FOTON 1 LCD 2x20 Display with 4 Keys

FOTON 1 LCD 2x20 Display with 4 Keys
FOTON 1
LCD 2x20 Display with 4 Keys
Revision: E
Doc. Code: 6116-811.4
3.2. Electrical Characteristics
1. Product Description
The FOTON 1 is a man-machine interface used to show
messages and operands values in a LCD, as well as interact
with the system through a membrane keyboard. The messages
may be composed by ASCII code characters and memory
operands, which are supervised while the message is being
displayed. The FOTON 1 sends to the PLC a scan code
correspondent to the pressed key. All communication between
FOTON 1 and PLC (messages upload and configuration) is
done through the serial port.
The FOTON 1 may be connected directly to the RS-232C port of
an AL-600, AL-2000, AL-3000, Quark and Piccolo PLC Series
or to the I/O Cards Bus by an AL-1401, QK1401, AL-1402 or
QK1402 interface cards. It is also possible to connect a FOTON
1 to a RS-485 serial port, for instance to a QK801 PLC using
the F-ALNET1.062 software function.
It may use the same message file from the FOTON 3 MMI, but
with a 50 messages limit, instead of 100.
The message programming is done by the PROFOTON
software.
2. Packing List
The following parts integrate the product:
n FOTON 1 interface
n 4 mechanical fixing support
3. Functional Characteristics
n Nominal voltage:
19.2 to 30 Vdc (ripple included)
n Bus power consumption:
42 mA @ 24 Vdc
n Electrostatic Surge Discharge:
according to IEC 1131, level 4
n Electrical noise immunity (oscillating wave):
according to IEC 1131, class III, and IEEE C37.90.1
(SWC)
n Fast transient pulse immunity (burst): according to IEC10004-4, level 4 for power supply port and level 3 for
communication port
n Irradiated electrostatic field noise immunity:
10 V/m @ 140 MHz
according to IEC 1131
3.3. Software Characteristics
n Up to 50 messages saved on EEPROM
n Memory operands supervision, in decimal or BCD format. The
number of operands to be displayed is limited by the
maximum number of characters per screen (40 characters)
n Configuration saved on EEPROM
n Storing of the value of each pressed key in operand M.
When the key is release, will be written a representative
value of inexistent key = 0 (zero)
4. Physical Dimensions
3.1. General Characteristics
n 2 lines 20 characters backlight LCD
n 4 keys keyboard
n RS-232C port:
9,600 baud, fixed
maximum distance of 15m
n RS-485 port:
9,600 baud, fixed
maximum distance of 2400m
The serial channel is the same, being used as RS-232C or RS485.
5. Installation
n Power Supply Connection by screwed terminal
n Connection cables diameter: 0.5 to 1.5 mm2
n MTBF 65,500 hours at 40°C
according to MIL-HDBK-217E
n Mechanical protection: IP 54
according to IEC 529
n Operation temperature: 0 to 60°C
exceed IEC 1131
n Stocking temperature: -20 to 70°C
according to IEC 1131
n Operation humidity: 5 to 95% non-condensing
according to IEC 1131 level RH2
n Weight:
net: 240g
packed: 300g
The FOTON 1 interface is installed at a panel of 127 x 76 mm.
The fixation is done at the backside, so that there is no need of
additional holes.
4.4/1
127
76
Fixation rip (mm)
Altus Sistemas de Informática S.A.
LCD 2x20 Display with 4 Keys
FOTON 1
Doc. Code: 6116-811.4
Revision: E
PLCs
AL-1338
6. Handbooks
For information about RS-485 Electrical Norm see the AL-1413
Utilization Handbook.
For information about PLC programming see the utilization
handbook of the programmer being used. (AL-3800, AL-3830,
AL-3832 or MASTERTOOL).
For information about FOTON 1 see the FOTON MMI Series
Utilization Handbook.
For information about programming FOTON 1, as well as
information about the PROFOTON Programming Software see
FOTON MMI Series Utilization Handbook.
RS485 cable Connect the FOTON 1 interface at
serial interface RS-485 of the PICCOLO PLCs or
at bus interface QK1401, AL-1401, QK1402 e
AL-1402.
* The QK1401 and AL-1401 modules are connected at PLC bus,
allowing the communication between PLC and IHMs without the
use of the serial channel. They have a serial interface RS485 and accept ALNET I commands for reading and updating of
operands M.
7. Ordering Data
7.1. Necessary Options
The following items must be ordered separately:
Description
PROFOTON
FOTON MMI Series programming software
IBM-PC ® compatible software for message
programming of the FOTON 1, FOTON 3, FOTON 5,
FOTON 10 MMI and AL-1471 Terminal.
AL-1330
MDB9-FDB9 cable (FOTON 1/IBM- Connect the
FOTON 1 interface at IBM-PC, to the load of
messages
AL-1331/3M
FOTON 1/PLC cable (RS-232C. Connects the FOTON
1 interface at QUARK, AL-600, AL-2000 and AL-3000
PLCs
7.2. Optionals
The following parts do not integrate the product and can be
ordered separatelly:
Description
MAN/FOTON -UT
FOTON MMI Series utilization handbook.
Includes FOTON 1, FOTON 3, FOTON 5 and
FOTON 10 products.
MAN/FOTON-PG
FOTON MMI Series programming handbook.
Includes FOTON 1, FOTON 3, FOTON 5 and
FOTON 10 products
QK1401
* bus interface.
RS-485 serial communication interface for the
QUARK PLC Series I/O cards bus.
AL-1401
* bus interface.
RS-485 serial communication interface for the
AL-1000, AL-600 and AL-2000 PLC Series I/O
cards bus.
QK1402
* general purpose bus interface.
RS-485 serial communication interface for the
QUARK PLC Series I/O cards bus.
AL-1402
* general purpose bus interface.
RS-485 serial communication interface for the AL1000, AL-600 and AL-2000 PLC Series I/O cards
bus.
AL-1332/3M
FOTON 1/PLC cable (RS-485) Connect the
FOTON 1 interface at serial interface RS-485 of
the QK801 PLC or at bus interface of the QK1401
or AL-1401
AL-1333
FT1 and FT3 cable/PICCOLO (RS-232C)
Connect the FOTON 1 interface at PICCOLO
Altus Sistemas de Informática S.A.
4.4/2
FOTON 1
LCD 2x20 Display with 4 Keys
Revision: E
Doc. Code: 6116-811.4
8. Revisions
The revision of this document is shown at the right upper
corner.
ALTUS reserve the rights to change this document without
previous notice.
The following historic shows changes to each revision:
Revision: E
Approval: Luiz Gerbase
Author: Valter Bianchi Filho - AP&D
Date: 2/3/2000
n Remarks:
n Product improved to use SMD components technology
n Features concerned to noise immunity updated.
n MTBF updated
n Physical dimensions updated
4.4/3