frequency transmitter

frequency transmitter
Space-saving Signal Conditioners M3-UNIT Series
FREQUENCY TRANSMITTER
(field- and PC-configurable)
M3LPA
MODEL
18 (.71)
MODEL & SUFFIX CODE SELECTION
M3LPA–❑/❑
MODEL
106
(4.17)
INPUT SELECTION
Open Collector
Mechanical Contact
Voltage Pulse
Two-wire Current Pulse
RS-422 Line Driver
110.5 (4.35)
mm (inch)
EXCITATION SELECTION
4V DC / 20mA
8V DC / 20mA
12V DC / 20mA
OUTPUT SELECTION
◆DC Current: Usable range 0 – 20mA; min. span 1mA
◆DC Voltage
Narrow Spans: Usable range ±2.5V; min. span 250mV
Wide Spans: Usable range ±10V; min. span 1V
POWER INPUT
M2 : 100 – 240V AC
R4 : 10 – 32V DC
CONFIGURATION OPTIONS
A : PC and field configurable
B : Field configurable
ORDERING INFORMATION
Specify code number. Orders will be shipped at default factory settings as shown in the table below.
Ordering example:
•Code number (e.g. M3LPA-R4/A)
ITEM
Input type
Frequency range
Sensor excitation
Output range
Threshold
FACTORY SETTING
Open collector
0 – 100 kHz
12V DC / 20mA
4 – 20mA
2V
Functions & Features
• Converts the output from a pulse-type transducer
into a standard process signal
• Sensor excitation
• Easy ‘One-Step Cal’ calibration using the front
three control buttons without needing a PC; PC
software is also usable.
• Both input and output type and range are
configurable
Typical Applications
• Positive displacement flowmeters, turbine
flowmeters and vortex flowmeters
• Measuring rotation speed of a machine generating dry contact signals
Configuration
‘One-Step Cal’ calibration: With I/O type and the
full-scale range configured via the
internal DIP switches, precise 0% and
100% ranges are calibrated via the front
control buttons with a help of LED.
PC configurator (model: M3CON): Via Windows
PC connected to the front jack.
Programmable features include:
•I/O type and range, threshold
•Zero and span adjustments
Status indicator LED: Tri-color (green/amber/red)
LED; Flashing patterns indicate operation status of the transmitter.
RELATED PRODUCTS
•PC configurator software (model: M3CON)
Downloadable at M-System’s web site:
http://www.m-system.co.jp
•PC configurator cable (model: MCN-CON)
GENERAL SPECIFICATIONS
Connection: Removable terminal block
Housing material: Flame-resistant resin (grey)
Isolation: Input to output to power
Overrange output: Approx. -15 – +115%
Fine zero and span adjustments: ±15% via the front
control buttons
INPUT
Measurable frequencies: Minimum span 10% of the
frequency range selected in Table 3.
See each input type for the maximum span.
Time constant is set to 50 msec. with the
‘large’ noise filter setting and to 10 msec.
with the ‘small’ noise filter setting (Table
9).
Pulse width time requirement: Min. 5 µsec.,
max. 10 sec.
P. 1 / 6
ES-2656 Rev.9
M3LPA
■OPEN COLLECTOR
Maximum frequency: 0 – 100 kHz
Input amplitude: Min. 4V, max. 12V
Sensing voltage/current: Approx. 12V, 8V or 4V DC
@1mA
Detecting levels: ≤200Ω for ON; ≥200kΩ for OFF
■MECHANICAL CONTACT
Maximum frequency: 0 – 10 Hz
Input amplitude: Min. 4V, max. 12V
Sensing voltage/current: Approx. 12V, 8V or 4V DC
@1mA
Detecting levels: ≤200Ω for ON; ≥200kΩ for OFF
■VOLTAGE PULSE
Maximum frequency: 0 – 100 kHz
Waveform: Square or sine
Input impedance: 10kΩ minimum
Input amplitude: Min. 0.1V p-p, max. 100V p-p
Max. voltage between input terminals: 100V
Detecting levels: -2 – +4V
■TWO-WIRE CURRENT PULSE
Maximum frequency: 0 – 100 kHz
Input resistance: Receiving resistor 100Ω
Input range: 0 – 25mA
Input amplitude: Min. 4mA, max. 20mA
Detecting levels: -2 – +4V
■RS-422 LINE DRIVER PULSE
Maximum frequency: 0 – 100 kHz
Receiver: Conforms to RS-422
Load resistance: Output drive 1mA maximum
(Range) 0 – 10V
: 10k (Ω minimum)
-10 – 0V
: 10k
0 – 2.5V
: 2.5k
-2.5 – 0V
: 2.5k
INSTALLATION
Power input
AC:
Operational voltage range 85 – 264V AC;
47 – 66 Hz; approx. 5VA at 100V
approx. 7VA at 200V
approx. 8VA at 264V
DC:
Operational voltage range 9 – 36V DC;
approx. 3W; ripple 10% p-p max.
Operating temperature: -25 to +65°C (-13 to +149°F)
Operating humidity: 0 to 95% RH (non-condensing)
Mounting: DIN rail
Dimensions: W18×H106×D110.5 mm
(0.71"×4.17"×4.35")
Weight:
100 g (0.22 lbs)
PERFORMANCE
Accuracy: Input accuracy + output accuracy
Input accuracy: ≤±0.03% of input range (Table 3)
Output accuracy: ≤±0.03% of output range (Table 10/11)
The input accuracy is inversely proportional to the input
span; while the output accuracy is likewise inversely
proportional to the output span.
Temp. coefficient: ±0.015%/°C (±0.008%/°F)
at -5 to +55°C (23 to 131°F) of I/O range
Response time: Ts + Td
Measuring Time
OUTPUT
■DC CURRENT
Maximum range: 0 – 20mA DC
Minimum span: 1mA
Conformance range: 0 – 24mA DC
Offset:
Lower range can be any specific value
within the output range provided that
the minimum span is maintained.
Load resistance: Output drive 12V maximum
(Range) 0 – 20mA
: 600Ω maximum
■DC VOLTAGE
Narrow Spans (mV)
Maximum range: -2.5 – +2.5V DC
Minimum span: 250mV
Conformance range: -3 – +3V DC
Wide Spans (V)
Maximum range: -10 – +10V DC
Minimum span: 1V
Conformance range: -11.5 – +11.5V DC
Offset:
Lower range can be any specific value
within the output range provided that
the minimum span is maintained.
Input
Output
Ts
Td
Ts : Measuring Time
Td : Delay caused by internal processing (50 – 100 ms)
Line voltage effect: ±0.1% over voltage range
Insulation resistance: ≥100MΩ with 500V DC
Dielectric strength: 1500V AC @1 minute
(input to output to power to ground)
STANDARDS & APPROVALS
CE conformity: EMC Directive (89/336/EEC)
EMI EN61000-6-4
EMS EN61000-6-2
Low Voltage Directive (73/23/EEC)
Installation category II
Pollution degree 2
Max. operating voltage 300V
Input or output to power – Reinforced insulation
Input to output – Basic insulation
Specifications subject to change without notice.
P. 2 / 6
ES-2656 Rev.9
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
■DC POWERED TYPE
STATUS
1
2
3
INPUT *1
RS-422
Receiver
CONTROL SW
DIP SW
Excitation
Supply
9
Isolation
Digital
Computation
Output
Driver
4
CONFIGURATOR
OUTPUT
8 –
6
5
7 +
10
Waveform
Shaper
11 +
*2
DC POWER
12 –
JACK
Terminal Block
■AC POWERED TYPE
STATUS
1
2
3
INPUT *1
RS-422
Receiver
CONTROL SW
DIP SW
Excitation
Supply
9
Isolation
Digital
Computation
Output
Driver
4
CONFIGURATOR
OUTPUT
8 –
6
5
7 +
10 U
Waveform
Shaper
*2
AC POWER
11
12 V
JACK
Terminal Block
*2. Be aware that the AC power and DC power connect to different terminals.
*1. Input Connection Examples
■Open Collector
■Voltage Pulse
–
–
6
■Two-wire Current Pulse
• Built-in Excitation
+
6
INPUT
+
5
+
5
■Excitation Supply
+
–
6
INPUT
5
■Mechanical Contact
■RS-422 Line Driver Pulse
–
–
6
+
1
INPUT
+
5
–
100Ω
4
• External DC Supply
2
6
+
5
100Ω
INPUT
–
3
EXCITATION
3
4
P. 3 / 6
ES-2656 Rev.9
6
M3LPA
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS mm (inch)
10 11 12
9
1
2
3
4
5
6
DIN RAIL
35mm wide
62 (2.44)
35.4 (1.39)
8
106 (4.17)
7
18 (.71)
110.5 (4.35)
[3.3 (.13)]
•When mounting, no extra space is needed between units.
ONE-STEP-CAL CALIBRATION
CONFIGURATION MODES & DIP SW
When you program the transmitter module, two configuration modes are available: Field Configuration using DIP SW
/ control buttons, and PC Software. (Option B type is for the
field configuration only.)
The internal DIP switches are used to configure input and
output type. Once the module is configured, precise ranges
are set up with the front control buttons using a simulator
connected to the input terminals and a multimeter connected
to the output terminals as a reference.
INPUT & OUTPUT RANGING
For example, suppose that the DIP switches are configured
for the voltage pulse (0 – 100kHz full-range). Turn the power
supply to the transmitter on and press MODE button to enter to the Input Calibration Mode. Apply the desired minimum (e.g. 0 Hz) and maximum (e.g. 1 kHz) input levels and
push the DOWN (zero) and UP (span) respectively to set the
input range to 0 – 1 kHz.
FINE ZERO & SPAN ADJUSTMENTS
After the transmitter is installed and operational, fine zero
and span tuning can be also performed using the front control buttons. Both zero and span are adjustable within ±15%.
PC SOFTWARE CONFIGURATION
When you need to apply the same setting to multiple transmitters, downloading one setting from the PC is convenient.
The PC Configurator Software (model: M3CON) is available
separately.
Turn the transmitter to PC Configuration Mode (See Table
1) and all programmable features can be set up on a PC regardless of other DIP SW setting except for the following:
the output type must be selected with the DIP SW1-1 through
SW1-4 (See Table 11), and the pulse sensing type and noise
filter must be selected with the DIP SW4-1 through SW4-3
(See Tables 8 and 9).
For detailed information on the PC configuration, refer to
the M3CON instruction manual.
Then the output range can be calibrated in a similar manner after moving to the Output Calibration Mode by pressing MODE button again. Increase or decrease the simulated
input until the output meter shows the desired levels and
push the DOWN (zero) and UP (span) respectively for the
minimum (e.g. 4mA) and maximum (e.g. 20mA) levels.
The front LEDs’ colors and flashing patterns help you to easily
identify the transmitter’s status and confirm the setup actions in each step of Calibration Modes. See detailed explanation in “Calibration Flow Chart.”
The calibrated input and output ranges are stored in the
internal memory. The module reads the DIP-switch-calibrated configuration only once after the power supply is
turned on. Set the switches with the power supply removed.
Specifications subject to change without notice.
P. 4 / 6
ES-2656 Rev.9
EXTERNAL & INTERNAL VIEWS
■FRONT VIEW
■SIDE VIEW
LED1 (LD1)
10 11 12
7
8
9
Configuration DIP SW
LED2 (LD2)
LED3 (LD3)
4 3 2 1
MODE Button
OFF
UP Button
ON
DOWN Button
Configurator Jack
SW1
8 7 6 5 4 3 2 1
SW2
OFF
SW3
ON
1
2
3
SW4
4 3 2 1
4
5
6
OFF
ON
DIP SWITCH SETTINGS
■CONFIGURATION MODE (SW3)
MODE
DIP SW
PC
SW3-8
OFF
ON
Table 1
Configuration mode can be
confirmed with the front LED.
■INPUT TYPE (SW2)
INPUT
Open Collector
Mechanical Contact
Voltage Pulse
Two-wire Current Pulse
RS-422 Line Driver Pulse
Table 2
SW2-2
OFF
ON
OFF
ON
OFF
ON
ON
FREQUENCY
0 – 10 Hz
0 – 100 Hz
0 – 1k Hz
0 – 10 kHz
0 – 100 kHz
SW2-5
ON
OFF
ON
OFF
ON
Table 3
SW2-4
OFF
ON
ON
OFF
OFF
■PULSE AMPLITUDE (SW2)
AMPLITUDE
MAXIMUM VOLTAGE SW2-8
50 – 100V p-p
100V
OFF
25 – 50V p-p
50V
ON
10 – 25V p-p
25V
OFF
5 – 10V p-p
10V
ON
1 – 5V p-p
5V
OFF
0.5 – 1V p-p
1V
ON
0.1 – 0.5V p-p
0.5V *1
OFF
*1. Max. input frequency limited to 50 kHz.
SW2-3
OFF
OFF
OFF
ON
ON
Table 4
SW2-7
OFF
OFF
ON
ON
OFF
OFF
ON
SW2-6
OFF
OFF
OFF
OFF
ON
ON
ON
Table 5
CUTOUT
With (0.1% fixed)
Without
SW3-7
ON
OFF
■POLARITY (SW3)
Table 6
POLARITY
SW2-1
OFF
■FREQUENCY RANGE (SW2)
■CUTOUT (SW3)
SW3-6
OFF
ON
Bipolor
Unipolor
■EXCITATION SUPPLY (SW3)
EXCITATION
4V
8V
12V
Table 7
SW3-5
ON
OFF
ON
SW3-4
OFF
ON
ON
■PULSE SENSING (SW4) *2
Table 8
SENSING
Capacitor Coupled
DC Coupled
SW4-3
OFF
ON
■NOISE FILTER (SW4) *2
FILTER
Large
Small
Without
Table 9
SW4-2
ON
OFF
OFF
SW4-1
OFF
ON
OFF
■OUTPUT TYPE (SW3 & 1)
Table 10
OUTPUT
SW3-3 SW3-2 SW3-1 SW1-4 SW1-3 SW1-2 SW1-1
0 – 20mA
OFF ON
ON OFF ON OFF OFF
-2.5 – +2.5V ON OFF OFF ON OFF OFF ON
-10 – +10V
OFF OFF OFF ON OFF ON OFF
■OUTPUT TYPE / PC CONFIG (SW1) *2
Table 11
OUTPUT
SW1-4
SW1-3
SW1-2
SW1-1
0 – 20mA
OFF
ON
OFF
OFF
-2.5 – +2.5V
ON
OFF
OFF
ON
-10 – +10V
ON
OFF
ON
OFF
*2. DIP SW setting is required for PC configuration type.
P. 5 / 6
ES-2656 Rev.9
M3LPA
CALIBRATION FLOW CHART
POWER ON
MODE
LD1
G
Fine Adjustments ?
LD2
Control
Buttons
UP
I/O Ranging ?
RUN MODE
DOWN
LD3
A Amber LED
OFF
G Green LED
ON
R Red LED
Blink
G
PUSH MODE 1 – 2 s
PRESS & HOLD MODE > 5s
LD1
R
LD2
G
LD3
FINE ZERO
CALIBRATION MODE
UP or DOWN
Once the transmitter
enters the fine zero
calibration mode,
the output goes to
preadjusted 0%
value regardless
of the present input
signal.
LD1
R
LD2
THRESHOLD
CALIBRATION MODE
LD3
UP or DOWN
PUSH MODE
In order to change the threshold, apply simulated
100% input signal and push UP (increase) or DOWN
(decrease) buttons until the output meter shows
100% output signal as in the example below.
[Example]
Input range: 0 to 100 Hz
Output range: -10 to +10V
Apply 100 Hz and the output meters must show +10V.
PUSH MODE
Apply simulated 0% input signal.
LD1
R
LD2
LD3
G
FINE SPAN
CALIBRATION MODE
UP or DOWN
Once the transmitter
enters the fine span
calibration mode,
the output goes to
preadjusted 100%
value regardless
of the present input
signal.
LD1
R
LD2
R
LD3
INPUT
CALIBRATION
MODE
PUSH DOWN
0% INPUT
CONFIGURED
PUSH
100% INPUT
CONFIGURED
UP
Apply simulated 100% input signal.
PUSH MODE
PUSH MODE
Adjust simulated input until the output meter
shows desired 0% output.
LD1
R
LD2
LD3
OUTPUT
CALIBRATION
MODE
R
PUSH DOWN
0% OUTPUT
CONFIGURED
PUSH
100% OUTPUT
CONFIGURED
UP
Adjust simulated input until the output meter
shows desired 100% output.
PUSH MODE
LD1
G
LD2
RUN MODE
LD3
When you set 0% or 100% input/output ranges,
keep pressing UP or DOWN button until the
LD1 flashes for approx. 5 seconds and turns off,
which indicates the setup is complete.
When you release the button, the LD1 is returned
to ON.
If the LED does not change, the entered level may
be inappropriate: e.g. out of usable range.
Specifications subject to change without notice.
P. 6 / 6
ES-2656 Rev.9