Multi Variable Air Conditioners Duct Type Indoor Unit

Multi Variable Air Conditioners Duct Type Indoor Unit
Multi Variable Air Conditioners
Duct Type Indoor Unit Owner’s Manual
Please read this manual carefully before operating
USER NOTICES
☆
When the unit is operating, the total capacity of the indoor units should be no more than the
capacity of outdoor unit. Otherwise, it can cause the shortage of cooling capacity (heating
capacity) of each indoor unit.
☆ The power supply of the indoor unit must be the unified power supply. The indoor unit
cannot have the individual power switch, and the entire indoor unit can only be controlled
by one main power control. Disconnect the main power of all the indoor units before
cleaning.
☆ In order to start the unit successfully, the general power supply switch of the air-conditioning
units should be turned to the “ON” position for 8 hours before running.
☆ After each of indoor units received the stop running signal, the fan motor of the indoor unit
will use the surplus cool or surplus heat of the heat exchanger go on running for 20-70
seconds, this is the preparation for the next time use and this is the normal phenomenon.
☆ When the selected mode of the indoor unit conflict with the mode of outdoor unit, after 5
seconds, the wired remote control will display the operation conflict, the indoor unit will stop
running, then to unify the running modes of the indoor unit and outdoor unit, the unit will
get right. There is no conflict in the COOL mode and DRY mode, the FAN mode will not
conflict with any other modes.
☆ The appliance shall not be installed in the laundry
☆ An all-pole disconnection switch having a contact separation of at least 3mm in all poles
should be connected in fixed wiring
1
Safety Precautions
Before using the appliance, read this manual thoroughly and operate under its direction.
“WARNING” and “ATTENTION” have the follow ing meanings in these instructions:
1.
2.
WARNNING! :This mark indicates procedures, which if improperly performed, might lead to
the death or serious injury of the users.
ATTENTION! :This mark indicates procedures, which if improperly performed, might possibly
result in personal injury to the user, or damage to property.
WARNNING !
●
When install the unit, please relegate to the special arrangement maintenance center. If improper performed, it
can cause the water leakage, electric shock and fire etc. accidents.
●
Please install the unit to a steady and stable place. If the intension is inadequate, the unit will drop off and will
lead to the personal injury and death.
●
In order to make sure the right water drainage, the installation of drainage pipe should be according to the
installation methods of this manual, and also adopt the heat retaining measure to prevent the water condensing. If
installed improperly, it will cause water leakage and might moisten the furniture.
●
Do not use or store the combustible and detonatable materials near the air conditioner.
●
When malfunction happed (there is the burning smell etc.), please power off the general power supply of the
units.
● Keep the well ventilation in order to avoid the oxygen lack.
● Do not insert hands or other objects into the inlet or outlet grille.
● Due to the long time use, please check the mounting frame if broken or not.
● Do not refit the unit. When need to maintenance or remove the unit, please contact with the local dealer or the
professional.
ATTENTION!:
●
Ensure the power supply correspond to the nameplate and check the security of the power source before
installation.
●
Make sure that the wires, pipes and drain hose are properly connected before operation to avoid a fire or electric
shock.
●
The general power supply must be reliably earthed! To ensure the units are earthed availably, to avoid the electric
shock. The earth wire can’t be connected to the gas pipe, water pipe, wires of the lightning rod and telephone.
●
Once the units start, need at least more than 5 minutes running then it could be turned off.
●
Don’t let children operate the units.
●
Do not operate the units with wet hands.
●
When cleaning the air conditioner or changing filters, please turn off the general power supply of the units firstly.
●
Switch off power source when the units will not be operated for a long period.
●
Do not expose the units to the water place or the damp place or the corrosion environment.
●
After installation, when electrified the electric leakage should be tested.
2
The selection of installation place and notice of the air conditioner unit
●
The selection of the installation place of the air conditioner unit
The installation must accord with the national and local safe criterion.
Since the quality of installation would affect the operation directly, user should contact the seller
and have the conditioner installed and tested by the professional install personnel according to
the install instruction instead of install by himself/herself.
Only connect the power after all the installation works are finished.
● The selection of the installation place of the indoor unit
☆ Prevent direct sun burn.
☆ Make sure that the top steeve, ceiling, and the structure of the construction etc. is strong enough to bear the weight
of the unit.
☆ The drainage pipe is easy to drain.
☆ The air flow is not blocked at the outlet and intake vents.
☆ The connecting pipe indoor and outdoor can by lead to outside conveniently.
☆ The unit cannot be installed in the place where stored the flammability, easy exploded thing or the place where
would have leakage of flammability and exploded gas.
☆ The unit cannot be installed in the place where has the corrupt gas and serious dust, saline fog, lampblack and
huge humidity.
Note!
The air conditioner unit installed in the following place may have malfunction, if the malfunction cannot prevent,
please contact the Registered Office Of MIRC ELECTRONICS LTD., MUMAI.
①the place with greasy all around; ②the seashore place with salinity and alkali; ③the place with vulcanized
gas( such as vulcanized hot spring); ④the place with high frequency equipment ( such as wireless equipment, electric
welding machine and medical treatment equipment);⑤the place with special environment.
●
The electric cord disposal
☆ The cord disposal should be installed according to the National Principal.
☆ The power must use the rated voltage and the electric circuit specific for air conditioner unit.
☆ Please don’t pull the power cord vigorously.
☆ All the electric equipment should be installed by the professional personnel according to the local law, regulation
and this instruction.
☆ The power cord diameter should be big enough, the destroyed power cord and connecting cord should be replaced
by the specific cord.
3
The selection of installation place and notice of the air conditioner unit
☆ The earthing should reliably connected with the specific earthing equipment in the architecture, and this should be
done by the professional personnel. There must be creepage protection switch and air switch with enough capacity
in the rated circuit (reference the following form). The air switch should maintain the functions of magnetic
de-buckle and heat de-buckle to assure the protection when circuit-short and overload happen.
●
☆
Earthing requirement
The air conditioner is class I appliance, so please do take the reliable measurement to earthing.
☆ The yellow and green cord in the air conditioner unit is earthing cord which cannot be used for other purpose, and
cut off, as well as fixed up with screw. Otherwise, it would lead electric shock.
☆ The reliable earthing terminal must be offered by the user power. And please don’t connect the earthing cord to the
following place:
①Tap water pipe; ② Coal gas pipe; ③ Ejection pipe; ④ The place that is consider to be not reliable by the
professional personnel.
●
The attachment used for installation
Every attachment used for installation of the indoor and outdoor unit please refer to the packing list in every
individual package carton.
4
● Install of the ducted type indoor unit
Shape dimension diagram of indoor unit
The following figure is applicable to the indoor units of OV(L)-R22P/NaB-K 、OV(L)-R28P/NaB-K 、
OV(L)-R36P/NaB-K 、OV(L)-R22PS/NaB-K 、OV(L)-R28PS/NaB-K 、 OV
(L)-R36PS/NaB-K 、
、
、
、
、OV(L)-R28PS/HB-K、
(
L
)
-R22P/HB-K
OV
(
L
)
-R28P/HB-K
OV
(
L
)
-R36P/HB-K
OV
(L)
-R22PS/HB-K
OV
、
、
、
OV
(L)-R36PS/HB-K OV
(L)-R22P/NaB-D OV
(L)-R28P/NaB-D OV
(L)-R36P/NaB-D。
Fig.1
The following figure is applicable to the indoor units of OV(L)-R45P/NaB-K、OV(L)-R56P/NaB-K、OV(L)-R71P/NaB-K、
OV
(L)-R90P/NaB-K、OV
(L)-R112P/NaB-K 、OV
(L)-R140P/NaB-K、OV
(L)-R45PS/NaB-K、OV(L)-R56PS/NaB-K 、
(L)-R45P/HB-K、
OV
(L)-R71PS/NaB-K、OV
(L)-R90PS/NaB-K、OV(L)-R112PS/NaB-K、OV
(L)-R140PS/NaB-K、OV
OV
(L)-R56P/HB-K 、OV
(L)-R71P/HB-K、OV(L)-R90P/HB-K、OV(L)-R112P/HB-K、OV
(L)-R140P/HB-K、
OV(L)-R45PS/HB-K、OV
(L)-R56PS/HB-K、OV
(L)-R71PS/HB-K、OV
(L)-R90PS/HB-K、OV
(L)-R112PS/HB-K、
OV(L)-R140PS/HB-K、OV
(L)-R56P/NaB-D、OV
(L)-R71P/NaB-D、OV
(L)-R90P/NaB-D、OV
(L)-R112P/NaB-D 、
OV(L)-R140P/NaB-D。
5
Install of the ducted type indoor unit
Fig.2
1、Look into from air outlet vent, the wiring is in the left of the unit.
2、The method of wind circle can be selected to bottom back wind or rear back wing according to the installation
circumstance of the reality.
MODEL NO.
OV(L)-R45P/NaB-K OV(L)-R45PS/NaB-K
OV(L)-R45P/HB-K OV(L)-R45PS/HB-K
OV(L)-R56P/NaB-K 、 OV(L)-R71P/NaB-K
OV(L)-R56PS/NaB-K 、 OV(L)-R71PS/NaB-K
OV(L)-R56P/HB-K
、
OV(L)-R71P/HB-K
OV(L)-R56PS/HB-K 、 OV(L)-R71PS/HB-K
OV(L)-R56P/NaB-D
OV(L)-R90P/NaB-K 、 OV(L)-R112P/NaB-K 、
OV(L)-R90PS/NaB-K 、 OV(L)-R112PS/NaB-K 、
OV(L)-R90P/HB-K 、 OV(L)-R112P/HB-K 、
OV(L)-R90PS/HB-K 、 OV(L)-R112PS/HB-K 、
OV(L)-R90P/NaB-D
OV(L)-R140P/NaB-K 、 OV(L)-R140PS/NaB-K
OV(L)-R140P/HB-K 、 OV(L)-R140PS/HB-K
OV(L)-R140P/NaB-D
●
A
B
C
D
E
F
G
H
I
J
932
430
738
892
980
721
738
125
203
266
1114
420
918
1074
1159
736
1010
207
207
300
1382
420
1155
1340
1425
736
1280
207
250
300
1382
420
1155
1340
1425
736
1280
207
250
300
Schematic diagram of installation spaces
Nut with
washer
Nut spring
pad
Fig.3
6
Install of ducted type indoor unit
● Schematic diagram of installation spaces
1. Ensure that the latches at top are firm enough to stand the weight of unit.
2. Convenience to drain by the drain hose.
3. There is no obstruct around intake and outlet vent keep well ventilation.
4. Ensure the install distance of the indoor unit as shown in fig.3, ensure the necessary space for care and
maintenance.
5. Far from space heater, leakage of combustible gas and place with fog.
6. This unit is model cassette type (hide installation type is hided in ceiling), as shown in fig.6.
7. Indoor unit, outdoor unit, power cord, and connection pipe should have at least 1m’s distance with TV set, radio, to
prevent the appearance of disturb picture and noise happened on the above mentioned home appliance. (If the
electric wave were strong, even though 1m had maintained, noise would still happened.
●
Install the indoor unit
1. Insert the M10 inflate bolt to the hole then nail the iron nails into the bolts. The distance between holes is shown in
fig.1. The install of inflate bolt is shown in fig.4.
Fig.5
Fig.4
≤48
2. Install the hook on the unit, as shown in fig.5.
3. Install the indoor unit to the ceiling as shown in fig.6.
Fig.6
Note:
☆ To open an opening on the ceiling, probably reinforce would to be
done to keep the ceiling smooth and to prevent vibration. Please
consult user or builder for detail.
7
Install of ducted type indoor unit
☆ If the ceiling if not strong enough, an angle iron stand can be
made and has the unit fixed on the stand.
●
Water lever test for indoor unit
The water lever test must be tested after installing the indoor unit to make the front, back, left and right or the unit are
horizontal, as shown below.
Horizontal tester
●
Install of wind supply pipe
Ceiling hoisting
Back wind
Wind supply
Back wind
Fig.7 Sketch of install ducted type unit
No.
1
Name
Hoisting
2
Back wind
pipe
3
Ducted type
indoor unit
4
Back wind
vent
5
Wind supply
bent
6
Wind
outlet
Note:Fig.7 only shows the install of rear back wind vent, button back wind vent can also been installed according to
the actual install need. The method of install is similar to the rear back wind vent’s. The wind supply pipe, which is
rectangle or circle and connect with the wind vent of the indoor unit, should at least keep one open. The circle wind
pipe type should adopt circle preservation pipe to transmit cool (heat) wind to room. The circle wind pipe should add
a transitionary pipe, which size should match the size of wind supply vent of the unit. After connecting the
transitionary pipe, install the circle wind outlet vent connection pipe, whose longest length to every individual wind
outlet vent should not over 10m. Ducted type indoor unit model 70 can share 3 trainsitional pipe, while model
100,120 can share 4. The transitional pipe, whose straight length is 200, and circle wind outlet connection pipe,
whose diameter is 200, produced by our company, can be ordered separately as standard fittings. Model 50 and the
model below it do not share circle wind vent. The following is the diagram for install circle wind pipe.
8
Install of ducted type indoor unit
Note: 1、The longest length of wind pipe means the general length of the wing supply pipe to the farthest
wind supply vent plus the general length of back wind pipe to the relative farthest back wind vent.
2、To the unit with auxiliary heater, if the circle wind pipe is need to connected, the straight
length of trainsitional wind pipe should not shorter than 200mm.
1
2
3
4
5
6
7
Number
1
2
3
4
5
6
7
Name
Screw
Back wind
pipe
Ducted type
indoor unit
Back wind
vent
Trainsitional
wind pipe
Wind supply
pipe
Wind outlet
pipe
● Install proceed of circle wind pipe
1. Preinstall the circle wing outlet vent on the transitional pipe and fixed it by screw;
2. Sheath the transitional wind pipe on the wind outlet vent and connect by rivet;
3. Sheath the wind outlet pipe on circle wind outlet vent and prick it tightly by strap, so the connection with the unit
finished. Other proceeds are omitted.
● Type and dimension of the back wind, wind supply vent
A
40
B
Product model
OV(L)-R22,28,36P(S)/HB-K
OV(L)-R22,28,36P(S)/NaB-K
OV(L)-R22,28,36P(S)/NaB-D
OV(L)-R45P(S)/HB-K
OV(L)-R45P(S)/NaB-K
OV(L)-R56,71P(S)/HB-K
OV(L)-R56,71P(S)/NaB-K
OV(L)-R56,71P(S)/NaB-D
O V ( L ) - R 9 0 , 11 2 , 1 4 0 P ( S ) / N a B - K
O V ( L ) - R 9 0 , 11 2 , 1 4 0 P ( S ) / N a B - K
O V ( L ) - R 9 0 , 11 2 , 1 4 0 P ( S ) / N a B - D
9
Dimention of
wind supply port
A
B
Dimention of
back wind port
A
B
125
635
203
738
125
738
203
738
207
918
250
1010
207
11 5 5
250
1280
● Install of ducted type indoor unit
Install the back wind pipe
1. Rear back wind type is adopted for the unit when the unit leaves the factory, and the back wind cover is installed at
the bottom as shown below.
2. When button back wind vent is needed to adopt, change the position of rectangle flange and back wind cover.
Ractangle flange
Rear back wind
Button back wind
Back wind cover
3. Connect the back wind pipe on the back wind vent of the indoor unit by rivet, and connect the other terminal to
back wind vent. In order to adjust the weight conveniently, pucker a canvas wind pipe, and strengthen it with 8# iron
thread.
☆ Install type can be selected according to the overall plans and all factors into the conditions of architect and
maintenance, as shown in fig.8a, and fig.8b.
5
4
5
Wind supply
3
Wind supply
2
4
1
Back wind
6
1
Back wind
Install the back wind pipe(b)
Install the back wind pipe (a)
Fig.8 Install the back wind pipe
No.
Name
No.
Name
1
Back wind vent (with filter)
4
Indoor unit
2
Canvas wind pipe
5
Wind supply pipe
3
Back wind pipe
6
Test grill
10
Install of ducted type indoor unit
● Install new wind pipe
1. When new wind pipe is need to be connected, cut the new wind baffle as shown in fig.9. Plug up the gap
of new wind baffle by sponge if new wind pipe is not used.
2. Install the circle flange so that the new wind pipe can be connected as fig.10.
Cut off
Cut off
New wind
baffle
Circle wind pipe
Fig.9
Fig.10
3. Well sealed and heat preservation should be done for both wind pipe and circle flange pipe.
4. New wind should be the air after filtrate treatment.
Attention:
● There should be thermal insulation layers around the air delivery and air return ducts as well as on
the new air ducts to protect against heat losses and condensation. Adhere the plastic nails onto the
ducts, and then attach a layer of insulation cloth with the tinfoil onto the ducts. Fix the plastic nail
and then seal tightly the joints by way of tinfoil tapes. Some other materials with good thermal
insulation properties can also be used.
● The air delivery and air return ducts should be fixed to the prefabricated ceiling boards with iron
stands. The joints of the air ducts should be sealed tightly to prevent from air leakage.
● The designing and operation of the air ducts should comply with the related state standards and
procedures for engineering.
● It is recommended to leave at least a space of 150mm between the edge of the air return duct and
the wall, and a filter screen should be placed at the air return opening.
● Muffling and vibration reduction should be taken into consideration during the designing and
operation of the air ducts. In addition, the noise source should be kept away from the crowds. It is
absolutely not allowed to design the placement of the air return opening right above the head of the
users (in the offices, lounges or other public sites).
● Installation of Condensed Water Pipes
☆ The condensed water pipes should be kept at 5—10 degrees of gradient to facilitate discharge of the
condensed water. Thermal insulation materials should be placed at the joints of the condensed water
pipes so as to prevent from dew condensation. (As shown in Fig.11)
There is an outlet for condensed water on the left and right side of the indoor unit. When the outlet of
the condensed water is determined, the outlet on the opposite side should be blocked with a stopper and
11
Install of ducted type indoor unit
wrapped with strings so as to prevent the water from leaking. Thermal materials will be used to wrap
the sealing properly.
Thermal insulation layer
water pipe
Cover of the pipe
Fig.11: Thermal insulation of the condensed water pipe
☆ The outlet for condensed water on the right side is blocked with a stopper when the product leaves
the factory.
Attention: It must be made sure that there is no leakage at the joints of the condensed
water pipes.
●
Designing of the Drainage Pipelines
☆ The drainage pipes should be kept at a certain gradient (1/50—1/100) so as to avoid bulges of pipes
where there might be water bends.
☆ When connecting the drainage pipes with the unit, care must be taken not to exert too much force
on the pipelines of either side of the unit, and the pipes should be fixed as close to the unit as
possible.
☆ The drainage pipes can be the locally purchased hard PVC pipes for common purposes. When
making the connections, the end of the PVC pipe should be inserted into the drainage hole. Use
drainage hose and wire bondage to fix it tightly. It is not allowed to use adhesive glue to join the
drainage hole and the drainage tube.
☆ When the drainage pipeline is laid for a couple of units, the position of the shared pipeline should
be approximately 100mm lower than the drainage outlet of each unit. In this case, some
special-purpose pipes with thicker walls sill be used.
● Installation of Drainage Pipeline
1. Diameter of drainage pipe should not be less than that of connecting pipe.(PE pipes: size: outer
diameter 255mm; wall thickness ≥1.5mm)
2.
Drain pipe should be as short as possible and its gradient at least should be 1/100 in order to
avoid forming air pocket.
12
Install of ducted type indoor unit
3.
If there is no enough gradient for discharge hose, riser pipe for drainage should be installed.
4. In order to prevent the discharge hose from bending, mutual distance of hanger brackets
should be at least 1.-1.5mm.
correct gradient is
over
wrong
5.
Insert discharge hose to drain outlet and then screw the pipe clamp up.
6.
For heat insulation, wrap the clamp of discharge hose with sponge.
7. Execute heat insulation to the indoor discharge hose.
●
Cautions of Riser Pipe for drainage
The installation height of riser pipe for drainage should less than 850mm.It should be perpendicular
to the unit and the distance between them should be less than 800mm.
hanger
bracket
ceiling
riser pipe for
drainage
discharge hose
accessories
clam p accessories
13
Install of ducted type indoor unit
Note:
●
The height of inclination of attached discharge hose should be within 75mm to prevent the drain
outlet from withstanding extra force.
●
If multi-discharge hoses converge, please follow the steps below.
joints for joined
d ischarge h ose
S electe d joints for joined discharge ho se sho uld be suitable
for run nin g cap a city of the unit.
discharge hose
accessories
●
Test of Drainage System
1.
Please test the drainage system after installation of electric appliances.
2.
During the test, check if the water correctly flows through the pipeline and observe the joints
to make sure that there is no leak. If the unit installs in new house, it is advised to execute the test
before decoration of the ceiling.
● Testing on the Drainage System
☆ Upon completion of the installation of the electric appliances, the testing on the drainage system
should be performed.
☆ During the testing, it should be made sure that the water flows through the pipeline in the correct
direction. Careful observations should be made on the joints to ensure that there is no leakage of
water at the joints.
☆ In the case that the unit is to be installed in a new building, it is recommended that the testing be
made prior to the decoration of the ceiling.
● Functional DIP switch S7 and Introduction to Address Code
☆ Introduction to Functional DIP Switch S7 and the Setting
14
Install of ducted type indoor unit
Caution ! Functional DIP switch S7 locates on the mainboard
of indoor unit. Only when the revision of default setting is required by
users, it can be operated or its original position should be maintained.
Functional DIP switch S7
DIP
switch
1(S / R)
2(L / I)
Code Setting
Description
0 (ON )
Memory mode
setting
Energized
Energized
standby
recovery
(S)
(R)
Control method
Wired control
Remote
setting
(L)
control (I)
Master
3(M / S)
Master/slave indoor
unit setting
indoor unit
(M)
Collection point
Slave indoor
unit(S)
Return air
4(I / O) setting for ambient
inlet (I)
temp.
Low static
5(L / H)
1
High-low static
setting of fan
receiver(O)
High static
pressure
pressure
(L)
(H)
Specific function of each function DIP switch is as follows:
DIP switch 1(S/R)——Memory mode setting; it includes energized standby mode and energized
recovery mode. Energized standby mode is that: after the unit resumes power supply,
the previous setting parameters will be maintained but cannot automatically run and
such setting is factory setting (dialing the DIP switch to “ON” position); For example,
setting parameters of a indoor unit are high fan speed before de-energization and 24
and after resuming power supply, the unit will be in standby status; Then manually turn
on the unit and its parameters are still high fan speed and 24
. Energized recovery
mode is that: after the unit resumes power supply, not only it will keep the previous
setting but also can automatically run; But if the unit is in turnoff status before
de-energization, it will still be that status after resuming power supply.
15
Install of ducted type indoor unit
DIP switch 2(L/I)——Control mode; it includes wired control mode and remote control mode. Wired
control mode is that: control the running of indoor unit by wired controller, which
is factory setting (dialing the DIP switch to “ON” position); When the setting is
wired control mode, “Memory mode setting” and “Master/slave indoor unit
setting” of S7 are invalid which can be directly set on the wired controller. Remote
control mode is that: control the running of indoor unit by remote controller; when
the setting is remote control mode, its functional code must be set in S7.
DIP switch 3(M/S)——Master/slave indoor unit setting; it is master/slave setting of indoor unit
running mode, which is mainly used for people’ priority requirements (such as
leaders, patients, etc.). The factory setting is master indoor unit( dialing the DIP
switch to “ON” position). When settings of all indoor units are slave indoor units,
outdoor unit will run in the mode of firstly started slave indoor unit. If the mode
of later started slave indoor unit and mode of firstly started slave indoor unit
conflict, the conflict modes error will be warned by the system and later started
indoor unit cannot run. In that case, the running of the unit is decided by firstly
started slave indoor unit.
When there is only one indoor unit that is set to be master indoor unit, in that case,
no matter if the master indoor unit is firstly started, the conflict mode error will be
warned by slave indoor unit once the mode of slave indoor unit and the mode of
master indoor unit conflict (except for turnoff mode of master/slave indoor unit).
And the unit will firstly run at the mode of master indoor unit
When there are multi indoor units that are set to be master indoor units, the unit
will run at the mode of master indoor unit with min. address code. When the
indoor unit with min. address code changes to the running status from turnoff
status, modes of other master indoor units or slave indoor unit should be in the
same mode with it, or the conflict mode error will be warned. Therefore, when
there are multi master indoor units, set the address code from high to low
according to priority.
16
Install of ducted type indoor unit
DIP switch 4(I/O)——Collection point setting of ambient temp.; the setting is mainly used when there
is high differential between temperatures of air conditioning area and return air of
the unit. The setting is valid only when there is receiver and includes collection
points setting of temperatures of return air inlet e and receiver head. The factory
setting is the collection points setting of temperature of return air inlet( dialing the
DIP switch to the “ON” position.
DIP switch 5(L/H)——High-low static pressure setting of fan; it includes high static pressure setting
of fan and low static pressure setting of fan, which should be adjusted according to
the project.
Cautions:
1).Code setting must be under off state of power.
2). There is 3-bit, 4-bit or 5-bit DIP switch. 4-bit or 5-bit DIP switch is only applicable to ducted type
unit(including OV Multi VRF ducted type units and ducted type split)
3).;
When the control setting is "L", the Master/slave and memory setting on the main board is invalid.
When the control setting is “I”, the code setting is valid.
4). The dial-up position shall be at ON which means 0 or at opposite position which means 1.
Dial-upswitch at middle position is prohibited.
5). After dialing up, please record address code of the unit (√).
S1 address code
S7 function code
5-bit functional DIP switch
17
Install of ducted type indoor unit
Functional DIP
Switch S7
Address
Switch S1
DIP
Mainboard of 4-bit Functional DIP switch
Installation Instruction of the Unit
1. Address Code
Address code must be set for multi VRF indoor units to ensure normal communication. The address
code is 4-bit. The highest value is 16 and the lowest value is 1.
Notice! If multiple indoor units are used at the same time, address setting must be modified
before installation. Different address codes must be set for them. If wired controller is used for them,
the address code of it (DIP switch at the back of it) must accord with corresponding indoor unit.
☆ Factory setting is as follow:
Default setting of address code is 0000 which mean 1 (dial-up method is shown in the above
figure.)
☆ Adress value
Binary system is used in address code setting, and the value is "0" when the switch is dialed to "ON"
while the opposite is "1". The four codes 4~1 on the address code, in which No. 4 is high level bit and
No. 1is low level bit. The "4" switch is the first digit while "1" is the last one.
18
Install of ducted type indoor unit
Address Value
1
2
3
4
5
6
7
8
Address Position 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Code
Address Value
0 0 0 0 1 0 0 0 0 1 0 0 1 1 0 0 0 0 1 0 1 0 1 0 0 1 1 0 1 1 1 0
9
10
11
12
13
14
15
16
Address Position 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Code
0 0 0 1 1 0 0 1 0 1 0 1 1 1 0 1 0 0 1 1 1 0 1 1 0 1 1 1 1 1 1 1
Example 1: Code “0111” represents that the address is “8”. 1,2,3, of the DIP switch should be
dialed to the number side and 4 should be dialed to “ON” position.
Example 2: Code is “1010” represents that the address is “11”.2,4 of the DIP switch should be
dialed to the number side and 1,3 should be dialed to the “ON” position as follows:
Address 8,Code0111
Address11
,Code1010
● Connection between the Electric Wires and the Terminals on the Te rminal Plate: (As shown in
Fig.12)
A. Connection of mono-branching wires
1. Use a wire stripper to strip off about 25mm of the insulation layer at the end of the
mono-branching wire;
2. Remove the screws on the wiring board of the air conditioner unit;
3. Use the pliers to bend the end of the wire into a ring shape corresponding the size of the screw;
4. Pass the screw through the wire ring and fix it onto the wiring board.
19
Install of ducted type indoor unit
B. Connection of multi-ply stranded wires
1. Use the wire stripper to strip off about 10mm of the insulation layer of the stranded wires;
2. Remove the screws on the wiring board of the air conditioner unit;
3. Use the wire pressing pliers to press the ends of the multi-ply stranded wires onto the terminals
corresponding to the size of the screws;
4. Pass the screws through the terminals of the multi-ply stranded wires and fixes them onto the
A.M ono-branching w ire
B. M ulti-ply stranded w ire
wiring board.
10
25
W iring term inal
Insulation
layer
Fig.12
Warning:
1. If the power cord or signal cord of the unit is damaged, special-purpose cords must be used for
replacement;
2. Please identify the voltages for the components indicated on the nameplate before doing the wire
connection, and then connect the wires in accordance with the schematic diagram of wiring.
3. The air conditioner unit should use the special-purpose power cord, and should be equipped with
breaker of air switch so as to handle the occurrence of overloads;
4. The air conditioner unit must be properly grounded to prevent from the damages caused by the
failure of insulation;
5. All the distribution wires must use the press-connecting terminals or single wires. The direct
connection between the multi-ply stranded wires and the terminal board might lead to sparking;
6. All the wiring must follow the schematic diagram for the electric circuits. Any erroneous wiring
and connection might result in the abnormal operations or damages of the air conditioner unit;
Do not allow the power cord to contact the pipelines or any moving parts like the compressor or
fan;
7. The internal wiring of the air conditioner unit should not be altered without authorization. The
manufacturer shall not be responsible for any losses or abnormal operations incurred from such
unauthorized alterations.
20
Install of ducted type indoor unit
● Connection of Distribution (Communication) Wires:
Open the cover of the electric box of the indoor unit;
Pass the distribution (communication) wire through the rubber gasket;
Insert the distribution (communication) wire into the three pin stands of CN15, CN16 or CN17 on the
electric circuit board of the indoor unit;
Bind the distribution (communication) wires firmly together and fix them.
● Connection of Power Supply Lines:
Attention: The power supply for various indoor units must be from the unified power
supply.
Air conditioner units using single-phase power supply
1. Remove the cover of the electric box of the indoor unit;
2. Pass the power supply cord through the rubber gasket;
3. Connect the power cord to the L and N terminals as well as the grounding screw;
4. Bind the cord and wires firmly together and fix them properly;
● Connection of Remote controller Signal Wire:
1. Open the cover of the electric box of the indoor unit;
2. Pass the signal line of the remote controller through the rubber ring;
3. Insert the signal line of the remote controller into the four-positioned pin stands on the electric
circuit board of the indoor unit;
4. Bind the signal lines of the remote controller firmly together and fix them.
Attention:
Special precaution must be taken when doing the following connections so as to prevent from the
failure of the air conditioner unit due to EMI (electromagnetic interference).
1. The signal lines and the distribution (communication) wires should be separated from the power
supply cord and the connection lines between the indoor and the outdoor units;
2. In the case that the air conditioner unit has to be installed at the places subject to the EMI, it is
advised to use shielded and double-strand wires for the signal lines and distribution
(communication) wires.
●
Others
1.Tomodelsof OV(L)-R22P/NaB-K,OV(L)-R28P/N aB-K,OV(L)-R36P/NaB-K,
OV(L)-R45P/NaB-K, OV(L)-R56P/NaB-K,
OV(L)-R71P/NaB-K, OV(L)-R90P/NaB-K, OV(L)-R112P/NaB-K,OV(L)-R140P/NaB-K,OV(L)-R22PS/NaB-K,
OV(L)-R28PS/NaB-K,OV(L)-R36PS/NaB-K, OV(L)-R45PS/NaB-K, OV(L)-R56PS/NaB-K,OV(L)-R71PS/NaB-K,
OV(L)-R90PS/NaB-K, OV(L)-R112PS/NaB-K,OV(L)-R140PS/NaB-K, OV(L)-R22P/HB-K,OV(L)-R28P/HB-K,OV(L)-R36P/HB-K,
OV(L)-R45P/HB-K, OV(L)-R56P/HB-K,OV(L)-R71P/HB-K, OV(L)-R90P/HB-K, OV(L)-R112P/HB-K,OV(L)-R140P/HB-K,
OV(L)-R22PS/HB-K,OV(L)-R28PS/HB-K,OV(L)-R36PS/HB-K, OV(L)-R45PS/HB-K, OV(L)-R56PS/HB-K,OV(L)-R71PS/HB-K,
OV(L)-R90PS/HB-K, OV(L)-R112PS/HB-K ,OV(L)-R140PS/HB-K、OV(L)-R22P/NaB-D,OV(L)-R28P/NaB-D,
OV(L)-R36P/NaB-D, OV(L)-R45P/NaB-D, OV(L)-R56P/NaB-D,OV(L)-R71P/NaB-D, OV(L)-R90P/NaB-D, OV(L)-R112P/NaB-D,
OV(L)-R140P/NaB-D according to requirements of the project, when it is necessary for higher
static pressure, realize it by changing indoor wire connection according to the enclosed
circuit diagram.
21
Name and Function of Each Part of Ducked Type Indoor Unit
RECTANGLE OUTLET VENT
CIRCLE OUTLET VENT
DUCTED TYPE INDOOR UNIT
①
②
③
Outlet vent
Air return vent
Condensation Pipe
NOTE: 1.Connection pipe and Air pipe are not included in this Air conditioner
2. Products are set for the rectangle outlet vent.
Working Temperature Range
Working Temperature Range
Indoor side state
Dry bulb temp.
Wet bulb temp.
Outdoor side state
Wet bulb temp.
Dry bulb temp.
Rated Cooling
27
19
35
24
Max. cooling
32
23
43
26
Min. cooling
21
15
18
—
Rated Heating
20
15
7
6
Max. heating
27
—
24
18
Min. heating
20
15
-15
-16
22
Wired Remote Controller Operation Procedure
MODE
FAN
SLEEP
TIMER
ON/OFF
Various Components of Wired Remote Controller
1
Operating mode display (Cool, Dry, Fan, Heat)
9
On/Off button
2
Sleep mode display
10
Timer button
3
Environmental temp. display /Malfunction display
11
Sleep button
4
Fan control display (automatic, high, media, low)
12
Swing display
5
Set Temp. display
13
Fan control button
6
Defrosting display
14
Temp./ Timer decrease button
7
Timer display
15
Temp./ Timer increase button
8
Signal receptor
16
Mode button
1) On/Off(Fig.13)
●
●
When press the ON/OFF key,the unit will start.
MODE
When press ON/OFF key again,the unit will stop.
NOTE:Fig.13 shows the closedown status after power on. When the
communication is normal, both at the running and stopping status will
FAN
display the environment temp. Here,there is no“graticule line”on the
SLEEP
LCD of Fig.14,it shows the unit is closedown..
TIMER
ON/OFF
Fig.13
23
Wired Remote Controller Operation Procedure
2)Timer setting (Fig.14,hereinafter will be displayed according to
the function of the wired remote controller.)
MODE
●
At stopping, press TIMER ON button, set ON TIME, at operating,
press TIMER OFF button, set OFF TIMER.
●
When it is not timed(i.e. there is no show content in the timing
FAN
display field ) ,press TIMER ON,the liquid will display the
SLEEP
pattern of “
” and “HOUR”the samples
TIMER
will be flashed in every 0.5second on and on,at this time press
ON/OFF
xx.x hour”, “
or
button to set time。After using
or
Fig.14
button,adjust to the desired temperature, then press the TIMER
button,at this time“
”and“HOUR”will not flash,that shows
the TIMER ON has been set.
●
After power on, to press the TIMER button once,LCD will display“
0.0 HOUR”,The sign of“
”and
“HOUR”will twinkle,when repress the TIMER button,the LCD will not display the sign,that shows the
TIMER ON has been canceled.
●
When the TIMER ON has been set,(i.e. the sign of“
TIMER button once more,LCD will show “
xx.x HOUR”
(Note:
“xx.x”is the time of last setting,after power
on it will be cleared automatically),the sign of“
press
●
or
”and “HOUR”will twinkle continuously),if press the
”and“HOUR”will twinkle continuously,at this time could
button for time setting,or press the TIMER button again to confirm the function of time.
The range of TIMER ON and TIMER OFF is from 0.5hour to 24hour. Press
or
button for each
time, the set time will be increased or decreased 0.5hour, hold the press
or
button, it will
increase 0.5hour or decrease 0.5hour every other 0.5second. The setting range of
0 to 24,and they are circulatory.
button:
button:
0.0
0.0
0.5
0.5
1.0
1.0
········
23.5
24.0
······
23.5
24.0
NOTE:The Fig. shows the relevant display area.
24
and
is from
Wired Remote Controller Operation Procedure
3 )SLEEP mode setting (Fig.15)
●
When PCB is running at COOL or DRY mode,after received
the SLEEP mode setting and run for 1 hour,the preset
MODE
temperature Tset will be increased 1
increased 1
,2 hours later it will be
again,it has been increased 2
totally within 2
hours,then the unit will run accord to the setting temperature.
●
FAN
When the PCB is running at HEAT mode,after received the
SLEEP
SLEEP mode setting and run for 1 hour,the preset
TIMER
temperature Tset will be decreased 1 ,2 hours later the Tset
will be decreased 1
ON/OFF
again,it has been decreased 2
totally within 2 hours,then the unit will run accord to the
Fig.15
setting temperature.
●
There is no SLEEP function in FAN mode.
4)Fan Speed Control(Fig.16)
●
Press FAN SPEED button each time,fan speed will be
changed as following:
AUTO
LOW
MODE
MED
HIG
FAN
●
AT DRY mode :The fan speed will be set to the LOW speed
SLEEP
automatically.
TIMER
ON/OFF
Fig.16
25
Wired Remote Controller Operation Procedure
5) Temp. adjusting (Fig.17)
●
When not setting the time,press
and
button,can set the
MODE
temperature adjustment.
For increasing setting temperature;
For decreasing setting temperature。
FAN
(When press this button,the temperature will be increased or
SLEEP
decreased in the unit of 1
●
The temperature setting range is 16
30
TIMER
at every kind off
ON/OFF
modes
6)Set of running mode(Fig.18)
●
Fig.17
When pressing MODE button each time,the mode will be
changed as following:
COOL
●
DRY
FAN
MODE
HEAT
At “COOL” mode,the COOL display will be light on,the
FAN
temperature of setting should be lower than the room
SLEEP
temperature. If the setting temperature is higher than the room
TIMER
sensor,the unit will not run at cool mode operation.
●
ON/OFF
At “DRY” mode,the DRY display will be light on. Fan motor
will run at low fan speed in the definite temperature range. The
Fig.18
dehumidifying effect of this mode is better than that in COOL
mode and more energy saving.
●
MODE
At “HEAT” mode,the HEAT display will be light on. The
temperature should be set higher than the room temperature;
If the setting temperature is lower than the room temperature, the
●
unit will not run at HEAT mode operation.
FAN
At“FAN”mode,the FAN display will light on.
SLEEP
7)Malfunction display(Fig.19)
●
TIMER
When the malfunction happened during the operation, the
ON/OFF
environment temperature display area will show the error code. As
shown in Fig.19 it shows the compressor high-pressure protection.
●
When the malfunction happened,except for the FAN mode is
in operation,at the mode of COOL, DRY, HEAT ,the outdoor
unit and fan motor are closedown, that will not affect the
LCD display.
26
Fig.19
Wired Remote Controller Operation Procedure
●
When the controller displays malfunction,please turn off the
unit to stop the malfunction display,ask for the professional
to debug.
The meaning of error codes as shown in below:
Malfunction code
Malfunction
E1
High pressure protection of compressor
E2
Indoor anti-frozen protection
E3
Low pressure protection of compressor
E4
Discharge temp. protection of compressor
E5
Compressor overload protection
E6
Transmit malfunction
E7
Modes conflict
F0
Fb
Indoor environment temp. sensor mal-function
Indoor pan tube inlet tube temp. sensor
malfunction
Indoor pan tube middle temp. sensor malfunction
Indoor pane tube outlet tube temp. sensor
malfunction
Outdoor environment temp. sensor mal-function
Outdoor pan tube inlet tube temp. sensor
malfunction
Outdoor pan tube middle temp. sensor
malfunction
Outdoor pan tube outlet tube temp. sensor
malfunction
Discharge temp. sensor 1 (rated frequency)
malfunction
Discharge temp. sensor 2 (digital) malfunction
Greasy temp. temp. sensor 1 (rated frequency)
malfunction
Greasy temp. temp. sensor 2 (digital) malfunction
FC
High pressure sensor malfunction
Fd
Low pressure sensor malfunction
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA
27
Ambient Temp Sensor Mode Setting of Indoor Unit
Under off state of unit, press FAN and SLEEP /SWING buttons at the same time for 5s into setting interface, as
shown in Fig.20.”01” is displayed in ambient temp displaying area and setting mode code is displayed in temp
displaying area which can be adjusted by pressing
or
, 4 kinds of selection:
①、 Indoor ambient temp is air inlet temp and setting temp area displays 01, as shown in Fig.21.
②、 Indoor ambient temp is wired controller temp and setting temp area displays 01, as shown in Fig.22.
③、 Under heating mode, select wired controller’s temp sensor or under other modes select air inlet’s temp
sensor and setting temp area displays 03, as shown in Fig.20.
④、 Under heating mode, select air inlet’s temp sensor or under other modes select wired controller’s temp
sensor and setting temp area displays 04, as shown in Fig.23.
Factory default is the third mode.
Fig.20
Fig.21
Fig.22
Fig.23
28
Remote controller operation procedure
Names and functions of every button of the remote control
NOTE!
●
Make sure that there is no obstruction between the remote control and the signal receptor.
● The remote control signal can be received at the distance of up to about 10m.
● Don’t drop or throw the remote control.
● Don’t let any liquid flow into the remote control.
● Don’t put the remote control directly under the sunlight or any place where is very hot.
SWING button
the guide louver swings
according to certain
angle when press once;
repress once to stop
operating.
FAN button
Press the button to
change the speed of the
fan according to the
following order.
SWING
FAN
AUTOFAN
TEMP. button
Set temp. increases 1 c
by pressing "+" and
decreases 1 c by pressing
"-" once.
Set temp. : 16 c~30 c
Set temp. : 16 c~30 c
AUTO FAN
SPEED
OPER
AUTO
AIR
SWINGHUMIDLIGHT SAVE
TIMER
ONOFF
HR.
COOL
DRY
FAN
HEAT
Set temp. : 16 c~30 c
Set temp. : 16 c~30 c
on/off button
Press the button to turn on
the unit. Press the button
once again to turn off the
unit and cancal the timer.
MODE button
Press the button to change
the mode according to the
following order
MODE
ON/OFF
NOTE: The cooling only
units have no
mode.
NOTE!
After every indoor unit received the turn off signal, the fan and electric inflate valve will continue to work for
20-70mins to make use of the rest cool or rest heat, while for preparation for the next work. And this is normal
phenomenon.
29
Remote controller operation procedure
Names and functions of every button of the remote control (Remove the cover)
NOTE!
This type of remote control is a kind of general use remote control that is suitable for several types (function) of
air conditioner units. Please understand that the functions and buttons that are not suitable for this air conditioner will
not be introduced.
Liquid crystal displayer
It shows all set contents.
SWING
FAN
AUTOFAN
SLEEP button
Press the button to set SLEEP
mode, and stop when repressed.
When the sleep mode is in the
cool and dry mode, the set
temp. will increases 1~2
during the set time, then the
unit will operate according to
the temp.. When sleep mode is
in the heat mode, the set temp.
decreases 1~2
during the set
time, then the unit will operate
according to the set temp..
OPER
AUTO
AIR
SWING HUMID
LIGHT SAVE
TIMER
ONOFF
HR.
SLEEP
AIR
LIGHT
HUMID
TIMER ONTIMER OFF ANION
SAVE
MODE ON/OFF
Temp./Timer button
When the unit is operating, increase 1
by pressing "+" button once, and
decrease 1 by pressing "-" button
once. The indoor temp. can be set in
the range of 16-30 .
Press the "Timer OFF/TIMER ON"
button at operating/ stopping to set the
off/on time. Press "Timer OFF/TIMER
ON" once to increase 0.5 hour for the
set time. The longest set time is 24
hours; repress it once to cancel timer.
30
Remote controller operation procedure
Operation procedure
Normal procedure
1. Press ON/OFF button after connected with the power, then the unit is operating.
2. Press MODE button to choose the need operation mode.
3. Press FAN button to set the fan speed.
4. Press +/- button to set the need temp..
Selectable procedure
5. Press SLEEP mode to set the sleep state.
6. Press TIMER OFF button to set the set time.
Note: When the operating mode selected by the indoor unit is clash with the one selected by the outdoor unit,
the remote controller will display the operating clash after 5 seconds and the power light will flicker, then the
indoor unit turns off. At this time, the units will become normal after the operating mode of the indoor unit is
changed to cooperate with the outdoor unit. Cool mode can cooperate with dry mode, and fan mode can
cooperate with any mode.
How to insert batteries
Two batteries (Two AAA dry-cell batteries) are used by the remote control
1. Remote the cover from the back of the remote control downward, take out the worn batteries and insert two new
ones (Make sure the two poles are correct)
2. Re-attach the cover.
ACL
1.All the prints and code no. will
be showed on the displayer after
the insert of batteries. The remote
control can be operated after 10sec.
2.The lifetime of the batteries is
about one year.
3.Don't confuse the new and worn
or different types of batteries.
4.Remove batteries when the
①Remove the cover remote control is not in use for a
③Re-attach the cover longtime to avoid mal-function
caused by liquid leakage.
5.The remote control should be
placed about 1m or more from the
open
TV set or any other electric
appliances.
6.The remote control should be
used in the receivable range (the
RESET KEY
reception range is 10m)
7.When the remote control can not
be controlled in the situation of
inserted batteries, please remove
the back cover and press "ACL"
button to make it normal.
②Insert 2AAA dry-cell
battaries(attachment)
31
Trouble Shooting
If the malfunction occurs, please check item shown below before requesting on service center.
Phenomenon
Cause
1. The power supply is not connected
The unit can’t start
well.
2. The electrical leakage cause the jump
3. The voltage is too low.
Although the unit can run, 1. The inlet vent and outlet vent are
after a while it will stop.
blocked
1. The air filter is dirty or blocked
2. There are heat sources in the air
conditioner room or too many people
in this room.
The cooling effect is not good. 3. The door or window is opened.
4. There are obstructions in the air inlet
or outlet grille.
5. The set temp. is too high, that will
affect the cooling effect.
1. The air filter is too dirty, or blocked.
2. The door or window isn’t closed well.
The heating effect is not good.
3. The set temp. is too low, that will
affect the heating effect.
1. When replacing batteries or under
other conditions, sometimes the “Machine
Death” phenomenon is shown on the
remote controller, please remove the rear
cover, then press “ACL”(reset key), the
unit will get back
2. Is it in the receiving range? Or are
The remote controller can not
there any obstructions?
work
3. For the ducted type indoor unit, the
remote controller should be aimed at
the wired remote control for the
control.
4. To check the voltage of batteries is
enough or not, if not enough please
change it.
NOTE:
After checking the above items, the unit still can’t be operated, please turn off the unit
immediately and contact with the local service center and ask for the professional to maintain.
32
Care and Maintenance
ATTENTION:Please pay more attention to the following items before cleaning the units
z
The general power supply of the indoor units must be powered off before contacting the wiring device;
z
Only when unit is turned off and the general power supply is cut off, the unit could be cleaned, otherwise it might
cause the electric shock or injury;
z
Do not use water to clean air conditioners, or it may cause electric shock;
z
Especially when cleaning the units you should pay more attention, to stand on the firm place.
Daily Care
(1)Clean the air filter
z
When not cleaning the air filter please do not disassembly the filter, or it will cause the malfunction.
z
When there is a lot of dust, the air filter should be cleaned many times (generally once for every two
weeks)
(2)The care of the season begin to use
z
Check the inlet and outlet of the indoor units blocked or not;
z
Check the wires earthed well or not;
z
Check the lines connected well or not;
z
After switching on, the indicator lights of the wired remote control should light.
NOTE: If there is any abnormal phenomenon, please operate the unit under the direction of after
service.
(3)The care of the season end to use
z
When the weather is fine, set the unit in the fan mode and running for half of the day.
z
When not to use the unit for a long time, please switch off the power supply, the indicator light of the
wired remote control should extinguish.
33