Universal converter

Universal converter
Universal converter
9116B
– Input for RTD, TC, Ohm, potentiometer, mA and V
– Supply for 2-wire transmitters
– Active / passive mA output and relay output
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501); process calibration, signal and relay
simulation.
• Advanced relay configuration, e.g. setpoint, window, delay,
sensor error indication and power monitoring.
• Copying of the configuration from one device to others of the
same type via PR4501.
• Reduced Uo Ex data < 8.3 V for active input signals.
• TC inputs with internal CJC or external CJC for higher
accuracy.
• The device automatically detects whether it must supply an
active or a passive current signal.
Connections
Application
• 9116B can be mounted in the safe area and in zone 2 / cl. 1
div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21,
22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature, voltage,
potentiometer and linear resistance signals.
• Power supply and signal isolator for 2-wire transmitters.
• Monitoring of error events and cable breakage via the
individual status relay and/or a collective electronic signal via
the power rail.
• The 9116 has been designed, developed and certified for use
in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 1 red front LED indicate operation status and
malfunction. 1 yellow LED indicates relay status.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Short circuit detection.................................... Yes
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Screw terminal torque....................................
Vibration.........................................................
Vibration: 2...13.2 Hz.....................................
Vibration: 13.2...100 Hz.................................
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
185 g
200 g / 285 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
0.5 Nm
IEC 60068-2-6 : 2007
±1 mm
±0.7 g
Common specifications
Supply
Supply voltage............................................... 19.2...31.2 VDC
Isolation voltage
Test /working: Input to any............................. 2.6 kVAC / 300 VAC
reinforced isolation
Analog output to supply................................. 2.6 kVAC / 300 VAC
reinforced isolation
Status relay to supply..................................... 1.5 kVAC / 150 VAC
reinforced isolation
Response time
Temperature input, programmable
(0...90%, 100...10%)...................................... 1...60 s
mA / V input (programmable)......................... 0.4...60 s
Auxiliary supplies
9116B1: 2-wire supply (terminal
54...52)........................................................... 28...16.5 VDC / 0...20 mA
9116B2: 2-wire supply (terminal
54...52)........................................................... 22...16.5 VDC / 0...20 mA
Fuse............................................................... 1.25 A SB / 250 VAC
Max. power consumption............................... ≤ 3.5 W
Communications interface............................. Communication enabler 4511
/ Programming front 4501
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.1% of selected
range
Input specifications
Current input
Measurement range.......................................
Programmable measurement ranges............
Input resistance..............................................
Sensor error detection...................................
0...20 mA
0...20 and 4...20 mA
Nom. 20 Ω + PTC 50 Ω
Loop break 4...20 mA
Voltage input
Measurement range....................................... 0...10 VDC
Programmable measurement ranges............ 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance.............................................. Nom. >10 MΩ
Output specifications
Current output
Signal range................................................... 0...20 mA
Programmable signal ranges......................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability.................................................. ≤0.01% of span / 100 Ω
Sensor error indication................................... 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
Relay output
Relay functions.............................................. Setpoint, Window, Sensor
error, Power and Off
ON and OFF delay......................................... 0...3600 s
Sensor error reaction..................................... Break / Make / Hold
Max. voltage................................................... 250 VAC / 30 VDC
Max. current................................................... 2 AAC / 2 ADC
Max. AC power.............................................. 500 VA / 60 W
Status relay
Max. voltage................................................... 110 VDC / 125 VAC
Max. current................................................... 0.3 ADC / 0.5 AAC
Max. AC power.............................................. 62.5 VA / 32 W
2-wire 4…20 mA output: External
2-wire supply range........................................
Signal range...................................................
Max. load resistance [Ω]................................
Load stability, 4…20 mA output.....................
Effect of external 2-wire
supply voltage variation.................................
3.5...26 VDC
4…20 mA
(Vsupply - 3.5) / 0.023 A
≤ 0.01% of span / 100 Ω
< 0.005% of span / V
Approvals
EMC...............................................................
LVD 2006/95/EC............................................
ATEX 2004/108/EC........................................
IECEx.............................................................
EN 61326-1
EN 61010-1
KEMA 10ATEX0053 X
KEM 10.0022X
9116B-082615
RTD input
RTD type........................................................ Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100,
Ni120, Ni1000
Cable resistance per wire
(max.)............................................................. 50 Ω
Sensor current............................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire)....................................................... < 0.002 Ω / Ω
Sensor error detection................................... Programmable ON / OFF
TC input
Thermocouple type........................................ B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection................................... Programmable ON or OFF
(only wire breakage)
FM.................................................................. 3038267-C
INMETRO....................................................... NCC 12.1309 X
UL................................................................... UL 61010-1
EAC TR-CU 020/2011................................... EN 61326-1
EAC Ex TR-CU 012/2011.............................. RU C-DK.GB08.V.00410
CCOE............................................................. P337349/4
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
9116B-082615