Cabinets
Gallagher Cabinets are secure enclosures for the Gallagher Controllers 6000,
3000 and 5000GL, and Gallagher HBUS, GBUS and LOCAL BUS I/O Devices.
Gallagher Cabinets are designed to house multiple Gallagher products. There are two cabinet
sizes available, accommodating either one or two printed circuit board (PCB) footprints.
Mounting options allow combinations of various PCB types to be installed.
1. Gallagher Cabinet
3. Gallagher Dual Cabinet
Manufactured from a stong polycarbonate/ABS plastic alloy,
the Gallagher Cabinet has a UL94 flame rating of HB. It
provides one footprint for Gallagher Controllers and LOCAL
BUS I/O PCBs. When a PCB is installed, optical tamper
protection is provided for both the front and the rear.
The Gallagher Dual Cabinet is a secure steel enclosure
accommodating two footprints, doubling the housing capacity
for any combination of Gallagher PCBs. When the PCB is
installed, optical tamper protection is provided for both the
front and rear of the Cabinet. The Cabinet is also available
with an optional 8 Amp power supply which has visible
indicators for ‘low mains’ and ‘low battery’ power monitoring.
A separate mounting plate and tamper board is available to
enable Gallagher GBUS I/O Devices (excluding the Gallagher
High Density I/O Interface) to be fitted with optical tamper
protection.
One cabinet houses any one of the following options:
•1x Gallagher Controller (6000, 3000 or 5000GL)
•1x Gallagher 4H, 8H, 4R or 8R Module
•1x Gallagher I/O Interface
•1x Gallagher Relay Interface
•1x Gallagher Reader I/O Interface
•2x Gallagher Universal Reader Interfaces
•2x Gallagher Strike Controllers
•1x Gallagher High Density I/O Interface. A second Gallagher
High Density I/O Interface can be installed in a single cabinet
using standoffs.
2. Gallagher GBUS I/O Accessory Cabinet
A variation of the Gallagher Cabinet, the Gallagher GBUS
I/O Accessory Cabinet is a secure enclosure providing one
footprint for Gallagher GBUS I/O devices. This cabinet is
supplied with a mounting plate and tamper board.
The input/output expansion boards are modular, designed
to be mounted on the mounting plate in the following
combinations:
•Up to 4x Gallagher 8-Input Expansion or Gallagher GBUS
Universal Reader Interfaces, or
•Up to 2x Gallagher I/O Expansion Interfaces, or
•1x Gallagher I/O Expansion and up to 2x Gallagher 8-Input
Expansion or Gallagher GBUS Universal Reader Interfaces
security.gallagher.com
All devices must be mounted in the Cabinets following the
installation instructions to comply with international emission
standards such as C-Tick, CE and FCC.
Gallagher Controller Sub-Plate
The Gallagher Controller Sub-Plate is designed to be mounted over a
• 1x Gallagher I/O Expansion Interface
Gallagher Controller 5000GL to allow either of the following to be
• 2x Gallagher 8-Input Expansion Interfaces.
installed in the same footprint*:
*It can also be installed over a Gallagher Controller 3000 where there is no Gallagher Dialler.
GALLAGHER CABINET AND GALLAGHER GBUS I/O ACCESSORY CABINETS
Housing
Height x Width x Depth
280 x 280 x 94 mm (11.02 x 11.02 x 3.7in)
Weight
1.9 kg (4.19lb)
Footprints
1
Temperature Range
-10° to +55° C (14°F to 131°F)
Humidity
95% non-condensing
Protection Rating
IP44
Fire Resistance
Flame rating of plastic used in Cabinet
UL94/VO
Compliance Standards
Compliance with other international standards will be proven as required. Please
contact Gallagher for the latest list of approvals. All Gallagher products must be
installed in accordance with the Installation instructions to
comply with international standards.C-Tick, CE
Environmental Data
GALLAGHER DUAL CABINET
Housing
Height x Width x Depth
620 x 372 x 150 mm (24.4 x 14.65 x 5.9in)
Weight
6.8 kg (14.99lb)
Footprints
2
Material
Approx 1mm thick steel (0.03 in)
Humidity
90% non-condensing
GALLAGHER POWER SUPPLY UNIT
Construction
Mean Well AD-155A PSU with customized monitoring board and isolated auxiliary power output. Please see the Dual Cabinet and
Power Supply Installation Note for full specifications.
Input Voltage
100 V AC - 240 V AC
Output Voltage
Current Range
Primary power output
13.8 V DC
Auxiliary isolated power output
13.5 V DC
Total output current: 8A (10A with cooling fan - fan not included)
Primary output current range: 0~8A (including max. 0.5A battery output)
Auxiliary isolated output current range
0 ~ 1 A*
*Total current output (primary + auxiliary outputs) may be configured to a maximum of 8A
Working Temperature
-10° to +50° C (14°F to 122oF)
Standards Compliance
EN55022 (EMC Standard)
EN60950 (Safety)
Built in Protection
Short circuit/Over load/Over voltage protection
Battery low and polarity protection
Monitoring
Mains power and low battery monitoring via visual LED indicators and
Gallagher Command Centre alarms
C200104
Ft Dual Cabinet No PS Cool Grey
C200103
Ft Dual Cabinet No PS Charcoal
C200107
Ft Dual Cab No PS Reinforced Cool Gry Ul
C200108
Ft Dual Cab No PS Reinforced Charcoal Ul
C200105
Ft Dual Cabinet 8A PS Cool Grey
C200109
Ft Dual Cabinet 8A PS Charcoal
C200001
Gallagher Mounting Plate
C200440
Gallagher Power Supply
C200002
Gallagher Controller Sub-Plate
C200610
Gallagher Tamper Board - Board Only
C200003
Controller 6000 I/0 Mounting Plate
4G2262
Gallagher Cabinet Master Key
GALLAGHER WORLD HEADQUARTERS
Kahikatea Drive, Hamilton 3206
Private Bag 3026, Hamilton 3240
New Zealand
TEL: +64 7 838 9800
EMAIL: security@gallagher.com
security.gallagher.com
security.gallagher.com
REGIONAL OFFICES
New Zealand................................... +64 7 838 9800
Americas ...................................... +1 877 560 6308
Asia ............................................... +852 3468 5175
Australia ...................................... +61 3 9308 7722
India ........................................... +91 80 2676 2084
Middle East................................... +971 4 2602145
South Africa ................................ +27 11 974 4740
United Kingdom / Europe.......... +44 2476 64 1234
DISCLAIMER: This document gives certain information about
products and/or services provided by Gallagher Group Limited
or its related companies (referred to as “Gallagher Group”). The
information is indicative only and is subject to change without
notice meaning it may be out of date at any given time. Although
every commercially reasonable effort has been taken to ensure the
quality and accuracy of the information, Gallagher Group makes no
representation as to its accuracy or completeness and it should
not be relied on as such. To the extent permitted by law, all express
or implied, or other representations or warranties in relation to the
information are expressly excluded. Neither Gallagher Group nor
any of its directors, employees or other representatives shall be
responsible for any loss that you may incur, either directly or
indirectly, arising from any use or decisions based on the
information provided. Except where stated otherwise, the
information is subject to copyright owned by Gallagher Group and
you may not sell it without permission. Gallagher Group is the
owner of all trademarks reproduced in this information. All
trademarks which are not the property of Gallagher Group, are
acknowledged. Copyright © Gallagher Group Ltd 2015. All rights
reserved.
3E1338 – 07/16
GALLAGHER PART NUMBERS
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising