motor,
constant current load, etc. is connected on the load side.
A-40
・All specifications are subject to change without notice.
DLP SERIES
Output-FG (Chassis)
500VDC 100MΩ or more
AC(L)
AC(N)
Alarm Indication
+V
−V
LED on the panel indicate whether the power supply unit
is working properly.
FG
Isolation
Tester
● The green LED is on and red LED is off in normal operation.
This series is designed to withstand 3.0kVAC between
input and output, 2.0kVAC between input and FG (Chassis) and 500VAC between output and the FG (Chassis)
each for 1 minute. When testing withstand voltage, set
current limit of the withstand voltage test equipment to
20mA (Output - FG (Chassis) : 100mA). The applied voltage must be gradually increased from zero to the testing
value and then gradually decreased for shut down. When
timer is used, the power supply may be damaged by high
impulse voltage at timer switch on and off. Connect input
and output as follows.
Input-Output (dotted line)
3kVAC 1min.(20mA)
Input-FG (Chassis)(solid line)
2kVAC 1min.(20mA)
AC(L)
AC(N)
Output-FG (Chassis)
500VAC 1min.(100mA)
AC(L)
AC(N)
+V
−V
FG
Withstand
Voltage
Tester
+V
−V
FG
voltage below 2V).
DLP
● Both LEDs turn off on the condition of input power
source failure or power supply damaged.
Power ON
Normal Output Over Load Input Voltage Low Output ShortOutput Stop*
DC ON (Green LED)
ON
ON
ON
OFF
OFF
ALM (Red LED)
OFF
ON
ON
ON
OFF
*At over load condition, no input voltage, no output power.
Output Voltage
Withstand Voltage
● The red LED turns on when O/P voltage drops below
approximatly 20V (ex: over current protection, output
voltage unregulated, output shorted conditions).
● The green LED goes out when output shorted (output
24V
About
20V
Green LED ON OCP operating
range
Red LED ON
Output Current
Withstand Voltage Tester
3. Mounting Directions
Recommended standard mounting method is (A). Please
do not use installation method (B). Refer to the derating
below. Do not exceed the load deratings.
85 - 132VAC or
170 - 265VAC
DLP100, DLP100/EJ
100
80
Load (%)
Output Derating according to the
Mounting Directions
60
40
20
0
-10
Normal mounting (A)
0
10
20
30
40
50
Ambient Tnmperature (℃)
60
Air Flo w
2 5m m
o r m o re
25m m
o r m o re
85 - 132VAC or
170 - 265VAC
DLP100/C2, DLP100/C2EJ
4
V .A D J
-V
+V
V .A D J
H
D C ON
D C ON
A LM
A LM
-V
V.ADJ
H
-V
H
3
D C ON
A LM
IN D C
. O N T .E Q .
4 5 JB
L
+V
IN D .C O NT .E Q .
4 5 JB
N
L
IN D .C ON T .E Q .
45 JB
N
L
Load (%)
+V
N
2
1
0
-10
2 5m m
o r m o re
20 mm
m in im u m
2 0m m
m in im u m
0
25 mm
o r m o re
10
20
30
40
50
60
Ambient Tnmperature (℃)
Air Flo w
DLP180, DLP180/EJ
Back Down Mounting (B)
85 - 265VAC
100
Load (%)
80
60
40
20
0
-10
0
10
20
30
40
50
Ambient Tnmperature (℃)
60
85 - 170VAC
DLP240, DLP240/EJ
Output Derating
Load (%)
100
80
60
80
Load (%)
DLP75, DLP75/EJ, DLP120, DLP120/EJ
60
40
20
40
0
-10
20
0
-10
170 - 265VAC
100
85 - 132VAC or
170 - 265VAC
0
10
20
30
40
50
60
70
Ambient Tnmperature (℃)
0
10
20
30
40
50
Ambient Tnmperature (℃)
60
・All specifications are subject to change without notice.
A-41
DLP SERIES
4. Wiring Method
● The output load line and input line shall be separated
and twisted to improve noise sensitivity.
● Use all lines as thick and short as possible to make
lower impedance.
● Noise can be eliminated by attaching a capacitor to the
load terminals.
● EMI reduction performance by winding the cable around
DLP
the toroidal ferrice core several times. Use any appropriate commecially available ferrite core from local
vendor.
● For safety and EMI considerations, connect FG terminal
of input connector and mountable FG to ground terminal of equipment.
● Recommened screw torque is 1.27N.m (DLP), 0.49N.m
(DLP/EJ).
● Recommened wire type: solid and stranded, AWG 12〜
20 (wire strip length: 6~7mm for DLP/EJ models).
● For case to meet EN60529 IP20, use the following
wiring method to prevent from electrical shock. (DLPstandard models).
Input and output
terminal block
Insulator
Wire
(Old version)
Terminal block cover
Input and output terminal block
(M422D Series(MORIMATSU)
Insulator
Wire
5. External Fuse Rating
Refer to the following fuse rating when selecting the
external fuses that are to be used on input line. Surge
current flows when line turns on. Use slow-blow fuse or
time-lag type fuse. Do not use fast-blow fuse. Fuse rating
is specified by in-rush current value at line turn-on. Do not
select the fuse according to input current (rms.) values
under the actual load condition.
DLP75, DLP75/EJ DLP75/C2, DLP75/C2EJ
DLP100, DLP100/EJ DLP100/C2, DLP100/C2EJ
DLP120, DLP120/EJ
DLP180, DLP180/EJ
DLP240, DLP240/EJ
5A
5A
5A
5A
6.3A
6. Power supply mounting
1Power supply mounting on
DIN RAIL (TS35 or equivalent)
(1)
Tilt the unit slightly rearwards, fit the unit over top hat
rail.
(4)In order to tighten the unit mounting, the Din rail stopper
attached on both sides of the unit is reco- mmended.
2Power supply removal from DIN RAIL
(2)
Slide it downward until it hits the stop.
(1)Switch main power off and disconnect your system
from the supply network. Push the button on the rear
upper edge of the unit or move the removal hole on
the rear down edge downwards by screw driver. Gently
lift lower front edge of the unit (tipping) and remove it.
(3)
Press against the bottom front side for locking.
Shake the unit slightly to check the locking action.
7. Before concluding that the unit is at fault...
Before concluding that the unit is at fault, make the following checks.
● Check if the rated input voltage is connected.
● Check if the wiring of input and output is correct.
● Check if the wire material is not too thin.
● Check if the output voltage control (V.ADJ) is properly
adjusted.
over specification.
● Audible noise can be heard during dynamic-load operation.
● Audible noise can be heard when input voltage waveform is not sinusoidal wave.
● Check if a mass inductor connected with the input line.
Operation of the unit may become unstable.
● Check if the output current and output wattage do not
A-42
・All specifications are subject to change without notice.
DLP SERIES
8. Notes
1) Meet EN50178 over voltage Category III (Primary).
Over voltage Category II (Secondary).
C2EJ are categorized as class2 output source.
3) Radio Interference Suppression Test is not performed.
2)
DLP75/C2, DLP75/C2EJ, DLP100/C2, DLP100/
9. Repair
In case of damage or repair of this product, please return
to our service center or factory.
Conditions of usage at the free of charge warranty are as
follows.
(1)Average operating temperature (ambient temperature
of the power supply unit) is under 40ºC.
(2)Average load factor is 80% or less.
(3)Installation method : Standard installation.
However, the maximum rating is within the output
derating.
・All specifications are subject to change without notice.
Following cases are not covered by warranty.
(1)Improper usage like dropping products, applying shock
and defects from operation exceeding specification of
the units.
(2)Defects resulting from natural disaster (fire, flood).
(3)Unauthorized modifications or repair by the buyers
defects not caused by DENSEI-LAMBDA.
DLP
A-43
DLP-PU SERIES
DLP-PU Instruction Manual
BEFORE USING THE POWER SUPPLY UNIT
Pay attention to all warnings and cautions before using the unit.
Incorrect usage could lead to an electric shock, damage to the
unit or a fire hazard.
8. Avoid places subject to shock or vibration.
A device such as a contact breaker may be a vibration
source. Set the product as far as possible from possible
sources of shock or vibration.
9. If the product is used in an area with excessive electronic noise, be sure to separate the unit as far as possible from the noise sources.
・Warning Symbols
CAUTION
DLP
・OPERATION TEMP RANGE -lO---+60℃ (100%LOAD) +70℃ (60%LOAD)
SEE INSTRUCTION MANUAL
Precautions in Using the product:
・DO NOT MODIFY, DISASSEMBLE THE POWER SUPPLY.
・INSTALLATION BY TRAlNED PERSONAL ONLY.
When the product is used under the circumstance or environment below, ensure adherence to limitations of the ratings and
fimctions.
Also take countermeasures for safety precautions such as failsafe installations.
1.Under the circumstances or environment which are not described in the instruction manual.
2.For nuclear power control, railway, aircraft, vehicle, incinerator, medical equipment, entertainment equipment, safety device etc . . .
3.For applications where death or serious property damage is
possible and extensive safety precautions are required.
4.Don't recommond using input power source with large inductance, which may cause unit operate unstablely.
5.The end equipment manufacturer must provide protection to
service personal against inadvertent contact with terminals.
These terminals must not be user accessible.
6.Ensure power supply with over current protection (less than
24A) function.
NOTICE :
(1) Installing/Storage Environment
1. Store the product with ambient temperature -30 to
+85℃, and relative humidity 10 to 95% (No Dewdrop).
2. Never operate the unit under over current or shorted
conditions for 30 seconds or more and out of Input Voltage Range in specification which could result in damage or insulation failure or smoking or burning.
3. Confirm connections to input/output terminals are correct as indicated in the instruction manual.
4. Use the product where the relative humidity is 30 to
90% (No Dewdrop).
5. Avoid places where the product is subjected to direct
sun light.
6. Avoid penetration of metal chips when processing
mounting holes.
7. Avoid places where the products are subjected to penetration of liquid, foreign substance, or corrosive gas.
1. Terminal Explanation
①
② ③ ④ ⑤
⑦
⑧
⑥
⑨ ⑩
Input channel A
monitor device
21∼28VDC
Input channel B
monitor device
①
②
③
④
⑤
⑥
⑦
⑧
⑨
⑩
OK: OK signal terminal of relay A
+: + Signal terminal of relay A (relay A common)
F: F signal terminal of relay A
OK: OK signal terminal of relay B
+: + Signal terminal of relay B (relay B common)
F: F signal terminal of relay B
A+: DC input + of channel A
B+: DC input + of channel B
+V: Output terminal +
−V: Ground of both input voltage and output voltage
LOAD
2. Terminal Connecting Method
Pay attention to the input wiring. If it is connected to wrong
①
terminal, the unit may be damaged.
② ③ ④ ⑤
⑥
Input channel A
monitor device
Input channel B
monitor device
● Input must be off when making counections.
● C onnect ground of input channel A, input channel B and
output together to -V tenninal.
When connecting or removing input and output wire, do not
apply stress to PCB.
⑦
A-44
⑧
⑨ ⑩
21∼28VDC
LOAD
・All specifications are subject to change without notice.
DLP-PU SERIES
Power
Supply
#1.
DLP-PU/EJ
Dual Input
+
Input channel A
3. Explanation of Functions and Precautions
monitor device
1Simplified DLP-PU/EJ connection block
A+
+V
B+
+V
+
−
−
F
+
Supply
−
#2)
in conformance
with UL508 safety requirement.
#2.
−
+DC
−BUS
DLP-PU/EJ
Single Input
A
+
F
Input channel B
+
B Single Input Mode
OK
LED
+
F
OK
Note: please
supplies
(#1 and
monitor
device
F
Power +use the same model power
+
LED
OK
A+
B+
+V
+V
−V
Power
Supply
+
−
−
Input channel A
monitor device
OK
A+
B+
+V
+V
−V
+
+
F
OK
DLP
Input channel B
monitor device
+
F
B
OK
+DC
-V
−BUS
2Input Voltage Range
Nominal input voltage range is 21 - 28VDC. Input voltage
above 35VDC (continuous), or reverse output voltage more
than 35VDC may cause unit damage.
3Output Voltage Range
Output voltage is the higher input voltage of both channels
decrease 0.5VDC (output drop voltage).
8Isolation Test
Isolation resistance shall be more than 10MΩ at 500VDC for
safety operation, voltage setting of DC isolation tester must
be done before the test. Ensure that it is fully discharged afier
the test. (Ref. to Fig C)
1 Input, Output - FG (Chassis) -- 500VDC 10MΩ or more
2 Input, Output - Relay Contact --500VDC lOMΩ or more
3 Relay Contact - FG (Chassis) -- 500VDC 10MΩ or more
4Nominal Input Current and Maximum Output Current
③
Nominal input current is 20A (A,B total), maximum output current is 20A.
5Input Voltage Supervision
Each channel is supervised. For voltages above low input
voltage alarm level (19.2VDC±1%), a relay is activated closing a galvanically free contact, + to OK (Normally Open, NO).
For voltages above high input voltage alarm level (30VDC±
5%) a relay is activated closing a galvanically free contact, +
to F. The relay also has a Normally Closed, NC contact set,
eg. + to F (Fail).
This voting device also is equipped with green Light Emitting
Diodes, Iighting simultaneously with the respective activated
relay. LED Iights when input voltage within input voltage
range, goes off when input voltage below low input voltage
alarm level or above high input voltage alarrn level.
6Supervision Built-in Relay Specification
Maximum relay contacts ratings is 28VDC, 1A. Minimum relay
contacts ratings is DC 1mA (5mA or more recommended).
The relay outputs need maximum 4A over current protection.
OK
F
+
OK
F
+
②
①
FG
A+ B+ +V +V −V
9Withstand Voltage
This model is designed to withstand 500VAC between input,
RELAY CONTACT
SHORT ALL PINS
output and FG (Chassis), input, output and relay contact,
relay contact and FG each for I minute. When testing with+ F of
+ F withstand voltage test
OK the
OK limit
stand voltage, set current
③
OK + F OK + F
equipment to 100mA. The applied voltage must be gradually
CHASSIS IS FG
increased from zero to the testing value and②then gradually
②
decreased for shut down. When timer is used, the power supply may be damaged
by
high
impulse
voltage
at timer switch
FG
FG
①
on and off. (Ref.
to
Fig
C)
A+ B+ +V +V −V
①
A+ B+ +V +V −V
1 Input, Output - FG (Chassis) -- 500VAC 100mA or more
2 Input, Output - Relay Contact --500VAC 100mA or more
SHORT ALL PINS
INPUT. OUTPUT
3 Relay Contact - FG (Chassis) -- 500VAC 100mA or more
③
Fig. C Test Method
7Operation Schematic
RELAY CONTACT
SHORT ALL PINS
Fig. A Dual Input Mode
Power
Supply
#1.
Power
Supply
#2.
+
+
−
−
+
+
−
−
DLP-PU/EJ
Dual Input
A+
B+
+V
+V
−V
OK
+
F
OK
+
F
③
Input channel A
monitor device
Input channel B
monitor device
+DC
DLP-PU/EJ
Single Input
OK
A+
+
B+
F
+V
Power +
OK
+V without notice.
・All specifications
+
Supply −are subject to change
−V
−
F
+
OK
+
F
OK
+
F
CHASSIS IS FG
①
②
FG
A+ B+ +V +V −V
SHORT ALL PINS
INPUT. OUTPUT
−BUS
Input channel A
monitor device
Input channel B
monitor device
A-45
DLP-PU SERIES
4. Mounting Directions
1Output Derating according to the Mounting Directions
Back Down Mounting (B)
Recommended standard mounting method is (A). Please do
not use installation method (B). Refer to the derating below.
Do not exceed the load deratings.
Normal mounting (A)
Air Flow
25mm
or more
25mm
or more
+V
-V
+V
V.ADJ
-V
+V
V.ADJ
H
H
DC ON
DC ON
ALM
ALM
ALM
IND.CONT.EQ.
45JB
L
25mm
or more
Vin=21∼28VDC
100
IND.CONT.EQ.
45JB
N
Output Derating (100% load=20A)
-V
V.ADJ
H
DC ON
L
N
20mm
minimum
80
IND.CONT.EQ.
45JB
L
20mm
minimum
Load (%)
DLP
N
60
40
20
25mm
or more
0
-10 0
10 20 30 40 50 60 70
Ambient Temperature (℃)
Air Flow
5. Wiring Method
●T
he output load line and input line shall be separated and
twisted to improve noise sensitivity.
● Use all lines as thick and short as possible to make lower
impedance.
● N oise can be eliminated by attaching a capacitor to the
load terminals.
● Recommened screw torque is 0.49N.m (5kg.cm).
● R ecommened wire type: solid and stranded single wire,
AWG 12〜20 (wire strip length: 7mm).
● Below appropriate over current protection is required when
make connection.
Over current protection rating is based on the
smallest wire connection to either the input or output
Maximum over current
Wire size
(AWG)Wire size
(mm2)
protection ratin (A)
20
0.52
5
18
0.82
7
16
1.3
10
14
2.1
20
12
3.3
25
6. Power supply mounting on DIN RAIL (TS35 or equivalent)
(1) Tilt the unit slightly rear- (2) S
lide it downward until it (3) Press against the bottom (4) In order to tighten the
wards, fit the unit over
hits the stop.
unit mounting, the Din
front side for locking.
top hat rail.
rail stopper attached on
Shake the unit slightly to
both sides of the unit is
check the locking action.
recommended.
Power supply removal
from DIN RAIL
Switch main power off
and disconnect your
system from the supply
network. Push the button
on the rear upper edge
of the unit or move the
removal hole on the rear
down edge downwards
by screw dnver. Gently
lift lower front edge of
the unit (tipping) and remove it.
7. Before concluding that the unit is at fault...
Before concluding that the unit is at fault, make the following
checks.
● Check if the rated input voltage is connected.
● Check if the wiring of input and output is correct.
● Check ifthe wire material is not too thin.
● Check if the output current and output wattage do not exceed specification.
8. Notes
1) Meet EN50178 over voltage Category I.
2) Radio Interference Suppression Test is not performed.
9. Repair
In case of damage or repair of this product, please return to our service center or factory.
A-46
・All specifications are subject to change without notice.