195454 - Banner Engineering
Sure Cross® DXM100-S1 Wireless Modbus Slave
Datasheet
The DXM100-S1 Modbus Slave can connect directly to an RS-485 serial bus or to a wireless
ISM network as a remote Modbus Slave device.
•
•
•
Power options include 12 to 30 V dc with or without a battery backup, or 12 V dc
solar panel with a sealed lead acid battery
Local I/O options: universal inputs, NMOS outputs, and analog outputs (0 to 10 V or 4
to 20 mA)
ISM radios available in either a 900 MHz band or 2.4 GHz band for local wireless
networks
WARNING: Not To Be Used for Personnel Protection
Never use this device as a sensing device for personnel protection. Doing so could lead to serious injury or death.
This device does not include the self-checking redundant circuitry necessary to allow its use in personnel safety
applications. A sensor failure or malfunction can cause either an energized or de-energized sensor output
condition.
CAUTION: Electrostatic Discharge (ESD)
ESD Sensitive Device. Use proper handling procedures to prevent ESD damage to these devices. The module does
not contain any specific ESD protection beyond the structures contained in its integrated circuits. Proper handling
procedures should include leaving devices in their anti-static packaging until ready for use; wearing anit-static wrist
straps; and assembling units on a grounded, static-dissipative surface.
Models
Base
Radio
Configuration
Additional
Features
R2
P
DXM100- S1
S1 = Power: 12−30 V dc/Solar/Battery
I/O: 4 programmable IN (discrete/voltage/current),
4 NMOS OUT, and
2 Analog OUT (0-10 V or 4-20 mA)
Blank = None
R2 = DX80 900 MHz, 1 Watt HE5 MulitHop Data Radio
R4 = DX80 2.4 GHz, 65 mW HE5 MultiHop Data Radio
R5 = DX80 900 MHz, 65 mW HE5L MultiHop Data Radio
R9 = DX80 900 MHz, 1 Watt HE5, MultiHop Data Radio
(Australia/New Zealand (-AN))
Blank = None
P = SAM4 Processor board
Some example models include, but are not limited to, the following:
Models
Description
DXM100-S1
DXM100-S1 Modbus Slave
DXM100-S1R2
DXM100-S1 Modbus Slave base with MultiHop ISM 900 MHz radio
DXM100-S1R2P
DXM100-S1 Modbus Slave base with MultiHop ISM 900 MHz radio and SAM4 processor board for logging, special configuration, and
ScriptBasic programming
Original Document
195454 Rev. B
30 May 2017
195454
Sure Cross® DXM100-S1 Wireless Modbus Slave
DXM100 Documentation
For more information about the DXM100 Slave family of products, please see additional documentation and videos on the Banner
website: www.bannerengineering.com.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
DXM Wireless Controller Sell Sheet, p/n 194063
DXM100-B1 Wireless Controller Datasheet, p/n 186724
DXM100-B2 Wireless Controller Datasheet, p/n 195232
DXM100-Bx Wireless Controller Instruction Manual, p/n 190037
DXM100-S1 Wireless Modbus Slave Datasheet, p/n 195454
DXM100-S2 Wireless Modbus Slave Datasheet, p/n 195231
DXM100-Sx Wireless Modbus Slave Instruction Manual, p/n 188231
DXM ScriptBasic Instruction Manual, p/n 191745
DXM Controller Configuration Quick Start, p/n 191247
DXM Configuration Tool software
DXM Configuration Tool Instruction Manual, p/n 158447
DXM EDS Configuration file
Tech Note: Activating and Provisioning Cellular Service
Additional technical notes and videos
Technical notes, configuration examples, and ScriptBasic program examples are available at www.bannerengineering.com.
DXM100-S1 Modbus Slave System Overview
Banner's DXM Logic Controller integrates Banner's wireless radio and local I/O for a remote I/O device.
I/O
Connectivity
Universal Inputs
Discrete Outputs
Courtesy Power
Switch Power
Sure Cross Radios
RS-485 Master
Inputs/Outputs—On-board universal and programmable I/O ports
connect to local sensors, indicators, and control equipment.
• Universal Inputs
• Discrete outputs
• Courtesy power
• Switch power
• Battery backup
• Solar controller
Connectivity—The integrated Sure Cross® wireless radio enables Modbus connectivity to remote sensors, indicators, and control
equipment.
Wired Connectivity
Field Bus: Modbus RS-485 Master
Wireless Connectivity
Sure Cross MultiHop 900 MHz, or MultiHop 2.4 GHz
Specifications
Supply Voltage
12 to 30 V dc (use only with a suitable Class 2 power supply (UL) or a SELV (CE)
power supply) or
12 V dc solar panel and 12 V sealed lead acid battery
Power Consumption
20 mA average at 12 Volts
Courtesy Power Out
One output at 5 Volts, 500 mA maximum
No short circuit protection
Switched Power Outputs
Two outputs at 5 or 16 Volts
5 V: 400 mA maximum
16 V: 125 mA maximum
2
Solar Power Battery Charging
1 Amp maximum with 20 Watt solar panel
Radio (ISM Band) Transmit Power
900 MHz at 1 Watt
2.4 GHz at 65 mW
Radio Transmit Power
900 MHz, 1 Watt: 30 dBm (1 W) conducted (up to 36 dBm EIRP)
2.4 GHz, 65 mW: 18 dBm (65 mW) conducted, less than or equal to 20 dBm
(100 mW) EIRP
900 MHz Compliance (1 Watt)
FCC ID UE3RM1809: This device complies with FCC Part 15, Subpart C, 15.247
IC: 7044A-RM1809
www.bannerengineering.com - Tel: +1-763-544-3164
P/N 195454 Rev. B
Sure Cross® DXM100-S1 Wireless Modbus Slave
Radio Range1
900 MHz, 1 Watt: Up to 9.6 km (6 miles)
2.4 GHz, 65 mW: Up to 3.2 km (2 miles)
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with FCC Part 15, Subpart C,
15.247
ETSI EN 300 328 V1.8.1 (2012-06)
IC: 7044A-DX8024
Minimum Radio Separation Distance
900 MHz, 1 Watt: 4.57 m (15 ft)
2.4 GHz, 65 mW: 0.3 m (1 ft)
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Construction
Polycarbonate; DIN rail mount option
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Communication Hardware (RS-232)
Baud rate: 9.6k or 19.2k (default)
Data format: 8 bits; odd, even, or no parity; 1 stop bit
Communication Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k
Data format: 8 data bits, no parity, 1 stop bit
Counters, Synchronous
32-bits unsigned
10 ms clock rate minimum
Analog Outputs (DAC)
0 to 20 mA or 0 to 10 V dc output
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Universal Inputs
Sinking/Sourcing discrete, 4–20 mA analog, 0–10 V analog, counter, and
temperature 10 kOhm thermistor
Operating Conditions2
–40 °C to +85 °C (–40 °F to +185 °F) (Electronics); –20 °C to +80 °C (–4 °F to
+176 °F) (LCD)
95% maximum relative humidity (non-condensing)
Radiated Immunity: 10 V/m (EN 61000-4-3)
Discrete Output Rating (NMOS)
Less than 1 A max current at 30 V dc
ON-State Saturation: Less than 0.7 V at 20 mA
ON Condition: Less than 0.7 V
OFF Condition: Open
Environmental Rating
IEC IP20
Certifications
Shock and Vibration
IEC 68-2-6 and IEC 68-2-27
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Accessories
For a complete list of all the accessories for the Sure Cross wireless product line, please download the Accessories List (p/n b_3147091)
Cordsets
MQDC1-506—5-pin M12/Euro-style, straight, single ended, 6 ft
MQDC1-530—5-pin M12/Euro-style, straight, single ended, 30 ft
MQDC1-506RA—5-pin M12/Euro-style, right-angle, single ended, 6 ft
MQDC1-530RA—5-pin M12/Euro-style, right-angle, single ended, 30 ft
Misc Accessories
BWA-CG.5-3X5.6-10—Cable Glands: 1/2-inch NPT, Cordgrip for 3 holes of 2.8
to 5.6 mm diam, 10 Pack
BWA-HW-052— Cable Gland Pack: 1/2-inch NPT gland, 1/2-inch NPT multicable gland, and 1/2-inch NPT vent plug
Static and Surge Suppressor
BWC-LFNBMN-DC—Surge Suppressor, bulkhead, N-Type, dc Blocking, N-Type
Female, N-Type Male
Antenna Cables
BWC-1MRSMN05—LMR100 RP-SMA to N-Type Male, 0.5 m
BWC-2MRSFRS6—LMR200, RP-SMA Male to RP-SMA Female, 6 m
BWC-4MNFN6—LMR400 N-Type Male to N-Type Female, 6 m
Short-Range Omni Antennas
BWA-2O2-D—Antenna, Dome, 2.4 GHz, 2 dBi, RP-SMA Box Mount
BWA-9O2-D—Antenna, Dome, 900 MHz, 2 dBi, RP-SMA Box Mount
BWA-9O2-RA—Antenna, Rubber Fixed Right Angle, 900 MHz, 2 dBi, RP-SMA
Male Connector
Long-Range Omni Antennas
BWA-9O8-AS—Antenna, Fiberglass, 3/4 Wave, 900 MHz, 8 dBi, N-Type Female
Connector
BWA-2O8-A—Antenna, Fiberglass, 2.4 GHz, 8 dBi, N-Type Female Connector
Medium-Range Omni Antennas
BWA-9O5-C—Antenna, Rubber Swivel, 900 MHz 5 dBi, RP-SMA Male
Connector
BWA-2O5-C—Antenna, Rubber Swivel, 2.4 GHz 5 dBi, RP-SMA Male Connector
Enclosures and DIN Rail Kits
BWA-AH864—Enclosure, Polycarbonate, with Opaque Cover, 8 × 6 × 4
BWA-AH1084—Enclosure, Polycarbonate, with Opaque Cover, 10 × 8 × 4
BWA-AH12106—Enclosure, Polycarbonate, with Opaque Cover, 12 × 10 × 6
BWA-AH8DR—DIN Rail Kit, 8", Includes 2 Trilobular/Self-Threading Screws,
and DIN Rail
BWA-AH10DR—DIN Rail Kit, 10", Includes 2 Trilobular/Self-Threading Screws,
and DIN Rail
BWA-AH12DR—DIN Rail Kit, 12", Includes 2 Trilobular/Self-Threading Screws,
and DIN Rail
Long-Range Yagi Antennas
BWA-9Y10-A—Antenna, 900 MHz, 10 dBd, N-Type Female Connector
Power Supplies
PSD-24-4—DC Power Supply, Desktop style, 3.9 A, 24 V dc, Class 2, 4-pin M12/
Euro-style quick disconnect (QD)
PSDINP-24-13 —DC Power Supply, 1.3 Amps, 24 V dc, with DIN Rail Mount,
Class I Division 2 (Groups A, B, C, D) Rated
PSDINP-24-25 —DC Power Supply, 2.5 Amps, 24 V dc, with DIN Rail Mount
BWA-SOLAR PANEL 20W—
1 Radio range is with the 2 dB antenna that ships with the product. High-gain antennas are available, but the range depends on the environment and line of sight. Always verify your wireless
network's range by performing a Site Survey.
2 Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.
P/N 195454 Rev. B
www.bannerengineering.com - Tel: +1-763-544-3164
3
Sure Cross® DXM100-S1 Wireless Modbus Slave
Warnings
Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations installed without surge suppressors invalidate the
manufacturer's warranty. Keep the ground wire as short as possible and make all ground connections to a single-point ground system to ensure no ground loops are created. No surge
suppressor can absorb all lightning strikes; do not touch the Sure Cross® device or any equipment connected to the Sure Cross device during a thunderstorm.
Exporting Sure Cross® Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export this product to a
country other than that to which it was sold must ensure the device is approved in the destination country. A list of approved countries appears in the Radio Certifications section of the
product manual. The Sure Cross wireless products were certified for use in these countries using the antenna that ships with the product. When using other antennas, verify you are not
exceeding the transmit power levels allowed by local governing agencies. Consult with Banner Engineering Corp. if the destination country is not on this list.
Banner Engineering Corp. Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or
replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover
damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY
OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT
DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously
manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the
product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the
product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time.
Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to:
www.bannerengineering.com.
© Banner Engineering Corp. All rights reserved
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising