Solo Ultra Extinguishing Panel
FIRE SUPPRESSION UNITS
PRODUCT CODE
NF-SOLO-ULTX
SOLO ULTRA EXTINGUISHING PANEL
FEATURES
ƒƒ For use on Land and Marine
transportation, Plant and Mobile
risks.
ƒƒ Dual Linear heat or point detection
loops with full fault monitoring.
ƒƒ Can be programmed for:
–– Manual only
–– Single stage detection, alarm
and release
–– Full Two stage detection, alarm
and release
ƒƒ Automatic Engine/fuel/fan shutoff
capability via volt free contacts.
NF-SOLO-ULTX
SOLO ULTRA
EXTINGUISHING CONTROL PANEL
ƒƒ Variable time delay for actuation.
ƒƒ Suppression activation button with
anti-tamper tag.
ƒƒ Universal 12 or 30 V DC electrical
power.
DESCRIPTION
ƒƒ Low input power consumption in
The Solo Ultra is a combination extinguishing control panel. It combines
detection zones with suppression control in a compact package.
ƒƒ Full fault monitoring on all detector
The design and configurable options allow for flexibility and versatility over a
wide range of applications.
ƒƒ Supports up to 6 Stat-X fire
Tamper evident tag technology and strict electronic design rules have
proven highly effective. To eliminate the inherent hazards of microprocessor
control, the Solo Ultra uses a fully parallel path programmable logic device,
which is coded using the VHDL language that was commissioned by the
US Department of Defence and is used for high reliability and safety critical
applications.
ƒƒ The unit is reverse polarity, transient
“PARKED/MOORED” mode.
and extinguisher circuits.
extinguishers.
and EMC protected.
ƒƒ An internal alarm sounder and
relay drive additional external
audible alarm units up to 2 Amps.
Uncommitted relay change-over
contacts for interface with fuel
shutoff, engine/fan shutdown etc.
www.technoswitch.co.za
E & OE Document No: DS NF-SOLO-ULTX 170207
FIRE SUPPRESSION UNITS
PRODUCT CODE
NF-SOLO-ULTX
SOLO ULTRA EXTINGUISHING PANEL
TECHNICAL SPECIFICATIONS
Power Supply
Operating Voltage
11 to 32 V DC
Quiescent Current Ign Off
Ign On
8.5 mA Typ (excluding external load currents)
16 mA Typ (excluding external load currents)
Max Alarm Current Draw
100 mA (excluding external load currents)
Max current draw
3 A (including extinguisher operate current)
Parked current draw
8.5 mA Typ
Suppressor Activation
Discharge Current
1 A to 4 A depending on voltage and number of suppressors
(Stat-X = 1.8 Ω nominal each unit).
Up to 2 units on 12 V, 4 units max on 24 V Connect in series with
bidirectional catch diodes across each element (see manual).
Current/Time Limit
Output is Vin via switch with 6 Ω in series.
Constant I2T limit = 9 Amp 2*Seconds
Monitoring current
<4 mA, Fault if loop R>300, 12 V max o/c voltage
Aux In (Override key)
Monitoring current
1.2 mA Nominal
Sense Logic
Norm S/C, >1K active typ.
Sensor Loop Inputs 1+2 Max Output voltage
12 V DC regulated, filtered and transient protected
Output current limit
25 mA per loop
Alarm condition threshold
<700 Ω Nominal
Fault condition threshold
Approximately 20 kΩ
End Of Line Resistor
10 kΩ
Fault monitoring
Open circuit or ground fault = fault indication
Alarm Output
Relay Contacts
2 A @ Vin DC (Vin thru NO relay circuit)
VFC Output
Relay Contacts (volt free)
2 A @ 24 V DC (relay changeover circuit)
Mechanical
Dimensions (H x W x D) mm
82 x 83 x 25
Mounting
75 mm diameter round hole,
retained by four #6*25 self tapping screws
Via 3 * 6 way terminal block accepting <1 mm2 wires with ferrules
Connections
ORDERING INFORMATION
Product Code
Product Description
NF-SOLO-ULTX
Solo Ultra Extinguishing Control Panel
NF-SOLO-SOVX
Solo Sovereign Extinguishing Control Panel
Please refer to the current Technoswitch Price List for the complete Stat-X Aerosol Unit and Peripheral range.
ƒƒDisclaimer
Although the contents of our product literature have been prepared with the greatest care, Technoswitch can accept no liability whatsoever for any direct or indirect damages of any kind
that may arise due to either errors or omissions in them, or amendments to products or other specifications following publication.
www.technoswitch.co.za
HEAD OFFICE - JOHANNESBURG
Cussonia Park, Ridge Road, Laser Park, Johannesburg
PO Box 1752, Randpark Ridge, South Africa, 2156
T +27 (0)11 794 9144 F +27 (0)11 794 9148 E info@technoswitch.co.za
CAPE TOWN
T +27 (0)21 948 4575 F +27 (0)86 638 5184
E info.ct@technoswitch.co.za
DURBAN
T +27 (0)31 266 8843 F +27 (0)86 750 6912
E info.dbn@technoswitch.co.za
E & OE Document No: DS NF-SOLO-ULTX 170207
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising