- No category
advertisement
Product description
• Compact dimensions for luminaire installation
• For up to 10 DSI or DALI devices (max. 5 per output channel)
• 2 DALI/DSI output channels with adjustable negative offset from channel 2 to channel 1
• Ambient light sensor with motion detector
• Max. installation height 16 m
• IP65 sensor head
• Switch input for on/off switching and dimming
• Can be remote controlled
• Individual adjustment of the parameters with
DSI-SMART Programmer
• 5-year guarantee
È
Wiring diagrams and installation examples, page 4 luxCONTROL lighting control system basicDIM
basicDIM ILD 16DPI 69f
Compact control module with ambient light sensor and motion sensor
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
1
luxCONTROL lighting control system basicDIM
basicDIM ILD 16DPI 69f
Compact control module with ambient light sensor and motion sensor
Technical data
Rated supply voltage
Mains frequency
Power
Stand-by power
220 – 240 V
50 / 60 Hz
2 W
0.5 W
Momentary-action switch input for dimming single
Digital control line DSI/DALI 2
Control output (devices) 10
Max. output cable length at 1.5 mm²
Operating temperature
Storage temperature
Type of protection controller
Type of protection sensor
Max. casing temperature tc
100 m
0 ... +60 °C
-25 ... +70 °C
IP20
IP65 ready
75 °C
93
120
110
5
99,3 9,9–14,9
37,9–42,3
5
Ordering data
Type basicDIM ILD 16DPI 69f
Article number
28001277
Mounting Packaging carton
Luminaire installation 10 pc(s).
Specific technical data
Type
Light detection angle Light measurement at the sensor head 1
Detection
Illuminance (factory default)
2
Motion detection angle high/low basicDIM ILD 16DPI 69f
13° 1 – 500 lx 150 lx
1 The measured value at the sensor head corresponds to approx. 15 to 2,000 lux on the surface measured.
2 The illuminance is set for a room defined by Tridonic. Depending on the actual room (reflectance) the measured illuminance may deviate from this value.
The illuminance should therefore be checked in the installation and adjusted if necessary.
72° / 60°
Max. cable length sensor
0.8 m
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
2
DSI SMART Programmer
44
2,5
100
Ordering data
Type
DSI-SMART Programmer
Article number
28000843
Packaging carton Weight per pc.
1 pc(s).
0.35 kg
Shading Set
AISLE HALF ENTRY
Ordering data
Type
ACU SHADING AISLE 16DPI highbay
ACU SHADING HALF 16DPI highbay
ACU SHADING ENTRY 16DPI highbay
Article number
28001658
28001660
28001659
Packaging bag
64 pc(s).
500 pc(s).
500 pc(s).
Weight per pc.
0.002 kg
0.002 kg
0.003 kg
luxCONTROL lighting control system basicDIM
DSI SMART Programmer
Product description
• Optional infra-red programming unit for DSI-SMART PTM or basicDIM ILD
1
• Settings can be read and modified
• Programmable functions such as light level, time delay,
P.I.R., bright-out, power up
44
2,5
100
1
At version 2.41 for basicDIM ILD.
Product description
• Shading set consisting of 3 different types of lenses
Ordering data
Type
DSI-SMART Programmer
Article number
28000843
Packaging carton Weight per pc.
1 pc(s).
0.35 kg
Shading Set
AISLE HALF ENTRY
Data sheet 01/17-CO081-8
Subject to change without notice.
Ordering data
Type
ACU SHADING AISLE 16DPI highbay
ACU SHADING HALF 16DPI highbay
ACU SHADING ENTRY 16DPI highbay
Article number
28001658
28001660
28001659
Packaging bag
64 pc(s).
500 pc(s).
500 pc(s).
Weight per pc.
0.002 kg
0.002 kg
0.003 kg www.tridonic.com
3
luxCONTROL lighting control system basicDIM
Mounting box 16DPI
Product description
• Easy adaptation of suspended lighting fixtures to a sensor solution, just by adding one additional hole
• Side entry screw connection in combination with rubber gasket gives a true IP65 protection for industrial applications
• Easy remote commissioning with IR interface while sensor is still protected
ACU MOUNTING BOX 16DPI HIGHBAY ACU MOUNTING BOX 16DPI HIGHBAY with sensor
ø11,4
Ordering data
Type
ACU MOUNTING BOX 16DPI HIGHBAY
93
123
Article number
28001568
Packaging carton Weight per pc.
64 pc(s).
0.105 kg
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
4
luxCONTROL lighting control system basicDIM basicDIM ILD
The basic DIM ILD provides the basis for an easy-to-use and cost-effective lighting system with motion detection.
When the sensor detects movement it triggers a individual adjustable motion detection profile in the control unit.
As the amount of natural ambient light changes the illuminance from the artificial lighting system is adjusted.
The connected luminaires can be switched on and off via momentary-action switch or remote control possible.
IR is always active.
Standards
EN 55015
EN 61000-3-2
EN 61347-1
EN 61347-2-11
EN 61547
EN 62386-101
Glow-wire test according to EN 61347-1 passed.
DALI standard
The basicDIM ILD is designed to control control gear with
DALI standard IEC 60929 (DALI V0) and IEC 62386 (DALI V1).
Installation
• Don‘t use the basicDIM ILD without a sensor.
• DSI/DALI is not SELV. The installation instructions for mains
voltage therefore apply.
• The maximum cable length between the external switch and
basicDIM ILD is 100 m.
• The cable between the luminaire installation sensor and the base
module must not be extended.
• A synchronous operation of DALI and DSI ballasts at the same
control gear is not possible.
• The maximum cable length of the DSI / DALI control signal
(for a cable cross-section of 1,5 m
2
) must not be exceeded .
• Any number of push to make switches may be connected in
parallel to the inputs.
• Do not connect standard switches to the input.
• Please ensure that the detection range of the sensor lies in the
lighting area of the controlled luminaires.
• Please ensure that the detection ranges of the sensors do not
overlap. This may have influence to the lighting control.
• Heaters, fans, printers and copiers located in the detection
zone may cause incorrect presence detection.
• Surface temperature is detected by the sensor.
Clothing or covers which reduce the surface temperature affect
the detection.
• To avoid false readings, the sensor should be installed so there is no direct light from the lamp in the detection zone.
Reflections can disturb the measurement results as well
(e.g. high-bay warehouse of metal shelfs).
• To avoid false measurements caused by the light from other luminaires we recommend that the sensor should be located centrally in the luminaire.
• Sensor wires must be routed separately from the lamp wires and mains cables, otherwise the lighting control system may malfunction.
If separate routing is not possible (for reasons of space) shielded lamp wires and mains cables must be used.
• By repeatedly adjusting the zoom (> 10), the IP protection may be impaired.
• Sensor must be installed according to the installation instructions to ensure the IP protection.
• Sensor head is not UV resistant.
Installation Mounting box 16DPI
• The sensor can be installed only once in the mounting box
(Sensor snap in permanent)!
• Insert the cable of the sensor before installing.
• There are 2 installation variants possible for the sensor.
The sensor can be turned through 180°.
Notes
• In a bright environment the application range of the DSI-SMART
programmer may be limited.
When programming the programmer should be direct pointed to the
sensor.
• In case of pollution or mechanical damage of the lens, the functionality
of the sensor may be limited.
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
5
Mounting variant luminair housing:
Sheet thickness: 1 – 4 mm
R6,5
70
Sensor mounting luxCONTROL lighting control system basicDIM
To change from position Low to
High rotate lens in arrow direction until it stops at High!
• Arrow shows the zoom position.
• To change the zoom rotate the lens until it stops at High or Low position.
• Positions in between High and Low are not allowed.
• See installation notes!
Shader mounting
All 6 snap-fits have to be snaped in
To gurantee IP65 the distance between sensor surface and luminaire surface must be less than 8.5 mm
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
6
Mounting box in luminair housing: luxCONTROL lighting control system basicDIM
ø16,5
Mounting box mounting
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
7
luxCONTROL lighting control system basicDIM
Switch basicDIM ILD has an input terminal for an external switch. Any number of switches can be connected in parallel to the terminal.
Short press (> 50–600 ms):
Long press (> 600 ms):
2 x short press:
ON/OFF
Dim up/down
A change in the light value deactivates lighting regulation only temporarily. As soon as the luminaire has been automatically switched on again (motion detection) or manually switched off and on again, regulation is activated again.
The overwritten setpoint light value is stored (luminaire acknowledges by flashing twice)
Function is lockable via the DSI programmer
DSI/DALI interface
The interface selection DSI or DALI is made by the DSI SMART Programmer.
Wiring diagram basicDIM ILD Cable types and cable cross-sections
Solid wire with a cable cross-section of 0.5 mm² to 1.5 mm².
wire preparation:
0.5 – 1.5 mm²
L
N
2
3
4
6
7
DA
DA
PCA
L
N
T
Sensor basicDIM ILD CH1
D1
D2
CH2
D1
D2
2
3
4
6
7
DA
DA
PCA basicDIM ILD Sensor
Enhancement of controllable light point
By using a combination of DALI Repeater and DALI Power Supply it is possible to enhance the sum of controllable light points. The schematic visualizes the wiring.
8 – 9 mm
L
N
Max. 2
2
3
4
6
7
DA
DA
LCA
N ~ L
PS2
DA DA
L
N
T
Sensor basicDIM ILD CH1
D1
D2
CH2
D1
D2
DA
DA
IN
DALI Repeater
OUT
DA
DA basicDIM ILD Sensor
Use only in combination with DALI Repeater (86458401) and one of the following DALI Power Supplies:
DALI PS1 (24034323), 200 mA, max. 100 additional devices
DALI PS2 (28000876), 240 mA, max. 120 additional devices
Wire length for 1.5 mm 2 cables:
• from basicDIM to DALI Repeater max. 100 m
• after DALI Repeater max. 300 m
This combination can be used on CH1 and CH2.
Max. 120
2
3
4
6
7
DA
DA
LCA
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
8
Light level recognition area h *
8 m d
1.8 m
10 m 2.3 m
12 m 2.7 m
14 m 3.2 m
16 m 3.7 m h
α = 13° d luxCONTROL lighting control system basicDIM
Presence / motion detection h
12 m
12 m
13 m
14 m
15 m
16 m h *
8 m
9 m
10 m
11 m low high high high high high
Zoom low low low low d
12.0 m
13.5 m
15.0 m
16.5 m
18.0 m
14.0 m
15.2 m
16.4 m
17.6 m
18.8 m α high
= 60°
α low
= 72° d
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
9
Presence / motion detection with shader luxCONTROL lighting control system basicDIM
α high
= 26°
α low
= 32° d h
α high
= 30°
α low
= 36° d
α high
= 13°
α low
= 16° h
α high
= 26°
α low
= 32° d h
Application
Data sheet 01/17-CO081-8
Subject to change without notice.
Sensor with or without Shutter
Shelf www.tridonic.com
10
luxCONTROL lighting control system basicDIM
The following operating modes can be set for the motion detector via the basicDIM ILD Programmer or DSI-Smart Programmer:
Active
Off Only
Never Off
Inactive
The light is switched on or off automatically depending on whether or not there is a person in the room.
The motion detector only switches the connected lighting off. The luminaires are switched on manually via the connected external switch or infra-red control.
If it has not detected any movement the sensor dims to the “second light value” parameter and remains at this value
The motion sensor is deactivated. The light must be switched on or off manually.
Switch-off delay
This is the time after which the lighting is switched off if no movement is detected. It can be set via the “time delay” parameter.
Manual-off delay
If the system is switched off manually via the switch or remote control the motion sensor is deactivated. At the end of a 10 minutes delay if motion has not been detected the motion sensor is activated again. If the sensor detects motion during the “Manual Off” delay, the time will be reset to the start.
The following operating modes can be set for lighting control via the DSI-
Smart Programmer:
Active
Inactive
Constant light control is active.
Constant light control is deactivated. The lighting is switched on at 100%.
The value is set with the “light-level” parameter. If the value is set to “max” then lighting control is deactivated. For all other values lighting control is active.
Second light value
On the basicDIM ILD you can set whether the light is to be switched off after the switch-off delay or dimmed to the second light value. The light value and the dwell time (how long the value is held) can be set via the “when vacant” and “sec. level” parameters.
Offset
The light level of channel 2 is less then the light level of channel 1.
The difference can be set with the parameter „Offset Value“ via basicDIM ILD Programmer or DSI-SMART Programmer.
Channel 2
40 %
Channel 1
70 %
Setpoint adjustment
• DSI-SMART Controller: Pressing the Set button stores the current light value as a new setpoint.
• basicDIM ILD Programmer or DSI-SMART Programmer:
Via the “light-level” parameter
• External switch: Briefly pressing the switch twice stores the current light value as a new setpoint. (Function is lockable via the basicDIM ILD
Programmer or DSI Programmer)
Bright-out
If the nominal illuminance (e.g. 500 lux) is exceeded for 10 minutes by more than 150 % (e.g. 750 lux), the lighting is switched off even if motion is detected. The lighting is switched on again when the measured light value falls below the setpoint.
The bright-out function is displayed by a green status indication LED at the sensor.
This function can be deactivated via the basicDIM ILD Programmer or
DSI-SMART Programmer.
500 LUX
Artificial light
Natural light
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
11
luxCONTROL lighting control system basicDIM
User-definable parameters basicDIM ILD have the following user-definable parameters (since DSI-SMART Programmer version 2.30):
The values in parentheses are the factory default settings.
The adjustable values for the basicDIM ILD Programmer is available in a separately documentation on www.tridonic.com.
Parameter light-level time delay if vacant sec. level
P.I.R
bright-out
Power up hold overwrite
PTM Set
DALIorDSI
Offset Mode
Offset Value
Range
(Factory setting)
1 – 100/max
(70)
30 s – 60 min/con
(20 min) off
30 s – 60 min/con
(off)
1 – 100 %
(1 %) active/inactive/off only
(active) yes/no
(yes) on/off
(on) on/off
(off) on/off
(on)
DSI/DALI
(DSI) fixed/converging
(converging)
0 to -70 %
(-30 %)
Description
Selectable lighting control set point, 1 – 100 increments.
“max” also makes it possible to set the control gear to full power. (DSI 255)
“man” indicates whether the adjustment value was overwritten by the SET function of the SMART Controller.
Delay time after the last detected movement
The following values can be set:
30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and “continuous” (no switch-off)
The “off” setting switches the luminaire off after the delay time has elapsed.
If a time value is set, the luminaire dims to the “sec. level” parameter and only switches off after the previously set time has elapsed. The following values can be set: off, 30 seconds, 1, 2, 3, 5, 10, 15, 20, 30, 45 and 60 minutes and “continuous” (“never OFF” function)
Second light level to which luminaire dims after the delay time has elapsed.
(in conjunction with the “if vacant” parameter)
With the “active” setting, the lighting is automatically switched on or off depending whether a person is present.
With the “inactive” setting, the basicDIM ILD/DSI-SMART (PTM) can, in combination with continuous “time delay”, only be used for lighting control.
With the “off only” setting, the lighting has to be switched on manually (momentary-action switch, remote control) but is switched off by the presence detector.
With the “yes” setting, the lighting switches off as soon as the light level exceeds 150 % of the set point for longer than 10 minutes, for instance, if the room is adequately illuminated by sunlight. If the actual value falls below 100
% of the set point, the lighting switches back on again.
With the “no” setting, the lighting remains switched on (at the minimum dimming level) even if the room is adequately illuminated by sunlight and no artificial lighting is required.
With the “on” setting, the luminaire switches on after a mains break.
With the “off” setting, the luminaire does not switch on after a mains break. The presence detector becomes active again after 15 seconds.
If the light level is manually dimmed via a momentary-action switch or remote control, lighting control stops. The previously set dimming level retains its fixed value as long as lighting control is not activated by manual intervention (momentary-action switch or remote control). If there is no movement in the room in this state and the “time delay” has elapsed, the control unit stores the fixed dimming level.
With the “off” setting, lighting control is restarted each time movement is detected.
With the “on” setting, the control unit switches the luminaires back to the fixed dimming level each time movement is detected and lighting control remains stopped. With this setting, lighting control can be activated again via the remote control (Automatic button).
If lighting control was active before repeated detection or if the lighting was switched off manually, the luminaires and lighting control are switched on after movement is detected in order to prevent people having to enter a dark room.
With the “on” setting, it is possible to save the currently set light level as a lighting control set point by pressing the momentary-action switch twice shortly.
With the “off” setting, this function is disabled.
With the “DSI” setting, DSI interface mode is enabled.
With the “DALI” setting, DALI interface mode in which DALI broadcast commands are sent is enabled.
This parameter specifies how the adjustable “Offset Value” of the basicDIM ILD behaves from channel 2 to channel 1 over the dimming range.
With the “fixed” setting, the previously set “Offset Value” remains the same across the dimming range. (e.g. with an “Offset Value” of -30 %, channel 2 remains at 70 % when channel 1 has reached 100 %).
With the “converging” setting, the previously set “Offset Value” remains the same up to a specific dimming level and decreases the closer one gets to 100%. (e.g., with an “Offset Value” of -30 %, the dimming level of channel 2 is 40 % and that of channel 1 is 70 %. but both channels simultaneously change to a dimming level of 100 % if the lighting is dimmed up).
Adjustable brightness difference between channel 2 and channel 1 of the basicDIM ILD.
The following values can be set:
0 %, -10 %, -20 %, -30 %, -40 %, -50 %, -60 % and -70 %
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
12
Default Parameter Motion Detector
Parameter
A light-level
1 time delay
B sec. level
2 if vacant luxCONTROL lighting control system basicDIM
Data sheet 01/17-CO081-8
Subject to change without notice.
www.tridonic.com
13
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project