User manual | Festo CTEU Fieldbus modules, CTEL Installation system Product details
Add to My manuals57 Pages
The CTEU fieldbus modules are a powerful solution for connecting valve terminals to a fieldbus. They offer a wide range of features, including a Festo-specific interface (I-Port), input modules for detecting sensor signals, cost savings, and universal connection technology. The CTEU is designed for universal use with valve terminals and can be used for different valve types. This allows you to create a more efficient and reliable automation system.
advertisement
Fieldbus modules CTEU/installation system CTEL
-V-
New
Fieldbus modules CTEU/installation system CTEL
Key features
The system
• Fieldbus modules CTEU for using valve terminals
• Festo-specific interface (I-Port)
• Input modules CTSL for detecting sensor signals
• Cost savings since less hardware is required for valve terminals with a large number of valves on the fieldbus
• Direct and simple networking of valve terminals and other devices via fieldbus
• Wide range of applications thanks to high protection to IP65/67
• Universal connection technology
(Sub-D, M12, terminal strip)
• Optional, decentralised installation of the bus node for connecting two valve terminals
• Basic diagnostics: undervoltage, short circuit
CTEU for universal use of valve terminals. The Festo-specific, uniformly defined interface (I-Port) enables the bus modules to be used for different valve types.
The following protocols are currently supported:
• CANopen
• DeviceNet
• CC-Link
• PROFIBUS
• EtherCAT
Valve terminal configurator
A valve terminal configurator is available online to help you select a suitable valve terminal.
Select the valve terminal with I-Port interface and order the associated bus node CTEU. The bus nodes then only need to be placed on the valve terminal.
The ident. code of the valve terminals specifies the valve functions, the number of valves, vacant positions as well as the additional functions and the type of compressed air supply.
As is the case with all Festo products, all valve terminals are supplied:
• Fully pre-assembled
• Equipped with fittings on request
Online via:
www.festo.com/us/engineering
• Tested for electrical function
• Tested for pneumatic function
• Securely packaged
• Manuals can be downloaded free of charge
2
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Key features
Fieldbus systems with CTEU
CANopen
A fieldbus system based on CAN.
Standardised by the "CAN in
Automation" (CiA) user group.
CANopen is characterised by its multi-master capability and high protocol efficiency. It is used throughout industrial automation.
DeviceNet
An open fieldbus system based on
CAN technology originally developed for the automotive sector. DeviceNet was developed by Rockwell
(Allen-Bradley) and is now an open standard. It is frequently used in
OMRON controllers.
CC-Link
"Control and Communications Link"
(CC-Link) was developed by Mitsubishi
Electric and has been available as an open fieldbus network since 1999.
-V-
New
PROFIBUS
Process fieldbus (PROFIBUS) is a fieldbus developed by Siemens and standardised in the IEC 61158 series of international standards that enables communication between devices without the need for any specific interface adaptations.
EtherCAT
EtherCAT was developed by Beckhoff and the EtherCAT Technology Group
(ETG). EtherCAT is an open technology that is standardised in the international standards IEC 61158 and IEC 61784 as well as in
ISO 15745-4. It is a high-speed industrial Ethernet system that is also suitable for use in time-critical motion control applications.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
3
-V-
New
Fieldbus modules CTEU/installation system CTEL
Key features
Classification of the I-Port interface/IO-Link
Different bus nodes are used for integration into the control systems of various manufacturers.
The following protocols are supported with the compatible node CTEU:
• CANopen
• DeviceNet
• EtherCAT
• CC-Link
• PROFIBUS
System overview, example
PLC
Fieldbus
Node CTEU
(I-Port master) on adapter CAPC
A second valve terminal can be
connected via a decentralised adapter
(
page 5).
CPX terminal with fieldbus node and CTEL master
Valve terminal VTUB-12 with fieldbus node CTEU
Valve terminal CPV with I-Port interface/IO-Link
IO-Link/I-Port
Input module CTSL
4
Pneumatic drive
• Communication with higher-level controller via fieldbus
• Use the fieldbus node CTEU compatible with the fieldbus protocol
Pneumatic drive with sensor
• Up to 64 inputs/outputs (solenoid coils), depending on the valve terminal
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Peripherals overview
Overview of CTEU with valve terminal VTUG
7
8 aJ aA
6
9
5
6 aB
5 aC aD
4
2 aE aF
3
1
Accessories
1 Manifold rail
2 Adapter
3 H-rail adapter
4 Connecting cable
5 Bus node
6 Inscription label
7 Power supply socket
8 Terminal strip
9 Bus connection aJ Fieldbus socket aA Plug aB Bus connection aC Plug aD Plug aE Threaded sleeve aF Input module
Type
VABM
CAPC
CAFM
NEBU
CTEU
ASLR
NTSD
FBSD-KL
FBA-1
FBSD-GD, NECU
FBS, NECU
FBA-2
FBS-SUB-9-BU
FBS-SUB-9-WS
UNC
CTSL-D-16E
Brief description
With I-Port interface, for connecting max. 35 valves
For connecting a further terminal (2 x I-Port interfaces)
For adapter CAPC
For IO-Link
–
For bus nodes
For power supply
For Open Style connection
Open Style for 5-pin terminal strip
For Micro Style connection, M12, 5-pin
For Micro Style connection, M12, 5-pin
Micro Style, 2xM12, 5-pin
Sub-D
Sub-D, angled
Sub-D mounting bolt
–
-V-
New
Page/Internet vtug
aslr
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
5
-V-
New
Fieldbus modules CTEU/installation system CTEL
Key features – Diagnostics
CTEU system diagnostics
Diagnostic LEDs on the fieldbus node CTEU
The fieldbus-specific LEDs indicate the communication status and the fieldbus function.
A further LED indicates the status of the power supply:
• Undervoltage/short circuit
• Power supply guaranteed
• Interruption of voltage
Diagnostic messages via the fieldbus
• Configuration error
• Short circuit/overload of output module
• Short circuit/undervoltage
• Undervoltage/load voltage of valves
1
Fieldbus
2
5
4
3
1 Diagnostics via fieldbus
2 Bus-specific LEDs
3 Switching position display via one LED per valve (on the manifold rail)
4 Additional communication and voltage status LED for decentralised installation
5 I-Port interface with the fieldbus module
6
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Key features – Power supply
Operating voltage and load current supply
The operating voltages for the valve terminal with I-Port interface are centrally connected via a 5-pin M12 plug on the bus node.
The operating voltages are required for the electronics of the fieldbus node and the load supply for the valves
(supplied separately from the electronics supply).
The power supplies do not have a common 0 V and are therefore
Example of the power supply concept for the CTEU with valve terminal VTUG completely galvanically isolated from each other.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
7
-V-
New
Fieldbus modules CTEU/installation system CTEL
Key features – Power supply
Power supply concept
Example of the power supply concept for the CTEU with decentralised adapter CAPC and valve terminal VTUG
8
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – I-Port interface/IO-Link of the valve terminal VTUG
Festo-specific, standardised interface for direct connection to the fieldbus by mounting the bus node CTEU or to an IO-Link master via a cable (in
IO-Link mode).
I-Port interface/IO-Link
Versions:
• I-Port interface for fieldbus nodes
(CTEU)
• IO-Link mode for direct connection to a higher-level
IO-Link master
The electrical supply/transmission of communication data takes place via an M12 plug.
The following protocols are supported:
• CANopen
• DeviceNet
General technical data
Communication types
Electrical connection
Baud rates COM3
COM2
Intrinsic current consumption, logic supply PS
Intrinsic current consumption, valve supply PL
Max. number of solenoid coils VAEM-L1-S-8-PT
Max. number of valve positions
VAEM-L1-S-16-PT
VAEM-L1-S-24-PT
VAEM-L1-S-8-PT
VAEM-L1-S-16-PT
VAEM-L1-S-24-PT
Ambient temperature
Protection class to EN 60529
LED display
Status LED X1
Colour Status
4
5
Red/green Off
2 Status green
3 Flashing green
Flashing red/green
Static red
Pin allocation – I-Port interface/IO-Link
4
5
2
3
Pin
1
Allocation
24V
EL/SEN
24V
VAL/OUT
0V
EL/SEN
C/Q
0V
VAL/OUT
[
IO-Link
• M12 plug, 5-pin
• A-coded
• Metal thread for screening
[kbps] 230.4
[kbps] 38.4
[mA] 30
[mA] 30
16
32
48
8
16
°C]
24
–5 … +50
IP67
Function
• CC-Link
• PROFIBUS
• EtherCAT
No 24 V logic
Everything OK
Communication error (in the I-Port or IO-Link protocol)
Load supply fault (undervoltage or no load supply)
Load supply fault and communication error
Description
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Data communication
Load voltage supply (valves/outputs)
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
9
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – I-Port interface/IO-Link of the valve terminal VTUG
Dimensions
Outlet on top Outlet on side
Download CAD Data
www.festo.com/us/cad
Type
VAEM-L1-S-…
B1
91
Outlet on top
L1
47.1
Accessories – I-Port interface/IO-Link
Description
Electrical interface for I-Port interface/IO-Link, outlet on top
Actuation of up to 8 double solenoid valve positions
Actuation of up to 16 double solenoid valve positions
Actuation of up to 24 double solenoid valve positions
Electrical interface for I-Port interface/IO-Link, outlet on side
Actuation of up to 8 double solenoid valve positions
Actuation of up to 16 double solenoid valve positions
Actuation of up to 24 double solenoid valve positions
Connection technology for I/O-Link
T-adapter M12, 5-pin for IO-Link and load supply
H1
25
Straight plug, for I-Port/IO-Link
Straight plug, M12, 5-pin
(in combination with adapter for separate load supply)
Inscription label for I-Port/IO-Link
40 pieces in frame
Connecting cable
B1
91.5
Outlet on side
L1
47.1
Part No.
Type
573384
573939
573940
VAEM-L1-S-8-PT
VAEM-L1-S-16-PT
VAEM-L1-S-24-PT
574207
574208
574209
VAEM-L1-S-8-PTL
VAEM-L1-S-16-PTL
VAEM-L1-S-24-PTL
171175 FB-TA-M12-5POL
L2
10
175487 SEA-M12-5GS-PG7
565306 ASLR-C-E4
574321
574322
574323
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
10
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – E-box CAPC
Function
The E-box CAPC enables decentralised installation of fieldbus nodes CTEU on a valve terminal or input modules with I-Port interface.
Application
• M12 connection technology
(two interfaces)
• Enables installation of valve terminals or other devices over a distance of 20 metres
• Accessory CAFM enables the E-box to be installed on an H-rail
General technical data
Type
Dimensions W x L x H
Fieldbus interface
Operating voltage range
Max. power supply
Nominal operating voltage
Product weight
Cable length
Materials
Housing
Note on materials
[mm]
[V DC]
[A]
[V DC]
[g]
[m]
CAPC-F1-E-M12
24
85
20
50 x 148 x 28
2x M12 socket, 5-pin
18 … 30
2
PA reinforced
RoHS-compliant
Operating and environmental conditions
Protection class to EN 60529
Ambient temperature
Storage temperature
Corrosion resistance class CRC
CE marking (see declaration of conformity)
[°C]
[°C]
IP65, IP67
–5 … +50
–20 … +70
2
1)
To EU EMC Directive
2)
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
11
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – E-box CAPC
Dimensions
CAPC
Download CAD Data
www.festo.com/us/cad
CAPC with mounted fieldbus node CTEU-CO
Type
CAPC B1
148
B2
140
B3
32
Pin allocation – Power supply/IO-Link interfaces
Pin Allocation
1
2
3
24V
EL/SEN
24V
VAL/OUT
0V
EL/SEN
C/Q 4
5 0V
VAL/OUT
Housing, FE
Accessories – CAPC
Description
E-box
–
B4
6.6
B5
91
D1
-N-
4.4
H1
27.3
H2
20.3
H3
19.3
Part No.
H4
9.6
Description
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Data communication
Load voltage supply (valves/outputs)
Functional earthing
570042
Type
H5
5.7
H6
54.8
CAPC-F1-E-M12
L1
50
L2
40
H-rail mounting
–
Connecting cable
–
570043 CAFM-F1-H
574321
574322
574323
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
12
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CO
The bus node handles communication between the valve terminal and a higher-level CANopen
® master.
The module has basic diagnostic functions. It has 5 integrated LEDs for on-site display. Max. 8 byte inputs and 8 byte outputs are transmitted in the cyclic process image.
Application
Fieldbus connection
The bus connection is established via a 9-pin Sub-D plug (pin) as per the CAN in Automation (CiA) specification DS 102 with additional 24 V CAN transceiver supply (option as per DS 102).
Implementation
Protocol chip used:
• CAN transceiver 82C251
Baud rates supported:
• 125 kbps
• 250 kbps
• 500 kbps
• 1 Mbps
The bus connector plug (with protection class IP65/IP67 from
Festo or IP20 from other manufacturers) facilitates the connection of an incoming and an outgoing bus cable.
Max. CANopen cable length (trunk cable):
• 40 m at 1 Mbps
• 100 m at 500 kbps
• 250 m at 250 kbps
• 500 m at 125 kbps
There are 4 contacts each available for the conductors (CAN_L/CAN_H and 24 V/0 V optional) of the incoming and outgoing bus cables.
The fieldbus parameters and the basic device parameter settings are set on the bus node via DIL switches.
Max. branch line length (drop cable):
• 0.30 m at 1 Mbps
• 0.75 m at 500 kbps
• 2.00 m at 250 kbps
• 3.75 m at 125 kbps
The following variants can be realised using an adapter:
• 2x Micro Style M12, protection class IP65, 5-pin, socket and pin
• Open Style plug, protection class
IP20, 5-pin, pin
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
13
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CO
General technical data
Fieldbus interface
Protocol
Baud rates
Internal cycle time
Operating voltage
Intrinsic current consumption at nominal operating voltage
Max. power supply
Parameterisation
Max. address capacity, inputs
Max. address capacity, outputs
Additional functions
Operating elements
Configuration support
Device-specific diagnostics
LED display
Protection class to EN 60529
Note on materials
Housing materials
Product weight
Temperature range
Dimensions W x L x H
Corrosion resistance class CRC
CE marking
Certification
Nominal value
Permissible range
Fieldbus-specific
Product-specific
Environment
Storage
• Sub-D socket, 9-pin
• Sub-D plug, for self-assembly
• 2x M12x1, 5-pin
• Terminal strip, 5-pin
CANopen
[kbps] 125, 250, 500 and 1,000
[V DC]
[V DC]
[mA]
[A]
1 ms per 1 byte of user data
24
18 … 30
Typically 65
4
Diagnostic behaviour
Fail state
8 byte
8 byte
• Emergency message
• Acyclic data access via "SDO"
DIL switch
[g]
[°C]
EDS files
• System diagnostics
• Undervoltage
• Communication error
• MNS: Network status
• IO: I/O status
• PS: Operating voltage for electronics and load supply
• X1: System status of module at I-Port 1
• X2: System status of module at I-Port 2
IP65/IP67
RoHS-compliant
• PC
• PA reinforced
90
–5 … +50
[°C]
[mm]
–20 … +70
40 x 91 x 50
2
1)
To EU EMC Directive
C-Tick
2)
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
14
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CO
Dimensions
CTEU-CO
-V-
New
Download CAD Data
www.festo.com/us/cad
Type
CTEU-CO
Pin allocation
Sub-D, 9-pin, CANopen interface
Power supply, M12, B-coded
B1
91
H1
39.8
Pin Allocation
5
6
7
3
4
1
2
8
9
Housing n.c.
CAN_L
CAN_GND n.c.
CAN_Shld
GND
CAN_H n.c.
CAN_V+
3
4
5
1
2
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
0 V
VAL/OUT
FE
Description
Not connected
Received/transmitted data low
0 V CAN interface (connected to pin 6)
Not connected
Optional screened connection
0 V CAN interface, optional (connected to pin 3)
Received/transmitted data high
Not connected
24 V DC supply for CAN interface
Cable screen, connection to functional earth FE
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Functional earth
L1
40
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
15
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CO
Pin allocation – CANopen interface
Fieldbus plug/adapter
Bus connection, FBA-2-M12-5POL
2
3
Bus IN
4
2
5
1 1
4
Bus OUT
5
3
Pin
1
2
3
4
5
Allocation
FE
CAN_V+
CAN_GND
CAN_H
CAN_L
Description
Functional earth
24 V DC supply for CAN interface
0 V CAN interface
Received/transmitted data high
Received/transmitted data low
Bus connection, FBA-1-SL-5POL with FBSD-KL-2X5POL
1 CAN_GND
1 2 3 4 5
2
3
CAN_L
FE
4
5
CAN_H
CAN_V+
0 V CAN interface
Received/transmitted data low
Functional earth
Received/transmitted data high
24 V DC supply for CAN interface
Connection and display components
3
1
1 Status LEDs (operating status/diagnostics)
2 DIL switches
3 Power supply for bus node and connected devices (valve terminal)
4 Fieldbus connection (Sub-D plug)
2 4
16
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CTEU-CO
Ordering data
Bus node
CANopen bus node
Bus connection
Sub-D plug, straight, A-coded
Sub-D plug, angled, A-coded
Micro Style bus connection, 2xM12, 5-pin, A-coded
Fieldbus socket for Micro Style connection
Plug for Micro Style connection, M12, 5-pin
Open Style bus connection
Terminal strip for Open Style connection, 5-pin
Fitting
Threaded sleeve for Sub-D
Plug socket
For power supply
Manual
Manual Bus node CTEU-CO German
English
Spanish
French
Italian
Chinese
Part No.
Type
570038 CTEU-CO
532219 FBS-SUB-9-BU-2x5POL-B
533783 FBS-SUB-9-WS-CO-K
525632 FBA-2-M12-5POL
18324
175380
525634
FBSD-GD-9-5POL
FBS-M12-5GS-PG9
FBA-1-SL-5POL
525635 FBSD-KL-2x5POL
533000 UNC4-40/M3X8
538999 NTSD-GD-9-M12-5POL-RK
573767
573768
573769
573770
573771
573772
P.BE-CTEU-CO-OP+MAINT-DE
P.BE-CTEU-CO-OP+MAINT-EN
P.BE-CTEU-CO-OP+MAINT-ES
P.BE-CTEU-CO-OP+MAINT-FR
P.BE-CTEU-CO-OP+MAINT-IT
P.BE-CTEU-CO-OP+MAINT-ZH
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
17
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-DN
The bus node handles communication between the valve terminal and a higher-level DeviceNet
® master.
The module has basic diagnostic functions. It has 5 integrated LEDs for on-site display. Up to 8 byte inputs and 8 byte outputs are typically transmitted in the cyclic process image.
Application
Fieldbus connection
The bus connection is established via a 9-pin Sub-D socket with a typical allocation (to EN 50170).
The bus connector plug (with protection class IP65/IP67 from
Festo or IP20 from other manufacturers) facilitates the connection of an
Implementation
Protocol chip used:
• CAN transceiver 82C251
Baud rates supported:
• 125 kbps
• 250 kbps
• 500 kbps
Max. DeviceNet cable length (trunk cable):
• 100 m at 500 kbps
• 250 m at 250 kbps
• 500 m at 125 kbps incoming and an outgoing bus cable.
The fieldbus parameters and the basic device parameter settings are
Max. branch line length (drop cable):
• 6 m at 500 kbps
• 6 m at 250 kbps
• 6 m at 125 kbps set on the bus node via DIL switches.
The following variants can be realised using an adapter:
• 2x Micro Style M12, protection class IP65, 5-pin, socket and pin
• Open Style plug, protection class
IP20, 5-pin, pin
18
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-DN
General technical data
Fieldbus interface
Protocol
Baud rates
Internal cycle time
Operating voltage
Max. address capacity, inputs
Max. address capacity, outputs
Additional functions
Operating elements
Configuration support
Device-specific diagnostics
Protection class to EN 60529
Note on materials
Housing materials
Nominal value
Permissible range
Intrinsic current consumption at nominal operating voltage
Max. power supply
Parameterisation
LED display
Product weight
Temperature range
Dimensions W x L x H
Corrosion resistance class CRC
CE marking
Certification
Fieldbus-specific
Product-specific
Environment
Storage
• Sub-D socket, 9-pin
• Sub-D plug, for self-assembly
• 2x M12x1, 5-pin
• Terminal strip, 5-pin
DeviceNet
[kbps] 125, 250, 500
[V DC]
[V DC]
[mA]
[A]
1 ms per 1 byte of user data
24
18 … 30
Typically 120
4
Diagnostic behaviour
Failsafe and idle response
8 byte
[g]
[°C]
[°C]
[mm]
8 byte
• Acyclic data access via "Explicit Message"
• Quickconnect
• System status can be displayed using process data
DIL switch
EDS files
• System diagnostics
• Undervoltage
• Communication error
• MNS: Network status
• IO: I/O status
• PS: Operating voltage for electronics and load supply
• X1: System status of module at I-Port 1
• X2: System status of module at I-Port 2
IP65/IP67
RoHS-compliant
• PC
• PA reinforced
90
–5 … +50
–20 … +70
40 x 91 x 50
2
1)
To EU EMC Directive
2)
C-Tick
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
19
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-DN
Dimensions
CTEU-DN
Download CAD Data
www.festo.com/us/cad
Type
CTEU-DN L1
91
H1
39.8
Pin allocation
Sub-D, 9-pin, DeviceNet interface
Power supply, M12, B-coded
Pin Allocation
5
6
7
3
4
1
2
8
9
Housing n.c.
CAN_V+ n.c.
CAN_L
CAN_GND n.c.
CAN_Shld
GND
CAN_H
3
4
5
1
2
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
0 V
VAL/OUT
FE
Description
Not connected
Received/transmitted data low
0 V CAN interface (connected to pin 6)
Not connected
Optional screened connection
0 V CAN interface, optional (connected to pin 3)
Received/transmitted data high
Not connected
24 V DC supply for CAN interface
Cable screen, connection to functional earth FE
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Functional earth
B1
40
20
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-DN
Pin allocation – DeviceNet interface
Fieldbus plug/adapter
Bus connection, FBA-2-M12-5POL
2
3
Bus IN
4
2
5
1 1
4
Bus OUT
5
3
Pin
1
2
3
4
5
Allocation
FE
CAN_V+
CAN_GND
CAN_H
CAN_L
Description
Functional earth
24 V DC supply for CAN interface
0 V CAN interface
Received/transmitted data high
Received/transmitted data low
Bus connection, FBA-1-SL-5POL with FBSD-KL-2X5POL
1 CAN_GND
1 2 3 4 5
2
3
CAN_L
FE
4
5
CAN_H
CAN_V+
0 V CAN interface
Received/transmitted data low
Functional earth
Received/transmitted data high
24 V DC supply for CAN interface
Connection and display components
1
3
1 Status LEDs (operating status/diagnostics)
2 DIL switch group
3 Power supply for bus node and connected devices (valve terminal)
4 Fieldbus connection (Sub-D plug)
2
4
-V-
New
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
21
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CTEU-DN
Ordering data
Bus node
DeviceNet bus node
Bus connection
Sub-D plug, straight
Micro Style bus connection, 2xM12, 5-pin, A-coded
Fieldbus socket for Micro Style connection, M12, 5-pin
Plug for Micro Style connection, M12, 5-pin
Open Style bus connection
Terminal strip for Open Style connection, 5-pin
Fitting
Plug socket
Threaded sleeve for Sub-D
For power supply
Manual
Manual Bus node CTEU-DN German
English
Spanish
French
Italian
Chinese
Part No.
Type
570039 CTEU-DN
532219 FBS-SUB-9-BU-2x5POL-B
525632 FBA-2-M12-5POL
18324
175380
525634
FBSD-GD-9-5POL
FBS-M12-5GS-PG9
FBA-1-SL-5POL
525635 FBSD-KL-2x5POL
533000 UNC4-40/M3X8
538999 NTSD-GD-9-M12-5POL-RK
573744
573745
573746
573747
573748
573779
P.BE-CTEU-DN-OP+MAINT-DE
P.BE-CTEU-DN-OP+MAINT-EN
P.BE-CTEU-DN-OP+MAINT-ES
P.BE-CTEU-DN-OP+MAINT-FR
P.BE-CTEU-DN-OP+MAINT-IT
P.BE-CTEU-DN-OP+MAINT-ZH
22
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CC
The bus node handles communication between the valve terminal and a higher-level Control &
Communication-Link (CC-Link
®
) master.
The module has basic diagnostic functions. It has 5 integrated LEDs for on-site display. Up to 8 byte inputs and 8 byte outputs are transmitted in the cyclic process image.
Application
Fieldbus connection
The bus connection is established by means of a screw terminal with
IP20 protection and a 9-pin Sub-D plug with IP65/IP67 protection from
Festo or IP20 protection from other manufacturers.
The module features a system and load supply, a fieldbus connection and a connection to the valve terminal with serial I-Port interface.
Both connection types have the function of an integrated
T-distributor and thus support the connection of an incoming and outgoing bus cable.
The integrated interface with RS 485 transmission technology is designed for the typical CC-Link 3-wire connection technology (in accordance with CLPA CC-Link Spec.
V1.1).
Implementation
Protocol chip used:
• MFP3 from Mitsubishi
Max. CC-Link cable length (at least.
0.2 m between devices):
• 100 m at 10 Mbps
• 150 m at 5 Mbps
• 200 m at 2.5 Mbps
• 600 m at 625 kbps
• 1,200 m at 156 kbps
If using branch lines: max. branch line length 8 m, max. 6 stations per branch line
Main string length:
• 100 m at 625 kbps, total branch line length 50 m
• 500 m at 156 kbps, total branch line length 200 m
Higher baud rate not permitted with branch lines.
The following variants can be realised using an adapter:
• Spring-loaded terminal In/Out with IP65 protection (adapter
532220)
• Screw terminal plug with IP20 protection (adapter 197962)
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
23
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CC
General technical data
Fieldbus interface
Protocol
Baud rates
Internal cycle time
Operating voltage
Permissible range
Intrinsic current consumption at nominal operating voltage
Max. power supply
Max. address capacity, inputs
Max. address capacity, outputs
Operating elements
Device-specific diagnostics
Additional functions
Parameterisation
LED display
Protection class to EN 60529
Note on materials
Housing materials
Product weight
Temperature range
Dimensions W x L x H
Product weight
Certification
Corrosion resistance class CRC
CE marking
Certification
Nominal value
Fieldbus-specific
Product-specific
Environment
Storage
• Sub-D socket, 9-pin
• Sub-D plug, for self-assembly
• Screw terminal strip, IP20
CC-Link
[kbps] 156 … 10,000
1 ms per 1 byte of user data
[V DC] 24
[V DC]
[mA]
[A]
[g]
[°C]
[°C]
[mm]
[g]
18 … 30
Typically 70
4
16 byte
16 byte
DIL switch
• System diagnostics
• Undervoltage
• Communication error
• System status can be displayed using process data
• Activate diagnostics
• Failsafe and idle response
• Err: Data transmission error
• Run: Bus active
• PS: Operating voltage for electronics and load supply
• X1: System status of module at I-Port 1
• X2: System status of module at I-Port 2
IP65/IP67
RoHS-compliant
• PC
• PA reinforced
90
–5 … +50
–20 … +70
40 x 91 x 50
90 cULus listed (OL)
2
1)
To EU EMC Directive
2)
C-Tick
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
24
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CC
Dimensions
CTEU-CC
-V-
New
Download CAD Data
www.festo.com/us/cad
Type
CTEU-CC B1
91
Pin allocation
Sub-D plug, 9-pin, CC Link interface
Pin Allocation
1
2
3
4
7
8
5
6 n.c.
n.c.
DB n.c.
9
Housing n.c.
n.c.
DA
DG n.c.
Power supply, M12, A-coded
1
2
3
4
5
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
0 V
VAL/OUT
FE
H1
39.8
Description
Not connected
Data A
Data ground
Not connected
Not connected
Not connected
Data B
Not connected
Not connected
Cable screen, connection to functional earth FE
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Functional earth
L1
40
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
25
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-CC-Link
Pin allocation – CC-Link interface
Fieldbus plug/adapter Pin Description
Bus connection with terminal strip, FBA-1-KL-5POL
FE Functional earth
SLD Cable screen
DG
DB
DA
Data ground
Data B
Data A
Bus connection, FBS-SUB-9-GS-24XPOL-B
DA
DB
DG n.c.
FE
Data A
Data B
Data ground
Not connected
Connected to the housing of the Sub-D plug via the clamp strap
Connection and display components
1
3
1 Status LEDs (operating status/diagnostics)
2 DIL switches
3 Power supply for bus node and connected devices (valve terminal)
4 Fieldbus connection (Sub-D plug)
4
2
26
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CTEU-CC-Link
Ordering data
Bus node
CC-Link bus node
Bus connection
Sub-D plug, straight
Screw terminal bus connection
Fitting
Threaded sleeve for Sub-D
Plug socket
For power supply, M12x1, 5-pin
Part No.
Type
1544198 CTEU-CC
532220 FBS-SUB-9-GS-2x4POL-B
197962 FBA-1-KL-5POL
533000 UNC4-40/M3X8
18324 FBSD-GD-9-5POL
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
27
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-PB
The bus node handles communication between the valve terminal and a higher-level PROFIBUS DP
® master.
The module has basic diagnostic functions. It has 4 integrated LEDs for on-site display. Up to 8 byte inputs and 8 byte outputs are transmitted in the cyclic process image.
Application
Fieldbus connection
The bus connection is established via a 9-pin Sub-D socket with a typical PROFIBUS allocation
(to EN 50170).
The bus connector plug (with protection class IP65/IP67 from
Festo or IP20 from other manufacturers) facilitates the connection of an incoming and an outgoing bus cable.
An active bus terminal can be connected using the DIL switch integrated in the plug.
Baud rate/cable length overview
Baud rates supported:
• 9.6 kbps
• 19.2 kbps
• 93.75 kbps
• 187.5 kbps
• 500 kbps
• 1.5 Mbps
• 3 - 12 Mbps
Maximum fieldbus length:
• 1,200 m
• 1,200 m
• 1,200 m
• 1,000 m
• 400 m
• 200 m
• 100 m
Maximum branch line length:
• 500 m
• 500 m
• 100 m
• 33.3 m
• 20 m
• 6.6 m
• –
The Sub-D interface is designed for controlling network components with a fibre-optic cable connection.
• RS 485 transceiver used: Analog
Devices ADM 2485
• PROFIBUS slave controller used:
Profichip VPC+S
28
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-PB
General technical data
Fieldbus interface
Protocol
Baud rates
Internal cycle time
Operating voltage Nominal value
Permissible range
Intrinsic current consumption at nominal operating voltage
Max. power supply
Parameterisation
Max. address capacity, inputs
Max. address capacity, outputs
Additional functions
Operating elements
Configuration support
Device-specific diagnostics
LED display
Protection class to EN 60529
Note on materials
Housing materials
Product weight
Temperature range
Dimensions W x L x H
Corrosion resistance class CRC
CE marking
Certification
Fieldbus-specific
Product-specific
Environment
Storage
[kbps]
[Mbps]
[V DC]
[V DC]
[mA]
[A]
[g]
[°C]
[°C]
[mm]
• Sub-D socket, 9-pin
• Sub-D plug, for self-assembly
• 2x M12x1, 5-pin, B-coded
PROFIBUS DP
9.6, 19.2, 93.75, 187.5, 500
1.5, 12
1 ms per 1 byte of user data
24
18 … 30
Typically 100
2
Diagnostic behaviour
Failsafe response
16 byte
16 byte
• System status via diagnostic programme
• Emergency message
DIL switch
GSD files
• System diagnostics
• Undervoltage
• Communication error
• BF: Bus error
• PS: Operating voltage for electronics and load supply
• X1: System status of module at I-Port 1
• X2: System status of module at I-Port 2
IP65/IP67
RoHS-compliant
• PC
• PA reinforced
90
–5 … +50
–20 … +70
40 x 91 x 50
2
1)
To EU EMC Directive
C-Tick
2)
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
29
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-PB
Dimensions
CTEU-PB
Download CAD Data
www.festo.com/us/cad
Type
CTEU-PB B1
91
Pin allocation
Pin Allocation
Sub-D plug, 9-pin, PROFIBUS interface
1
2
3
4
Screened n.c.
RxD/TxD-P
CNTR-P
7
8
5
6
DGND
VP n.c.
RxD/TxD-N
9
Housing n.c.
Power supply, M12, A-coded
1
2
3
4
5
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
0 V
VAL/OUT
FE
H1
39.8
Description
Functional earth
Not connected
Received/transmitted data positive
Repeater control signal
Data ground GND
Supply voltage - positive (+ 5 V)
Not connected
Received/transmitted data negative
Not connected
Cable screen, connection to functional earth FE
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Functional earth
L1
40
30
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-PB
Pin allocation – PROFIBUS interface
Fieldbus adapter
Bus connection, FBA-2-M12-5POL-RK
2
3
4
Bus IN
1
5
1
4
Bus OUT
2
3
5
Pin
1
2
3
4
5
Bus IN n.c.
RxD/TxD-N n.c.
RxD/TxD-P
FE
Bus OUT
VP
RxD/TxD-N
DGND
RxD/TxD-P
Functional earth
Connection and display components
3
1
1 Status LEDs (operating status/diagnostics)
2 DIL switches
3 Power supply for bus node and connected devices (valve terminal)
4 Fieldbus connection (Sub-D plug)
2
4
-V-
New
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
31
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CTEU-PB
Ordering data
Bus node
PROFIBUS bus node
Part No.
Type
570040 CTEU-PB
Bus connection
Sub-D plug, straight
Sub-D plug, angled
532216 FFBS-SUB-9-GS-DP-B
533780 FBS-SUB-9-WS-PB-K
Bus connection M12 adapter, B-coded 533118 FBA-2-M12-5POL-RK
Socket M12x1, 5-pin, straight, for self-assembly of a connecting cable, compatible with
FBA-2-M12-5POL-RK
1067905 NECU-M-B12G5-C2-PB
Plug M12x1, 5-pin, straight, for self-assembly of a connecting cable, compatible with
FBA-2-M12-5POL-RK
1066354 NECU-M-S-B12G5-C2-PB
Terminating resistor, M12, B-coded for PROFIBUS 1072128 CACR-S-B12G5-220-PB
Fitting
Threaded sleeve for Sub-D
Plug socket
For power supply, M12x1, 5-pin
Manual
Manual Bus node CTEU-PB German
English
Spanish
French
Italian
Chinese
533000
18324
UNC4-40/M3X8
FBSD-GD-9-5POL
575392
575393
575394
575395
575396
575397
P.BE-CTEU-PB-OP+MAINT-DE
P.BE-CTEU-PB-OP+MAINT-EN
P.BE-CTEU-PB-OP+MAINT-ES
P.BE-CTEU-PB-OP+MAINT-FR
P.BE-CTEU-PB-OP+MAINT-IT
P.BE-CTEU-PB-OP+MAINT-ZH
32
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-EC
The bus node handles communication between the valve terminal and a higher-level EtherCAT
® master.
The module has basic diagnostic functions. It has 6 integrated status
LEDs for on-site display.
Up to 16 byte inputs and 16 byte outputs are transmitted in the cyclic process image.
Application
Fieldbus connection
The bus connection is established via two M12 sockets, D-coded to
IEC61076-2-101 with IP65/67 protection.
Both connections are equivalent
100BaseTX Ethernet ports with integrated auto MDI functionality
(cross-over and patch cables can be used) that are brought together via an internal switch.
The module features a system and load supply, a fieldbus connection and a connection to the valve terminal with serial I-Port interface.
Note the applicable specifications, for example cable specifications for
Ethernet networks to ISO/IEC11801 as well as ANSI/TIA/EIA-568-B.
EtherCAT bus node
The EtherCAT bus node supports the
EtherCAT protocol on the basis of the
Ethernet standard and TCP/IP technology to IEEE802.3.
This guarantees data exchange with a high data transmission rate, for example I/O data from sensors, actuators or robot controllers, PLCs or process equipment. Furthermore, non real-time critical information such as diagnostic information, configuration information, etc. can be transferred.
The data bandwidth is sufficient to transmit both data types (real-time and non-real-time) in parallel.
The bus node features a system and load supply, EtherCAT input and output port, LEDs for status and diagnostic messages as well as DIL switch elements. Diagnostics are possible directly on the bus node and/or via fieldbus.
The bus node has a separate operating and load voltage supply.
It is mounted on a Festo device
(e.g. valve terminal or E-box)
• Maximum cable length (between network stations): 100 m
• Baud rate:
100 Mbps
• EtherCAT communication chip:
ASIC ET1100 compatible with I-Port and supplies downstream devices connected via the
I-Port interface with voltage.
Set using DIL switches:
• Station addresses
• Diagnostics on/off
• Failstate behaviour
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
33
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-EC
General technical data
Fieldbus interface
Protocol
Baud rates
Internal cycle time
Operating voltage (PS)
Device-specific diagnostics
Additional functions
Configuration support
Parameterisation
Operating elements
Parameterisation via
DIL switches
Protection class to EN 60529
Corrosion resistance class CRC
Certification
Temperature range
Note on materials
Housing materials
Nominal value
Permissible range
Power failure buffering
Load voltage (PL) Max.
Typ. tolerance range
Max. power supply
Intrinsic current consumption at nominal operating voltage
Max. address capacity, inputs
Max. address capacity, outputs
LED display Fieldbus-specific
Product-specific
CE marking (see declaration of conformity)
Operation
Storage/transport
[Mbps]
[V DC]
[V DC]
[ms]
[V DC]
[V DC]
[A]
[mA]
[byte]
[byte]
[°C]
[°C]
2x M12 socket, D-coded, 4-pin
EtherCAT
100
1 ms per 1 byte of user data
24
18 … 30
10
30
18 … 30
4
Typically 60
16
16
• Run: Operating status (communication status)
• L/A2: Network active (connection status) port 2 (Out)
• L/A1: Network active (connection status) port 1 (In)
• PS: Operating voltage for electronics and load supply
• X1: System status of module at I-Port 1
• X2: System status of module at I-Port 2
• System diagnostics
• Undervoltage
• Communication error
• Diagnostic object
• Acyclic data access via "SDO"
• Emergency message
• Modular device profile (MDP)
XML file
• Diagnostic behaviour
• Failsafe response
DIL switch
• Failsafe and idle response
• Diagnostics on/off
IP65
2
1)
To EU EMC Directive
2)
C-Tick
– 5 … +50
–20 … +70
RoHS-compliant
• PC
• PA reinforced
40 x 91 x 50
90
Dimensions W x L x H
Product weight
[mm]
[g]
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
34
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
Fieldbus modules CTEU/installation system CTEL
Technical data – CTEU-EC
Dimensions
CTEU-EC
-V-
New
Download CAD Data
www.festo.com/us/cad
Type
CTEU-EC L1
91
H1
45.3
Pin allocation
EtherCAT interface, M12, D-coded
Pin Allocation
1
2
3
4
Housing
RX-
TX+
RX+
TX-
Description
Transmitted data+
Received data+
Transmitted data-
Received data-
Cable screen, connection to functional earth FE
Power supply, M12, A-coded
3
4
1
2
5
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
0 V
VAL/OUT
FE
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Functional earth
Connection and display components
3
1
4
2
4
1 Status LEDs (operating status/diagnostics)
2 DIL switches
3 Power supply for bus node and connected devices (valve terminal)
4 Fieldbus connection (Sub-D plug)
B1
40
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
35
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CTEU-EC
Ordering data
Bus node
Bus node CTEU-EC (EtherCAT)
Bus connection
Plug M12x1, 4-pin, D-coded
Plug socket
For power supply, M12x1, 5-pin
Manual
Manual Bus node CTEU-EC German
English
Spanish
French
Italian
Chinese
Part No.
Type
572556 CTEU-EC
543109 NECU-M-S-D12G4-C2-ET
18324 FBSD-GD-9-5POL
575400
575401
575402
575403
575404
575405
P.BE-CTEU-EC-OP+MAINT-DE
P.BE-CTEU-EC-OP+MAINT-EN
P.BE-CTEU-EC-OP+MAINT-ES
P.BE-CTEU-EC-OP+MAINT-FR
P.BE-CTEU-EC-OP+MAINT-IT
P.BE-CTEU-EC-OP+MAINT-ZH
36
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Interface CPX-CTEL
The electrical interface CPX-CTEL master establishes the connection to modules with I-Port interface (device) from the CTEL/CTEU series. The I/O data from the connected devices is transferred to the connected CPX bus node and therefore transferred to the higher-level controller via fieldbus.
A maximum of 4 devices can be connected to a CPX-CTEL master via appropriate M12- interfaces.
Application
I-Port interface
As well as transmitting the communication data, the I-Port interfaces of a CPX-CTEL master also transmit the power supply for the connected sensors and the load supply for the valves (or outputs).
Both circuits are supplied separately with 24 V, with a separate reference potential.
The connecting cables used must meet the increased requirements resulting from their double function as a signal line and power supply cable.
Sample configuration – CPX-CTEL master with CTEL modules
The CPX-CTEL master provides four
I-Port interfaces to which one device each can be connected. I-Port is an interface for exchanging serial data for connecting decentralised modules or valve terminals from
Festo. The I-Port interface is based on IO-Link and is compatible with it in certain areas.
The connection type corresponds to a star topology. In other words, only one module or valve terminal can be connected to each I-Port.
The restrictions compared to IO-Link include:
• Permanently set baud rate of
230.4 kbps
• SIO mode is not supported
• Max. 32 bytes of input data and
32 bytes of output data
• Only one dump of the master commands is used
• "Festo plug & work" principle, configuration via IODD is not supported
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
37
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Interface CPX-CTEL
Implementation
The CPX-CTEL master from Festo enables modules with an I-Port interface to be connected to a CPX system:
• Max. 4 devices with individual electronic fuse protection
• Max. 64 inputs/64 outputs per
I-Port interface
• The maximum length of a string is
20 m
The following device variants are available:
• Input modules with 16 digital inputs (3-pin M8 and 5-pin M12 connection technology)
• Valve terminals with I-Port interface
(up to 48 solenoid coils, different valve functions)
The decentralised arrangement of the modules and valve terminals with
I-Port enables them to be mounted near the cylinders and actuators/sensors to be controlled.
This allows the use of shorter air supply lines and sensor cables or possibly smaller valves, which saves costs.
Several CPX-CTEL masters can be combined in one CPX terminal, depending on the address capacity of the bus node.
Example:
• CPX-FB13 (512 I/O)
• Max. 2 CPX-CTEL masters (256 I/O each) possible
Configuration
Setting
The precise number of I/O bytes made available is geared towards the requirements of the connected devices and the selected operating mode.
The operating mode and configuration presetting of the CPX-CTEL master can be defined by the user.
DIL switches are used for selecting the operating mode and making the setting for manual configuration.
These DIL switches are not required during operation and are only accessible in unassembled condition.
Manual configuration
With manual configuration (tool change mode), the number of inputs and outputs in the process image of the CPX system or higher-level fieldbus can be manually defined via the DIL switches.
The process image then always has the same number of bytes, regardless of the connected devices.
The defined I/O length always applies to all four I-Ports (max. 8 bytes per
I-Port).
Automatic configuration
With automatic configuration, the I/O length for each I-Port is individually determined and this value is used to select the appropriate or next highest configuration presetting.
Power supply for I-Port devices
The CPX-CTEL master provides two separate power supplies for the connected devices:
• One for operating the device and the inputs connected to it
• One for outputs and valves connected to the device
The power supply for devices and inputs comes from the power supply for the electronics and sensors of the
CPX terminal.
The power supply for outputs and valves comes from the power supply for the valves of the CPX terminal.
The interlinking block with additional power supply enables a separate voltage supply for valves and outputs.
This allows this supply voltage to be switched off separately.
In other words, the valves and outputs of the connected I-Port devices can be switched off separately without having to switch off the devices themselves.
38
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Interface CPX-CTEL
General technical data
Type
Protocol
Max. address capacity
I-Port connection
Number of I-Port interfaces
Max. cable length
Internal cycle time
Electrical isolation
LED displays
Outputs
Inputs
Channel – channel
Channel – internal bus
Diagnostics
Parameterisation
Additional functions
Operating elements
Operating voltage Nominal value
Permissible range
Power failure buffering
Intrinsic current consumption at nominal operating voltage
Max. power supply per channel
Max. residual output current per channel
Protection class to EN 60529
Temperature range Operating
Storage/transport
Materials
Note on materials
Grid dimension
Dimensions (incl. interlinking block) W x L x H
Product weight
Note
Please observe the general limits and guidelines for the system when configuring the electrical modules.
[bit]
[bit]
[m]
[ms]
[V DC]
[V DC]
[ms]
[mA]
[A]
[A]
[°C]
[°C]
[mm]
[mm]
[g]
CPX-CTEL-4-M12-5POL
I-Port
256
256
4x M12 socket, 5-pin, A-coded
4
20
1 per 8 bits of user data
No
Yes, using an intermediate supply
X1 … 4 = Status of the I-Port interface 1 … 4
PS = Electronics supply
PL = Load supply
-P-
= Module fault
• Communication error
• Module short circuit
• Module-oriented diagnostics
• Undervoltage
• Diagnostic behaviour
• Failsafe per channel
• Forces per channel
• Idle mode per channel
• Module parameters
• Tool change mode
Tool change mode
DIL switch
24 (reverse polarity protected)
18 … 30
10
Typically 65
4x 1.6
4x 1.6
IP65/IP67
–5 … +50
–20 … +70
PA reinforced, PC
RoHS-compliant
50
50 x 107 x 55
110
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
39
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Interface CPX-CTEL
Connection and display components
1 2
3
4
Pin allocation – I-Port interface/IO-Link
4
5
2
3
Pin
1
Allocation
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
C/Q
0 V
VAL/OUT
1 Status LEDs for I-Port interfaces
2 CPX-specific status LEDs
3 Holders for inscription labels
(IBS 6x10)
4 I-Port interfaces for up to
4 devices
Description
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Communication signal
Load voltage supply (valves/outputs)
Dimensions Download CAD Data
www.festo.com/us/cad
Type
CPX-CTEL-4-M12-5POL
B1
108.1
B2
118.9
B3
124.9
H1
55.1
L1
50
40
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – Interface CPX-CTEL
Ordering data
Designation
CPX-CTEL master
Interface for max. 4 I/O modules and valve terminals with I-Port interface (devices)
Part No.
Type
1577012 CPX-CTEL-4-M12-5POL
Bus connection
Cover cap
Inscription label holder for manifold block
Connecting cable
–
Manual
Manual CPX-CTEL master
M12
German
English
Spanish
French
Italian
Swedish
165592
536593
ISK-M12
CPX-ST-1
574321
574322
574323
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
574600
574601
574602
574603
574604
574605
P.BE-CPX-CTEL-DE
P.BE-CPX-CTEL-EN
P.BE-CPX-CTEL-ES
P.BE-CPX-CTEL-FR
P.BE-CPX-CTEL-IT
P.BE-CPX-CTEL-SV
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
41
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CPV valve terminals
-M-
Flow rate
CPV10: Up to 400 l/min
CPV14: Up to 800 l/min
-K-
Valve width
CPV10: 10 mm
CPV14: 14 mm
-P-
Voltage
24 V DC
I-Port interface for communication between a CPV valve terminal and an
I-Port master. It activates a CPV valve terminal with up to 16 solenoid coils on max. 8 valve positions.
The connection to a higher-level controller can be realised by:
• Connecting an I-Port master from
Festo (CPX-CTEL)
• Mounting a fieldbus node CTEU directly
• Connecting to an IO-Link master (in
IO-Link mode)
General technical data
Protocol
IO-Link
Baud rate
Max. number of valve positions
Nominal operating voltage
Nominal load voltage
Operating voltage range
Intrinsic current consumption
Reverse polarity protection
Diagnostics
LED display
Connection technology
Protocol
Communication mode
Port type
Number of ports
Process data width OUT
Min. cycle time
Electronics/sensors
Load voltage
Operating voltage
Load voltage
Bus-specific
Product-specific
[bit]
[ms]
[kbps]
[V DC]
[V DC]
[V DC]
[V DC]
[mA]
[mA]
IO-Link/I-Port
5-pin
V 1.0
COM2 (38.4 kB), COM3 (230 kB)
B
1
16
3.2
38.4/230.4
8
24
24
18 … 30
21.6 … 26.4
35
700
For operating voltage
Undervoltage of load voltage supply
1 Communication status
16 Valve status
Materials
Cover
Note on materials
PA
RoHS-compliant
Operating and environmental conditions
Mounting position
Protection class to EN 60529
Ambient temperature
Storage temperature
Relative air humidity
CE marking (see declaration of conformity)
Certification
[°C]
[°C]
[%]
Any
IP65 (when fully plugged in or fitted with protective cover)
–5 … +50
–20 … +70
93 (non-condensing)
To EU EMC Directive
1) cULus listed (OL)
1) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
42
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – CPV valve terminals
Connection and display components
CPV10
1
2
CPV14
1
2
1 Earthing screw 2 I-Port interface/IO-Link
Pin allocation – I-Port interface/IO-Link
Pin
3
4
1
2
5
Allocation
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
C/Q
0 V
VAL/OUT
1 Earthing screw
Description
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Communication signal
Load voltage supply (valves/outputs)
2 I-Port interface/IO-Link
Dimensions
1 I-Port interface/IO-Link
Download CAD Data
www.festo.com/us/cad
Type
CPV10-GE-PT-8
CPV14-GE-PT-8
B1
71
89
B2
62
78
B3
32
32.4
H1
38.3
38.3
H2
26.2
26.2
L1
110
152
L2
101.8
142
L3
30.2
56.5
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
43
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – CPV valve terminals
Ordering data
I-Port node
Type
Node with I-Port interface/IO-Link and
8 valve positions
(max. 8 double solenoid valves)
CPV10
CPV14
Device ID Weight
0x 000410 108.5 g
0x 000510 200 g
Part No.
Type
1565761 CPV10-GE-PT-8
1564984 CPV14-GE-PT-8
Connection technology for I/O-Link
T-adapter M12, 5-pin for IO-Link and load voltage supply
Straight plug, M12, 5 pin (for T-adapter)
171175 FB-TA-M12-5POL
175487 SEA-M12-5GS-PG7
Connecting cable
– 574321
574322
574323
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
44
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – MPA-L valve terminals
-M-
Flow rate
VMPA1: Up to 360 l/min
VMPA14: Up to 670 l/min
VMPA2: Up to 700 l/min
-K-
Valve width
VMPA1:
VMPA14:
VMPA2:
-P-
Voltage
24 V DC
10 mm
14 mm
20 mm
I-Port interface for communication between an MPA-L valve terminal and an I-Port master. It activates an MPA-L valve terminal with up to 32 solenoid coils on max. 32 valve positions.
The connection to a higher-level controller can be realised by:
• Connecting an I-Port master from
Festo (CPX-CTEL)
• Mounting a fieldbus node CTEU directly
• Connecting to an IO-Link master (in
IO-Link mode)
General technical data
Protocol
IO-Link
Baud rate
Operating pressure
Pilot pressure
Nominal operating voltage
Intrinsic current consumption
Reverse polarity protection
Diagnostics
LED display
Connection technology
Protocol
Communication mode
Port type
Number of ports
Process data width OUT
Min. cycle time
Operating voltage
Load voltage
[bit]
[ms]
[kbps]
[bar]
[bar]
[V DC]
[mA]
[mA]
IO-Link/I-Port
5-pin
V 1.0
COM2 (38.4 kB), COM3 (230 kB)
B
1
8 … 32
3.2
38.4/230.4
–0.9 … 10
3 … 8
24
30
30
For operating voltage
Undervoltage of load voltage supply
1 Communication status
Materials
End plate
Note on materials
PPA reinforced
RoHS-compliant
Operating and environmental conditions
Mounting position
Ambient temperature
Storage temperature
Corrosion resistance class CRC
1)
[°C]
[°C]
Any
–5 … +50
–20 … +40
3
1) Corrosion resistance class 3 according to Festo standard 940 070
Components subject to high corrosion stress. Externally visible parts with primarily functional surface requirements which are in direct contact with a normal industrial environment or media such as solvents and cleaning agents.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
45
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – MPA-L valve terminals
Connection and display components
VMPAL-EPL-IPO32
1
3
1 Status LED
2
2 Earthing screw
Pin allocation – I-Port interface/IO-Link
4
5
2
3
Pin
1
Allocation
24 V
EL/SEN
24 V
VAL/OUT
0 V
EL/SEN
C/Q
0 V
VAL/OUT
3 I-Port interface/IO-Link
Description
Operating voltage supply (electronic, sensors/inputs)
Load voltage supply (valves/outputs)
Operating voltage supply (electronic, sensors/inputs)
Communication signal
Load voltage supply (valves/outputs)
Dimensions Download CAD Data
www.festo.com/us/cad
Type
VMPAL-EPL-IPO32
1 I-Port interface/IO-Link
B1 B2 B3
64.8
34.5
5.7
B4
6.2
B5
4
B6
1
D1
6.4
D2 H1 L1 L2 L3 L4
4.5
41.8
110 107 66.3
33.5
L5
65
L6
23.5
L7
26
46
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – MPA-L valve terminals
Ordering data
I-Port node
Device ID Weight
Node with I-Port interface/IO-Link and up to 32 valve positions (max. 16 double solenoid valves)
0x 000620 170 g
Part No.
Type
575667 VMPAL-EPL-IPO32
Connection technology for I/O-Link
T-adapter M12, 5-pin for IO-Link and load voltage supply
Straight plug, M12, 5 pin (for T-adapter)
Connecting cable
–
171175 FB-TA-M12-5POL
175487 SEA-M12-5GS-PG7
574321
574322
574323
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
47
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Input modules CTSL
Function
Digital input modules facilitate the connection of proximity sensors or other 24 V DC sensors (inductive, capacitive, etc.).
Plugs with double allocation are separated using a DUO plug or DUO cable.
Application
• Input modules for 24 V DC sensor signals
• M12 connection technology
• Display of the input states for each input signal via an assigned LED
• Operating voltage supply 24 V DC for all connected sensors
• Diagnostic LED for short circuit/overload of sensor supply
• Labelling options on all sides with large, hinged inscription labels
• Earthing plate and H-rail mounting already integrated
General technical data
Type
Electrical connection
Protocol
IO-Link Connection technology
Protocol
Communication mode
Port type
Number of ports
Process data width OUT
Min. cycle time
Device ID
Baud rate
Max. number of inputs
Nominal operating voltage
Operating voltage range
Current consumption of logic at nominal operating voltage
Max. residual current per module
Reverse polarity protection
Fuse protection (short circuit)
Electrical isolation, channel – channel
Switching level Signal 0
Signal 1
Input debounce time
Input characteristic
Switching logic at inputs
LED display Bus-specific
Product-specific
[bit]
[ms]
[ms]
[kbps]
[V DC]
[V DC]
[mA]
[mA]
[V]
[V]
[ms]
CTSL-D-16E-M8-3 CTSL-D-16E-M12-5
16x M8 socket, 3-pin
IO-Link/I-Port
5-pin
B
1
V 1.0
COM2 (38.4 kB), COM3 (230 kB)
8x M12 socket, 5-pin
16
3.2
0x 700410
38.4/230.4
16
24
18 … 30
Max. 35
1.2
For operating voltage
Internal electronic fuse protection for each group
No
≤5
≥11
0.5 (3 ms, 10 ms, 20 ms parameterisable)
IEC1131 Part 2
PNP (positive switching)
X20: I-Port/IO-Link
1 Operating voltage
16 Channel status
2 Group diagnostics
48
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Input modules CTSL
Materials
Housing
Cover
Note on materials
Product weight
Dimensions (W x L x H)
[g]
[mm]
PA reinforced
PA reinforced
RoHS-compliant
250
143 x 103 x 32
Operating and environmental conditions
Type of mounting
Protection class to EN 60529
Ambient temperature
Storage temperature
Corrosion resistance class CRC
1)
CE marking (see declaration of conformity)
Certification
[°C]
[°C]
Optionally via H-rail or through-holes
IP65, IP67 (when fully plugged in or fitted with protective cap)
–5 … +50
–20 … +70
2
1)
To EU EMC Directive
2) cULus listed (OL)
C-Tick
1) Corrosion resistance class 2 according to Festo standard 940 070
Components subject to moderate corrosion stress. Externally visible parts with primarily decorative surface requirements which are in direct contact with a normal industrial environment or media such as coolants or lubricating agents.
2) For information about the applicability of the component see the manufacturer’s EC declaration of conformity at: www.festo.com
Support User documentation.
If the component is subject to restrictions on usage in residential, office or commercial environments or small businesses, further measures to reduce the emitted interference may be necessary.
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
49
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Input modules CTSL
Connection and display components
CTSL-D-16E-M8-3
4
5
3
6
7
2
1
7 7
8
1 Earth terminal
2 I-Port interface/IO-Link
3 Status LED for power supply (PS)
4 Status LED for I-Port (X20)
5 Status LEDs for inputs (status display, green)
6 Status LED (group) for short circuit/overload of sensor supply (red)
7 Fixture for inscription label holder ASCF-H-E2
8 Sensor connections
(1 input per socket)
Pin allocation – I-Port interface/IO-Link
Pin
3
4
1
2
5
Allocation
24 V
EL/SEN
–
0 V
EL/SEN
C/Q
–
Description
Operating voltage supply (electronic, sensors/inputs)
–
Operating voltage supply (electronic, sensors/inputs)
Communication signal
–
Pin allocation – Sensor connections CTSL-D-16E-M8-3
Pin allocation Pin
1
Allocation
24 V
Description
Operating voltage 24 V
3 0 V Operating voltage 0 V
4 Ix* Sensor signal
* Ix = Input x
50
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Input modules CTSL
Connection and display components
CTSL-D-16E-M12-5
4
5
3
6
7
2
1
7 7
7
8
1 Earth terminal
2 I-Port interface/IO-Link
3 Status LED for power supply (PS)
4 Status LED for I-Port (X20)
5 Status LEDs for inputs (status display, green)
6 Status LED (group) for short circuit/overload of sensor supply (red)
7 Fixture for inscription label holder ASCF-H-E2
8 Sensor connections
(2 inputs per socket)
Pin allocation – I-Port interface/IO-Link
Pin
3
4
1
2
5
Allocation
24 V
EL/SEN
–
0 V
EL/SEN
C/Q
–
Description
Operating voltage supply (electronic, sensors/inputs)
–
Operating voltage supply (electronic, sensors/inputs)
Communication signal
–
Pin allocation – Sensor connections CTSL-D-16E-M12-5
Pin allocation Pin
1
Allocation
24 V
Description
Operating voltage 24 V
2 Ix+1*
3 0 V
4 Ix*
5 Ground
Sensor signal
Operating voltage 0 V
Sensor signal
Earth terminal
* Ix = Input x
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
51
-V-
New
Fieldbus modules CTEU/installation system CTEL
Technical data – Input modules CTSL
Dimensions
CTSL-D-16E-M8-3
Download CAD Data
www.festo.com/us/cad
CTSL-D-16E-M12-5
Type
CTSL-D-16E
B1
103
B2
87
B3
7
B4
35.5
B5
32.8
D1
9
D2
4.3
H1
32
H2
9.4
L1
143
L2
127
L3
7
T1
3.5
52
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Accessories – Input modules CTSL
Ordering data
Designation
Input modules
16 sensor connections M8, 3-pin, single allocation
8 sensor connections M12, 5-pin, double allocation
Part No.
Type
1387363 CTSL-D-16E-M8-3
1387359 CTSL-D-16E-M12-5
Plug connector
Straight plug, M12
Straight plug, M8
Plug for 2 cables, M12, PG11
Push-in T-connector
5-pin, PG7
4-pin, PG7
4-pin, 2.5 mm
2
O.D.
∅
3-pin, solderable
3-pin, screw-in
4-pin
5-pin
2x socket M12, 5-pin
1x plug M12, 4-pin
175487
18666
192008
18696
192009
18779
192010
541596
SEA-M12-5GS-PG7
SEA-GS-7
SEA-4GS-7-2,5
SEA-GS-M8
SEA-3GS-M8-S
SEA-GS-11-DUO
SEA-5GS-11-DUO
NEDU-M12D5-M12T4
Connecting cables
DUO cable, 1x straight plug M12
Connecting cable, M12, 4-pin, straight plug-straight socket
Connecting cable, M8, 3-pin, straight plug-straight socket
–
2x straight socket M8
1x straight socket M8 and
1x angled socket M8
2x angled socket M8
2.5 m
5.0 m
0.5 m
1 m
2.5 m
5 m
18685
18688
18687
539052
539052
539052
539052
539052
539052
KM12-DUO-M8-GDGD
KM12-DUO-M8-GDWD
574321
574322
574323
KM12-DUO-M8-WDWD
NEBU-M12G4-K-2.5-M12G4
1)
NEBU-M12G4-K-5-M12G4
1)
NEBU-M8G3-K-0.5-M8G3
1)
NEBU-M8G3-K-1-M8G3
1)
NEBU-M8G3-K-2.5-M8G3
1)
NEBU-M8G3-K-5-M8G3
1)
NEBU-M12G5-E-5-Q8N-M12G5
NEBU-M12G5-E-7.5-Q8N-M12G5
NEBU-M12G5-E-10-Q8N-M12G5
Inscription label holder
Inscription label holders for EL modules, bag of 10 547473 ASCF-H-E2
1) Modular product, further information
Internet: nebu
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
53
-V-
New
Fieldbus modules CTEU/installation system CTEL
Example of a valve terminal VTUG with I-Port interface
Dimensions – Example of a valve terminal with I-Port interface, size 10
Download CAD Data
www.festo.com/us/cad
1 Ports 1, 3 and 5: Gx
(at both ends)
3 Ports 12/14: M5 (at both ends)
4 Ports 82/84: M5 (at both ends)
5 CTEU-CANopen
6 For mounting valves/blanking plates/supply plates on manifold block: M2
7 Blanking plate
8 Supply plate, ports 1,3 and 5:
M7
9 H-rail mounting aJ Inscription label holder
54
Internet: www.festo.com/catalog/...
Subject to change – 2013/05
-V-
New
Fieldbus modules CTEU/installation system CTEL
Example of a valve terminal VTUG with I-Port interface
Type
VABM
No. of valve positions
4-24
Size 10
B1 B2 B3 B4 B5 B6
91.5
54 52.4
41.5
25.6
9.8
B7 B8
16 17.7
D1
∅
4.5
H1 H2 H3 H4 H5 H6 H7 H8
102.3
77.1
67 56.1
54.1
15.2
11.5
15.5
Type No. of valve positions
VABM 4-24
H9
12.4
Type
H10
5.5
VABM
No. of valve positions
8
9
10
6
7
4
5
12
16
20
24
L1
103
113.5
124
134.5
145
155.5
166
187
229
271
313
H11
54.8
H12
4.8
L4
10.5
Size 10
L5
57.3
Size 10
L2
94
104.5
115
125.5
136
146.5
157
178
220
262
304
L6
2.5
L7
4.5
L8
36
L3
31.5
42
52.5
63
73.5
84
94.5
115.5
157.5
199.5
241.5
L9
20
L10
42.5
2013/05 – Subject to change
Internet: www.festo.com/catalog/...
55
Product Range and Company Overview
A Complete Suite of Automation Services
Our experienced engineers provide complete support at every stage of your development process, including: conceptualization, analysis, engineering, design, assembly, documentation, validation, and production.
Custom Automation Components
Complete custom engineered solutions
Custom Control Cabinets
Comprehensive engineering support and on-site services
Complete Systems
Shipment, stocking and storage services
The Broadest Range of Automation Components
With a comprehensive line of more than 30,000 automation components, Festo is capable of solving the most complex automation requirements.
Electromechanical
Electromechanical actuators, motors, controllers & drives
Pneumatics
Pneumatic linear and rotary actuators, valves, and air supply
PLCs and I/O Devices
PLC's, operator interfaces, sensors and I/O devices
Supporting Advanced Automation… As No One Else Can!
Festo is a leading global manufacturer of pneumatic and electromechanical systems, components and controls for industrial automation, with more than 12,000 employees in 56 national headquarters serving more than 180 countries. For more than 80 years, Festo has continuously elevated the state of manufacturing with innovations and optimized motion control solutions that deliver higher performing, more profitable automated manufacturing and processing equipment. Our dedication to the advancement of automation extends beyond technology to the education and development of current and future automation and robotics designers with simulation tools, teaching programs, and on-site services.
Quality Assurance, ISO 9001 and ISO 14001 Certifications
Festo Corporation is committed to supply all Festo products and services that will meet or exceed our customers’ requirements in product quality, delivery, customer service and satisfaction.
To meet this commitment, we strive to ensure a consistent, integrated, and systematic approach to management that will meet or exceed the requirements of the ISO 9001 standard for Quality
Management and the ISO 14001 standard for Environmental Management.
© Copyright 2008, Festo Corporation. While every effort is made to ensure that all dimensions and specifications are correct, Festo cannot guarantee that publications are completely free of any error, in particular typing or printing errors. Accordingly, Festo cannot be held responsible for the same. For Liability and
Warranty conditions, refer to our “Terms and Conditions of Sale”, available from your local Festo office. All rights reserved. No part of this publication may be reproduced, distributed, or transmitted in any form or by any means, electronic, mechanical, photocopying or otherwise, without the prior written permission of
Festo. All technical data subject to change according to technical update.
Printed on recycled paper at New Horizon Graphic, Inc., FSC certified as an environmentally friendly printing plant.
Festo North America
Festo Regional Contact Center
5300 Explorer Drive
Mississauga, Ontario L4W 5G4
Canada
USA Customers:
For ordering assistance,
Call:
1.800.99.FESTO (1.800.993.3786)
Fax:
1.800.96.FESTO (1.800.963.3786)
Email: [email protected]
For technical support,
Call:
1.866.GO.FESTO (1.866.463.3786)
Fax:
1.800.96.FESTO (1.800.963.3786)
Email: [email protected]
Canadian Customers:
Call:
1.877.GO.FESTO (1.877.463.3786)
Fax:
1.877.FX.FESTO (1.877.393.3786)
Email: [email protected]
USA Headquarters
Festo Corporation
395 Moreland Road
P.O. Box 18023
Hauppauge, NY 11788, USA www.festo.com/us
USA Sales Offices
Appleton
North 922 Tower View Drive, Suite N
Greenville, WI 54942, USA
Boston
120 Presidential Way, Suite 330
Woburn, MA 01801, USA
Chicago
1441 East Business Center Drive
Mt. Prospect, IL 60056, USA
Dallas
1825 Lakeway Drive, Suite 600
Lewisville, TX 75057, USA
Detroit – Automotive Engineering Center
2601 Cambridge Court, Suite 320
Auburn Hills, MI 48326, USA
New York
395 Moreland Road
Hauppauge, NY 11788, USA
Silicon Valley
4935 Southfront Road, Suite F
Livermore, CA 94550, USA
Central USA
Festo Corporation
1441 East Business
Center Drive
Mt. Prospect, IL 60056, USA
Phone: 1.847.759.2600
Fax: 1.847.768.9480
United States
USA Headquarters, East: Festo Corp., 395 Moreland Road, Hauppauge, NY 11788
Phone: 1.631.435.0800; Fax: 1.631.435.8026;
Email: [email protected]
www.festo.com/us
Canada
Headquarters: Festo Inc., 5300 Explorer Drive, Mississauga, Ontario L4W 5G4
Phone: 1.905.624.9000; Fax: 1.905.624.9001;
Email: [email protected]
www.festo.ca
Mexico
Headquarters: Festo Pneumatic, S.A., Av. Ceylán 3, Col. Tequesquinahuac,
54020 Tlalnepantla, Edo. de México
Phone: 011 52 [55] 53 21 66 00; Fax: 011 52 [55] 53 21 66 65;
Email: [email protected]
www.festo.com/mx
Western USA
Festo Corporation
4935 Southfront Road,
Suite F
Livermore, CA 94550, USA
Phone: 1.925.371.1099
Fax: 1.925.245.1286
Festo Worldwide
Argentina Australia Austria Belarus Belgium Brazil Bulgaria Canada Chile China Colombia Croatia Czech Republic Denmark
Estonia Finland France Germany Great Britain Greece Hong Kong Hungary India Indonesia Iran Ireland Israel Italy Japan Latvia
Lithuania Malaysia Mexico Netherlands New Zealand
Slovakia Slovenia South Africa South Korea Spain
Norway
Sweden
Peru
Switzerland
Philippines
Taiwan
Poland
Thailand
Romania
Turkey Ukraine
Russia Serbia
United States
Singapore
Venezuela
www.festo.com
advertisement
Key Features
- Festo-specific interface (I-Port)
- Cost savings
- Direct and simple networking
- High protection to IP65/67
- Universal connection technology
- Decentralised installation of the bus node
- Basic diagnostics
Related manuals
Frequently Answers and Questions
What are the supported protocols for the CTEU fieldbus modules?
What is the purpose of the I-Port interface?
How can I connect a second valve terminal to a CTEU?
advertisement
Table of contents
- 2 Key features
- 5 Peripherals overview
- 6 Key features – Diagnostics
- 7 Key features – Power supply
- 9 Technical data – I-Port interface/IO-Link of the valve terminal VTUG
- 9 technical data
- 9 Pin allocation
- 10 Dimensions
- 10 Accessories –
- 10 Electrical interface
- 10 Connection technology
- 10 Straight
- 10 Inscription label
- 10 Connecting cable
- 11 Technical data – E-box CAPC
- 11 technical data
- 12 Dimensions
- 12 Pin allocation
- 12 Accessories – CAPC
- 12 E-box
- 12 H-rail mounting
- 12 Connecting cable
- 13 Technical data – CTEU-CO
- 14 technical data
- 15 Dimensions
- 15 Pin allocation
- 16 Connection and display components
- 17 Accessories – CTEU-CO
- 17 Bus node
- 17 Bus connection
- 17 Fitting
- 17 Plug socket
- 17 Manual
- 18 Technical data – CTEU-DN
- 19 technical data
- 20 Dimensions
- 20 Pin allocation
- 21 Connection and display components
- 22 Accessories – CTEU-DN
- 22 Bus node
- 22 Bus connection
- 22 Fitting
- 22 Plug socket
- 22 Manual
- 23 Technical data – CTEU-CC
- 24 technical data
- 25 Dimensions
- 25 Pin allocation
- 26 Connection and display components
- 27 Accessories – CTEU-CC-Link
- 27 Bus node
- 27 Bus connection
- 27 Fitting
- 27 Plug socket
- 28 Technical data – CTEU-PB
- 29 technical data
- 30 Dimensions
- 30 Pin allocation
- 31 Connection and display components
- 32 Accessories – CTEU-PB
- 32 Bus node
- 32 Bus connection
- 32 Fitting
- 32 Plug socket
- 32 Manual
- 33 Technical data – CTEU-EC
- 34 technical data
- 35 Dimensions
- 35 Pin allocation
- 35 Connection and display components
- 36 Accessories – CTEU-EC
- 36 Bus node
- 36 Bus connection
- 36 Plug socket
- 36 Manual
- 37 Technical data – Interface CPX-CTEL
- 39 technical data
- 40 Connection and display components
- 40 Pin allocation –
- 40 Dimensions
- 41 Accessories – Interface CPX-CTEL
- 41 CPXCTEL master
- 41 Bus connection
- 41 Connecting cable
- 41 Manual
- 42 Technical data – CPV valve terminals
- 42 technical data
- 43 Connection and display components
- 43 Pin allocation –
- 43 Dimensions
- 44 Accessories – CPV valve terminals
- 44 I-Port node
- 44 Connection technology for I/O-Link
- 44 Connecting cable
- 45 Technical data – MPA-L valve terminals
- 45 technical data
- 46 Connection and display components
- 46 Pin allocation –
- 46 Dimensions
- 47 Accessories – MPA-L valve terminals
- 47 I-Port node
- 47 Connection technology for I/O-Link
- 47 Connecting cable
- 48 Technical data – Input modules CTSL
- 48 technical data
- 50 Pin allocation –
- 51 Pin allocation –
- 52 Dimensions
- 53 Accessories – Input modules CTSL
- 53 Input modules
- 53 Plug connector
- 53 Connecting cables
- 53 Inscription label holder
- 54 Example of a valve terminal VTUG with I-Port interface
- 54 Dimensions