857-560 JUMPFLEX® Signal Conditioners Voltage Signal Conditioner

857-560 JUMPFLEX® Signal Conditioners Voltage Signal Conditioner
857-560
JUMPFLEX® Signal Conditioners
Voltage Signal Conditioner
<_________ 97,8 mm/3.85 in. _______>
Special Functions
<_________ 94 mm/3.68 in. _________>
Short description:
The Voltage Signal Conditioner measures AC and DC voltages up to 300 V AC/DC and
converts the input signal into an analog standard signal at the output.
Features:
• Two isolated measurement inputs for 30 V and 300 V AC/DC
• True RMS measurement or arithmetic mean value
• A digital signal output reacts to configured measuring range limits (switching ON/OFF
delay and threshold value switch function configurable with up to two threshold values)
• Switchable filter function
• Safe 3-way isolation with 3 kV test voltage per EN 61010-1
Technical Data
Configuration
Configuration
Input
Input Signal
Response threshold
Input resistance
Frequency range
Overload capacity
Resolution
Output
Output signal
Load impedance
Output – Digital
Max. switching voltage
Max. continuous current
General specifications
Nominal supply voltage US
Supply voltage range
Current consumtion at 24 VDC
Measuring procedure
Max. operating frequency
Response time typ. signal cycle
duration
Response time (T10-90)
Temperature coefficient
Linearity error
Measurement error
Conformity marking
Standards/Approvals
WAGO Kontakttechnik GmbH & Co. KG
subject to design changes
_>
_>
____________
Configuration via
6 mm/0.23 in.
Description
Item No.
JUMPFLEX® Voltage Signal Conditioner, current input signal for AC and DC
voltages, current and voltage output
signal, digital output, configuration via
software/DIP switch, supply voltage 24
VDC, width 6 mm
857-560
Pack.
Unit
1
Technical Data
DIP switch, interface configuration software, interface configuration app
300 V AC/DC oder 30 V AC/DC
IN 1: 300 mV, IN 2: 30 mV
> 300 kΩ
AC 10 … 100 Hz
IN 1: 600 V; IN 2: 60 V (permanent)
IN 1: 30 mV, IN 2: 3 mV
(+/−)0 … 20 mA, 4 … 20 mA,
(+/−0 … 10 mA, 2 … 10 mA
(+/−)0 … 10 V, 2 … 10 V,
(+/−0 … 5 V, 1 … 5 V
≤ 600 Ω (I output);
≥ 1 kΩ (U output)
Envronmental Requirements
Ambient operating temperature
Storage temperature
Safety and Protection
Test voltage
(input/output/supply)
Protection type
Connection and type of mounting
Wire connection
Cross sections
Solid
stranded
Strip length
Dimensions and Weight
Dimensions (mm) W x H x D
Weight
-40 … +70 °C
-40 … +85 °C
AC 3 kV, 50 Hz, 1 min
IP20
Push-in CAGE CLAMP®
0.08 … 2.5 mm² / 28 … 14 AWG
0.34 … 2.5 mm² / 22 … 14 AWG
9 … 10 mm / 0.35 … 0.39 inch
6 x 97,8 x 94, Height from upper-edge of DIN 35 rail
55 g
Supply voltage applied
100 mA
24 VDC
US -30 … +30 %
46 mA + IDO
Effective value (RMS) or arithmetic
mean value
2 kHz
1 ms
60 ms
≤ 0.01 %/K
≤ 0.1 %
< 0.5 %
1
EN 61010-1, EN 61326-1
28.09.2016
Postbox 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0
Fax: +49(0)571/887-169
E-Mail: info@wago.com
www.wago.com
857-560
DIP Switch Adjustability
● = ON
DIP Switch S1
1
2
Input
3
300 V
●
●
●
Measuring Method
4
RMS
150 V
●
Filter
O
Arithmetic mean value
●
Active
30 V
●
15 V
DIP Switch S1
5
6
7
Output Signal Range
(+/-) 0 ... 20 mA
●
4 ... 20 mA
●
●
(+/-) 0 ... 10 V
●
2 ... 10 V
●
●
●
●
●
(+/-) 0 ... 10 mA
●
2 ... 10 mA
●
(+/-) 0 ... 5 V
●
1 ... 5 V
DIP Switch S1
8
9
●
●
Measuring Range Under ow
Measuring Range Over ow
Lower limit of measuring range
-5 %*
Upper limit of measuring range +2.5 %*
Lower limit of measuring range
Upper limit of measuring range +2.5 %
●
Lower limit of measuring range
Upper limit of measuring range
●
Lower limit of measuring range
Upper limit of measuring range
10
Digit Output DO/
Signaling
DO Vs+ switching
●
DO GND switching
*
per NAMUR NE 43
Filter
The lter function allows a low-pass lter to be switched on in order to mask
or “smooth out” oscillating measured values (e.g., during trailing edge ows).
Default Setting
All DIP switches are in “OFF“ position for delivery.
Input
Digital Output DO/Signaling
Input
300 V
The digital output (DO) signals error messages and can be congured as
follows:
24 V → 0 V/0 V → 24 V.
Measuring Method
RMS
Filter
O
Output
Output Signal
0 ... 20 mA
Measuring Range Underow
0 mA
Measuring Range Overow
20.5 mA
Overcurrent
21 mA
Digital Output DO
Vs+ switching