Electrical network management Vigilohm The IT earthing system to improve electrical network availability Catalogue 2013 Vigilohm General contents Presentation 3 Insulation Monitoring Devices 16 Fault Location Devices Measurement per feeder 26 28 Communication interfaces 30 Accessories 31 Dimensions and connections 40 Commercial references 52 1 2 Presentation Ensuring continuity of service in the event of an insulation fault Continuity of service in an essential operational requirement for power networks. The installation must also comply with specific rules to protect people and property. These safety requirements involve the use of protective devices which operate when there is a risk that could cause the network to become partially unavailable. The consequences can be significant: > Total or partial stopping of the process. > Partial or total loss of production. An IT ("isolated from earth") earthing system is the only one in which safety is assured without the need for additional protective equipment. The installation can operate without endangering people even in the presence of an initial insulation fault. What do the standards say? The IT earthing system is described in several standards: > IEC 60364-4-41 These standards clearly state that, with the IT earthing system, the installation must be isolated from earth or connected to earth through a sufficiently high impedance. > IEC 60364-7-10 In the event of only one ground or earth fault, the fault current is very low and interruption is unnecessary. > IEC 61557-8 Insulation monitoring devices for IT earthing systems. Since a second fault would cause a circuit breaker to trip, an insulation monitoring device (IMD) is required to indicate an initial fault. > IEC 61557-9 This device must activate an audible and/or visual signal. Electrical installation in buildings: - protection for safety, - protection against electric shock. Requirements for special installations or locations - Medical locations. Equipment for insulation fault location in IT earthing systems. IEC Our solution complies with international standards 3 Presentation The IT earthing system The neutral of the transformer's secondary is not connected to earth, and the load casing is connected to earth. In the event of an insulation fault, current cannot loop via the transformer's neutral: > IT earthing system 3 L1 L2 L3 N PE > No dangerous contact voltage when touching metal parts. > Very low fault currents. Frame Therefore, an IT earthing system guarantees the best continuity of service. However, the faulty circuit must be detected and repaired before a second fault occurs because a second fault would cause a short circuit between phases and trigger protective devices. The installation can operate without endangering people and equipment even in the presence of an insulation fault. As a result, protective devices are not triggered. 230 V TT 110 V 110 mA 230 V IT 0.7 V < 1 mA 4 Insulation monitoring devices An indispensible solution for implementing an IT earthing network. Insulation monitoring device (IMD): These devices are mandatory in an IT earthing system. An insulation monitoring device injects DC or low-frequency AC voltage between the network and earth. The resulting current that flows through the IMD is then measured. The insulation value is calculated from this low-frequency current. Depending on the device, it can also be used to: > Display the insulation resistance value locally. > Display the leakage capacitance value for the monitored network. > Store time-stamped alarms. > Communicate with a supervisor. Note: in an IT earthing system, a 50 Hz fault current is difficult to measure since it loops through the capacitances distributed in the network. The injected current will go through the insulation monitor. The IMD indicates the fault locally on its front panel depending on the adjustable threshold set on the device. It also activates a relay output to a visual or audible indicator. CPI PE PE Fault location: On networks with many circuits, the IMD can be associated with a locator (XD301 – XD312) that can identify the faulty circuit. Such locators use the 2.5 Hz signal injected by the IMD to determine through which circuit the fault current is flowing. There is no link between the locators and the IMD. Measure - Indicate - Locate - Repair IMD 12-circuit Locator 12-circuit Locator No connection between the locator and the IMD. Possibility of R and C measurements per circuit (XL and XML series). 1-circuit Locator Manual fault finding 2.5 Hz current These locators can be fixed devices connected to toroids that measure the injected current, or mobile. They can monitor 12 circuits or one separate circuit. Advanced versions of these locators (XL and XML) provide the insulation value on a circuit by circuit basis. This simplifies maintenance of large networks. 5 Presentation A reliable and effective solution Schneider Electric, a global specialist in electrical power management, offers a range of solutions tailored to your network. We accommodate expanse, number of circuits, presence of coupling, etc. Schneider Electric has been in the IMD business for more than 50 years. Small networks or islands (C max = 40 µF) Network with many feeders: simple solution IM400 IM10 XD312 Easy to install and use > T here is a transformer to create the IT island. Its neutral is not connected to earth. > T here is an IMD (IM9 or IM10) to detect the first fault: - it is generally powered by the network that it monitors, - it is connected to neutral (or to one phase) and earth, - its only setting is the fault threshold level, - it has a single relay output to a light or alarm sound. These products are available in both Multi 9 (DIN rail) and flush-mount formats. Further options depending on model include > Display of R value to facilitate preventive Advanced monitoring and fault location This architecture is simple to implement since there are no connections between the various modules.The IMD (IM400) injects a 2.5 Hz current and measures R and C using this current. When the IM400 indicates a fault, the maintenance team must locate and clear the fault. On a continuous process, this fault tracing operation cannot be done by tripping circuit breakers. The XD312 modules measure the 2.5 Hz current in each circuit and compare it with a threshold value. The fault can then be located without interference on the network. maintenance. > Display of the network's C value. > Modbus serial link. > Alarm log. Advantage of the Schneider Electric offer Measurement and display of C Monitoring of C is essential on large networks since the C‑related impedance can cause these networks to drift towards a TT arrangement, which would give rise to a dangerous contact voltage and a high fault current after an insulation fault. Only Schneider Electric displays the C value. 6 Fault location without connection to the IMD This feature can simplify the implementation and use of the system. It also removes any limit on the number of XD312 locators. A reliable and effective solution Per-feeder measurements for highly critical networks. Large networks and/or several buildings Improvement of preventive maintenance Easy to manage IT islands are ideal for large networks. If this is not possible, then it is beneficial to have R and C measurements per building or per critical circuit. Per-feeder measurements enable constant monitoring of the insulation change for each group of critical circuits. This feature, which is exclusive to Schneider Electric, can meet the following needs. This gives the maintenance team a better overview of the entire network and the capability to anticipate issues. Supervisor MT/BT MT/BT XLI300 XML316 XML308 Per-feeder measurement In this architecture, the XML products provide both the IMD function and per-feeder measurements. All measurements and time-stamped alarms are accessed via the supervisor. XML316 The XLI300 provides both a communication interface and IMD exclusion when the second circuit breaker is closed (1). This solution can also be combined with fault location by an XD product, thereby enabling fault location lower down in the network tree. (1) Exclusion The IMD injects a low frequency into the network. In a network with several incoming feeders, depending on the circuit breaker position, there must be no more than one IMD injecting into the network. This injection exclusion is managed by the XLI300 interface. At least one IMD, but no more than one, per subnetwork. 7 Presentation Fault locating Fault locating Manual fault locating Once detected, an insulation fault must be located and eliminated in order to guarantee maximum continuity of supply. XGR Manual fault locating The fault is located by testing different points in the installation, one after another, using a Vigilohm System XRM mobile receiver and a current probe. The receiver captures the low-frequency fault locating signal. Two cases may be encountered: > the installation is equipped with an IM400 or an XM300C. In this case, the manual system is used to fine-tune the results of the automatic locating system. > the installation (relatively small or a sub- IM10 IM20 on P12 P50p P100 XRM Automatic fault locating IM400 network) is equipped with an insulation monitoring device with a small measurement current (IM10, IM20). In this case, a Vigilohm XGR portable generator is used together with an XRM receiver. XM200 XD312 1 2 3 4 5 6 7 8 9 XD312 test M 10 11 12 reset M Automatic fault locating For easy locating of insulation faults, the Vigilohm System makes it possible to combine the IM400 and XM300C insulation monitoring devices with: > XD301/XD312 fault detectors to monitor the different circuits of the installation. > XRM receivers for mobile fault locating. Fault locating in hospitals The safety of the patient and operating room staff is critical and standards prohibit measurement currents greater than 1 mA. This is not compatible with automatic fault locating or the XGR portable generator. However, the need to have automatic fault locating is limited for two reasons: > an insulation fault is rare in such a limited area. It is not not so urgent to localize the fault as the probability of having a second fault is close to zero. > it is easy to locate the fault by disconnecting equipment or sequentially opening the circuit breakers after using the room. on P12 P50 P100 XRM Automatic fault locating with R & C measurement per feeder Supervisor Interface XML308/316 Printer XAS XML316 défaut test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 valeur d'isolement 040 K MENU TEST XL308/316 XL308c test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 test/reset XD308c XD308c XRM XD312 1 2 3 4 5 6 7 8 9 XD312 test M 10 11 12 reset 50536 M on 8 P12 P50 P100 Hospital: dedicated modules To secure power distribution and monitoring solution for operating theatres. Operating rooms require extremely high availability and quality of electric power to offer patients maximum safety. For this reason, the standards lay down very strict rules to ensure the continuity of service of electrical installations. What do the standards say? > In group 2 rooms for medical use, the medical IT system should be used for the circuits powering medical electrical equipment and systems for survival and surgical applications, and the other equipment located in the environment of the patient. > An audible and visual alarm must be provided in the room in question to alert medical personnel. > For the satisfactory operation of medical equipment, prevention of electromagnetic disturbances may be necessary. > Monitoring of overload and high temperature for the medical IT transformer is required. > An alarm should take place if the earth connection or the connection to the system is disconnected. > Operating activities must have continuity of electric power supply. IEC Our solution complies with international standard IEC 60364-7-710 and national standards and regulations IM10-H and HRP (Hospital Remote Panel) for the "Classic" solution > G raphic display. > B argraph. > S mart HMI. > 8 languages. > E arth and injection connection monitoring. Simple and efficent > A udible and visual alarm for an insulation or electrical fault (transformer overload or circuit breaker tripping). > T esting of the insulation monitoring system. > A udible alarm stoppage. > 2 4 V DC power supply. > A ntibacterial. > T ested with Anios products (disinfection products). > C omplies with IEC 60601-1 (medical equipment). IM20-H as a brick of the advanced solution > M odbus Communication. > D atalog with timestamping of all events. > T ransformer management: - secondary load current display, - alarm on threshold (in % of nominal current), - alarm on temperature through the sensor (bimetal). Hospital version specificities > T hreshold minimum: 50 kOhm. > M easurement current < 1 mA. > M easurement voltage < 25 V. > T ransformer monitoring (IM20-H). > IM20-H outputs can be connected to the HRP for a simple solution with transformer management. XD312-H for simple fault location in hospitals > Locating fault up to 12 feeders > 1 Led per feeder > 1 output contact > Compatible with IM10-H & IM20-H Hospital version specificities > Operating threshold 50K Ohm > Auxiliary supply voltage 220/240 VAC 9 Presentation Product selection according to type of installation Markets Industrial & Marine (for hospital, see page 17) Small Networks Medium & Large Networks (2) Medium networks up to 60 µF (IT island) (3) Networks Machine Off-line Motor Large network Simple fault location Measurement per Feeder Compatible control networks No No Yes Yes Yes Yes Yes Threshold + Alarm Yes Yes Yes Yes Yes Yes Yes R Display No No Yes Yes Yes Yes Yes AC Network Yes Yes Yes Yes Yes Yes Yes DC or AC with DC components Network No No Yes Yes Yes Yes Yes Communication No No No Yes Yes Yes Yes Automatic fault location compatible No No No No Yes Yes Yes C No No No Yes Yes Yes Yes Zc No No No Yes Yes No No Alarm Log No No No Yes Yes Yes Yes HV Subassembly No No No Yes Yes Yes Yes Motor Off-Line No Yes No No No No No Input for Injection inhibition No No No Yes Yes No No Form Factor Multi 9 Insert screws for panel mount IM9 IM9-OL Panel Mount & DIN Rail (Multi 9 compatible) IM10 Panel Mount Platine Mount IM20 IM400 Panel Mount XM300C XML308/ 316 CPI + Measurement per feeder Insulation Monitoring Device 110 - 415 V AC 125/250 V DC 380/415 V AC Auxiliary supply 115/127 or 220/240 or 380/415 V AC XD301 Fault Location Devices No No No No XD312/XD308C Measurement per feeder No No No No No XL308/316 Communication interfaces No No No No No XLI300 or XTU300 IM20-1700 IM400-1700 or PHT1000 Accessories (1) PHT1000 Cardews - Limiting impedance (ZX) Toroids Mobile fault locating (1) Except IM9-OL. (2) Choice between IM10/IM20 and IM400 - see page 12. (3) 150µF in photovoltaic farms - see page 14. 10 Choosing the best architecture A variety of possibilities depending on the type of network. What kind of network? > A simple motor or a small AC network: IM9. > A motor that is normally off: IM9-OL. > A small DC network, or for AC: the IM10 or Selection criteria > A larger network for which fault location would > is there a requirement for a prevention IM20 range (IM10-H or IM20-H for hospitals). be a long and tedious task if done manually: IM400 + XDs. > A very large network for which main-circuit measurements would be beneficial: XML308/ XML316 or XM300 + XL308/316 if the circuits are not in the same substation. > A photovoltaic farm (see page 13) Except in simple cases, particular features of the network to be supervised can also affect choice: > is it a large network where it is preferable to measure the earth leakage capacitance? threshold indicating a change in insulation to less than a non-critical value set by the user? > is there coupling present in the network? > are there electrical disturbances generated by consumers such as variable-speed drives, UPSs, etc.? Supervision and event logging System choice There are three steps to choosing a system: To define the need: network size, DC or AC, display, automatic fault location, additional features… Printer Supervisor Select the appropriate locators (XD locators, XML or XL local measurement). Interface XLI300 Check whether an interface is necessary.> A very Permanent insulation monitoring XML308/316 XM300C IM400 IM20 IM10 IM9 Fault XD301 XD301/312/308C XD312 XL308/316 Sensors This system is scalable. It is simply a matter of adding devices to adapt it to changes in the network or in the degree of monitoring. 11 Presentation Selecting the correct device For monitoring different types of installation. IT system for part of an installation MV/LV The requirement for continuity of supply may apply to only a part of an installation, for example a single shop or plant, or a circuit subject to special conditions (safety lighting). In this case, it is recommended to use the IT system for this part of the installation, whatever the system used for general distribution. IMD = IM9 or IM10 or IM20 - Depending on the characteristics and function of the network (see table, page 10). TN or TT LV/LV L1 L2 L3 N L1 L2 L3 N IT Sub-network CPI MV/LV TN or TT L1 L2 L3 In hospitals, for the operating rooms, it is necessary to use either the IM10-H or the IM20-H according to the desired functionalities. machine tool or robot Control and auxiliary circuits LV/LV CPI IT control/monitoring + DC sub-network _ CPI IT system for the entire installation The requirement for continuity of supply may apply to the entire installation or to a large sub-network. MV/LV For this kind of network it is necessary to have a monitor compatible with the fault localization or the measurement par feeder. IMD = IM400 or XM300C (communication with a supervisor) or XML308/316 (local measurement) (see table, page 10). L1 L2 L3 N CPI L- L+ MV/LV PHT 1000 CPI Choice between IM10/IM20 and IM400 Automatic fault location The IM10/IM20 is not compatible with this feature; the IM400 is. Medium or large networks The limit is linked to the network capacitance as the maximum for the IM10/IM20 is 40 µF. To estimate this value it is necessary to take into account the cables and the loads. Cables: for 3 phases the capacitance is approximately 1 µF/km. Loads (capacitive filters): Guideline capacitive values for HF filters built into various devices Device Micro-computer UPS Variable speed controllers Fluorescent tubes (in ramp of 10) Network/earth capacity 20 nF to 40 nF 40 nF 70 nF 20 nF Off-line insultation monitoring Using motors in industrial processes creates further need for insulation monitoring. By checking insulation with power off, insulation faults can be determined before starting motors (fire pumps, smoke extractors, etc.). It is also possible to automatically prevent motor starting if the insulation resistance is below a certain threshold. 12 L1 L2 L3 M CPI The photovoltaic power system Photovoltaic is a unique application which introduces the following specifications: Selecting the IT Power System In industry, the IT power system is used when availability is required. It’s the only grounding scheme that provides people safety on first insulation fault without having to operate the protection devices and interrupting the power system. It also allows limiting the faulty current on insulation fault in area that shows fire or explosion risks. Insulation Monitoring Devices such as Vigilohm provide then an insulation alarm but do not trig the interruption of the power system. In photovoltaic applications, the IT power system allows limiting of the faulty current. People safety against the risk of electric shock is provided by using class II DC power system (double isolation) in combination with class II PV modules. Within a grounded photovoltaic installation, an insulation fault may allow the circulation of an important faulty current with risk of fire and/or destruction of material. Using the IT power system (ungrounded power system) would allow limiting the faulty current on a first insulation fault thus preventing any risk for the installation. However it is then required to correct the insulation fault reported by the IMD as in case of a second insulation fault the faulty current would be very important. In some cases, upon detection of a first insulation fault the faulty part of the PV field and/or the inverter may be disconnected; insulation fault correction is to be executed Selecting the relevant Vigilohm device IM10 / IM20 / IM400 Selection is to be made mainly on the leakage capacitance linked to the size and peak power of the PV fields. The IM400 is designed for the demanding applications including paralleled inverters. IM10 IM20 IM400 Insulation Monitoring Device PV field peak power (1) 250kW 750kW 5MW 40µF 150µF (2) 2000µF 345 V DC 600 V AC L-L 345 V DC 600 V AC L-L 480 V DC 830 V AC L-L N.A. 1000 VDC 1700 V AC L-L 1200 V DC (4) 1700 V AC L-L Leakage Capacitance Maximum voltage (direct connection) (3) Maximum voltage (with HV subassembly) (3) Communication No Yes Yes (1) Total power of the PV modules connected to the power system monitored by the IMD (2) The filtering value is to be set to 160s (3) In case of connection on the AC side of non isolated inverter, the device must be choice taking in account also the DC side voltage and then the higher value of both AC & DC. (4) 1000 V DC with IM400-1700 and 1200 V DC with PHT1000 13 The photovoltaic power system Architectures Several architectures can be found, hereafter some common ones: Non isolated inverter Isolated inverter On installation with non isolated inverter, the IMD can be placed either on AC or on the DC side. On installation with isolated inverter, the IMD must be placed on the DC side. Optionally an IMD can be placed on the AC side (if in IT power system). Non isolated inverter Isolated inverter In some installation, the insulation alarm output of the IMD can be used to disconnect the PV field from the inverter. Increased value of C Given the large surface area of PV modules constituting the photovoltaic field or the installation condition, it is possible to have a value of the leakage capacitance (C) much higher than those usually witnessed in industry. In industry, if the C value is very high, the impedance (Zc) linked to C could drive this network towards a TT network leading to risk of dangerous contact voltage and high faulty current. In photovoltaic applications like every DC applications, the high value of C has no consequences on people’s safety nor on the faulty current. Determining the C value The value of the leakage capacitance of a photovoltaic system depends on several factors: • Total capacity of the installation (related to the total surface area of the PV modules) • PV modules technology • Environmental conditions • Installation topology (inverters in parallel or isolated by the primary transformer LV/MV) • Day or night • Age of the installation • Capacity of the inverter Measurements taken on numerous sites shows that the capacity does not exceed 2 μF/100 Kw under favourable conditions (in the daytime) and do not exceed 20 μF / 100 Kw in less favourable conditions (dawn, frost). Increased values often occur regularly (a few seconds to a few minutes) during phases of low production. 14 Selecting a communication interface (for XM300C & XML308/316) The power of a communicating system. Connect all devices The power of the Vigilohm System lies in the capacity it offers for communication between all its devices, thereby ensuring insulation monitoring and complementary functions such as automatic locating of faults or the anticipation of their occurrence. supervisor or PLC In addition, the Vigilohm System is capable of communicating with a supervisor or a PLC, i.e. it can both transmit data to and receive data from such units. The transfer of information takes place: > via the internal Vigilohm System bus for communication between the devices; MV/LV MV/LV XLI300 XML308 XM300c > via the external bus for communication with a supervisor or PLC. In both cases, the use of an internal or external bus requires a communication interface. XL308 Two interfaces > XLI300 interface, for the transmission of measurements and measurement parameters from the XM300C and XD308C devices to a supervisor. This interface is used on single busbar installations. The exclusion of other insulation monitoring devices found on the same installation is managed automatically. One set of busbars with supervisor. supervisor or PLC > XTU300 interface, for communication between the Vigilohm MV/LV System and a supervisor, like the XLI300 interface. This interface is required for installations with multiple busbars and bus coupler circuit breakers. It manages the exclusion of other insulation monitoring devices found on the same installation and the link between the locators and their corresponding insulation monitoring devices. MV/LV XTU300 XML308 XM300c Interface selection table One XML308/316 device Without supervision With supervision IMD with at least 1 locator + 1 set of busbars XLI300 XLI3000 XLI3000 IMD with at least 1 locator + serveral sets of busbars with bus coupling XL308 Several sets of busbars with coupling and with or without supervisor. XTU3000 XTU3000 Application of the measurement voltage Internal Vigilohm System bus Modbus 15 PB106370_47 Insulation Monitoring Devices Vigilohm IM9 Vigilohm IM9 Type of installation to be monitored LV AC IT systems Phase-to-phase voltage with IM9 connected to neutral 600 V AC max with IM9 connected to phase 480 V AC max Frequency 45-440 Hz Limited in size IT subsystem Electrical characteristics Fault signalling Number of thresholds 2 (sealable) Thresholds Pre-alarm: 2-5-10-20-50-100-200500 kΩ Alarm 1-2,5-5-10-25-50-100250 kΩ y7s Response time Device operating test Local and remote Failsafe feature (1) Output contact Option on the front face Number 1 (standard or failsafe) Type of contact Breaking capacity Changeover AC 250 V DC 12 to 24 V 6A 6A Use Maximum consumption IT systems: bb LV AC installations up to: vv 415 V ph-ph bb one device only for each separate installation bb isolated from earth or connected to earth through an impedance bb remote test (for machine control). Impedance Thermoplastic case Mounting Horizontal or vertical Operation Degree of protection Front IP40 Case IP20 bb Injection of DC voltage. bb An electronic device measures insulation from the leakage current created in the installation by the voltage injected between the installation and earth and trips the alarm pre-set by the user. Earth coupling capacitances do not affect insulation measurement. 7 VA 230 kΩ 50/60/400 Hz 115/415 V AC ±15 % DC 125/250 V DC ±15 % 70 µA Auxiliary supply voltage Mechanical characteristics Weight < 0.2 kg Other characteristics Temperature range For operation -25 ºC to +55 ºC For storage -40 ºC to +70 ºC Climatic conditions (2) Standards Installation and connection bb Live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover. bb Horizontal or vertical mounting on symmetrical rail. bb Connection by tunnel terminals for 2.5 mm² wiring. At 50 Hz Maximum current injected Product IEC 61557-8 Safety IEC 60664-1 EMC IEC 61326-2-4 Marine DNV approval Fault locating with other device Mobile XGR portable generator and XRM receiver + probes Standards bb Product: IEC 61557-8. bb Safety: IEC 60664-1. (1) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (2) Suitable for use in all climates: b damp heat, equipment not operating (IEC 60068-2-30) b damp heat, equipment operating (IEC 60068-2-56) b salt mist (IEC 60068-2-52). Auxiliaries Commecial reference: IMD-IM9 bb Cardew C surge limiter (only downstream of MV/LV transformer): see page 33. bb ZX impedance: see page 34. 16 Vigilohm IM9-OL PB106371_47 (Off-Line) Vigilohm IM9-OL Type of installation to be monitored LV AC IT / TT /TN-S systems (de-energised) Phase-to-phase voltage y 690 V (1) Frequency 45-440 Hz DC (de-energised) Voltage between polarities y 690 V (1) Electrical characteristics Fault signalling Number of thresholds 2 Thresholds Prealarm 0.5-1-1.5-2-3-5-7.5 - 10 MΩ Motor no start 0.25-0.5-0.75-1-1.251.5-1.75-2 MΩ Response time y2s Device operating test Yes Motor no start inhibition Use Monitors de-energised equipment (e.g. motors, fire pumps, etc.) whatever the earthing system (IT / TT / TN-S). De-energised installations: bb AC or DC (up to 690 V) bb when associated with a circuit breaker possessing an MN or MX release or with a contactor, the IM9-OL protects motors against insulation faults that may be produced during operating shutdowns (e.g. due to condensation), by initiating an alarm or startup lock-out. Operation bb Injection of DC voltage. Voltage is applied, with the motor de-energised, between the stator and earth, thereby creating a leakage current in the motor insulation resistances. bb 2 pre-set thresholds: vv 1 prealarm threshold, adjustable in 8 steps from 0.5 to 10 MΩ vv 1 motor no start threshold, adjustable in 8 steps from 0.25 to 2 MΩ. An electronic device measures insulation from the leakage current created by the voltage injected and activates the prealarm or prevents starting when insulation drops below the corresponding threshold. Installation and connection bb Live part in moulded, insulating, disconnectable, modular case, eight 9 mm modules wide, with transparent sealable cover. bb Horizontal or vertical mounting on symmetrical rail. bb Connection: wires up to 2.5 mm². bb The IM9-OL is used with a contact that opens to disconnect the device from the installation when the installation is energised. By selector switch Failsafe feature (2) As standard (3) Internal impedance DC 1 MΩ At 50-60 Hz 500 kΩ Measurement voltage 20 V max Measurement current Output contact 20 µA max Number 2 Breaking Capacity Auxiliary supply voltage Motor no start 1 standard Prealarm 1 failsafe AC 250 V 6A DC 12 to 24 V 6A 50/60/400 Hz 110/415 V AC ±15 % DC 125/250 V DC ±15 % Mechanical characteristics Weight < 0.2 kg Thermoplastic case Mounting Horizontal or vertical Degree of protection Front IP40 Case IP20 Other characteristics Temperature range For operation -25 ºC to +55 ºC For storage -40 ºC to +70 ºC Climatic conditions (4) Standards Product IEC 61557-8 Safety IEC 60664-1 EMC IEC 61326-2-4 Marine DNV approval (1) Depends on rated voltage withstand of the contact used to disconnect the IM9-OL when the network is energised. (2) Failsafe: the relay is desactivated on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (3) Only the first prealarm contact. (4) Suitable for use in all climates: b damp heat, equipment not operating (IEC 60068-2-30) b damp heat, equipment operating (IEC 60068-2-56) b salt mist (IEC 60068-2-52). Commercial reference: IMD-IM9-OL Standards bb Product: IEC 61557-8. bb Safety: IEC 60664-1. 17 PB106374_55 Insulation Monitoring Devices Vigilohm IM10 and IM20 Vigilohm IM10 and IM20 Type of installation to be monitored LV AC / DC IT systems (4) DC or rectified systems Phase-to-phase voltage With IM10/IM20 connected to neutral 600 V AC max With IM10/IM20 connected to phase 480 V AC max Frequency 45-440 Hz Line voltage 345 VDC max Limited in size IT subsystem Electrical characteristics Range for insulation resistance readings 0.1 kΩ to 10 MΩ Range for capacitance readings (IM20) 0.1 µF to 60 µF (150 µF (5)) Fault signalling Number of thresholds 2 (password protected) Prevent 1 kΩ to 1 MΩ Fault 0.5 kΩ to 500 kΩ Accuracy 5% Response time y 5 s typical Device operating test Use Internal impedance IT systems: bb LV AC/DC installations up to: vv 600 V AC max phase to phase vv 345 V DC bb For sub-networks or small networks up to 60 µF without automatic insulation fault detectors . bb One device only for each separate installation. bb Isolated from earth or connected to earth through an impedance. Failsafe feature (1) Output contact Self-test and manual At 50 Hz Number Measurement bb Insulation resistance. bb Earth leakage capacitance (IM20). Indications bb Satisfactory insulation resistance (green light). bb Drop in insulation resistance: vv below prevention threshold (white light) vv below fault threshold (orange light + popup window) vv transient fault (flashing orange light + popup window) vv earth or injection connection lost. Breaking Capacity 6A Voltage supplied 24 V Circuit breaker position Minimum load 5 mA Time delay on signalling 0 s to 7200 s Auxiliary supply voltage 18 110 to 415 V AC ±15 % DC 125/250 V DC ±15 % 12 VA Measurement voltage 75 V peak Measurement current <0.4 mA Dielectric strength 4000 V AC / 5500 V DC Mechanical characteristics Weight 0.25 kg Thermoplastic case Mounting Panel or DIN rail Degree of protection Front IP52 Other characteristics Temperature range For operation -25 ºC to +55 ºC (65 ºC) (6) For storage -40 ºC to +70 ºC Climatic conditions (2) IEC 60068 Indoor use Altitude up to 3000m Pollution degree 2 Maximum overvoltage CAT III Standards Additional functions with IM20 bb Module compatible with DIN rail and panel mounting. 50/60/400 Hz Maximum device consumption bb All values, thresholds, settings are accessible on the graphic display. Installation 6A Input contact (injection inhibition input) Display (8 languages (5)) bb Modbus communication. bb Earth leakage capacitance. bb Impedance of the capacitance Zc. bb Input injection inhibition (for easy exclusion management). bb Datalog with timestamping of all events. bb Compatible with HV plate IMD-IM20-1700 for networks up to 1.7 kV. Changeover AC 250 V DC 12 to 24 Others (5) French, English, Spanish, Italian, Portuguese, German, Russian, Chinese. 1 (standard or failsafe) Type of contact Operation bb Injection of low-frequency AC voltages between the installation and the earth. 110 kΩ 1 (standard) Product IEC 61557-8 Safety IEC 61010-1 (3) Installation IEC 60364-4-41 EMC IEC 61326-2-4 Marine DNV approval Fault locating with other device and accessories Mobile XGR portable generator and XRM receiver + probes HV plate reference IMD-IM20-1700 (for networks up to 1.7 kV) (1) Failsafe: the relay is disactivated either on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (2) Suitable for use in all climates: b damp heat, equipment not operating (IEC 60068-2-30) b damp heat, equipment operating (IEC 60068-2-56) b salt mist (IEC 60068-2-52). (3) The assigned voltage is 415 V AC / 300 V DC according to the IEC 61010-1. (4) When the insulation monitor is linked to a non-insulated inverter it is necessary to take into account the DC voltage limit rather than the AC limit. (5) With a limited range for R. See the photovoltaic example page 13. (6) The limit 65' C is for specific conditions: Commecial references: - Auxiliary power supply 230 V +15% max. bb IMD-IM10 - Utilization of the HV plate. bb IMD-IM20 Vigilohm IM10-H and IM20-H PB106375_55 (For hospitals) Vigilohm IM10-H and IM20-H Type of installation to be monitored LV AC / DC IT systems Phase-to-neutral voltage y 230 V AC +15 % y 230 V DC +15 % Frequency 50/60 Hz Electrical characteristics Range for insulation resistance readings 1 kΩ to 10 MΩ Fault signalling 1 (password protected) Number of thresholds 50 kΩ to 500 kΩ Thresholds y1s Response time Device operating test Yes Failsafe feature (1) As standard Internal impedance At 50 Hz Accuracy Output contact IM10-H 5% Number 1 (standard or failsafe) Type Breaking Capacity Output contact IM20-H 110 kΩ Changeover AC 250 V 6A DC 12 to 24 V 6A Number 2 Type Breaking Capacity Static DC 12 to 48 V y 50 mA Input contact Voltage supplied 24 V Use Transformer bimetal Minimum load 5 mA These modules are dedicated to hospital IT networks. Auxiliary supply voltage 50/60 Hz 110/230 V AC ±15 % DC 125/250 V DC ±15 % Operation bb Injection of a low-frequency AC voltage between the network and the earth. Measurement bb Insulation measurement through the earth leakage current in the IMD. Indication bb Satisfactory insulation resistance (green light). bb Drop in insulation resistance below the fault threshold (orange light). bb Earth or injection connection lost. Display (8 languages (3)) Cable size 0.2 to 2.5 mm2 Maximum device consumption 12 VA Measurement voltage 25 V max Measurement current 0.2 mA Dielectric strength 4000 V AC / 5500 V DC Mechanical characteristics Weight Mounting Panel mount or DIN rail Degree of protection Front IP52 Installation Cat. III, pollution 2, moulded case, disconnectable assembly, symetrical or embedded Other characteristics bb Insulation resistance. bb Thresholds. bb Alarms with dedicated pop-up windows. Temperature range (3) French, English, Spanish, Italian, Portuguese, German, Russian, Chinese. Climatic conditions (2) Standards Additional functions with IM20-H bb Modbus communication. bb Datalog with timestamping of all events. bb Transformer management: vv secondary load current display (in %) vv alarm on a threshold (in % of nominal current) vv alarm on temperature through the sensor (bimetal). vv specific output for the transformer. Accessories Hospital Remote Panel HRP (ref 50168) see pages 36 and 37. Or as part of the solution for operating theatres. 0.25 kg Thermoplastic case For operation -25 ºC to +55 ºC For storage -40 ºC to +70 ºC Product IEC 61557-8 Safety IEC 61010-1 EMC IEC 61326-2-4 Installation IEC 60364-7-710 (1) Failsafe: the relay is deactivated on occurrence of a fault or if the auxiliary supply voltage accidentally fails. (2) Suitable for use in all climates: b damp heat, equipment not operating (IEC 60068-2-30) b damp heat, equipment operating (IEC 60068-2-56) b salt mist (IEC 60068-2-52). Commercial references: bb IMD-IM10-H bb IMD-IM20-H Hospital fault location See page 26. 19 Vigilohm IM400 ???????? Insulation Monitoring Devices Functions and characteristics Overall insulation monitoring The IM400 provides overall insulation monitoring of electrical installations by injecting a special signal between the installation and earth. The IM400 accurately measures insulation of systems that contain switching power electronics (speed drives, motor starters, inverters, Thyristors…) and DC components. The IM400 is compatible with the following applications: bb Power Circuits. bb Control Circuits. bb Photovoltaic Systems. bb Impedant IT systems (HRG). Main functions bb Measurement vv insulation resistance. vv earth leakage capacitance. bb Indications vv satisfactory insulation resistance (green light). vv drop in insulation resistance: - below prevention threshold (white light and prevention relay actuated) - below fault threshold (yellow light and alarm relay actuated). vv transient faults (yellow light blinking). vv Loss of connection (wiring) of Vigilohm to the system or to earth. bb Display: vv measurements. vv logging of events detected by IM400. vv trend of system insulation during the last day, week, month, year. vv all this data is accessible locally on the LCD screen of the IM400 and remotely via a built-in Modbus RS485 communication. DB127888 Insulation monitoring Supervisor IM400 Insulation fault locating Locating faulty circuits obtained by using the IM400 with XD301, XD312 and XD308C. In addition, an XRM mobile receiver and a current probe can determine the exact location of the fault on the faulty circuit. Insulation fault detection and locating P12 on RM 10N Sensors P50 P100 Configuration management On installations with monitoring devices covering variable configurations, only one device at once is allowed to inject a voltage between earth and the installation downstream on the incoming circuit breaker. The system must therefore manage the exclusion of other monitoring devices. This is handled by either: vv External logic relays for simple configurations. vv Programmable Logic Controller for complex configurations. In both cases, the injection inhibition input of the IM400 will be used. Communication IM400 has a built in Modbus RS485 port, it is used for remote monitoring and control. P O S1 S2 Standards and certifications The IM400 complies with standards: bb IEC 364, parts 4 and 5. bb IEC 61557-8. bb IEC 61010-1. bb UL508 (pending). bb C22.2 No 14-05CSA (pending). bb DNV (pending). Installation bb Horizontal flush mounting on the front face of a cubicle or enclosure. bb Easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs. bb Wall mounting using inserts on the back of the IM400. Auxiliaries Cardew surge limiter: page 33. ZX impedance: page 34. IMD-IM400-1700: page 37. PHT1000: page 36. 20 Vigilohm IM400 Type of installation to be monitored AC or mixed AC/DC IT systems (1) DC or rectified systems Phase-to-phase voltage with IM400 connected to neutral y 830 V AC (1)(4) or 1700 V AC (5) With IM400 connected to phase y 480 V AC (1)(4) or 1000 V AC (5) Frequency 45-440 Hz Line voltage < 480 V DC (1)(4) or 1200 V DC (5)(6) Electrical characteristics 10 Ω to 10 MΩ Range for insulation resistance readings Range for capacitance readings 0.1 µF to 500 µF (2000 μF for PV applications) 1. Display indicating: b the value of the overall insulation resistance R b other information as selected via function keys. 2. Red self-test light, indicating internal IM400 fault or wiring connection lost or over capacitance. 3. Yellow light, flashing according to the communication. 4. Green light, indicating a normal insulation value. Blinking indicates the injection inhibition. 5. White light, indicating a pre-alarm. 6. Yellow light, indicating an insulation fault. Blinking indicates a transient fault. 7. Function key to access the menu. 8. Function key to Escape to the previous screen. 9. Three contextual keys. Signalling Number of thresholds 2 (protected password) Threshold settings Insulation Alarm 0.1 kΩ to 500 kΩ Preventative Insulation Alarm 1 kΩ to 1 MΩ Time delay for signaling 0s to 7200s Dielectric strength 4000 V AC / 5500 V DC 7.3 kV impulse Auxiliary supply voltage 50/60/400 Hz 100 to 440 V AC DC 100 to 440 V DC Auxiliary supply voltage tolerances +/-15 % Monitored system voltage tolerances IM400 directly connected +5% IM400 used with IM400-1700 +15% Maximum device consumption 25 VA / 10W Measurement voltage Variable 15 Vp, 33 Vp, 120 Vp Measurement current Variable 375 μAp, 825 μAp, 3 mAp Fault Locating current 3.75 mAp Extraneous DC voltage Ufg 506 V 50 Hz/DC impedance 40 kΩ (directly connected) Device test Output contact Self-test / manual test Quantity 2 Type of contact Breaking Capacity Injection inhibition (voltage supllied by the IM400) Changeover AC 250 V 3A DC 48 V 1 A, 10 mA min. load Voltage 24 V DC Current 5 mA Installation Category 300 V/OVC III, degree of polution 2 600 V/OVC II, degree of polution 2 Mechanical characteristics Weight Degree of protection 0.75 kg Front face IP54 Back case IP20 Other characteristics Multi-language display Inverter without transformer (1) 8 languages Tamperproof settings Temperature range Password Operating -25ºC to +55ºC [65ºC (3)] Storage -40ºC to +70ºC Fault locating with other devices and accessories Automatic Detectors XD301/312/308C Manual Mobile receiver XRM + probes HV plate commercial reference IMD-IM400-1700 (for network up to 1.7 kV without fault location) 50248 (for network up to 1.7 kV with fault location) (1) When the insulation monitor is linked to a non insulated inverter it is necessary to take into account the DC voltage limit rather than the AC limit. (2) Failsafe: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) With HV subassembly and 230 +15% V AC power supply. (4) IM400 directly connected to the power system (5) IM400 used with IM400-1700 or PHT1000 subassemblies (6) 1000 V DC with IM400-1700 and 1200 V DC with PHT1000 Commercial reference: bb IMD-IM400 21 Vigilohm XM300C 044148_SE_52 Insulation Monitoring Devices Functions and characteristics Overall insulation monitoring The XM300C provides overall insulation monitoring of electrical installations by injecting a low-frequency AC voltage between the installation and earth. Main functions bb Measurement: vv insulation resistance vv earth leakage capacitance. bb Indications: vv satisfactory insulation resistance (green light) vv drop in insulation resistance: - below prevention threshold (orange light and relay actuated) - below fault threshold (red light and two relay actuated, including one with failsafe feature). vv transient faults (orange light). bb Display: vv measurements vv events detected by any XL308/316 locators connected. All this data is accessible locally on the LCD screen of the insulating monitoring device and remotely via the Vigilohm System bus. DB401218 Additional functions with other devices Locating faulty circuits obtained by using the XM300C with: bb XL308 and XL316 locators connected to 8 or 16 toroids; they are linked to the XM300C by the Vigilohm System bus. bb XD308C communicating detectors; they are linked to the XM300C by the Vigilohm System bus and connected to the toroids on the circuits being monitored. bb XD301 and XD312 detectors connected to toroids on the circuits being monitored. bb XRM mobile receiver and current probe to fine-tune automatic locating results. All these devices can be combined on a given installation. Distributed measurements This function is provided by combining an XM300C (or an XML308/316) with XL308 or XL316 locators. These locators measure insulation resistance and earth leakage capacitance of each circuit. They have a fault alarm threshold that can be set to different levels for each channel. Interfaces XLI300C X L I3 0 0 d é f a u t Communication XLI300 and XTU300 interfaces allow monitoring devices, locators, and communicating detectors to exchange data with a supervision system via Modbus protocol. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events. Insulation monitoring XM300C XM 300c Configuration management On installations with monitoring devices covering variable configurations, only one device at once is allowed to inject a voltage between earth and the installation downstream on the incoming circuit breaker. The system must therefore manage the exclusion of other monitoring devices and each locator must identify the monitoring device it is capturing the signal from. This is handled by either: bb by the XTU300 interface for multiple busbar installations bb by the XLI300 inrterface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the digital inputs of the XM300C or the XML308/316. If only XD308C detectors are associated with the XM300C, monitoring device exclusion is handle by the XLI300. test valeur d'isolement 040 K MENU TEST P 100 Insulation fault detection and locating XRM XL308/316 XL316 test 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 P 5 0 P 1 2 o n test/reset R M 1 0 N Standards The XM300C complies with the following standards: bb IEC 364 parts 4 and 5 bb IEC 61557-8. Sensors P O S1 S2 22 Installation and connection bb Horizontal flush mounting on the front face of a cubicle or enclosure. bb Easy mounting in Prisma enclosures using the corresponding mounting plates and front plates appropriate cutouts. bb The devices are interconnected by shielded cables (double 0.75 mm2 twisted pair). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF. DB127892 Vigilohm XM300C Type of installation to be monitored i AC or mixed AC/DC IT systems (4) DC or rectified systems 1 7 6 2 4 5 3 Phase-to-phase voltage with XM300C connected to neutral y 760 +20% or 1700 V AC (1) With XM300C connected to phase y 440 +20% or 1000 V AC (1) Frequency 45-440 Hz Line voltage < 500 V DC or 1200 V DC (1) Electrical characteristics Ohmmeter Digital Range for insulation resistance readings 0.1 kΩ to 999 kΩ 1. Display indicating: b the value of the overall insulation resistance R b other information as selected via function keys. 2. Red self-test light, indicating internal XM300C faults. 3. Light indicating that a transient fault has occurred. 4. Five lights indicating the insulation level. 5. Instruction manual stored in a drawer on the front face of the device. 6. Sealable cover ensuring tamperproof settings. 7. Function keys for: b accessing earth coupling capacitance readings b setting thresholds b displaying the value of the last transient insulation fault b choosing language. Range for capacitance readings 0.1 µF to 999 µF Auxiliaries b Cardew surge limiter: page 33. b ZX limiting impedance to create an impedanceearthed neutral: page 34. b PHT1000 subassembly if the device is used on 1000-1700 V installations: page 34. Device test Signalling Number of thresholds 2 (sealable settings) Threshold settings 0.2 to 99.9 kΩ 1st threshold (prevent) 1 to 299 kΩ 2nd threshold (fault) Dielectric strength 2500 V Auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC Auxiliary supply voltage tolerances -15 % to +10 % Maximum device consumption 30 VA Measurement voltage 6 V max Measurement current 5 mA max 50 Hz/DC impedance 22 kΩ Self-test & manual test Failsafe feature (2) Output contacts As standard Changeover Breaking capacity Quantity 3 (1 failsafe) AC 400 V pf = 0.7 3A AC 230 V pf = 0.7 5A DC 220 V L/R = 1 ms 0.45 A DC 48 V L/R = 1 ms 2.5 A DC 24 V L/R = 1 ms 10 A Circuit breaker position indication contacts (3) (voltage and current supplied by XLI or XTU interfaces) Voltage supplied 24 V Max current supplied 10 mA (short circuit) Connection cross-sections Rigid conductors 1 to 1.5 mm2 Flexible conductors 0.75 to 1.5 mm2 Mechanical characteristics Weight Sheet-metal case 3.5 kg Horizontal Degree of protection Disconnectable screw terminal block Flush mounting IP30 Other characteristics Interfacing possible with supervisor Multi-language display English/French Tamperproof settings Behind sealable cover Temperature range Operating -5 ºC to +55 ºC Storage -25 ºC to +70 ºC Fault locating with other device Inverter without transformer (4) Automatic Detectors XD301/312 Manual Mobile receiver XRM + probes (1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status. (4) When the insulation monitor is linked to a non insulated inverter it is necessary to take into account the DC voltage limit rather than the AC limit. Commercial references: bb 115/127 V AC: 50540 bb 220/240 V AC: 50541 bb 380/415 V AC: 50542 23 Vigilohm XML308 and XML316 044149_SE_60 Insulation Monitoring Devices Functions and characteristics Overall and individual circuit insulation monitoring The XML308 and XML316 monitoring-locating devices combine the functions of: bb the XM300C insulation monitoring device bb XL308 or XL316 insulation fault locators, they monitor the insulation of: vv the whole installation by injection of a low-frequency AC voltage between the installation and earth vv 8 or 16 individual circuits via detection toroids. Main functions bb Measurement of the overall installation and each monitored circuit: vv insulation resistance vv earth leakage capacitance. bb Indications: vv satisfactory insulation resistance (green light) vv drop in insulation resistance: - for the overall installation, below prevention threshold (orange light and relay actuated) - for the overall installation and each monitored circuit, below adjustable fault threshold (red light and two relays actuated, including one with a failsafe feature). vv transient faults (orange light) last three values stored vv faulty circuit by 8 or 16 indicator lights (1 per circuit). n Display: vv measurements accessible locally on the display unit of the device vv events detected by connected XL308/316. All this data available on the LCD screen and remotely via Vigilohm System bus. DB401439 Additional functions with other devices Monitor more than 8 or 16 circuits by adding: bb XL308 or XL316 locators bb XD308C to automatically detect faults and communicate via XLI300 or XTU300 bb XD301 and XD312 detectors that provide local indications. Communication XLI300 and XTU300 interfaces allow monitoring devices, locators, and communicating detectors to exchange data with a supervisor. The XLI300 and XTU300 interfaces connect to the Vigilohm System bus and allow timestamping of insulation monitoring events. Interfaces XLI300C X L I3 0 0 d é f a u t Insulation monitoring XML308/316 XML316 test 3 4 5 6 7 8 1 2 9 10 11 12 13 14 15 16 valeur 040 K TEST d'isolement MENU P 100 Insulation fault detection and locating XRM Configuration management On installations with monitoring devices covering variable configurations, only one device at once is allowed to inject a voltage between earth and the installation downstream on the incoming circuit breaker. The system must manage the exclusion of other monitoring devices and each locator must identify the monitoring device it is capturing the signal from. This is handled by either: bb the XTU300 interface for multiple busbar installations bb the XLI300 inrterface for single busbar installations. In both cases, the circuit breaker position indication contacts are wired to the digital inputs of the XM300C or the XML308/316. Standards bb IEC 364, parts 4 and 5 bb IEC 61557-8. P 5 0 P 1 2 o n R M Toroids XML308 and XML316 can operate with type A , OA, and XS toroids. 1 0 N Sensors P O S1 S2 24 Installation and connection bb Horizontal flush mounting on the front face of a cubicle or enclosure bb Easy mounting in Prisma enclosures using the corresponding mounting plates and front plates appropriate cutouts bb The devices are interconnected by shielded cables (double 0.75 mm2 twisted pair). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF. DB127893 Vigilohm XML308 and XML316 XML316 Type of installation to be monitored test 1 2 3 4 5 6 7 8 i 9 10 11 12 13 14 15 16 AC or mixed AC/DC IT systems Phase-to-phase voltage with XM308/316 connected to neutral y 760 or 1700 V AC (1) DC or rectified systems With XM308/316 connected to phase Frequency Line voltage y 440 or 1000 V AC (1) 45-440 Hz < 500 or 1200 V DC (1) Electrical characteristics 9 8 10 1 7 2 3 6 4 Ohmmeter Digital Range for insulation resistance readings Range for capacitance readings Signalling Number of thresholds per installation Number of thresholds per circuit Threshold 1st threshold (prevent) settings 2nd threshold (fault) 0.1 kΩ to 999 kΩ 5 1. Display indicating: b the value of the overall insulation resistance R b other information as selected via function keys. 2. Red self-test light, indicating internal device faults. 3. Light indicating that a transient fault has occurred. 4. Five lights indicating the insulation level. 5. Instruction manual stored in drawer on front of device. 6. Sealable cover ensuring tamperproof settings. 7. Function keys for: b accessing earth coupling capacitance readings b setting thresholds b displaying three last values of transient insulation faults b reading measurements made on individual circuits by the internal locator b remote access to faults located by XL308 or XL316 detectors b choice of language (English or French). 8. Two indicator lights continuously display insulation level of the whole installation. 9. 8 or 16 lights indicating faulty circuits. 10. Light indicating transient fault event. Auxiliaries b Cardew surge limiter: page 33. b ZX limiting impedance to create an impedanceearthed neutral: page 34. b PHT1000 subassembly if the device is used on 1000-1700 V installations: page 34. Dielectric strength Auxiliary supply voltage 0.1 µF to 999 µF 2 (sealable settings) 1 (sealable settings) 1 to 299 kΩ 0.2 to 99.9 kΩ Auxiliary supply voltage tolerances 2500 V 115/127 V AC 220/240 V AC 380/415 V AC -15 % to +10 % Maximum device consumption Measurement voltage 30 VA 6 V max Measurement current 50 Hz/DC impedance Device test Failsafe feature (2) Output contacts Breaking capacity 5 mA max 22 kΩ Self-test & manual test 50/60 Hz Changeover Circuit breaker position indication contacts (3) (voltage and current supplied by XLI or XTU interfaces) Connection cross-sections As standard Quantity AC 400 V pf = 0.7 AC 230 V pf = 0.7 DC 220 V L/R = 1 ms DC 48 V L/R = 1 ms DC 24 V L/R = 1 ms Voltage supplied Max current supplied 3 (1 failsafe) 3A 5A 0.45 A 2.5 A 10 A 24 V 10 mA (short circuit) Rigid conductors Flexible conductors 1 to 1.5 mm2 0.75 to 1.5 mm2 Mechanical characteristics Weight Sheet-metal case Degree of protection 4.5 kg Horizontal Disconnectable screw terminal block Flush mounting IP30 Other characteristics Types of toroid used Interfacing possible with supervisor Multi-language display Tamperproof settings Temperature range A, OA, (XS compliant) English/French Behind sealable cover Operating -5 ºC to +55 ºC Storage -25 ºC to +70 ºC (1) The upper limit is extended to the second value by adding a PHT1000 subassembly. (2) Failsafe: a failsafe relay operates in the event of an accidental interruption of auxiliary power or a fault. (3) This contact is an auxiliary switch mounted on the circuit breaker and used to indicate its operating status. Commercial references: bb XML308: vv 115/127 V AC: 50490 vv 220/240 V AC: 50491 vv 380/415 V AC: 50492 bb XML316: vv 115/127 V AC: 50322 vv 220/240 V AC: 50323 vv 380/415 V AC: 50324 25 Fault Location Devices Vigilohm XD301 / XD312 / XD312-H Automatic insulation fault locators 044144_SE_52 Insulation fault detectors XD301 XD312 XD312-H Electrical characteristics Use XD301 & XD312 insulation fault locators have two functions: Type of installation to be monitored Low voltage AC 45-400 Hz / Hospital DC Operating threshold 2.5 mA at 2.5 Hz Polling time 20 s 20 s per channel Fault indications 1 indicator light 12 channel indicator lights (+ 1 general) Local tests For indicator lights and output relay Clearing of indications Reset button on device Latching of transient fault indications On/off via selector Output relay Number of contacts 1 failsafe Breaking capacity of output contacts AC 400 V pf = 0.7 3A AC 230 V pf = 0.7 5A DC 220 V L/R = 1 ms 0.45 A DC 120 V L/R = 1 ms 0.65 A DC 48 V L/R = 1 ms 2.5 A DC 24 V L/R = 1 ms 10 A 50/60 Hz 115/127 V AC bb fault detection (with respect to the fault threshold) bb automatic locating of the faulty circuit. Operation bb XD301 and XD312 insulation fault detectors are fixed receivers used with (but not connected to) XM300C, XML308/316 and IM400 insulation monitoring devices. Via measurement toroids, they detect and automatically locate insulation faults. bb The XD312-H is compatible with IM10-H and IM20-H. bb The XD312/XD312-H detector, with 12 channels connected to a maximum of 12 toroids installed on different circuits of the installation, includes the following features on its front face: vv 12 fault indicator lights corresponding to 12 channels vv a selector to enable or disable latching of transient fault indications until reset. bb Detector XD301 is a single-channel version designed for use with one measurement toroid. Installation and connection bb Live part is in an insulated case with a sealable, transparent sealable cover. Width equal to 8 (XD301) or 12 (XD312) 9 mm width modules. bb Horizontal flush or surface mounting on DIN rail. bb Tunnel terminals for 1.5 mm2 wiring. Toroids DB127894 bb XD301 and XD312 insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids. bb The XD312-H must be used with the toroid TA30 with a specific wiring. 1 2 3 4 5 6 7 8 9 Auxiliary supply voltage 380/415 V AC Auxiliary supply voltage tolerances -15 % to +10 % Consumption 6 VA Dielectric strength 2500 V Connection with insulation monitoring device None Weight 0.3 kg Thermoplastic case Horizontal mounting Degree of protection IP30 Surface mount IP20 For operation -5 ºC to +55 ºC For storage -25 ºC to +70 ºC Other characteristics Temperature range Types of toroids to be used A, OA, (N and O compatible) TA30 Toroid for direct connection to case 30 & 50 mm None type A Fault locating with other device Mobile XGR portable generator and XRM receiver + probes (1) The operating threshold of the XD301/312 detectors is not adjustable. These devices are designed to detect low-impedance faults. The detection threshold varies between 100 Ω and 2 kΩ depending on the characteristics of the installation, and around 50K Ω for the XD312-H. Commercial references bb XD301: vv 115/127 V AC: 50506 vv 220/240 V AC: 50507 vv 380/415 V AC: 50508 bb XD312: vv 115/127 V AC: 50535 vv 220/240 V AC: 50536 vv 220/240 V AC: 50536-H vv 380/415 V AC: 50537 reset 2 4 5 6 1. Lights indicating the faulty circuit. 2. Selector to enable or disable transient fault indication latching 3. Sealable cover. 4. General fault indicator light. 5. Test button for indicator lights and output relay. 6. Reset button (to clear fault indications). 26 0.6 kg Flush mount test 3 - Mechanical characteristics To improve the toroid sensitivity it is necessary to have two loops (3 crossings) in the toroid. 1 - 220/240 V AC XD312 10 11 12 50KΩ Vigilohm XD308C Communicating automatic insulation fault locator 044143_SE_29 Type of installation to be monitored Electrical characteristics Type of installation to be monitored Low voltage AC 45-400 Hz /DC Operating threshold 2.5 mA at 2.5 Hz (1) Polling time 20 s per channel Fault indications 8 indicator lights Operating tests Local Functions tested Indicator lights and electronics Clearing of memorised faults Local reset on front face Remote reset from supervisor Auxiliary supply voltage 50/60 Hz 115/127 V AC 220/240 V AC XD308C 1 2 3 test 4 5 6 7 8 reset 1 4 5 3 2 6 1. Lights indicating faulty circuit. 2. General fault indicator light. 3. Power on. 4. Test button for indicator lights. 5. Device internal fault indication (self-test). 6. Self-test fault indicator light. -15 % to +10 % 6 VA 2500 V Via 4-wire Vigilohm System bus Mechanical characteristics Weight Metal case with insulated front Degree of protection 0.6 kg Vertical mounting Flush mount IP 30 Other characteristics Temperature range For operation For storage -5 ºC to +55 ºC -25 °C to +70 °C A, OA, (N and O compatible) Types of toroids to be used (1) The operating threshold of the XD308C detectors is not adjustable. This device is designed to detect low-impedance faults. The detection threshold varies between 100 Ω and 2 kΩ depending on the characteristics of the installation. Use The XD308C provides 3 functions: bb detection of insulation faults bb automatic locating of the faulty circuit, identified by the number of the illuminated indicating light bb communication of this information to an XLI300 or XTU300 interface for transmission to a supervisor or PLC. Commercial references bb 115/127 V AC: 50723 bb 220/240 V AC: 50724 bb 380/415 V AC: 50725 DB127887 DB127895 380/415 V AC Auxiliary supply voltage tolerances Consumption Dielectric strength Connection with insulation monitoring device Interfaces XLI300C Operation bb The XD308C is a fault locator with communication. When associated with an IM400 it enables a simple solution for remote fault location. It can also be used with the XM300C and the XML308/316. bb The XD308C detector, with 8 channels connected to a maximum of 8 toroids installed on different circuits of the installation, includes the following features: vv 8 fault indicator lights corresponding to the 8 channels vv 1 general fault indicator light signalling that a fault has occurred vv 1 light indicating the device operating status vv 2 pushbuttons (self-test and reset). X L I3 0 0 d é f a u t Insulation monitoring IM400 P 100 Insulation fault detection and locating XRM XD308C XD308c Installation and connection bb Live parts in a disconnectable metal case. bb Vertical mounting on front plate. bb Tunnel terminals for 1.5 mm2 wires. bb The devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). Resistance between the two most distant points must not exceed 12 Ω. Coupling capacitance between pairs must not exceed 250 nF. test 1 3 2 4 5 6 7 8 on test reset P 5 0 P 1 2 o n R M 1 0 N Sensors P O S1 S2 Toroids bb XD308C insulation fault detectors operate with type A and OA toroids. They are also compatible with the older type N and O toroids. 27 Measurement per feeder Vigilohm XL308 & XL316 044145_SE_51 Insulation fault local measurement Functions and characteristics Basic function Local insulation fault monitoring. Used together with an XM300C or XML308/316 monitoring device, XL308 and XL316 locators monitor the insulation of 8 or 16 individual circuits and automatically locate any faults. Main functions bb Measurement: vv insulation resistance of each monitored circuit vv earth leakage capacitance of each monitored circuit. bb Indications: vv satisfactory insulation resistance (green light) vv drop in insulation resistance below fault threshold (red light and two relays actuated, including one with a failsafe feature). The fault threshold is adjustable for each of the 8 or 16 channels corresponding to the monitored circuits vv transient faults on each of the monitored circuits. bb Display: vv faulty circuits are indicated by the corresponding LEDs (8 or 16 depending on the model) vv a flashing LED indicates a transient fault on the corresponding circuit. Communication Faults detected by XL308/316 locators can be displayed on the insulation monitoring device associated with the locator. The information transmitted to the insulation monitoring device can be transmitted to a supervisor via an XLI300 or XTU300 interface connect to the Vigilohm System bus. Standards XL308 and XL316 locators comply with the following standards: bb IEC 364, parts 4 and 5 bb class DLD/M of UTE C 63-080 They are implemented in accordance with standard NF C 15-100 paragraph 413.4 bb IEC 61557-8. DB401218 Toroids XL308 and XL316 locators operate with type A and OA toroids. Installation and connection bb Horizontal flush mounting on the front face of a cubicle or enclosure. bb Easy mounting in Prisma enclosures using the corresponding mounting plates and front plates that come with the appropriate cut-outs. bb The devices are interconnected by shielded cables (double 0.75 mm2 twisted pairs). The resistance between the two most distant points must not exceed 12 Ω. The coupling capacitance between pairs must not exceed 250 nF. bb Connection of toroids using twisted, shielded cable (1 pair). Interfaces XLI300C X L I3 0 0 d é f a u t Insulation monitoring XM300C XM 300c test valeur d'isolement 040 K MENU TEST P 100 Insulation fault detection and locating XRM XL308/316 XL316 test 2 3 4 5 6 7 8 1 1 0 1 1 1 2 1 3 1 4 1 5 1 6 9 P 5 0 P 1 2 o n test/reset R M 1 0 N Sensors P O S1 S2 28 DB127896 Insulation fault locators XL31 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 - 1 XL308 XL316 Electrical characteristics 2 + 9 test/reset i ∝F ! 7 8 5 6 4 3 Ohmmeter Digital Range for insulation resistance readings 0.1 to 999 kΩ Range for capacitance readings 0.1 µF to 999 µF Signalling 8 lights (1/channel) Signalling threshold and setting range (per channel) Fault threshold 1 0.2 to 99.9 kΩ Polling time 15 seconds per channel Device test Self-test and manual test Dielectric strength Auxiliary supply voltage 1. Display indicating measured insulation resistance and earth coupling capacitance value. 2. Light indicating measurement units for displayed value (kΩ, μF, etc.). 3. Red self-test light, indicating device faults 4. Yellow light indicating that a transient fault has occurred. 5. 2 lights indicating the insulation level: b green light: normal b red light: insulation resistance below fault threshold on one of the circuits. 6. Instruction manual stored in a drawer on the front face. 7. Function keys for: b accessing earth leakage capacitance readings b setting thresholds b accessing three last values of transient insulation faults. 8. Sealable cover ensuring tamperproof settings. 9. Lights indicating faulty circuits. 16 lights (1/channel) 2500 V 50/60 Hz 115/127 V AC 220/240 V AC 380/415 V AC Auxiliary supply voltage tolerances -15 % to +10 % Consumption 30 V A Indicator and output relay Local or from insulation monitoring device Output relays 2 ( 1 failsafe) Breaking capacity of output AC 400 V pf = 0.7 contacts AC 230 V pf = 0.7 3A 5A DC 220 V L/R = 1 ms 0.45 A DC 120 V L/R = 1 ms 0.65 A DC 48 V L/R = 1 ms 2.5 A DC 24 V L/R = 1 ms 10 A Connection with insulation monitoring device Connection cross-sections Rigid conductors Flex conductors Via 4-wire communication bus 1 to 1.5 mm2 0.75 to 1.5 mm2 Mechanical characteristics Weight 3.5 kg Sheet-metal case Horizontal mounting Disconnectable screw terminal block Other characteristics Temperature range Types of toroids to be used For operation -5 °C to +55 °C For storage -20 °C to +70 °C A, OA, (N and O compatible) Commercial references bb XL308: vv 115/127 V AC: 50606 vv 220/240 V AC: 50607 vv 380/415 V AC: 50608 bb XL316: vv 115/127 V AC: 50615 vv 220/240 V AC: 50616 vv 380/415 V AC: 50617 29 Communication interfaces Vigilohm XLI300, XTU300 044141_SE_30 Device XLI300 / XTU300 Function Interface between the Vigilohm System bus and a supervisor or PLC Operates with Monitoring device XM300C b Mon./locating device XML308/316 b Locator XL308/316 b Detector XD301/312 b XD308C Maximum configuration b b Power supply to Vigilohm System bus Monitoring device XM300C and/or XML308/316 4 Locator XL308/316 8 Detector XD308C 8 50/60 Hz 115/127 V AC Electrical characteristics Use Auxiliary supply voltage 220/240 V AC When two or more communicating devices (XM300C, XML308/316, XL308/316 or XD308C) are used or when communication with a supervisor is required, it is necessary to connect one (and only one) interface to the communication bus. Maximum device consumption 30 VA Dielectric strength 2500 V Functions Weight The interface allows communication between the Vigilohm System and a supervisor or PLC using a Modbus type protocol. It transmits the information provided by the Vigilohm System: bb prevention and fault alarms from XM300C or XML308/316 monitoring devices bb fault alarms from XML308/316 or XM308/316 locators bb insulation resistance and capacitance measurements bb threshold settings bb fault alarms and faulty circuit identification from XD308C detectors. The interface also allows the thresholds to be set form the supervisor. Metal case with insulated front 1.864 kg b Degree of protection IP30 Degree of protection of front IP40 As the IMD injects a low frequency into the network, it is necessary to have at least one IMD, but no more than one, per subnetwork. 380/415 V AC Mechanical characteristics Other characteristics b Interface possible with supervisor Communication with other devices Sub D 9-pin (not supplied) b b Via 4-wire data bus Temperature range Operation -5 ºC to +55 ºC Storage -25 ºC to +70 ºC Modbus connector Installation b Vertical mounting on front plate Connection Vigilohm System bus 1.5 mm2 tunnel terminals b External bus RS485 b Sub D9 female connector Communication Speed (baud) Adjustable 300... 19200 Per fault 9600 Data length (bits) 8 Exclusion Parity None This injection exclusion is managed by the interface. With two or several set of busbars with bus coupling, the exclusion becomes more complex and is managed by a PLC inside the XTU300. Start bits 1 Stop bits 1 XTU300 = XLI300 + PLC function. The configuation is made by Schneider Electric according to the wiring diagram. Commercial references bb XLI300 115/127 V AC: 50515 bb XLI300 220/240 V AC: 50516 bb XLI300 380/415 V AC: 50517 bb XTU300 220/240 V AC: 50546 (1) bb XTU300 380/415 V AC: 50547 (1) (1) Please consult Schneider Electric for configuration. 30 XRM mobile fault locating Accessories 051350_SE_25 Receiver & current probes Functions and characteristics Operation The XRM mobile receiver, used with a current probe, is mainly intended as an enhancement to automatic fault locating systems. It can be placed at various points along a faulty circuit, capturing the signal emitted by an XM300C, XML308/316 or IM400 insulation monitoring device to determine the exact location of the fault. Three current probes are available, the XP15, XP50 and XP100. The set of live conductors to be tested must have a maximum diameter of 12, 50 and 100 mm respectively. Display The XRM receiver displays a number from 0 to 19, corresponding to the insulation level: bb 0: no fault bb 19: solid fault (no insulation). DB101070 XRM receiver. DB100471_SE_50 Note: the photographs are for information purposes only. There are two types of probes that function in the same way but are different in shape and colour. DB127889 The XP15, XP50 and XP100 current probes. Insulation monitoring Insulation fault detection and locating XD301 XD312 XRM P12 on P50 P100 RM 10N Sensors P O S1 S2 31 Vigilohm mobile fault locating Accessories 053130_SE_63 Kit XGR + XRM + probes Type of installation to be monitored General LV AC or mixed AC/DC IT systems DC or rectified systems y 760 V AC Phase-to-phase voltage with XGR connected to neutral With XGR connected to phase Frequency Voltage between polarities y 440 V AC 45-400 Hz 500 V DC Electrical characteristics Auxiliary supply voltage Presentation The mobile fault locating kit comes in the form of a case containing: bb a locating signal generator, XGR, supplied with 220 - 240 V AC bb a locating signal receiver XRM bb three tong-type current probes: XP15, XP50 and XP100. The devices making up the kit and the XGR for other voltages are all available individually. See catalogue number tables. XGR 50/60 Hz XRM Max consumption IEC alkaline 9 V cell Display XRM Calibration Impedance Maximum current injected XRM XGR XGR Type Scale 115/127 V AC 220/240 V AC 380/415 V AC 15 VA PP3 or 6 LR61 type (not supplied) Digital 0 to 19 By potentiometer 40 kΩ 2.5 mA Mechanical characteristics Weight Case XGR XRM XGR XRM Plastic Plastic 0.85 kg 0.2 kg Portable Portable For cables up to For cables up to For cables up to 12 mm 50 mm 100 mm Associated equipment Probes (1) XP15 XP50 XP100 Fault locating with other device Use Automatic Detectors XD301/312 Manual Mobile receiver XRM + probes (1) Maximum diameter of all live conductors together. The kit is used on LV IT systems (i.e. installations with an unearthed or impedance-earthed neutral). It enables fault locating on: bb AC installations 50 to 400 Hz bb DC installations. It is used mainly with insulation monitoring devices that inject DC currents (IM9) or too small AC current (IM10, IM20). Commercial references: bb XRM: 50278 bb XGR 115/127 V AC: 50281 bb XGR 220/240 V AC: 50282 bb XGR 380/415 V AC: 50283 bb Empty case: 50285 bb Kit case: 50310 bb XP15 probe: 50494 bb XP50 probe: 50498 bb XP100 probe: 50499 051350_SE_19 DB100471_SE_36 047166_SE_30 bb The XGR generator injects a 2.5 Hz AC voltage between the installation and the earth, thereby creating a leakage current which passes through the installation insulation impedance. bb The XRM mobile receiver is associated with one of the three tong-type probes, XP15, XP50 or XP100, and detects this leakage current at 2.5 Hz. It displays a value between 1 and 19 according to the current passing through the probe, thus detecting the leakage current. bb Three current probes are available, the XP15, XP50 and the XP100, for cables with diameters up to 12, 50 and 100 mm respectively. Older probe models are not compatible with the XRM. DB101070 Operation of the XGR XRM locating signal receiver. XGR locating signal generator. 32 Vigilohm toroids 051352_SE_60 Earth leakage current detectors Toroids Use The toroids are used to detect the earth leakage currents. They are used with the Vigilohm System for the detection, locating and measurement of earth fault currents on IT systems. Closed toroids (type A) are suitable for new installations and extensions. Split toroids (type OA) are suitable for renovated installations and extensions. Functions These toroids detect leakage current and transmit a proportional signal to the associated receiver. Closed toroids (type A). 042589_SE_46 Compatibility All type A and OA toroids are compatible with the various devices of the Vigilohm System range: XD301, XD312, XD308C, XL308, XL316, XML308 and XML316. Installation and connection Closed toroids (type A) bb Enclosed in an insulated casing. bb 2 possibilities for mounting: vv diam. 30-50-80 mm on symmetrical rail vv all diameters on plate and cables. bb Connection: vv diam. 30 to 200 mm by tunnel terminals for 0.22 mm2 wires (minimum) vv diam. 300 mm by 6.35 mm tab connectors. N1 2 3 PE DB127911 DB127910 Split toroids (type OA). N1 2 3 PE Split toroids (type OA) bb Enclosed in an insulated casing bb Mounting on plate and cable bb Connection by 5 mm diam. screws for 0.22 mm2 wires. (see table page 32) Immunity to line overcurrents Line overcurrents, due to motor starting or transformer energising, may result in unnecessary fault detection by the detector. A number of simple precautions can help prevent this from happening: when used together they are even more effective: bb place the toroid on a straight part of the cable bb carefully centre the cable in the toroid bb use a toroid with a diameter far larger than the diameter of the cable (2 x diameter) (figure 1). Figure 1. Figure 2. For severe operating conditions, use of a mild steel sleeve placed around the cable, in the toroid, considerably increases immunity. Recommended characteristics bb Mild steel foil, 1/10 mm thick, to be wound several times around the cable in the toroid (at least 1 mm thick). bb Internal diameter of toroid > 1.4 x external diameter of the cable bundle (figure 2). bb Toroid-detector link: vv resistance y 3 Ω vv cross-sectional area of wires: 0.75 mm² to 1.5 mm². bb Maximum length: 100 m (see the toroid user manual for details). 33 Vigilohm toroids Accessories Type A closed toroid, Type OA split toroid Type OA split toroid DB127916 Type A closed toroid DB127915 Sensors General characteristics Type of installation to be monitored LV 50/60/400 Hz & DC LV 50/60/400 Hz & DC Insulation voltage Ui 1000 V 1000 V Closed sensor b - Split sensor - b Operating temperature -35 ºC to +70 ºC -35 ºC to +70 ºC Storage temperature -55 ºC to +85 ºC -55 ºC to +85 ºC Degree of protection IP30 (IP20 connections) IP30 (IP20 connections) Transformation ratio 1/1000 1/1000 3-phase short-circuit withstand current lcw of 100 kA/0.5 s b b b b Electrical characteristics Differential short-circuit withstand current lDw of 85 kA/0.5 s (as per IEC60947-2 in kA rms) Overvoltage category 4 4 Rated impulse withstand voltage Uimp (kV) 12 12 Sensor characteristics TA30 PA50 IA80 MA120 SA200 GA300 POA GOA Max cross-section area of conductors per phase (mm2 of copper) 25 50 95 240 240 2 x 185 2 x 240 50 Mechanical characteristics Type of sensor Diameter (mm) Weight (kg) Diameter (mm) Weight (kg) Toroid TA30 Ø 30 0.120 - - Toroid PA50 Ø 50 0.200 - - Toroid IA80 Ø 80 0.420 - - Toroid MA120 Ø 120 0.590 - - Toroid SA200 Ø 200 1.320 - - Toroid GA300 Ø 300 2.230 - - Toroid POA - - 46 1.300 Toroid GOA - - 110 3.200 Mounting Horizontal or vertically on symmetrical DIN rail TA30, PA50, IA80, MA120 - On plain or slotted backplate or profiled sheet metal TA30, PA50, IA80, MA120, SA200 POA, GOA On cable IA80, MA120, SA200, GA300 - Environment (1) Damp heat, equipment not operating (IEC 60068-2-30) 28 cycles +25 °C/+55 °C / HR 95 % 28 cycles +25 °C/+55 °C / HR 95 % Damp heat, equipment operating (IEC 60068-2-56) 48 hours, environment category C2 48 hours, environment category C2 Salt mist (IEC 60068-2-52) KB test, severity 2 KB test, severity 2 Degree of pollution (IEC 60664-1) 3 3 Calorific value (MJ) 0.98 (1) Allows use in all climates. Commercial references: bb TA30: 50437 bb PA50: 50438 bb IA80: 50439 bb SA200: 50441 bb MA120: 50440 bb GA300: 50442 bb Open POA: 50485 bb Open GOA: 50486 bb 100 m cable (shielded): 50136 34 1.42 3.19 3.89 7.05 - 8.02 16.35 Vigilohm auxiliaries 041857_SE_20 Accessories for various installations (Cardew) Auxiliary characteristics Cardew C surge limiter bb On LV network with isolated or impedance earthed neutral. bb Connected to the secondary of the MV/ LV transformer to discharge overvoltages to earth. bb Capable of withstanding the short-circuit current of the transformer. bb Its operation causes continuous indication on the insulation monitor. 130 Characteristics bb Non-arcing voltage at 50 Hz y 1.6 x nominal U. bb Certain arcing voltage at 50 Hz >2.5 x nominal U (3 x nominal U for 220 V). bb Maximum current after arcing: 40 kA/0.2 sec. bb Insulation resistance > 1010 W. bb Cartridge not reusable. bb Temperature range: vv operating: -5 °C to +40 °C vv storage: -25 °C to +70 °C. DB127914 DB127913 DB127912 Connection 160 50 Standards bb NF C 63-150, NF C 15-100. bb Weight: 1 kg. 2 Ø13 DB127953 Ø70 2 Ø7 M12 100 L3 L2 L1 N MV/LV cardew C Cardew selection table The selection depends on: bb the operating voltage Un of the installation bb the installation insulation level bb the connection point (neutral-earth or phase-earth). Connecting conductor size bb Cable or bar with a size adapted to the transformer rating. bb The connecting conductor should be considered to be a protective conductor (PE) and the calculation of its crosssectional area must satisfy applicable installation standards, considering that this part of the installation is protected by protective devices located upstream of the MV/LV transformer. bb According to standard IEC 364, the formula for the calculation of the of the size of the PE conductor is: S = √I2t/k where S is the cross-sectional area of the PE conductor in mm2, I is the fault current, t is the operating time of the protective device and k is a coefficient that depends on the metal and insulation material used for the conductor. bb Recommendation: if insulation monitoring is provided using the Vigilohm System, install a type A toroid on the Cardew earthing circuit in order to monitor operation of the Cardew. The toroid can be connected to an XD301/312 detector or an XL308/316 or XML308/316 locating device. Un: ph-ph operating voltage of AC installation Ui arcing voltage Neutral distributed U y 380 V 380 V < U y 660 V 660 V < U y 1000 V 1000 V < U y 1560 V Neutral not distributed U y 220 V 220 V < U y 380 V 380 V < U y 660 V 660 V < U y 1000 V 400 V < Ui y 750 V 700 V < Ui y 1100 V 1100 V < Ui y 1600 V 1600 V < Ui y 2400 V Cardew C “type” “250 V” “440 V” “660 V” “1000 V” 35 Vigilohm auxiliaries Accessories 019303_SE_20 Accessories for various installations The ZX is not mandatory. The ZX prevents variation of potential so is useful if there is sensitive low-power equipment placed close to the MV/LV transformer, e.g. modem power supplies. DB127951 ZX limiting impedance subassembly L3 L2 L1 N MV/LV 1 ZX Connection bb Creates an installation with an impedance earthed neutral. bb Remains connected during fault locating at 2.5 Hz: vv 1500 Ω at 50 Hz vv 1M Ω at 2.5 Hz. bb U y 500 V AC. IMD 2 Dimension, mounting 1 2 DB127917 Weight: 3.500 kg 360 380 190 170 185 4 Ø8.2 15 Commercial reference: 50159 044139_SE_30 Page 36 additional subassembly PHT1000 DB127952 Connection MV/LV bb For use with Vigilohm System XM300C and XML308/316 on the following installations: 2 vv 440 V AC y U y 1000 V AC neutral not We are missing 3the IM400 PHT between the last of PHT1000 accessible 1 vv 760 V AC y U y 1700 V AC neutral, 14 section and the13PHT1000 XM accessible 22 dimensions vv 500 V DC y U y 1200 V DC: installation. Connection Connection bb For use with Vigilohm IM400 and fault For uselocation with Vigilohm andinstallations: fault on theIM400 following location on the following vv 480 V AC y Uinstallations y 1000 V AC: neutral 480VAC U <= 1000VAC neutral not not<= accessible accessible vv 830 V AC y U y 1700 V AC neutral 830 V accessible AC <= U <= 1700VAC neutral accessible vv 480 V DC y U y 1200 V DC 480VDC <= U <= 1200VDC Dimension, mounting DB127918 Weight: 2 kg 4 holes Ø7 110 Schneider Electric - Division - Name – Date 200 30 220 184 26 150 36 80 Vigilohm auxiliaries PB106376_32 Selection table HV-IM20 additional subassembly Connection bb For use with Vigilohm System IM20 on the following installations: vv 600 V AC y U y 1700 V L-L AC neutral accessible vv 440 V AC y U y 1000 V L-L AC neutral not accessible vv 345 V DC y U y 1000 V DC It is recommended to have the subassembly close to the IM20 (max 3m) Dimension, mounting Weight: 0.2 kg 440 V~ < U < 1000 V ~ L-L (injection on phase) 600 V~ < U < 1700 V ~ L-L (injection on neutral) 345 VDC~ < U < 1000 V DC ≤ 3m 6A 1 2 3 1 IM20-1700 Cardew C 2 IM20 4 3 Wiring diagram PB106376_32 Commercial reference: IMD-IM20-1700 HV-IM400 additional subassembly Connection bb For use with Vigilohm System IM400 on the following installations: vv 830 V AC y U y 1700 V L-L AC neutral accessible vv 480 V AC y U y 1000 V L-L AC neutral not accessible vv 480 V DC y U y 1000 V DC It is recommended to have the subassembly close to the IM400 (max 3m) Dimension, mounting Weight: 0.2 kg 480 V~ < U < 1000 V ~ L-L (injection on phase) 830 V~ < U < 1700 V ~ L-L (injection on neutral) 480 VDC~ < U < 1000 V DC ≤ 3m 6A 1 Cardew C 2 3 IM400-1700 1 2 IM400 4 3 Commercial reference: IMD-IM400-1700 Wiring diagram Selection of auxiliaries - some are required for Vigilohm installations, some are optional b Essential auxiliary v Optional auxiliary Vigilohm XM300C / XML308 / XML316 U < 760 V AC (3) 760 to 1700 V AC (3) U < 440 V AC (4) 440 to 1000 V AC (4) U < 500 V DC (5) 500 to 1200 V DC (5) IM400 IM10 IM20 IM9 Commercial references “250 V” Cardew C (1) or b (7) b (7) b (7) b (7) 50170 “440 V” Cardew C (1) or b (7) b (7) b (7) b (7) 50171 “660 V” Cardew C (1) or b (7) b (7) b (7) b (7) b (7) b (7) v b (7) v b (7) v “1000 V” Cardew C (1) or Cardew C base v PHT1000 additional subassembly v v bj v (6) 50169 IMD-IM20-1700 v (8) IM400-1700 subassembly ZX limiting impedance v v (2) IM20-1700 subassembly 50172 50183 IMD-IM400-1700 v v 50159 50248 (1) See choice of the type of Cardew C (250, 440, 600 or 1000 V). (2) Required for IM20 used on installation with U > 440 V (neutral not accessible) or U> 600 V (neutral accessible). (3) Neutral distributed. (4) Neutral not distributed. (5) DC installation. (6) When fault location is needed or 1000 V DC < U ≤ 1200 V DC, the PHT1000 is used instead of IM400-1700. (7) Cardew C not required for DC installation (8) Required for IM400 used on installation with U > 480 V AC (neutral not accessible) or U > 830 V AC (neutral accessible) or U > 480 V DC 37 Accessories HRP PB105943_58 Hospital Remote Panel Presentation This accessory provides the interface for an electrical installation monitoring system in hospitals. Installed in the operating theatre, the Vigilohm HRP informs hospital personnel, in real time, of correct operation or the presence of a fault: bb faulty insulation of operating theatre equipment bb electrical fault following a circuit breaker trip or transformer overload. Use bb Insulation fault signal light (orange). bb Electrical fault signal light (red). bb Correct operation signal light (green). bb Push button to test installation insulation. bb Push button to stop alarm buzzer. Vigilohm HRP Mechanical characteristics Weight Case 0.5 kg Plastic Degree of protection Vertical mounting IP54 IK08 Dimensions Buzzer Height 170 mm Width 170 mm Depth 20 mm Factory setting 80 db 24 V DC 65 mA Electrical characteristics Auxiliary supply voltage Environment Operating temperature 0 °C to 40 °C Storage temperature -25 °C to +70 °C Maximum relative humidity 90 % Altitude 2000 m Standards Complies with IEC 60364-7-710 Medical locations IEC 61557-8 Electrical safety IEC 60601-1 Medical electrical equipment Tested with Anios products (disinfection, antiseptis and detergency products). Commercial reference: 50168. PB105945 Functions identification Visual alarm on insulation fault Right operation lamp isual alarm on electrical fault (overload or overheating transformer or circuit-breaker V fault tripping) est button of the insulation monitoring system (daily test in compliance with T IEC 60364-7-710 standard) udible alarm stoppage, in case of insulation fault or electrical fault. The alarm A volume setting is made at the mounting phase (available in the rear) 38 DB127897 HRP and IM10-H or IM20-H Example architecture 1 using IM10-H and HRP CPI Cabinet 2 CPI Cabinet 1 Electrical fault Insulation fault This monitoring system makes it possible, with the Vigilohm HRP in the operating room, to gather and display information concerning the alarms generated by the electrical installation. Electrical fault Vigilohm Insulation HRP fault IM10-H Vigilohm HRP 1 wire electrical fault (CB fault tripping or transformer overload) HRP 2 wires (NC Contact) 2 wires (N, Earth) 2 wires (+24 V 0 V) ABL8MEM24003 DB127898 Existing or specific power supply Ex: ABL8MEM24003 Example architecture 2 using IM20-H the HRP in the operating room and a global supervision The Modbus communication provides the nurses' room, and/or the maintenance personnel: bb insulation value bb transformer load level bb alarms bb timestamping of events. This enables event traceability. IM20-H Supervision 4 wires Modbus 3 wires (common, insulation fault, transformer monitoring) HRP 2 wires (+24 V 0 V) ABL8MEM24003 Existing or specfic power supply Ex: ABL8MEM24003 39 Installation and connection Dimensions and connections Product dimensions IM9, IM9-OL Cutout DB127905 Mounting on symmetrical DIN rail 2 Ø3.85 = 45 90 46.5±0.3 85 66±0.3 = 61±0.3 = = 71 44 67.5 72.5±0.4 IM10, IM20, IM10-H, IM20-H Cutout DB127906 Mounting on symmetrical DIN rail 96 110 93.7 92.4±0.4 45 96 46.3 92.4±0.4 59 IM400 Cutout ?????? 90 73 159 112 101 110 123 4-RS DB127938 Flush mounting 143.4 XM300C, XL308, XL316 Cutout DB127899 DB127938 Flush mounting 112 129 153 9.5 12 192 XD301, XD312 65 Cutout Surface mounting XD301 2 Ø4.2 46 45 XD312 2 Ø4.2 66 46 6.5 37.5 49.5 73.5 XD301 XD312 5 57 73 DB127937 DB127936 Flush mounting XD301 2 Ø4.2 66 7 81 81 66 10 93 110 4.5 40 XD312 2 Ø4.2 57 72 66 1 6.5 93 106 7.5 XLI300, XTU300 Cutout DB127939 DB127900 Flush mounting 129 112 76 9.5 192 8 71.5 XD308C DB127939 Cutout DB127901 Flush mounting 129 112 76 9.5 192 8 71.5 XML308, XML316 DB127940 Cutout DB127902 Flush mounting 129 229 12 9.5 192 XRM + probes DB127941 DB127903 XRM manual receiver Inside dimensions: XP15: 12 mm XP50: 50 mm XP100: 100 mm 145 37 80 XP15, XP50 and XP100 probes. 41 Installation and connection Dimensions and connections Product dimensions DB127904 XGR 59 189 108 HRP DB127908 DB127907 Flush mounting 130 40 min. H Test W D H 170 mm W D Weight 170 mm 20 mm 0.5 kg Ø50 min. Ø80 max. 2 2 (1) 1 (1) Support in nonflammable material: concrete, plasterboard, stainless steel... 42 Toroids (type A and OA) Flush mounting DB127920 Types A Ø80 to Ø300 2 Ø4.5 16 F Ø Ø5 123 DB127919 Type A Ø30 and Ø50 F H E G K B D 8 J E 4 21 B 5 Ø C Type C D L 29 Ø B C D E F TA30 30 31 60 53 82 50 PA50 50 45 88 66 108 60 Ø B C D E F G H J K L IA80 Type 80 122 26.5 35 150 80 55 40 126 65 44 MA120 120 164 26.5 35 190 80 55 40 166 65 44 SA200 196 256 29 37 274 120 90 60 254 104 46 GA300 291 360 28 37 390 120 90 60 369 104 46 DB127922 Type A Ø30, type OA Ø46 and Ø110 Ø5 B Ø L Type H Ø H L B POA 46 38 148 57 GOA 110 44 224 76 Mounting examples for Type A torids On plate or section Type A Ø30 to Ø200 mm 042591_SE_45 On rail Ø30 to Ø80 mm 042593_SE_45 044666_SE_42 On XD301 detector Ø30 to Ø50 On cable Ø120 to Ø300 mm 43 Installation and connection Dimensions and connections Product connection U y 600 V a L-N DB127954 PB106370_32 IM9 P+N L1 N A 3P U y 480 V a L-L L1 L2 L3 A 3P+N U y 600 V a L-L 10 L1 L2 L3 N 6A 110...415 Va A 6A A PB106371_32 DB127955 IM9-OL U y 690 VaL-L 2P/3P U y 690 V a L-L 3P 12...24 Vc 6 A y 250 Va 6 A KM1 6A 12...24 Vc 6 A y 250 Va 6 A KM1 6A 6A 6A - KM3 110...415 Va 6A 6A 110...415 Va U1 V1 W1 L1 L2 L3 - KM1 M 3a - F1 L1 L2 L3 - F1 - KM1 - KM2 U1 V1 W1 U2 V2 W2 M1 3a U1 V1 M 1a R y 10 kΩ 3xR - KM4 PB106374_32 DB127956 IM10, IM20 P+N U y 480 V a max. 3P U y 480 V L-L a max. L1 3P+N U y 600 V L-L a max. L1 L2 L3 N L1 L2 L3 N A B — max. DC U y 345 V --- C D A B C D 110...415 Va 6A 6A 1 2 3 6 7 8 Failsafe wiring 12...24 Vc 6 A y 250 Va 6 A 44 6A 11 12 13 14 15 16 u 5 mA 24 V c Standard wiring 6 7 8 4 5 6 7 8 12...24 Vc 6 A y 250 Va 6 A 11 to 16: IM20 only 6A 0V D0 = A’ / Rx-, A / TxD1 = B’ / Rx+, B / Tx+ PB106375_32 DB127957 IM10-H L U 110....230 Va N 6A 6A 1 2 3 4 5 6 7 8 Relay setting: Failsafe (recommended) Relay setting: Standard IM 10-H IM 10-H 6 7 8 6 7 8 Vigilohm HRP Vigilohm HRP DB127957 044147_SE_32 IM20-H L U 110....230 Va N IT transformer Page 43 2/3: bimetal contact 24 VDC 5mA EN & FR 6A 6A 1 2 3 6 7 8 Output setting: Failsafe 6 3 Vigilohm 2 HRP 1 24 VDC 5 mA 4 5 Shorting block For the IM20-H part 9 10 1112 13141516 0V IM20-H 7 8 Optional: Circuit Breaker Auxiliary Contacts D0 = A’ / Rx-, A / TxD1 = B’ / Rx+, B / Tx+ Modbus RS 485 Am I to creat this image or does it exist somhere? (NC contacts) 45 Dimensions and connections 044147_SE_32 IM400 46 Installation and connection Product connection Installation and connection Dimensions and connections Product connection DB400264 XM300C 12 11 10 9 8 7 6 5 4 ut ut Tunnel terminals for 1.5 mm² wiring fault (failsafe feature) 1 adress 1 fault 4 prevention 21 Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz ut: application r: installation terminal 13: earth connection by round lug (4 mm diameter) to be crimped. *connection supplied with PHT1000. 2 1 aa 13 23 20 24 19 18 17 16 15 14 22 I1 I2 VB V+ S DB127926 r 12 fault (failsafe feature) 11 DB127925 044148_SE_32 XM300C 3 2 1 N MT/BT 10 9 ut 8 14 fault cardew C 7 XM300C 13 6 5 3 MT/BT 4 2 1 14 cardew C XM300C 13 + 14 XM300C DB127961 13 23 * aa 2 1 13 14 22 XM300C PHT1000 24 18 17 16 15 VB V+ S 1 2 3 r 47 DB400265 044149_SE_60 XML308, XML316 ut ut 12 11 10 9 8 7 6 5 4 XML308 XML316 fault (failsafe feature) 21 1 1 fault 4 21 20 24 19 Tunnel terminals for 1.5 mm² wiring Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz ut: application r: installation terminal 13: earth connection by round lug (4 mm diameter) to be crimped. *connection supplied with PHT1000. aa 2 1 13 18 17 16 15 14 22 t1 2 1 I1 I2 VB V+ S t8 21 2 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2 9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2 prevention 23 t16 t9 1 address 12 11 fault (failsafe feature) DB127927 DB127926 r 3 2 1 N MV/LV 10 9 ut 8 fault 14 cardew C 7 XML316 13 6 5 4 3 MV/LV 2 1 14 cardew C XML316 13 + 14 XML316 13 48 Installation and connection Dimensions and connections Product connection DB127928 044144_SE_32 XD301 t 5 6 XD301 Tunnel terminals for 1.5 mm² wiring 7 8 9 10 11 aa ut Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA DB127929 044144_SE_32 XD312 n° 1 n° 2 n° 12 1 2 3 4 5 6 7 8 9 1011 12 XD312 Tunnel terminals for 1.5 mm² wiring 15 16 21 22 23 26 ut aa Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA DB127930 044143_SE_32 XD308C aa 1 2 t1 t8 XD308c V B V+ S Tunnel terminals for 1.5 mm² wiring 3 4 5 6 7 8 9 10 11 1 adress 4 8 Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz t: toroid A or OA 49 DB126931 044145_SE_60 XL308, XL316 fault (failsafe feature) 12 11 10 9 8 7 6 5 4 ut 1 2 1 1 address 3 1-1 1-2 2-1 2-2 3-1 3-2 4-1 4-2 5-1 5-2 6-1 6-2 7-1 7-2 8-1 8-2 9-1 9-2 10-1 10-2 11-1 11-2 12-1 12-2 13-1 13-2 14-1 14-2 15-1 15-2 16-1 16-2 fault 2 1 aa XL308 XL316 t1 t8 2 1 21 2 t16 t9 8 13 18 17 16 15 VB V+ S Legend aa: AC auxiliary supply a 15 %, +10 %, 50-60 Hz ut: application t: toroid A or OA terminal 13: earth connection by round lug (4 mm diameter) to be crimped. *connection supplied with PHT1000. DB127926 Tunnel terminals for 1.5 mm² wiring 12 11 fault (failsafe feature) 10 9 ut 8 fault 7 6 5 4 a.a DB126933 DB126932 DB127890 XGR MV/LV 3 2 1 N CPI XGR XGR r + DB127934 Legend aa: auxiliary supply r: installation CPI 50 XGR Installation and connection Dimensions and connections Product connection DB127949 XLI300, XTU300 bb Never connect more than one interface to the Vigilohm System bus. bb To connect devices to the communication bus (shielded, double twisted pair) it is recommended to interconnect their respective terminals S, B, V+ and V-. 18 V17 B not used XLI300 Sub D9 16 V+ 1 6 5 9 RS485 15 S 1 signal ground 4 received data 5 transmitted data - RS482 8 received data + 1 6 9 5 1 : GND 4 : B'(RD-) 5 : B(TD-) 8 : A'(RD+) 9 : A(TD+) 9 transmitted data + 2 aa 1 RS485 13 DB127935 Example of line connection VXM300c B V+ S XL308 XL316 V- V- V- B B B XD308c V+ V+ S S XML308 XML316 VXLI300 XTU300 XAS V+ S B V+ S DB127909 PB105943_42 HRP 6 2.5 mm² max. 1 34 V c 14.5 mA 2 3 4 5 Electrical fault Common 34 V c 14.5 mA Insulation fault +24 V c 65 mA 0V c Auxiliary power supply 6 7 N 51 Commercial references Vigilohm insulation monitoring Vigilohm commercial references Reference 110/415 V AC 50/60 Hz IMD-IM9 PB106370_15 Auxiliary supply voltage IM9-OL Off-line insulation monitoring device PB106374_15 Product IM9 Insulation monitoring device IM10 & IM20 Insulation monitoring devices IM9 IM9-OL 044147_SE_20 IM400 044148_SE_20 IM10-H & IM20-H XM300C 110/415 V AC 50/60 Hz IMD-IM9-OL IM10 110/415 V AC 50/60 Hz IMD-IM10 IM20 110/415 V AC 50/60 Hz IMD-IM20 Insulation monitoring devices for hospitals IM10-H 110/240 V AC 50/60 Hz IMD-IM10-H IM20-H 110/240 V AC 50/60 Hz IMD-IM20-H 110/440 V AC/DC 50/60/400 Hz IMD-IM400 XM300C 115/127 V AC 50/60 Hz 50540 XM300C 220/240 V AC 50/60 Hz 50541 XM300C 380/415 V AC 50/60 Hz 50542 XML308 115/127 V AC 50/60 Hz 50490 XML308 220/240 V AC 50/60 Hz 50491 XML308 380/415 V AC 50/60 Hz 50492 XML316 115/127 V AC 50/60 Hz 50322 XML316 220/240 V AC 50/60 Hz 50323 XML316 380/415 V AC 50/60 Hz 50324 Insulation monitoring device IM400 044149_SE_30 XML308 & XML316 044144_SE_20 XD301 & XD312 044143_SE_12 XD308C 044145_SE_22 XL308 & XL316 52 Insulation monitoring device Monitoring-locating devices Automatic insulation fault detectors XD301 115/127 V AC 50/60 Hz 50506 XD301 220/240 V AC 50/60 Hz 50507 XD301 380/415 V AC 50/60 Hz 50508 XD312 115/127 V AC 50/60 Hz 50535 XD312 220/240 V AC 50/60 Hz 50536 XD312-H 220/240 V AC 50/60 Hz 50536-H XD312 380/415 V AC 50/60 Hz 50537 Communicating automatic insulation fault detector XD308C 115/127 V AC 50/60 Hz 50723 XD308C 220/240 V AC 50/60 Hz 50724 XD308C 380/415 V AC 50/60 Hz 50725 XL308 115/127 V AC 50/60 Hz 50606 XL308 220/240 V AC 50/60 Hz 50607 XL308 380/415 V AC 50/60 Hz 50608 XL316 115/127 V AC 50/60 Hz 50615 XL316 220/240 V AC 50/60 Hz 50616 XL316 380/415 V AC 50/60 Hz 50617 Insulation fault locators Commercial references Vigilohm insulation monitoring Vigilohm commercial references 051350_SE_10 Product XGR & XRM & probes Voltage range Kit case: XGR (50282) + XRM + XP15 + XP50 + XP100 50310 Toroids Auxiliaries (2) 50278 XGR 115/127 V AC 50/60 Hz 50281 XGR 220/240 V AC 50/60 Hz 50282 XGR 380/415 V AC 50/60 Hz 50283 XP15 probe 50494 XP50 probe 50498 XP100 probe 50499 Empty case 50285 Communication interfaces XLI300 115/127 V AC 50/60 Hz 50515 XLI300 220/240 V AC 50/60 Hz 50516 XLI300 380/415 V AC 50/60 Hz 50517 XTU300 220/240 V AC 50/60 Hz 50546 (1) XTU300 380/415 V AC 50/60 Hz 50547 (1) Earth leakage current detectors TA30 50437 PA50 50438 IA80 50439 MA120 50440 SA200 50441 GA300 50442 Open POA 50485 Open GOA 50486 100 m cable (shielded) 50136 Accessories for various installations 250 V Cardew C 50170 440 V Cardew C 50171 660 V Cardew C 50172 1000 V Cardew C 50183 Cardew C base 50169 HV-IM20-1700 subassembly IMD-IM20-1700 HV-IM400-1700 subassembly IMD-IM400-1700 ZX limiting impedance 50159 PHT1000 additional subassembly 50248 HRP 50168 PB105943_22 044139_SE_18 041857_SE_10 042589_SE_20 051352_SE_25 044141_SE_15 PB100471_SE_25 XRM XLI300 & XTU300 Reference Mobile fault locating (1) Please consult Schneider Electric for configuration. (2) See choice of Cardew on page 33 and auxiliary selection table on page 35. 53 54 35, rue Joseph Monier CS 30323 F- 92506 Rueil Malmaison Cedex RCS Nanterre 954 503 439 Capital social 896 313 776 € www.schneider-electric.com PLSED310020EN ART838019 © 2013 - Schneider Electric - All rights reserved Schneider Electric Industries SAS As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printing: Altavia Connexion - Made in France 01-2013
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertising