RTU500 series

RTU500 series
Data Sheet Power Supply 560PSU40
Power Supply 560PSU40
Application
The power supply unit 560PSU40 is a galvanic
isolated DIN rail power supply. It is designed to
supply the RTU560 DIN Rail I/O-modules and
communication units (CMU).
To increase availability, two power supplies can
be operated in parallel. External diodes are not
necessary.
Characteristics

Ultra compact Plastic Housing

Reliable snap-on Mounting at DIN-Rails

Universal Input 85 - 264 V AC,
50/60 Hz, or 85 – 375 V DC

Output Voltage adjustable

Power Good Signal

Low Ripple and Noise

Overload and Short-circuit Protection

Worldwide Safety Approvals

Parallel Operation possible
Connections
Input AC
1
2
3
Input DC
PE
N
L
Doc.-Nr. 1KGT 150 559 V006 1
1
2
3
PE
-Vin
+Vin
1
2
3
4
5
Output DC
+Vout
+Vout
-Vout
-Vout
DC OK
1
RTU500 series
Data Sheet
Power Supply 560PSU40
560PSU40
Technical Data

Mechanical Layout
Dimension
HxWxD
Enclosure material
Mounting
Case protection
Safety class
Safety approvals
Safety standards
75 x 45 x 100 mm
Plastic FR2010-110C (UL 94V-0 rated)
35 mm DIN-rails as per EN 50022 (snap-on with self-locking pring)
or for Wall-Mounting
IP 20 (IEC 60529)
Degree of protection class 1
UL/cUL 60950 recognized,
File E181381 UL 508C listed, File E210002 CB-Report per
EC 60950
IEC 60950, EN 60950 (output SELV), UL 60950, UL 508,
N 50178, EN 60204, EN 61588-2-8.
- NECC class 2
Electrical Layout
Electromagnetic compatibility
(EMV), Immunity
Electromagnetic compatibility
(EMV), Emissions
EN 61000-6-2
EN 61000-6-3
Input Specifications
Input voltage range
85 ... 264 V AC / 85 ... 375 V DC
Output de-rating of operation between 85 ... 93 VAC / 85 ... 130 VDC:
15%
Input frequency
47 - 63 Hz
Harmonic limits
EN 61000-3-2 Class A
Input current at full load (typ.) 115 VAC: 1.2 A
230 VAC: 0.6 A
Recommended circuit break- 5.0 A
er
(Characteristic C or slow blow
fuse)
2
Doc.-Nr. 1KGT 150 559 V006 1
RTU500 series

Data Sheet
Power Supply 560PSU40
Output Specifications
Output voltage adj. range
(Pot meter on front panel)
Output current
Output power
Output regulation
(10 to 90 % load variation)
Ripple and Noise
(20 VHz Bandwidth)
Electronic short circuit protection
Parallel operation
Over voltage protection, trigger
point
Hold-up time
at max. load
Hold-up time for 8*
23BA40/23BE40 or 560MPR01
Power good signal
24 - 28 VDC
2,5 A max.
60 W
2.5 % (1 % for TCL 60-112)
< 50 mV pk-pk
Current limitation at 120 % typ.
(constant current, automatic recovery)
Output current characteristic suitable for parallel operation of max.
5 units
< 40 VDC
115 VAC - min. 15 ms
230 VAC - min. 125 ms
50 ms
Trigger point: > 22 V
Output signal (reference to - Vout): >22 V 2.0 V / 30 mA max.
Environmental Conditions
Temperature ranges
Temperature derating
Humidity
Temperature coefficient
Switching frequency
Efficiency
Insulation
Operating: -10 C ... +70 C max.
Storage:
-25 C ... +85 C
At 93 ... 132 VAC or 130 ... 187 VDC operating
1.1 % /K above 40 C
At 187 ... 264 VAC or 265 ... 375 VDC operating
1.7 % /K above 50 C
At 85 ... 130 VDC operating
1.3 % /K above 30 C
95 %
(non condensing)
0.02 % /K
55-180 kHz depending on load
(frequency modulation)
88 % typ.
According to IEC/EN 60950, UL 60950, UL 508, EN 50178,
EN 60204, EN 61588-2-8
5 kV EN 60 255-5 1,2/50 ms
2,5 kV EN 60 255-5 50 Hz
>100 MΩ at 500 V EN 60 255-5
Ordering Information
560PSU40 R0001
Doc.-Nr. 1KGT 150 559 V006 1
1KGT 011 600 R0001
3
RTU500 series
Data Sheet
Power Supply 560PSU40
560PSU40

Note:
We reserve the right to make technical changes or modify
the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars
shall prevail. ABB AG does not accept any responsibility
whatsoever for potential errors or possible lack of information
in this document.
We reserve all rights in this document and in the subject matter
and illustrations contained therein. Any reproduction, disclosure
to third parties or utilization of its contents - in whole or in parts –
is forbidden without prior written consent of ABB AG.
Copyright© 2013 ABB
All rights reserved
4
Doc.-Nr. 1KGT 150 559 V006 1
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising