TOTAL FIRE DETECTION AND EMERGENCY SOLUTIONS

TOTAL FIRE DETECTION AND EMERGENCY SOLUTIONS
ALARM
SYSTEMS
TOTAL FIRE DETECTION AND EMERGENCY SOLUTIONS
INDEX
INTRODUCTION
The Company
Founded in 1985, GLT Exports have specialised
in the manufacture of early warning ? re
detection systems for more than 20 years.
Our brand name Zeta Alarm Systems is
well known throughout the industry and is
acclaimed in over forty countries worldwide.
We are currently represented in the UK,
Europe, Africa, and the Middle East, along
with Southern Asia and South America and
this list continues to grow.
Complete Solution Provider
To meet the requirements of our ever-changing market, we pride ourselves on being a
complete system provider. This means our
customers can rely on us for all their ? re system requirements.
As a testament, our product range now
incorporates conventional and analogue
addressable ? re detection systems, ? re
? ghting telephone systems, voice evacuation
systems, carbon monoxide and combustible
gas detection systems along with state of the
art aspiration detection systems; all of which
are detailed in this publication.
The Future
Our continued inward investment and constant
endeavour to offer the very best products is
recognised by our increased turnover and
pro? t margin year-on-year. Our mission is to
support our existing and future customers
and provide them with the best quality at the
most competetive prices.
System/Warranty
This publication has been created to provide
a “One Stop Shop” for all ? re alarm system
needs. Our dedicated support team will be
able to assist with sales, technical or logistical
queries.
The advantage of using a system supplier,
rather than a component supplier is that
system wide compatibility is assured.
Marketing our products as systems has played
an important part in the success of Zeta
branded products worldwide. When the system
is sourced from one manufacturer, there is
one point of contact, and no compatibility
issues.
Our products carry a full 24-month manufacturers guarantee from the date of purchase.
Our network of authorised agents are fully
trained in the use of Zeta products, and will
provide a helpful & friendly service for all
your ? re alarm requirements.
Research & Development
As with all electronic equipment there is an
ever present drive to manufacture products
that are increasingly effective and are more
cost effective.
GLT Exports Limited spend a signi? cant
percentage of the pro? ts on the continued
development of products, whether it be
introducing new items, or improving existing
ones.
We have a dedicated team of designers with
many years experience of ? re alarm and
related product design. They are always keen
to accept a new challenge.
As a manufacturer we always follow the
market needs closely, to judge if we need to
make changes to our products. And of course
customer feedback is always welcomed.
Statement Of Quality Policy
GLT Exports Limited’s quality policy is to
design, manufacture and supply Fire Alarm
systems in accordance with BSEN 54-2:
1998, BSEN 54-4: 1998, BSEN 54-5: 2001,
BSEN 54-7: 2001 and BS 5839-8:1998; and
then to have them approved to these
standards by the Loss Prevention Council
via their approval system.
The company also aims to develop its
business through investing in training and
development of the employees to ensure
that the company’s growth is matched
by the growth of employee skills and
development.
We maintain a Quality System, which conforms to BS EN ISO9001:2000. We are committed, where applicable to manufacture
in compliance with appropriate legislation
& regulatory requirements.
We are committed to the continual
improvement of the Quality System.
The Quality Objectives are reviewed
continually
at
Management
Review
meetings. These are maintained in the
Master Quality File and circulated to all
employees.
The compilation, revision and maintenance
of these manuals and speci? cations are the
responsibility of the Quality Manager who
answers directly to the Managing Director.
The Systems, Procedures and Test
Speci? cations contained in or referred to
by the Quality Manual are strictly adhered
to by ALL Directors, staff and employees of
the company.
GLT Exports Limited is committed to
Customer Satisfaction at all times and
ensures through the Quality Assurance
System that the customer’s requirements
are and always will be met.
Managing Director
ALARM
SYSTEMS
PRODUCT INFORMATION
Fire
Detection
System
Zoning
Risk A s s e s s m e n t
In order to aid identification of the source of a possible
fire, the protected building should be divided into
‘zones’. When deciding on a suitable zoning scheme for
a building, consideration should be given to the size, any
existing fire routines, escape routes, zone accessibility,
and structural fire compartmentation.
& Ala r m S y s t e m s B S 5 8 3 9
Information
The ‘Fire precautions (Workplace) Regulations’ require any
business employing five or more persons to hold a written
‘Fire Risk Assessment’ and ‘Emergency Plan’. This must be
periodically reviewed.
The local fire brigade can enforce compliance, and close
any building that does not meet this act.
In the event of a fire in a building without a written ‘Fire
Risk Assessment’, those responsible may face fines and
imprisonment, and/or private litigation.
What t h e l a w r e q u i r e s y o u t o do:
• Complete a fire risk assessment for your work place
(considering all employees, the public, disabled people
and people with special needs).
• Identify and record any significant findings or persons at
risk.
• Provide and maintain fire precautions.
• Provide information, instruction and training.
• Nominate persons responsible to implement your
emergency plan.
• Consult employees about the above nominations and
your proposals to improve fire precautions.
• Inform other employees who may have work places
in the building about any significant risks which may
affect their safety and co-operate with them to reduce/
control these risks.
• If you are not an employer, but control premises which
contain more than one workplace, you are responsible
for complying with fire regulations.
• You must establish a suitable means of contacting the
emergency services.
• Your employees must co-operate to ensure the
workplace is safe from fire and its effects.
The following guide lines should
be observed:
• If the total floor area of the building is less than
300m2 then the building needs only one zone,
regardless of the number of storeys.
If the total floor area is greater
than 300m 2 :
• The maximum area for a zone is 2000m2
• If a stairwell (or similar) extends beyond one floor it
should be a separate zone.
• If a zone covers more than one fire compartment
then the zone boundaries should follow the
compartment boundaries.
• The search distance within the zone in order to
ascertain the position of the fire should not exceed
60m. Remember that the use of Remote Indicator
lamps may help to reduce the distance travelled.
• If a building is divided between occupiers, zones
must not be shared between them.
Manual Call Points
A ‘Manual Call Point’ is a device which enables personnel
to raise an alarm in the event of a fire incident by pressing
a frangible element to activate the alarm system.
Manual Call Points should be installed at a height of
1.4m above floor level at easily accessible, conspicuous
positions, on exit routes, at the entry floor landings of
staircases and at all exits to the open air.
Manual Call Points should be spaced so that one may
always be found within a maximum distance of 30m
apart.
Automatic Detectors
When deciding on the type of detector to be used in
any area it is important to remember that the detector
has to discriminate between a genuine fire and the
normal conditions existing therein.
6
Issue N u m b e r : 2 . L a s t U p d a t e : 1 5 / 0 6 / 2 0 0 7 .
Detector
Information
Smo k e D e t e c t o r s
Detection In Apex Roofs
In open spaces under flat horizontal ceilings, every point
should lie within 7.5m of a smoke detector.
if the ceiling is pitched or sloping, smoke will tend to rise
towards the highest point (apex) of the roof, therefore
detection should be placed in the apex. As the slope
tends to reduce the delay before smoke or heat reaches
the detectors, it is permissible to use a greater spacing
between the detectors mounted there.
Smoke detection should be generally avoided in the
following areas to avoid unwanted alarms. They should
be protected by means of other detectors such as heat
detectors.
Contamination in dusty areas may cause unwanted
alarms and reduce the life of the detector.
Damp or humid conditions such as showers, bathrooms
and external areas should be avoided as the water
vapour may cause unwanted alarms and reduce the life
of the detector.
Detectors should not be mounted where gases, vapours
or fumes are present.
Detectors should never be used at low temperature where
ice or condensation can affect detector sensitivity.
Fire Alarm Sounders
Fire Alarm Sounders should be installed throughout the
building with an even distribution, to generally provide
a minimum sound level of 65dB(A) or 5dB(A) above any
background noise which is likely to persist for more than
30 seconds.
Where the alarm may have to arouse sleeping persons e.g.
Hotel bedrooms, nursing homes, etc, a minimum sound
level of 75dB(A) is required, at the bed head with all the
doors shut.
Kitchens, garages, welding shops and boiler houses
should generally be avoided.
All fire alarm sounders in a building should produce the
same sound, distinct from any other audible warning
devices in the building.
Hea t D e t e c t o r s G e n e r a l
Where fire alarm sounders are required in extremely noisy
areas e.g. Machine shops, it may be necessary to install
additional ‘Visual Indication Beacons’.
In open spaces under flat horizontal ceilings, every point
should lie within 5.3m of a heat detector.
Heat detectors are designed to either detect a rapid rise
in temperature or to operate at a fixed temperature.
Although they provide a slower response time than
smoke detectors they do provide a method of protection
for areas where smoke detectors cannot be used.
Heat detectors should not be used for the protection of
life or where extensive property loss may be expected.
‘Ra t e o f R i s e ’ H e a t D e t e c t o rs
‘Rate of Rise’ heat detectors respond to both
rapid increases of temperature and to fixed top
temperature.
Cabling
The operation of a Fire Alarm and Detection System’
depends on the cabling and connections between the
components. It is essential that connection between
Manual Call Points and Detectors function correctly when
they are operated.
Cables within the system are required to function correctly
for significant periods after being attacked by fire. These
include the power supply cables to the control panel, the
detection circuits and the fire alarm sounder circuits. Thus
the cables chosen must be correctly rated to withstand
these conditions.
‘Fix e d Te m p e r a t u r e ’ H e a t
Det e c t o r s
Fixed temperature heat detectors are available with
different temperature settings, and are normally
installed in kitchens, boiler rooms, etc.
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
7
User
Responsibilities
Intro d u c t i o n
the responsible person is
required under BS5839
to undertake certain
tasks with respect to the
testing and maintenance
of the fire alarm system.
The responsible person
is also required to
liaise with the building
maintenance personnel
to ensure that their
work does not impair
or
otherwise
affect
the operation of the
fire alarm system, and
to ensure that a clear
space is maintained in
the vicinity of detectors,
and call-points remain
unobstructed
and
conspicuous.
Routi n e Te s t i n g
The responsible person
should also ensure that
the following routine
is carried out. If there
is a link to a remote
monitoring centre it will
be necessary to advise
the centre prior to a
test. On larger systems
it may be necessary
to
isolate
building
services interfaces to
avoid disruption to the
occupants. In any case
the panel should provide
audible
and
visual
indication that parts of
the system are disabled.
indicates
normal
operation and that any
fault is recorded. Also
check that the recorded
faults have been dealt
with.
confirm the operation of identification of false
alarms by observing the
the system.
following:
Any defects should be
recorded in the log Always make a note of
book
and
reported all illuminated indicators
to
the
responsible and messages displayed
person A certificate of at the control panel.
We e k l y
testing should also be Try and identify the
Every week, a different completed and given to activated device i.e. Do
Manual Call Point should the responsible person. not reset the system until
be operated to test the Annually
the area of the incident
ability of the control
has been inspected.
Each device on the
equipment to receive
any
other
system should be tested Record
a signal and sound the
for correct operation as incidents occurring at
alarm.
The results
the same time which
before.
should be recorded in
could affect the system,
Any defects should be
the log book.
e.g. Power supply failure,
recorded in the log
building works, etc.
book
and
reported
Biannually
to
the
responsible The service organisation
The system should be person. A certificate of will be more likely to
checked by a fire alarm testing should also be trace the false alarm if
service
organisation. completed and given to the above information is
This may be the system the responsible person.
available.
installer or an approved
maintenance company,
Action by The
Action By The
and is normally arranged
User Following
via
a
maintenance User After A
A Fault
agreement
which Fire
specifies the number of
Advise the servicing When a fault is reported
visits and the level of
company and arrange for by the control panel,
service. The agreement
the system to be tested the user should note
should also cover non- by them. A certificate of all illuminated LED’s,
maintenance visits, e.g. testing should be issued and the circumstances
Call outs to attend to to confirm the system at the time the fault
faults, etc.
operation
following occurred, and report to
The standard specifies a the inspection and any the servicing company.
number of maintenance
tasks which include a
visual inspection of the
installation to ensure that
there are no alterations
or obstructions which
could
affect
the
Daily
operation of the system,
Check that the panel and functional checks to
8
remedial work that is The service company will
necessary.
be able to advice if the
system is still able to
respond to a fire alarm or
Action By The
whether extra vigilance
user After Any
should be observed until
False Alarm
the fault is rectified.
The user can assist the Faults should not be left
servicing company in the unreported.
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Addressable Fire Alarm
Introduction
Addressable fire alarm systems have traditionally been associated with
the larger, more complicated applications. But with downward price
trends, they have become feasible for smaller systems that would have
historically been designed with conventional fire alarm equipment.
A ddressable systems can o f f e r t h e f o l l o w i ng advantages over con v e n t i o n a l s y s t e m s : • Each detector communicates directly with the control panel, so it
knows the exact location of any alarm reported.
• Each detector can be assigned a courtesy label to help identify the
device.
• The detector reports a smoke value to the panel. The Panel decides
if this is an alarm. This allows some panels to make detectors more or
less sensitive according to current conditions, or time of day.
• Detectors, sounders, Manual Call Points and interfaces are all
connected to the same loop of wire.
• Detectors are assigned to zones by the panel,
which allows for easier zone changes if the
building layout is altered at a future date.
AM
AS
AH
• Addressable panels usually have an event
log to recall past system.
• Some addressable panels allow for
AM
AM
AH
complicated Cause & Effect Programming,
AS
where outputs are only triggered by certain
AM
detectors.
AS
AH
1
2
15
3
14
13
4
5
AS/H
6
7
ZIU
AS
AS
8
ZTZM
12
AS/H
11
10
AS
S
S
E.O.L.
9
AS
AS
16
17
19
18
20
21
22
AS
AS/H
AS
23
Protocol Statement
24V DC
30
I
Zeta Protocol is unique to GLT Exports Ltd.
All Zeta addressable devices can only be
installed on Zeta control panels. No mixing
with any other manufacturer’s products or
control panels is permitted and warranty will
be void.
AM
29
AH
28
AH
27
ZIOU
26
25
AH
AS
ZSCC
S
E.O.L.
24
AM
FIRE
DET: 021
RECEPTION
FIRE ALARM CONTROL PANEL
AS
AH
AS/H
AM
230V AC
2x12V DC
(INTERNAL)
REPEATER PANEL
AS
AS
I
ZIU
ZIOU
ZSCC
ZTZM
S
S
E.O.L.
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ADDRESSABLE SMOKE DETECTOR
ADDRESSABLE HEAT DETECTOR
ADDRESSABLE SMOKE & HEAT DETECTOR
ADDRESSABLE BREAK GLASS
ADDRESSABLE SOUNDER
ADDRESSABLE SOUNDER/FLASHER
BASE SOUNDER
ISOLATOR BASE
STAND ALONE ISOLATOR
INPUT UNIT
INPUT/OUTPUT UNIT
SOUNDER CONTROL CIRCUIT
ZONE MONITOR
CONVENTIONAL SMOKE DETECTOR
CONVENTIONAL SOUNDER/FLASHER
END OF LINE DEVICE
9
PR-AL
Premier AL Addressable Fire Alarm Control Panel
LPCB
ed
Approv
4
to EN5
pt. 2 &
:1998
4
Optional Extras
Panel Printer:
Add to panel to have a permanent record of all events printed.
Repeater interface card:
Fit to panel to allow repeater panels to be added (supplied with
repeater)
Network interface card:
Fit to panel to allow up to 15 panels to be networked, and to
add Global Network Repeater Panels.
With optional panel printer:
PART NO.
MODEL
DESCRIPTION
37-201P
PR-AL/1P
Premier AL 1 Loop Addr FACP, c/w Printer
37-202P
PR-AL/2P
Premier AL 2 Loop Addr FACP, c/w Printer
37-203P
PR-AL/3P
Premier AL 3 Loop Addr FACP, c/w Printer
37-204P
PR-AL/4P
Premier AL 4 Loop Addr FACP, c/w Printer
The Premier AL 1-4 loop panel can use the Standard Repeater
(for a stand alone panel) or a Global Network Repeater (for a
networked system)
PART NO.
MODEL
DESCRIPTION
37-250P
REP-AL/P
Premier AL Repeater Panel
37-255
REP-AL/G
Premier AL Global Network Repeater
10
The Premier AL range of display
control panels are built to • Devices can be grouped
EN54 Pt 2 & 4. The Premier into 32 zones.
AL is a fully configurable • User friendly controls
system, with all its Zones enabled by keyswitch
& output functions fully (no trying to remember
programmable.
access codes when sirens
are sounding)
The panel is available in 1,
• Extensive mode change
2, 3 or 4 loop versions, and
options
is available with a built in
• Can network up to 15
printer to record events.
panels (giving a total of
Its features include:
60 loops)
•
Windows
based
• LPCB Approved to EN54
configuration software.
Parts 2&4
• Extensive panel & loop
• Complies with EMC & LVD
I/O facilities
• 1-4 addressable loops,
• Monitored remote input
each capable of 126
facility for fault, silence,
devices.
evacuate & reset.
• 4 x 20 character LCD
• Global repeater option.
MODEL
PRAL/1
PRAL/2
PRAL/3
PRAL/4
PART NO.
37-201
37-202
37-203
37-204
DETECTION LOOPS
1
2
3
4
REPEATER MODEL
Premier AL Repeater (REP-AL)
REPEATER PART NO.
37-220
MAINS VOLTAGE
230V AC + 10% / -6% @ 50/60 Hz
SYSTEM VOLTAGE
28V DC (nominal)
LOOP VOLTAGE
24V DC + 9V AC Signal (nominal)
SOUNDER ALARM OUTPUT
2 x 1 A Common @ 24V DC (nominal)
FAULT RELAY
1 x Relay SELV @ 1A maximum
FIRE RELAY
2 x Relay SELV @ 1A maximum
ZONE CAPACITY
32 programmable zones
SOUNDER EOL
10 K resistor (Brown, Black, Orange,
Gold)
CHARGER VOLTAGE
27.1 Volt (with battery
disconnected)
CHARGER SIZE
3 Amp
AUX SUPPLY
500mA max
BATTERIES (MIN. SIZE)
2 x 12V, 12AH SLA Batteries
INGRESS PROTECTION
IP43
ENCLOSURE
410 W x 480 H x 144 D (mm)
WEIGHT
15kg (Excluding Batteries)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
PR-AL/8
Premier AL 8 Loop Analogue Addressable Fire Alarm Control Panel
The Premier AL 8 loop analogue addressable fire
alarm control panel has been designed because of
the demand for larger centralised panels, rather
than smaller panels distributed on a network.
The Panel consists of a large enclosure that houses
two 4 loop panels that are networked together,
and run off a single power supply. The second
panel has its screen facing inwards behind the
blank door.
Because of this configuration, it is recommended
to use the network repeater with this control
panel.
This panel will occupy 2 network addresses.
When viewing the loop contents, loop 1 to 4 can
be viewed from the main screen. Loops 5 to 8
must be viewed using the internal display.
1
POWER
SUPPLY ON
FIRE
DELAY ON
GENERAL
DISABLEMENT
SYSTEM
FAULT
BUZZER
SILENCED
GENERAL
FAULT
2
SCROLL
MESSAGES
3
TEST
ALARMS
4
TEST
DISPLAY
5
ACCESS MENU
MENU UP
6
MENU DOWN
SILENCE
BUZZER
POWER
SUPPLY ON
SILENCE / RESOUND
ALARMS
FIRE
MAINTENANCE
ALERT
1
OVERRIDE
DELAY
EVACUATE
GENERAL
DISABLEMENT
ALERT
<
ENTER
>
SYSTEM
FAULT
BUZZER
SILENCED
GENERAL
FAULT
TEST
ALARM FAULT/
MORE
DISABLEMENT MESSAGES
DELAY ON
MAINTENANCE
RESET
ESCAPE
2
SCROLL
MESSAGES
3
TEST
ALARMS
4
TEST
DISPLAY
5
ACCESS MENU
MENU UP
6
MENU DOWN
SILENCE
BUZZER
RESET
ESCAPE
<
ENTER
>
ACCESS
CONTROLS
O
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
ZONAL FIRE AND FAULT INDICATION
ZONAL FIRE AND FAULT INDICATION
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Display to view contents of loops 1 to 4
PR-AL/6
PR-AL/7
PR-AL/8
37-211
37-212
37-213
37-214
SUPPLY VOLTAGE
230V AC +/- 10%
SYSTEM VOLTAGE
28V DC (Nominal)
ADDRESSABLE LOOPS
I
ACCESS
CONTROLS
PR-AL/5
PART NO
SILENCE / RESOUND
ALARMS
TEST
ALARM FAULT/
MORE
DISABLEMENT MESSAGES
I
O
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
OVERRIDE
DELAY
EVACUATE
MODEL
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Display to view contents of loops 5 to 8
The Premier AL/8 loop panel uses the Global
network repeater.
PART NO.
MODEL
DESCRIPTION
37-255
REP-AL/G
Premier AL Global Network Repeater
5
6
7
8
LOOP VOLTAGE
24V + 9 V Data
LOOP CAPACITY
500mA
SOUNDER OUTPUT
4 X 1A @ 24V DC
SOUNDER EOL
10 K Resistor
SOUNDER DELAY
0 TO 9 Minutes
FIRE RELAY
4 x Relay, SELV @ 1A
FAULT RELAY
2 x Relay, SELV @ 1A (Normally Energised)
AUX SUPPLY
2 x 500mA (Monitored)
OTHER CONNECTIONS
Class Change Input, Remote Fault Input,
Remote Evacuate Input, Remote Reset
Input, Remote Silence Input
OPERATING TEMPERATURE
-0°C to +50°C
ENCLOSURE SIZE
960 x 480 x 144mm
WEIGHT
28 KG (Excluding Batteries)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
11
Addressable System Network
To connect a Premier AL panel to a network,
each panel will require a network card (Part
No: 37-205).
The Premier AL uses an “All-talk, selective
listen” peer to peer network.
That is, every panel transmits all its events
data to the network, and the other panels on
the network are programmed whether of not
they will react to that event.
Because it is a peer-to-peer network, there is
no “master panel”, so the network will still
function in the event of a failure of one or
more of the panels.
The network can contain up to 15 active nodes
(panels), which gives a total of up to 60 loops.
The network can also contain up to 17 passive
nodes (global repeater panels).
The premier AL panel can be supplied with a The system can be programmed with full cause
Windows based configuration software to ease the & effect across the network. Any device on
any panel can be programmed to trigger any
programming of large or complicated systems.
output device.
Smaller systems could be set up via the membrane
An alarm manager graphics system can also be
keypad if desired.
added to the network. It can be configured as
A network of panels is configured in 2 stages:
active or passive.
Firstly, each of the panels is configured as if it The Premier AL panel also has a separate I/O
were a stand-alone panel.
Network. This allows the connection of up to
Secondly, the cross-panel cause and effect is 31 eight way Input Output Modules.
programmed.
These can be supplied with relay outputs or
Using this approach breaks the system into alarm (Sounder) outputs, and can be mixed in
smaller pieces, thus helping to minimise faults any combination on the network.
& ease fault-finding if the initial programming is They can be individually programmed using
not correct.
the Premier AL’s cause & effect software.
12
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Alarm Manager Graphics System
For the Premier AL Analogue Addressable Control
Panels.
The Alarm Manager system is designed as a user-friendly
tool to view a potentially complex fire situation. Once
the system has been set up on-site by a qualified
engineer, the keyboard is no longer required, as all
event maps and user buttons will appear on the screen
as necessary to manage the particular event taking
place. The end user, who may not be technicallyminded, will still be able to operate the system on
a daily basis. All the system’s management functions
are protected via up to 7 different password levels.
When an event occurs, the first map will appear along
with the relevant user controls. There are up to 5
different maps for each sensor showing the device
location in different degrees of accuracy and also a
procedure page which is allocated to each type of
event as prioritised within the configuration menu.
There is also an instantly available current event
log.
Key Features
• Ideal for use with the
Premier AL analogue
addressable control
panels
• End-user friendly
• Up to 5 map pages
per sensor
• Up to 32 devices or
groups of devices per
map page
• Up to 999 maps
• 2,000 event historic
log
• All functions
protected via up to
7 different password
levels
• Identifies each user
separately
• Up to 3 networks may
communicate with
the Alarm Manager
Technical
Specifications
The full Alarm
Manager package
includes:
• PC
• 15” TFT Monitor
• USB Network
Interface for 1
Network
•Installed Alarm
Manager software
Part Numbers
• 37-300
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
13
NPAD
Premier AD 2 loop Analogue Addressable Fire Alarm Panel
s
Complie
4
5
N
E
with
Pt 2, 4
The Premier AD 2 loop analogue addressable
fire alarm panel has been designed to be as
simple to use as a conventional fire alarm
panel.
It has 2 addressable loops, divided into 16
zones, and 4 conventional sounder circuits. The
sounder circuits operate on common alarm,
but can be individually tested or disabled.
The Premier AD supports a serial repeater,
and now includes a real time clock, and 2048
capacity event log. It can also be connected to
an RS232 desktop printer for real time event
log printing. (Epson LQ300+ recommended)
14
LOOP & ADDRESS
ZONE
Loop 1: Address 1-16
Zone 1
Loop 1: Address 17-32
Zone 2
MODEL
NPAD
Loop 1: Address 33-48
Zone 3
PART NO
37-150
Loop 1: Address 49-64
Zone 4
SUPPLY VOLTAGE
230V AC +/- 10%
Loop 1: Address 65-80
Zone 5
SYSTEM VOLTAGE
24V DC (NOMINAL)
Loop 1: Address 81-96
Zone 6
NUMBER OF LOOPS
2
Loop 1: Address 97-112
Zone 7
LOOP CAPACITY
252 DEVICES
Loop 1: Address 113-126
Zone 8
NUMBER OF ZONES
16
LOOP & ADDRESS
ZONE
SOUNDER OUTPUT
4 x CONV. SOUNDER CIRCUITS, 250mA EACH
OR ADDRESSABLE SOUNDERS
Loop 2: Address 1-16
Zone 9
FAULT OUTPUT
1 X RELAY SELV @ 1A (NORMALLY ENERGISED)
Loop 2: Address 17-32
Zone 10
FIRE OUTPUT
1 X RELAY SELV @ 1A
Loop 2: Address 33-48
Zone 11
Loop 2: Address 49-64
Zone 12
OPERATING
TEMPERATURE
-0°C to 50°C
Loop 2: Address 65-80
Zone 13
ENCLOSURE SIZE
485 X 395 X 120mm
Loop 2: Address 81-96
Zone 14
WEIGHT
6 KG
Loop 2: Address 97-112
Zone 15
Loop 2: Address 113-126
Zone 16
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
SP-64 , SP-126
Simplicity Plus Analogue Addressable Fire Alarm Panel
s
Complie
4
5
N
E
with
Pt 2, 4
The Simplicity Plus is the ideal introduction to
the world of addressable fire alarm panels.
As its name suggests, it has been designed with
ease of use in mind, using pre-programmed values
for its programming options. The installer simply
needs to configure the loop, and enter text labels
via the built in keyboard.
The Simplicity Plus is available in 64 device, and
126 device versions, and now includes a real
time clock, and 2048 capacity event log. It can
also be connected to an RS232 desktop printer
for real time event log printing. (Epson LQ300+
recommended).
It can also drive a serial repeater model AD-REP,
part no. 37-156.
Loop & Address
SP-126
SP-64
1: Address 1-16
Zone 1
Zone 1
1: Address 17-32
Zone 2
Zone 2
1: Address 33-48
Zone 3
Zone 3
1: Address 49-64
Zone 4
Zone 4
1: Address 65-80
Zone 5
-
1: Address 81-96
Zone 6
-
1: Address 97-112
Zone 7
1: Address 113-126
Zone 8
MODEL
SP-64
SP-126
PART NO
37-160
37-165
SUPPLY VOLTAGE
230V AC +/- 10%
230V AC +/- 10%
SYSTEM VOLTAGE
24V DC (NOMINAL)
NUMBER OF LOOPS
1
LOOP CAPACITY
64 DEVICES
126 DEVICES
NUMBER OF ZONES
4
8
SOUNDER OUTPUT
ADDRESSABLE SOUNDERS ONLY
FAULT OUTPUT
28 V REPEAT OUTPUT TO DRIVE RELAY
(NORMALLY ENERGISED)
-
FIRE OUTPUT
28 V REPEAT OUTPUT TO DRIVE RELAY
-
OPERATING
TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
355 X 275 X 100mm
WEIGHT
3.5 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
15
AD-REP
Premier Addressable Repeater Panel
s
Complie
4
5
N
E
with
The Premier Addressable Repeater panel is a
serial repeater panel for use with the Premier
AD and Simplicity Plus Addressable Fire alarm
panels
Pt 2, 4
It is a display only repeater (no controls), and
indicates power, general fault and general fire
by LEDs, and gives information for the device
in fault or alarm on the LCD screen. It also has
an internal buzzer to indicate that it requires
attention.
(Note that a standard Simplicity 126 panel can
be upgraded to a Simplicity Plus by replacing
the CPU card)
t
t
MODEL
t
16
t
AD-REP
PART NO
37-156
SUPPLY VOLTAGE
20 – 30 V DC
SYSTEM VOLTAGE
29V DC (NOMINAL)
CONNECTIONS
SUPPLY +
SUPPLY –
DATA +
DATA -
OPERATING TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
355 X 275 X 70mm
WEIGHT
1 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
FEAO2000
Fyreye Addressable Optical Smoke Detectors
LPCB
ed
Approv
4
to EN5
000
pt. 7.2
The FEAO2000 is an analogue addressable Optical smoke
detector that works to the Zeta Addressable protocol,
compatible with Zeta alarm system control panels only.
The optical chamber consists of a removable plastic mesh,
an IR LED & an IR receiver. These are arranged such that in
normal conditions (clean air), no IR from the LED will reach
the IR receiver.
Every second, the IR LED emits a burst of collimated infra
red light. If there is any smoke in the chamber, it will scatter
the IR, allowing it to reach the receiver. The amount of IR
reaching the receiver is converted to an analogue smoke
value, and sent digitally back to the fire alarm control
panel as part of the detectors communication protocol.
The detector is supplied with a locking screw to prevent
removal of the head by unauthorised personnel. The
detector will return an analogue value of 55 counts with a
smoke obscuration level of 2.4% obscuration per metre.
The Fyreye optical smoke detector is particularly suitable
for detecting optically dense smoke, involving materials
such as soft furnishings, PVC, plastic, foam, and similar
materials which produce large visible small particles
(0.5mm to 10 mm).
MODEL
FEAO2000
PART NO.
80-120
CAPCITY PER LOOP
126
OPERATING VOLTAGE
17-28VDC
STANDBY CURRENT
340uA @ 24V
OPERATING TEMPERATURE
-20 to 60°C
MIN> CONTINUOUS TEMP.
0°C
RETURNS VALUE OF 55 AT
2.4% obscuration per metre
DETECTOR CLASS
Optical smoke
MAX. HUMIDITY
95%RH non condensing
MAX. WIND POWER
Not affected
ATMOSPHERIC PRESSURE
Not affected
It is not affected by wind speed, so can be used in exposed
places, where an ionisation detector might give false
readings.
Frequent Questions
• How many of these can I connect to my system? 126 per
loop
• Do I have to set a loop address? Yes. Set with DIL switch
on rear.
• How do I test the detector? The detector can be tested
with a smoke test can, or a smoke detector test pole.
• Do these detectors need cleaning? We recommend that
the detectors are checked at least yearly, and cleaned
with a hand held vacuum cleaner, if necessary.
IP RATING
43
COVERAGE
100m²
STORAGE TEMPERATURE
-30°C to 80°C
PART NO.
MODEL
DESCRIPTION
ALARM CURRENT
2mA
80-050
FE-CB
Fyreye Common Base
SIZE: DIAMETER X HEIGHT
(BASE)
100mm x 39mm (100 x 47)
80-080
FEA-RB
Fyreye Addressable Relay Base
80-090
FE-IB
Fyreye Isolating Base
WEIGHT (BASE)
100g (157g)
80-100
FEA-SB
Fyreye Sounder Base
Compatible Bases (6” Versions available)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
17
FEAH2000/FEAHH2000
Fyreye Addressable Heat Detectors
LPCB
ed
Approv
4
to EN5
000
pt. 5.2
The FEAH2000 is an analogue addressable Heat
detector that works to the Zeta Addressable
protocol.
The FEAHH2000 is an analogue addressable high
temperature heat detector.
The measuring circuit is based on a single precision
thermistor, whose characteristics change according
to temperature in a defined manner.
This change in characteristics is converted to an
analogue value, and sent digitally back to the fire
alarm control panel.
On the FEAH2000, the analogue reading is the
temperature in Centigrade (°C), so an analogue value
of 55 will be returned at 55°C.
On the FEAHH2000, the analogue reading changes by
one count when the temperature rises by 2.17 °C, so
the detector will return a value of 55 at 90 °C.
The detectors can be supplied with a locking screw
to prevent removal of the head by unauthorised
personnel.
The Fyreye Heat Detector is particularly suitable for
rooms where smoke detectors cannot be used due to
a high level of smoke or steam, such as kitchens.
The Fyreye High Temperature Heat Detector is
particularly suitable for environments with high
ambient temperatures, such as boiler rooms & laundry
drying rooms.
Compatible Bases (6” Versions available)
18
PART NO.
MODEL
DESCRIPTION
80-050
FE-CB
Fyreye Common Base
80-080
FEA-RB
Fyreye Addressable Relay Base
80-090
FE-IB
Fyreye Isolating Base
80-100
FEA-SB
Fyreye Sounder Base
MODEL
FEAH2000
PART NO.
80-130
FEAHH2000
80-131
OPERATING VOLTAGE
17-28VDC
STANDBY CURRENT
300uA @ 24V
OPERATING
TEMPERATURE
-20 to +50°C
MIN. CONTINUOUS
TEMP.
-20 to + 80°C
0°C
RETURNS VALUE OF
55 AT
55 °C
90 °C
DETECTOR CLASS
AS
CS
MAX. HUMIDITY
95%RH non condensing
MAX. WIND SPEED
Not affected
ATMOSPHERIC
PRESSURE
Not affected
IP RATING
43
COVERAGE
50m²
STORAGE
TEMPERATURE
-30°C to 80°C
ALARM CURRENT
2mA
SIZE: DIAMETER X
HEIGHT (BASE)
100mm x 39mm (100 x 47)
WEIGHT (BASE)
100g (157g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
FEAOH2000 Fyreye Extra
Analogue Addressable Opto Heat Multi-Point Detector
APPROVED
The Fyreye “Extra” range of analogue detectors
have an extra LED to improve detector
identification in an alarm condition. The 2 LEDs
allow an alarm to be observed from all angles.
The Detector works with the Zeta Addressable
Protocol, and is compatible with all current Zeta
Analogue addressable control panels. It comes
supplied with a locking grub screw to prevent
unauthorised head removal.
The FEAOH2000 is a dual type detector, which
reacts to both smoke & heat independently. It is
suitable for use in places where traditionally an
ionisation type detector may have been chosen.
MODEL
FEAOH2000
PART NO
80-140
DETECTOR CLASS
Optical Smoke, Rate of Rise &
Fixed Heat
DESIGN STANDARD
EN54 Part 5 & Part 7
APPROVAL
DIFT
OPERATING VOLTAGE
17-28V DC (Plus Protocol Signal)
QUIESCENT CURRENT
520µA
ALARM CURRENT
2.3mA
OPERATING TEMPERATURE
-10°C to +50°C
MINIMUM CONTINUOUS TEMP.
0°C
MAX HUMIDITY
95% RH Non Condensing
RETURN VALUE OF 55 (NOMINAL
ALARM LEVEL)
2.4% Obscuration per metre
RETURN VALUE OF 75
Rate of Rise Trigger
RETURN VALUE OF 95
Fixed heat trigger
COVERAGE
100m²
IP PROTECTION RATING
IP43
START-UP TIME
30 Seconds
SIZE, DIAMETER X HEIGHT (WITH
BASE)
100 x 48 mm (101 x 64 mm)
WEIGHT (WITH BASE)
100g (158g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
19
FEAOE2000
Fyreye-Extra Analogue Addressable Optical Smoke Detector
APPROVED
The Fyreye “Extra” range of analogue
detectors have an extra LED to improve
detector identification in an alarm condition.
The 2 LEDs allow an alarm to be observed from
all angles.
The Detector works with the Zeta Addressable
Protocol, and is compatible with all current
Zeta Analogue addressable control panels. It
comes supplied with a locking grub screw to
prevent unauthorised head removal.
The FEAOE2000 is particularly suitable for
detecting optically dense smoke, involving
materials such as soft furnishings, PVC, plastic,
foam, and all similar materials which produce
small visible particles (0.5 to 10 μm)
MODEL
20
FEAOE2000
PART NO
80-125
DETECTOR CLASS
Optical Smoke
DESIGN STANDARD
EN54 Pt 7
APPROVAL
DIFT
OPERATING VOLTAGE
17 – 28V DC (Plus Protocol)
QUIESCENT CURRENT
480μA
ALARM CURRENT
2.3mA
OPERATING TEMPERATURE
-10°C to +50°C
MINIMUM CONTINUOUS TEMP.
0°C
MAX. HUMIDITY
95% RH Non Condensing
RETURN VALUE OF 55 (NOMINAL
ALARM LEVEL)
2.4% Obscuration per metre
COVERAGE
100m2
IP PROTECTION RATING
IP43
START-UP TIME
10 Seconds
SIZE, DIAMETER X HEIGHT
(WITH BASE)
100 x 37 mm (101 x 53 mm)
WEIGHT (WITH BASE)
95 g (153g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
FEAHE2000 / FEAHHE2000
Fyreye-Extra Analogue Addressable RoR Heat Detector
DIFT CERTIFICATE
NUMBER 875
The Fyreye “Extra” range of analogue detectors have an
extra LED to improve detector identification in an alarm
condition. The 2 LEDs allow an alarm to be observed from
all angles.
The Detector works with the Zeta Addressable Protocol, and
is compatible with all current Zeta Analogue addressable
control panels. It comes supplied with a locking grub screw
to prevent unauthorised head removal.
The FEAHE2000 is an Analogue Addressable rate of rise heat
detector. It will respond with a value of 75 if the detector
is triggered by a rate of rise alarm, and a value of 95 if the
detector is triggered through a fixed heat alarm of 57°C.
The FEAHHE2000 is an Analogue Addressable fized heat
detector. It will respond with a value of 95 if the detector
is triggered through a fixed heat alarm of 90°C.
MODEL
FEAHE2000
FEAHHE2000
PART NO
80-135
80-136
DETECTOR CLASS
RATE OF RISE
& FIXED HEAT
FIXED HEAT ONLY
DESIGN STANDARD
EN54 part 5
APPROVAL
DIFT
OPERATING VOLTAGE
17 to 28V DC (Plus Protocol)
QUIESCENT CURRENT
440 μA
ALARM CURRENT @
24V DC
2.4mA
OPERATING
TEMPERATURE
-10°C to 50°C
MINIMUM CONTINUOUS
TEMP.
0°C
MAX HUMIDITY
95% RH non condensing
ALARM CONDITION
Rate of Rise or Fixed
Heat trigger @ 57°C
Fixed Heat trigger
@ 90°C
COMPATIBLE BASES
FE-CB – Common Base
FE-IB – Isolator Base
FEA-RB – Addressable Relay Base
FEA-SB – Addressable Sounder Base
FEA-SFB – Addressable Sounder Flasher Base
COVERAGE
50m2
IP PROTECTION RATING
IP43
START UP TIME
30 seconds
SIZE, DIAMETER X
HEIGHT (WITH BASE)
100 x 48 mm (101 x 64 mm)
WEIGHT (WITH BASE)
100g (158g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
21
FE-CB, FE-IB & FEA-RB
Fyreye Addressable Detector Bases
There are 6 different Fyreye detector bases
available for the addressable range of
detectors, namely, common base, isolator
base, addressable relay base, and the 6”
versions of these three bases.
The common base is the standard base, which
will be used with most heads.
The isolator base is used to protect the loop
against short circuits. They should be used at
least every 32 devices, but it is better practice
to use them at the end of every zone.
The Relay base is mainly used where the
activation of a particular detector requires a
signal to nearby equipment (door holders, or
air handling units, for example).
DO NOT CONNECT CONVENTIONAL REMOTE
LEDS TO THE –R TERMINAL.
6” Variations
MODEL
FE-CB6
FE-DB6
FE-RB6
PART NO.
80-060
80-091
80-081
BASE SIZE
152mm diameter x 35mm deep
WEIGHT
136g
136.2g
Isolator Base
Common Base
LOOP + IN
LOOP + OUT
EARTH
L2
L1
O
U
T
L
I1
N
R
-
LOOP - IN
R
-
LOOP - OUT
LOOP + IN
LOOP + OUT
EARTH
C
R
-
22
PART NO.
80-050
SUPPLY VOLTAGE
FE-IB
FEA-RB
80-090
80-080
17-33V DC
AVERAGE QUIESCENT CURRENT AT
24V
0uA
35uA
0uA
ALARM CURRENT AT 24V
0mA
0mA
15mA
ISOLATED CURRENT AT 24V
N/A
5.4mA
N/A
RELAY MAX. SWITCHING POWER
N/A
N/A
30W,
50VA
+ - -IN+ OUT
L1
O
U
T
RELAY MAX. SWITCHING CURRENT
N/A
N/A
1A Res.
RELAY MAX. SWITCHING VOLTAGE
N/A
N/A
L
I1
N
50V AC
LOOP - IN
LOOP - OUT
RELAY MINIMUM CAPABILITY
N/A
N/A
10uA,
10mV
LOOP + IN
LOOP + OUT
RELAY DROPOUT VOLTAGE
N/A
N/A
<6V
OPERATING TEMPERATURE
Addressable Relay Base
L2
FE-CB
EARTH
L2
LOOP - IN
171.4g
MODEL
L1
O
U
T
MAX. WIND SPEED
Not affected
CONNECTIONS
L1in, L1out (not used), L2,
-R (not used), Earth
BASE SIZE
100mm diameter x 15mm
deep
RELAY
OUTPUT
L
I1
N
LOOP - OUT
-20° to +90°C (non
condensing or icing)
WEIGHT
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
50g
50.2g
85.4g
FEA-SFB Fyreye Addressable Sounder Flasher Base
With Built In Short Circuit Isolator
Fyreye addressable sounder-flasher base has
been designed to meet the increasing demand of
having a sounder and flasher in each room that
has a detector fitted.
As a step to making our equipment more user
friendly, the address is set by 3 rotary switches.
This means that addresses are set in Decimal,
rather than Binary. Valid addresses are 1 to 126.
Each sounder flasher base also has a built in short
circuit isolator, to help maintain system integrity
in the event of a fault condition. This means that
stand alone isolators or isolator bases are often
not required.
It has a red LED flasher incorporated into the
base, with a flash rate of 1 per second.
ZONE + IN
ZONE + OUT
L2
EARTH
UT
L1O
23
901
23
901
23
IN
901
-R
456
L1
78
456
78
ZONE - IN
78
456
ZONE - OUT
MODEL
FEA-SFB
PART NO
80-101
SUPPLY VOLTAGE
18 – 33 V DC
QUIESCENT CURRENT
1mA
SOUND OUTPUT @ 1m (LO)
83dB(A)
OPERATING CURRENT (LO)
14.5mA
SOUND OUTPUT @ 1m (HI)
87dB(A)
OPERATING CURRENT (HI)
16.5mA
NUMBER OF TONES
3 (Dependant on control panel)
SOUND FREQUENCY
440 – 1200 Hz
FLASH COLOUR
RED
FLASH RATE
1 PER SECOND
CONNECTIONS
Loop + = L2
Loop - IN = L1 IN
Loop - OUT = L1 OUT
OPERATING TEMPERATURE
-0oC to 50oC
IP RATING
IP43
ENCLOSURE SIZE
105mm DIAMETER, 35mm DEEP
WEIGHT
130g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
23
ZTA-LE2
Addressable Remote Indicator LED
On modern addressable fire alarm systems,
the remote output of a detector may often
be unavailable because it is used for another
purpose, to drive a sounder base, or a relay
base for example.
Because of this, we designed our addressable
remote indicator, to ensure that a remote LED
indication would always be available. The
remote Indicator can either be connected as
part of the loop, or as a spur from the detector
it is indicating.
It has the same address as the detector it is
indicating, and will now light whenever the
panel tells the detector to light.
There is also a version that will listen to a
number of consecutive addresses, designed
for when there are more than one detectors
behind a locked door.
Wired as a SPUR
ON
1 2 3 4 5 6 7 8
Remote Indicator
+
+
IN
L1
-R
IN
L2
IO
L1
UT
IO
UT
IO
-R
-R
L1
L1
L2
L1
UT
IN
L1
L2
Loop out to next
detector or return
to panel.
Loop in from
Fire alarm panel
Wired as part
of the loop
IN
L1
1 2 3 4 5 6 7 8
ON
IN
L1
-R
IN
L1
-R
-R
L1
L2
UT
IO
L2
UT
24
+
+
IO
L1
UT
IO
L1
Loop in from
Fire alarm panel
Remote Indicator
MODEL
ZTA/LE2
ZTA/LE2-10
PART NO
48-020
48-020A
INPUT VOLTAGE
17 -33V DC
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
10mA
ADDRESSES
REPEATED
1
1-10
COLOUR
White Plastic, Red LEDs
OPERATION COLOUR
Red
OPERATING
TEMPERATURE
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
86 x 86 x 23
WEIGHT
40 g
L2
Loop out to next
detector or return
to panel.
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
ZTA-LE3
Addressable Remote Indicator LED
The ZTA- LE3 is a low cost alternative to the fully
addressable remote LED indicator ZTA-LE2.
Remote LEDs are used in installations where a
detector going into alarm is likely to occur behind
a locked door, or in a ceiling void. The Indicator
will then show the location of the alarm.
D
The ZTA-LE3 is designed to work with ADDRESSABLE
Fyreye detectors on the Premier AL panel only.
They will need to be programmed to operate,
and can be triggered from a single detector or a
group of detectors.
MODEL
ZTA-LE3
PART NO
48-021
QUIESCENT CURRENT
0 mA
ALARM CURRENT
10mA
COLOUR
WHITE PLASTIC, RED LEDs
OPERATION COLOUR
RED
OPERATING TEMP.
0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
86 X 86 X 23
WEIGHT
40 g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
25
ZT-50RA / ZT-100RA
Fyreye 50/100R Addressable Reflective Beam Smoke Detector
Vds
ed
approv
4
5
N
E
to
Pt 12
The Fyreye Reflective Beam
Detector comprises a single
unit incorporating an Infrared transmitter and receiver.
The signal is reflected by a
prism and analysed for smoke
presence.
ease set-up.
• Microprocessor controlled.
• Automatic contamination
compensation.
• Selectable sensitivity.
• Robust construction.
• Conforms to:
– BS 5839 Part 5
Should a predetermined level
– EN54 Part 12
be reached, the detector will
– UL
signal an alarm.
- VDS
The system is designed to be
mounted so that the beam Typical Applications
will project between 0.3 and
Beam detectors are generally
0.6 metres below the ceiling,
used for 2 reasons; to cover
and parallel to it. Lateral
a wide-open space, or in
detection may be up to 7.5
places where several regular
metres either side of the
smoke detectors would be
beam.
aesthetically unacceptable.
Such places could include:
Features include:• Single compact housing.
• 50 metre or 100 metre
version available.
• Horizontal or vertical
mounting.
• 12-24V dc operation.
• Low current consumption.
• Latching or non latching
alarm.
• Reflector targeting mode to
117mm
Heritage sites
Churches or Mosques
Museums
Leisure centres
Open Plan offices
Warehouses
Factories
Power stations, etc.
ZT-50RA
PART NO.
47-055
RANGE
26
•
•
•
•
•
•
•
•
MODEL
SUPPLY VOLTAGE
210mm
• Shopping Centres
ZT-100RA
47-056
17-33VDC
5-50 metres
50-100 metres
QUIESCENT CURRENT
5mA
OPERATING TEMP.
-20 °Cto +55 °C
MAX HUMIDITY
95%RH N/C
MAX WIND SPEED
Not affected
ALARM CURRENT
9 mA
FIRE OUTPUT
Analogue value to panel
FAULT OUTPUT
Analogue value to panel
CONSTRUCTION
Flame Retardant ABS (Grey / Black). IP50
DETECTOR SIZE
210 x 117 x 120 mm
WEIGHT
0.7 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZT-CP2/AD
Addressable Call point
Complies
with EN54
Part 11
The ZT-CP2/AD is the latest addressable call point
from Zeta Alarm Systems. It has a modern design,
and has been built to EN54 part 11.
It comes supplied with a back box which has
plenty of room for fitting the cables, and has 2 x
20mm knockouts for glanded cable entry.
It is a resettable call point that signals an alarm
with a yellow flag entering the window area, and
a red alarm LED.
It is available in 2 versions The CP1 version does
not have the Perspex protective cover. The CP2
version has the protective Perspex cover as well
as a “SNAPLATCH” catch that needs to be broken
off before the call point cover can be lifted. This
acts as a deterrent to malicious activations and
allows double action activation.
MODEL
ZT-CP2/AD
ZT-CP1/AD
PART NO
43-305
43-306
INPUT VOLTAGE
17-33V DC
ELEMENT TYPE
RESETTABLE
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
18 mA
ALARM ACTIVATION
BREAK SNAPLATCH
LIFT PERSPEX
PRESS ELEMENT
PRESS ELEMENT
OPERATING
TEMPERATURE
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
111 X 100 X 67
105 X 100 X 58
WEIGHT
198 g
175 g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
27
ZTA-BGU/WP
Addressable Weatherproof Break Glass Unit
s
Complie
4
5
N
E
with
Part II
This weatherproof addressable Break Glass
unit is manufactured from aluminium in order
to withstand harsh environments. It has a built
in push button activator to signal an alarm
activation.
The address of the call point is set via an
internal address module. Valid addresses are 1
to 126. The call point will return an analogue
value of 16 for normal conditions, and a value
of 64 during an alarm condition.
The unit is finished in red anti-corrosive epoxy
powder coating, with 2 x 20mm cable entries.
The unit is supplied with a hammer and chain
to operate the unit.
28
MODEL
ZTA-BGU/WP
PART NO
43-410
INPUT VOLTAGE
17-33V DC
ELEMENT TYPE
GLASS
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
3 mA
ALARM ACTIVATION
BREAK GLASS WITH HAMMER
OPERATING TEMPERATURE
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 65
SIZE (WxHxD mm)
260 X 260 X 110 105 X 100 X 58
WEIGHT
1.5 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZAMDD
Addressable Miditone Sounder
s
Complie
4
5
N
E
with
Pt 3
The midi-tone addressable sounder is a small, high
output sounder from Zeta Alarm Systems. It can
be used on any panel using the Zeta Addressable
Protocol. It is available in red or white.
It is a compact unit that fits a standard UK
back box, and can be either surface or flush
mounted.
It has an internal 8 way dip switch for setting the
device address, and a sound output of 90 dBA @
1m.
MODEL
ZAMDD/R
ZAMDD/W
PART NO
42-060
42-060A
INPUT VOLTAGE
17-33V DC
17-33V DC
QUIESCENT CURRENT
1.5 mA
1.5 mA
ALARM CURRENT
10 mA
10 mA
SOUND OUTPUT
90 dBA @ 1m
90 dBA @ 1m
NUMBER OF TONES
2 (CONTROLLED BY
FACP)
2 (CONTROLLED BY
FACP)
COLOUR
RED
WHITE
OPERATING
TEMPERATURE
-20°C to +50°C
-20°C to +50°C
MAX. HUMIDITY
95% RH N/C
95% RH N/C
IP RATING
IP 43
IP 43
SIZE, WxHxD (With
Back box)
85 x 85 x 35 mm (85 x
85 x 67 mm)
85 x 85 x 35 mm (85 x
85 x 67 mm)
WEIGHT (With Back
box)
102 g (152g)
102 g (152g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
29
ZAMDF/R
Midi-Tone Addressable Electronic sounder & LED Flasher
s
Complie
4
5
N
E
with
Pt 3
The midi-tone sounder-flasher is the latest
addressable combined sounder flasher from
Zeta Alarm Systems. It can be used on any
panel using the Zeta Addressable Protocol. It
is available in red, amber, blue or clear.
It is a compact unit that fits a standard
European back box, and can be either surface
or flush mounted.
It is an ideal way to upgrade an existing sounder
to a sounder-flasher unit.
It has an internal 8 way dip switch for setting
the device address, and a sound output of 90
dBA @ 1m
MODEL
ZAMDF/R
ZAMDF/A
ZAMDF/B
ZAMDF/C
Part No
42-062
42-062A
42-062B
42-062C
Lens Colour
Red
Amber
Blue
Clear
Operating Voltage
30
17-33V DC
Quiescent Current
1.7 mA
Sound Output
90 dBA @ 1m
Alarm Current @
24V dc
9.9 mA MAX
Operating
Temperature
-10°C to +50°C
Minimum Continuous
Temp
0°C
Max Humidity
95% RH Non Condensing
IP Protection Rating
IP 43
Size, WxHxD
(With Back box)
85 x 85 x 35 mm
(85 x 85 x 67 mm)
Weight (With Back
box)
112 g (162g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZAST
Addressable Securetone Sounder
s
Complie
4
5
N
E
with
Pt 3
The Securetone addressable sounder is a medium
sized, round style sounder suitable for many
applications. It can be used on any panel using
the Zeta Addressable Protocol. It is available in
red or white. It is intended for indoor use only.
It comes supplied with its own mounting plate,
which allows the sounder to be fitted with no
visible screw fittings.
It has an internal 8 way dip switch for setting the
device address, and a sound output of 88 dBA @
1m.
90mm
MODEL
ZAST/R
ZAST/W
PART NO
42-030
42-030A
INPUT VOLTAGE
17-33V DC
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
10 mA
SOUND OUTPUT
88 dBA @ 1m.
NUMBER OF TONES
COLOUR
100mm
2 (CONTROLLED BY FACP)
RED
WHITE
OPERATING
TEMPERATURE
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
100 x 100 x 70 mm
WEIGHT
230 g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
31
ZAMT
Addressable Maxitone Sounder
s
Complie
4
5
N
E
with
Pt 3
The maxitone addressable sounder is a large
horn sounder suitable for many applications.
It can be used on any panel using the Zeta
Addressable Protocol. It is available in red or
white. It is suitable for indoor & outdoor use
It has a large back-box with knockout cable
entries, which has plenty of room for fitting
the cables.
It has an internal 8 way dip switch for setting
the device address, and a sound output of 94
dBA @ 1m.
120mm
126mm
MODEL
ZAMT/R
ZAMT/W
PART NO
42-007
42-007A
INPUT VOLTAGE
17-33V DC
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
10 mA
SOUND OUTPUT
94 dBA @ 1m
NUMBER OF TONES
COLOUR
107mm
32
2 (CONTROLLED BY FACP)
RED
WHITE
OPERATING
TEMPERATURE
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 65
SIZE (WxHxD mm)
124 x 129 x 100 mm
WEIGHT
350 g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZIU
Zeta Addressable Input Unit
s
Complie
4
5
N
E
with
Pt 18
The ZIU is used to interface any equipment that
has a volt free normally open contact to a Zeta
Analogue Addressable fire alarm control panel.
In accordance with our policy of continual
improvement of our products, the ZIU interface
now includes a built in loop short circuit
isolator.
The unit has internal LED indications for Loop
Isolator active, Fault on input, and Alarm (Panel
controlled) . During the system set-up, the lid
can be removed from this box to allow these LEDs
to be viewed.
O
OO
O
7
7
7
O
MODEL
ZIU
PART NO
48-100
INPUT VOLTAGE
17 -33V DC
QUIESCENT CURRENT
1.5 mA
ALARM CURRENT
5 mA
INPUT
NORMALLY OPEN CONTACT
INPUT END OF LINE
47K RESISTOR
OPERATING TEMPERATURE
-0oC to 50oC
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
127 x 88 x 57
WEIGHT
220 g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 2 / 0 6 / 2 0 0 7 .
33
ZIOU & ZIOU/230
Zeta Addressable Input Output Units
s
Complie
4
5
N
E
with
Pt 18
The ZIOU is used to interface any equipment
that has a volt free normally open contact
to a Zeta Analogue Addressable fire alarm
control panel. Two versions are available. One
for switching low voltage, one for switching
mains.
In accordance with our policy of continual
improvement of our products, these interfaces
now include a built in loop short circuit
isolator.
As with all Addressable interfaces, the outputs
are controlled by the panel to which they are
connected. Consequently the interfaces will
behave differently on different panels. Ie some
may allow the outputs to be programmed,
others will have a default “pre-programmed”
operation.
The unit has internal LED indications for Loop
Isolator active, Fault on input, and Alarm
(Panel controlled) . During the system set-up,
the lid can be removed from this box to allow
these LEDs to be viewed.
O
O
O
O
O
MODEL
ZIOU
ZIOU/230
PART NO
48-105
48-106
INPUT VOLTAGE
17 -33V DC
QUIESCENT
CURRENT
1.5 mA
ALARM CURRENT
OO
INPUT
O
7
7
7
O
25 mA
NORMALLY OPEN CONTACT
INPUT END OF LINE
OUTPUT
34
10 mA
47K RESISTOR
1 x VOLT FREE
RELAY: 1A @ SELV
1 x VOLT FREE
RELAY: 5A @ 230V AC
OPERATING
TEMPERATURE
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
127 x 88 x 57
195 x 143 x 79
WEIGHT
220 g
400 g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
ZSCC & ZSCC/4
Zeta Addressable Sounder Control Units
s
Complie
4
5
N
E
with
Pt 18
The ZSCC AND ZSCC/4 modules are used to connect
conventional fire alarm devices (Bells, Flashers
or Sounders) to a Zeta Addressable loop. Two
versions are available. One has a single sounder
circuit, the other has 4 sounder circuits. Both
versions require a separate 24V power supply.
In accordance with our policy of continual
improvement of our products, these interfaces
now include a built in loop short circuit isolator.
As with all Addressable interfaces, the outputs
are controlled by the panel to which they are
connected. Consequently the interfaces will
behave differently on different panels. Ie some
may allow the outputs to be programmed,
others will have a default “pre-programmed”
operation.
The unit has internal LED indications for Loop
Isolator active, and Sounder circuit Active (Panel
controlled) . During the system set-up, the lid
can be removed from this box to allow these LEDs
to be viewed.
O
O
O
O
O
OO
O
7
7
7
O
Q
O
O
2
OO
3
CONN.
7
7
7
This module occupies 4 addresses:
The address on the dip switch, and
the 3 following addresses
O
MODEL
ZSCC
ZSCC/4
PART NO
48-110
48-111
INPUT VOLTAGE
17 -33V DC
17 -33V DC
QUIESCENT CURRENT
1.5 mA
1.5 mA
ALARM CURRENT
(EXCLUDING SOUNDER
LOAD)
10 mA
40 mA (10mA per
Circuit)
NUMBER OF SOUNDER
CIRCUITS
1
4
SOUNDER END OF LINE
10K RESISTOR
10K RESISTOR
OUTPUT
1 x 24V @ 400mA
4 x 24V @ 400mA
OPERATING
TEMPERATURE
-0°C to 50°C
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
95% RH N/C
IP RATING
IP 43
IP 43
SIZE (WxHxD mm)
127 x 88 x 57
195 x 143 x 79
WEIGHT
220 g
400 g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
35
ZTZM & ZTZM/4
Zeta Addressable Zone Monitoring Units
s
Complie
4
5
N
E
with
Pt 18
Zone monitors are used to connect conventional
detectors to an addressable loop. This may be
for economic reasons (because conventional
detectors are less expensive than addressable
ones), or for technical reasons (The required
detector may not be available in an addressable
form (EG Flame detectors)
The ZTZM is a single zone, loop powered
interface.
The ZTZM/4 is a 4 zone interface that requires
a separate 24V supply. This unit also includes a
built in loop short circuit isolator.
The unit has internal LED indications for
Loop Isolator active, and Zone Alarm (Panel
controlled). During the system set-up, the lid
can be removed from this box to allow these
LEDs to be viewed.
MODEL
Z
Z
Z
Z
CONN.
H
7
7
7
This module occupies 4 addresses:
The address on the dip switch, and
the 3 following addresses
36
Z
ZTZM
ZTZM/4
PART NO
48-115
48-118
INPUT VOLTAGE
17 -33V DC
17 -33V DC
QUIESCENT CURRENT
3.5 mA
9.5 mA
ALARM CURRENT
(EXCLUDING SOUNDER
LOAD)
15mA
60mA (15 per
Circuit)
NUMBER OF ZONES
1
4
ZONE END OF LINE
10K RESISTOR
10K RESISTOR
ALARM EQUIVALENT
LOAD
470R RESISTOR
470R RESISTOR
OPERATING
TEMPERATURE
-0°C to 50°C
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
95% RH N/C
IP RATING
IP 43
IP 43
SIZE (WxHxD mm)
127 x 88 x 57
195 x 143 x 79
WEIGHT
220 g
400 g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
Conventional Fire Alarm
Introduction
Conventional fire alarm systems have been
around for many years. They range from
simple 1 or 2 zone systems, to systems
with over 100 zones. The largest panel we
currently manufacture is 48 zones.
An end of line unit is fitted to the last device
in each circuit (Detection Zone, or sounder), in
order to monitor the line for breaks.
Conventional detection offers a good basic
system, ideal for small applications, or
projects on a tight budget.
• Control panel & devices tend to be cheaper
• Simple setup. No configuration required
• Wide range of compatibility between
manufacturers.
The detectors in a zone (or area) of the
building are all connected to the same pair
of wires. If any of these detectors reports
an alarm, a single indication is shown on
the control panel, meaning that the exact
location of the alarm is not shown.
Conventional systems offer the following
advantages over addressable systems:-
The sounders (including sounder bases) are
wired on a separate circuit.
M
S
H
S/H
S
M
S
E.O.L.
M
M
H
S/H
S
S
S
E.O.L.
S
E.O.L.
M
E.O.L.
S
M
H
S/H
M
H
H
H
H
S
E.O.L.
S
S
S
S
E.O.L.
ZONE: 1, 2, 3, 4, ... 48
FIRE ALARM CONTROL PANEL
S
H
S/H
M
230V AC
2x12V DC
(INTERNAL)
REPEATER PANEL
S
S
E.O.L.
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
SMOKE DETECTOR
HEAT DETECTOR
SMOKE & HEAT DETECTOR
MANUAL CALL POINT
SOUNDER
COMBINED SOUNDER/FLASHER
BASE SOUNDER
END OF LINE DEVICE
37
PE1, PE2
Premier Elite 1 or 2 Zone Fire Alarm Panel
to
EN54
pt. 2 &
4
The Premier Elite 1 & 2 zones panels are the
ideal entry-level panel for small premises that
require a fire alarm system. Their low cost and
simple installation will make them favourites
for years to come.
Calling on our years of experience in fire alarm
design, we have developed the Premier Elite
system to give everything that is required from
a small panel, whilst maintaining a competitive
price.
For larger systems, 4 zone, 6 zone and 8 zone
versions are also available.
ZONE +
MODEL
PE1
PE2
PART NO
37-040
37-041
SUPPLY VOLTAGE
230V AC +/- 10%
SYSTEM VOLTAGE
24V DC (NOMINAL)
DETECTION ZONES
IN
L1
IN
L1
-R
-R
IN
ZONE VOLTAGE
-R
L2
UT
IO
L1
UT
IO
L1
UT
IO
L1
L2
L1
L2
ZONE From
Fire alarm panel
38
To next
detector or EOL
1
2
22V DC (OFF LOAD)
ZONE END OF LINE
10 K RESISTOR
SOUNDER OUTPUT
2 X 400mA @ 24V DC
SOUNDER EOL
10 K RESISTOR
FIRE RELAY
1 RELAY, SELV @ 1A
OPERATING
TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
355 X 275 X 100mm
WEIGHT
2.5 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
PE4, PE6, PE8
Premier Elite 4 to 8 Zone Fire Alarm Panel
to
EN54
pt. 2 &
4
The Premier Elite 4-8 zone fire alarm panels are
ideal for small to medium sized installations.
They meet all the requirements of EN54 parts 2 &
4, and come in an attractively styled enclosure.
In addition to the Premier Elite 1-2 zone features,
the 4-8 zone versions also have:• Fault Relay
• Current limited charger to prevent flat batteries
drawing too much current
• Built in diode base compatibility
• Sounder Delay facility
• Connection to optional add on zonal output card.
• Zone disablement facility
• One man test facility.
The zonal output card gives a drive voltage to
operate zonal alarm relays, or a hardwired
repeater panel.
73mm
20 mm
355mm
+
-
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8
SND 1
SND 2
+
+
+
-
+
-
+
-
+
-
+
-
+
-
+
-
-
FIRE RELAY
CLASS
CHANGE
-
18
CONN1
PE6
PE8
PART NO
37-042
37-044
37-044
SUPPLY VOLTAGE
230V AC +/- 10%
SYSTEM VOLTAGE
29V DC (NOMINAL)
4
6
ZONE VOLTAGE
22V DC
ZONE END OF LINE
1N4002 DIODE
SOUNDER OUTPUT
2 X 400mA @ 24V DC
8
CONN5
EARTH
FS4
SND1
400mA
275mm
FS5
SND2
400mA
17
14 15 16
0
1
EARTH NEUTRAL
MAINS FUSE
1A HRC CERAMIC
12 13
1 2 3 4 5 6 7 8 910 11
CONN 27
60 mm
20 LIVE
FAULT RELAY
NO CM NC NO CM NC
PE4
DETECTION ZONES
12 x 19mm grommet cable entries
ZONE 1
MODEL
FS1
FS3
CHARGER En54 SUP
1.6A
1.6A
FS2
BATTERY
1.6A
+
- AC AC +
BATTERY
En54 pt4
24V SLA FROM
TRANSFORMER SUPPLY
SECONDARY
(OPTIONAL)
LIVE NEUT- EARTH
RAL
19
SOUNDER EOL
10 K RESISTOR
SOUNDER DELAY
0 TO 9 MINUTES
FIRE RELAY
1 RELAY, SELV @ 1A
FAULT RELAY
1 RELAY, SELV @ 1A (NORMALLY ENERGISED)
OTHER
CONNECTIONS
CLASS CHANGE INPUT (N/O CONTACT)
ZONAL OUTPUT CARD INTERFACE (20 WY
RIBBON)
MAINS TO TRANSFORMER PRIMARY
SEALED LEAD ACID BATTERY
SEALED LEAD ACID BATTERY
12V / 6 Ah
12V / 6 Ah
2 x 19mm
knock-out
cable entries
Flush / Wall
Mount
OPERATING TEMP.
-0°C to 50°C
ENCLOSURE SIZE
355 X 275 X 100mm
WEIGHT
3.25 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
39
NPSX1, NPSX2, NPSX4, NPSX6 & NPSX8
Premier SX Fire Alarm Control Panel
LPCB
ed
Approv
4
to EN5
4
pt. 2 &
The Premier SX Control Panel range is available
in 1,2,4,6 and 8 zones, housed in a light grey
flame retardant ULV0 enclosure, designed to
meet modern architectural surroundings, with
a removable hinged door.
The Premier SX has been designed with ease of
installation in mind, in addition to the robust
electronic design expected from GLT Exports
Ltd.
Flush/Wall
Mount
73mm
12 x 19mm grommet cable entries
2 x 19mmknock-out cable entries
355mm
60 mm
20 mm
ZONE 1
+
18
SND 1
SND 2 CLASS
CHANGE
FIRE RELAY FAULT RELAY
+
+
+
NO CM NC NO CM NC
-
+
-
+
-
+
-
+
-
+
-
+
-
-
-
1 2 3 4 5 6 7 8 910 11
20 LIVE
12 13
CONN5
EARTH
CONN1
78
FS4
SND1
400mA
275mm
FS5
SND2
400mA
17
14 15 16
23
90 1
456
FS1
FS3
FS2
CHARGER En54 SUP BATTERY
1.6A
1.6A
1.6A
+
AC AC
BATTERY
24V SLA
-
+
FROM
En54 pt4
TRANSFORMER SUPPLY
SECONDARY
(OPTIONAL)
SEALED LEAD ACID
BATTERY
12V / 6 Ah
40
EARTH NEUTRAL
MAINS FUSE
1A HRC CERAMIC
CONN 27
-
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8
19
LIVE NEUT- EARTH
RAL
MAINS TO TRANSFORMER PRIMARY
SEALED LEAD ACID
BATTERY
12V / 6 Ah
MODEL
NPSX1
NPSX2
NPSX4
NPSX6
NPSX8
PART NO
37050
37051
37052
37053
37054
DETECTION ZONES
1
2
4
6
8
MAINS VOLTAGE
230 VAC +10% / -15% @ 50/60Hz
SYSTEM VOLTAGE
24 VDC (Nominal)
ZONE VOLTAGE
21 VDC (Nominal)
SOUNDER ALARM O/P
2 x 400 mA @ 24V DC (Nominal)
FAULT RELAY OUTPUT
1 x Relay SELV ( 1 Amp maximum)
FIRE RELAY OUTPUT
1 x Relay SELV ( 1 Amp maximum)
ZONE CAPACITY
32 Devices per zone
REMOTE SOUNDER
ACTIVATION
Via N/O contact (class change)
SOUNDER ACTIVATION
DELAY
0-9 minutes in 1 minute increments
ZONE END OF LINE
IN4002 Diode (cathode stripe to +)
SOUNDER END OFLINE
10K Resistor
CHARGER VOLTAGE
28.4V @ 20°C (with battery
disconnected)
CHARGER SIZE
1.1 Amp
ZONE SHORT CIRCUIT
PROTECTION
100mA
CHARGER SHORT
CIRCUIT PROTECTION
Battery Voltage less than 20 V
ENCLOSURE SIZE
355 L x 275 H x 100 D (mm)
WEIGHT
3.25kg (Excluding Batteries)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
NPSX8ZC
Conventional Panel Zonal Output Card
The Zonal output card is designed to work with
Premier SX, Optima or Premier Elite control
panels. The board connects to the repeater
interface socket on the control panel display PCB
via a 20 way ribbon cable. The repeater has 28V
outputs for Common alarm, Zonal Alarm (zones
1 to 8), Common Fault & tone (buzzer) active.
These outputs can be used to drive individual
relays, or to connect to a hard wired repeater
panel.
Fitting the Zone Output PCB.
• Power Down the control panel before fitting this
PCB.
• The zonal output PCB is fitted to the left hand
side of the display PCB.
• It is attached with 2 x self tapping screws, and 2
x self adhesive PCB support posts.
• The ribbon cable connects to the repeater
interface connector CONN 4 on the bottom right
hand corner of the display PCB.
FITTING THE ZONE OUTPUT PCB
POWER DOWN THE CONTROL PANEL BEFORE FITTING
THIS PCB.
CONV-ZC
PART NO
37-069
COMPATIBILTY
Premier SX, Optima, Premier Elite (4-8
zones)
OPERATING VOLTAGE
20-30V DC
QUIESCENT CURRENT
10 mA
MAXIMUM CURRENT PER
CURCUIT
50 mA
FUSE RATING
400 mA
OPERATING TEMP.
-10°C to +50°C
MINIMUM CONTINUOUS TEMP.
0°C
MAX. HUMIDITY
95% RH Non-Condensing
IP PROTECTION RATING
N/A
0
1
MODEL
Screw
PCB Support
The zonal output PCB is fitted to the left hand side of
the display PCB.
It is attached with 2 x self tapping screws, and 2 x self
adhesive PCB support posts.
The ribbon cable connects to the repeater interface
connector CONN 4 on the bottom right hand corner of
the display PCB
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
41
PRE-REP
Premier Repeater Panel
The Premier Repeater panel is a hard-wired
repeater panel for use with the Premier SX (all
sizes), and the Premier Elite (4-8 zones)
It is display only (no controls), and indicates
power, general fault, general fire, and the
zone in alarm. It also has an internal buzzer to
indicate that it requires attention.
It comes supplied with an interface card to
connect to the Premier SX and Premier Elite
(4-8 zone) panels.
T1
SILENCE TONE K/S
+
D12
-
NC
R12
MODEL
PRE-REP
PART NO
37-045
SUPPLY VOLTAGE
20 – 35 V DC
SYSTEM VOLTAGE
29V DC (NOMINAL)
NOTE - ALL LEDS FITTED TO REVERSE SIDE
LED1
A8
LED2
A7
LED3
A6
LED5
LED4
A5
A4
LED6
LED7
A3
A2
LED8
LED9
PWR
A1
LED10
ALM
LED11
R1
R2
R3
R4
R5
R6
R7
R8
D1
D2
D3
D4
D5
D6
D7
D8
GLT 21 904
NPSXREP
17/11/06
TO GLT 21 896
ZONAL OUTPUT PCB
42
A+ GA- TN- CF-
Z8- Z7- Z6- Z5- Z4- Z3- Z2- Z1- 0V
FLT
R9
R10
R11
D9
D10
D11
CONNECTIONS
SUPPLY +VE
SUPPLY –VE
GENERAL ALARM
COMMON FAULT
TONE (BUZZER
ACTIVE)
ZONAL ALARM
A+
0V
GACFTNZ1- TO Z8-
OPERATING
TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
355 x 275 x 100mm
WEIGHT
1 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
PRE 8M+ Premier M Plus Control Panel
8 Zone - 24 zone
s
Complie
4
to EN5
pt. 2 &
4
The Premier M plus control panels are designed
to fulfill the requirements of EN54 part 2 and
part 4 as well as being easy to install, operate
and maintain.
Being of modular construction, the basic Mplus
panel has 8 zone capacity, expandable to 12,16,20
and 24 zones with M+4Z and M+8Z expansion
cards.
Should zonal alarm be required, M+4ZA and M+8ZA
cards can be added, and they will provide 50mA,
24 Vdc output per zone in alarm condition.
Mounting the panel
The Premier M Plus is suitable for Surface
Fitting, or Semi-flush fitting, with just the door
protruding.
73mm
95mm
275mm
395mm
430mm
485mm
100mm
Wall Mount
Flush Mount
MODEL
PRE 8M+
PART NO
37-020
DETECTION ZONES
8
EXPANDABLE TO
12,16,20 & 24
MAINS VOLTAGE
230 VAC± 10% / -15% @ 50/60 Hz
SYSTEM VOLTAGE
24 Vdc (Nominal)
ZONE VOLTAGE
21 Vdc
SOUNDER ALARM O/P
4 x 250 mA @ 24 Vdc
FAULT RELAY O/P
1 x relay SELV @ 1 A Maximum
FIRE RELAY O/P
1 x relay SELV @ 1 A Maximum
ZONE CAPACITY
32 Devices
ZONE E.O.L
100µF Capacitor
CHARGER VOLTAGE
28.4 Vdc (batteries disconnected)
CHARGER SIZE
3.0 Amp
ENCLOSURE
480L x 395H x 100D mm
WEIGHT
14.00 Kg
IP RATING
IP 43
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
43
PMP-REP & PMP-REP/M
Premier M Plus Repeater Panel
The Premier M Plus repeater is available in 2
versions.
The standard repeater offers display & control
functions, but is limited to one per system.
The second version allows multiple repeaters
on the system, but they do not have any control
functions. IE they can not be used to silence or
reset the system.
A single repeater can be powered from the
panel’s Auxiliary 24V supply. If more than one
repeater is to be used, a separate 24V supply
should be used.
MODEL
PMP-REP
PMP-REP/M
PART NO
37-026
37-027
SUPPLY VOLTAGE
255mm
330mm
406mm
480mm
44
20 – 30V DC
FUNCTIONS
DISPLAY &
CONTROL
DISPLAY ONLY
QUANTITY PER SYSTEM
1
5
CONNECTIONS
SERIAL REPEATER A
SERIAL REPEATER A
+24V DC
0V
OPERATING
TEMPERATURE
0°C to 50°C
ENCLOSURE SIZE
480 x 330 x 60 mm
WEIGHT
4.8 kg
60mm
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
PMP48
Premier 24 to 48 Zone Conventional Fire Alarm Panel
s
Complie
4
5
with EN
pt. 2 &
4
The Premier 48M Plus control panels are
designed to fulfil the requirements of EN54 parts
2 & 4 as well as being easy to install, operate &
maintain.
Being of modular design, the basic panel has 24
zones built in, and it can be expanded to 28, 32,
36, 40, 44 & 48 zones by using combinations of
M+4Z and M+8Z expansion modules. These are the
same modules as used on the Premier M+ panel.
Unlike the Premier M+, this panel does NOT
support zonal alarm circuits.
The construction of the panel is epoxy painted
steel enclosure, with top & rear cable entries.
MODEL
T
T
T
T
T
T
T
T
PMP48
PART NO
37-030
SUPPLY VOLTAGE
230V AC +10%/-15% @ 50/60 Hz
SYSTEM VOLTAGE
29V DC (Nominal)
DETECTION ZONES
24
EXPANDABLE TO
28, 32, 36, 40, 44 & 48
ZONE VOLTAGE
21V DC
ZONE END OF LINE
100μF capacitor
ZONE CAPACITY
Up to 32 Devices
SOUNDER OUTPUT
4 X 400mA @ 24V DC
SOUNDER EOL
10K Resistor
SOUNDER DELAY
0 TO 9 Minutes
FIRE RELAY
1 Relay, SELV @ 1A
FAULT RELAY
1 Relay, SELV @ 1A (Normally
Energised)
OTHER CONNECTIONS
Class Change Input (N/O Contact)
/ F.A.R.E. Output / Serial
Repeater Output (4 Wire)
T
CHARGER SIZE
3 Amp
CHARGER VOLTAGE
28.4V DC (Batteries disconnected)
IP RATING
IP43
OPERATING TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
675 x 480 x 135 mm
WEIGHT
13 kg
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
45
PMP48-REP , PMP48-REP/M
Premier M 48 Repeater Panel
The Premier M 48 repeater is available in 2
versions.
The standard repeater offers display & control
functions, but is limited to one per system.
The second version allows multiple repeaters
on the system, but they do not have any control
functions. IE they can not be used to silence or
reset the system.
A single repeater can be powered from the
panel’s Auxiliary 24V supply. If more than one
repeater is to be used, a separate 24V supply
should be used.
MODEL
255mm
330mm
406mm
480mm
46
PMP48-REP
PMP48-REP/M
PART NO
37-037
37-038
SUPPLY VOLTAGE
20 – 30V DC
20 – 30V DC
FUNCTIONS
Display & Control
Display Only
QUANTITY PER
SYSTEM
1
5
CONNECTIONS
Serial Repeater A /
Serial Repeater A /
+24V DC / 0V
Serial Repeater A /
Serial Repeater A /
+24V DC / 0V
OPERATING
TEMPERATURE
0°C to 50°C
0°C to 50°C
ENCLOSURE SIZE
480 x 330 x 60 mm
480 x 330 x 60 mm
WEIGHT
4.8 kg
4.8 kg
60mm
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
MX-16, MX32
Premier MX LPCB Approved Fire Alarm Panel
LPCB
ed
Approv
4
to EN5
4
pt. 2 &
The Premier MX range of panels are approved by LPCB to
EN54 parts 2 & 4.
The panels have an extensive range of configuration
options, but remain easy to install and configure.
The programming options include:•
•
•
•
MX-16
MX-32
Repeater Panel
The Premier MX supports up to 5 fully-functional
repeater panels via the RS485 port (2 cores).
37-145
37-147
Latching or non-latching zones
Delayed or non delayed zone operation
Standard or intrinsically safe zone mode
Short circuit to fire mode for compatibility with old
detectors.
• Zonal or common alarm operation (Requires output
expansion PCBs)
• Latching or non-latching fault modes.
• Fault Routing, Fire Routing & Fire Protection relays can
be programmed as 24V output (monitored) or volt free
• Fault Routing, Fire Routing & Fire Protection relays can
have delayed operation in any configuration.
The panel is available as flush mount on request.
MODEL
MX-16
MX-32
PART NO
37-140
37-142
SUPPLY VOLTAGE
230V AC +/- 10%
SYSTEM VOLTAGE
24V DC (NOMINAL)
DETECTION ZONES
16
32
ZONE VOLTAGE
24V DC (Nominal)
RELAY, SELV @ 1A
ZONE END OF LINE
22uF, 35V Axial Capacitor
SOUNDER OUTPUT
4 X 1.0A @ 24V DC
SOUNDER EOL
3k9 RESISTOR
PANEL INPUTS
REMOTE EVACUATION
REMOTE SILENCE ALARMS
REMOTE RESET
CLASS CHANGE
PANEL OUTPUTS
FAULT ROUTING RELAY, SELV @ 1A
FIRE ROUTING RELAY, SELV @ 1A
FIRE PROTECTION RELAY, SELV @ 1A
DISABLEMENT ACTIVE (OPEN COLLECTOR
OUTPUT)
EVACUATION ACTIVE (OPEN COLLECTOR
OUTPUT)
BUZZER ACTIVE (OPEN COLLECTOR OUTPUT)
RS 485 REPEATER CONNECTION
OPERATING
TEMPERATURE
-0°C to 50°C
MX-16 Repeater
MX-32 Repeater
ENCLOSURE SIZE
325 X 340 X 126mm
400 X 441 X 131mm
WEIGHT
7.05 KG
9.35 KG
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
47
FEO2000
Fyreye Conventional Smoke Detector
LPCB
ed
Approv
4
to EN5
pt. 7
The Fyreye optical smoke detector incorporates
a pulsing infra red LED Located in an optical
chamber inside the detector. The chamber
is designed to eliminate the effect of any
external light source.
A Photodiode is located inside the optical
chamber at an angle to the IR LED. Under normal
conditions no IR reaches the photodiode. But
when smoke enters the chamber it causes the
IR to scatter, and this will then be picked up
by the photodiode. If the photodiode “sees”
smoke on the 2 following pulses, the detector
enters the alarm state, and lights its LED
MODEL
FEO2000
PART NO
80-020
SUPPLY VOLTAGE
9-33V dc
AVERAGE QUIESCENT CURRENT
AT 9V
AVERAGE QUIESCENT CURRENT
AT 24V
24.5
17
38
55
100
40µA
ALARM INDICATION
Clear LED, Red in alarm
ALARM CURRENT AT 9V
17mA
ALARM CURRENT AT 24V
52mA Max
ALARM TRIGGER CONDICTION
3% per Metre smoke obscuration
OPERATING TEMPERATURE
-20 to +60°C (non condensing or
icing)
MAX. WIND SPEED
Not affected
REMOTE OUTPUT
CHRACTERISTICS
Current Sink to –ve line (17mA
max)
FE-CB Fyreye Common Base
FE-DB Fyreye Diode Base
FE-RB Fyreye Relay Base
FE-SB Sounder Base
FE-SFB Sounder Flasher Base
FE-RB/AR 12V Auto Relay Base
COMPATIBLE BASES
48
35µA
DETECTOR SIZE (WITHOUT BASE)
100mm diameter x 40mm deep
WEIGHT (WITHOUT BASE)
94g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
FEHR2000 & FEFH2000
Fyreye Conventional Heat Detectors
LPCB
ed
Approv
4
to EN5
pt. 5
The Fyreye Class A1R (rate of rise) heat detector
operates by utilising a matched pair of thermistors
to sense heat. One of these thermistors is exposed to
the ambient temperature, while the other is sealed
inside the detector housing. Under normal conditions,
both thermistors register similar readings. As fire
develops, the temperature registered by the exposed
thermistor will rise rapidly, resulting in an imbalance,
causing the detector to go into its alarm condition.
Rate of rise heat detectors also have an upper
temperature limit at which the detector will go
into alarm if the rate of temperature increase was
too slow to trigger the detector earlier. The Fyreye
Class CS (Static response or fixed temperature) heat
detector has only one thermistor, and changes to the
alarm state at a preset temperature.
24.5
17
38
55
100
MODEL
FEHR2000
FEFH2000
PART NO
80-030
80-040
SUPPLY VOLTAGE
9-33V DC
AVERAGE QUIESCENT CURRENT AT 9V
40µA
AVERAGE QUIESCENT CURRENT AT 24V
45µA
ALARM INDICATION
Red LED
ALARM CURRENT AT 9V
17mA
ALARM CURRENT AT 24V
52mA Max
ALARM TRIGGER CONDITION
Rise, or 57°C
90°C
OPERATING TEMPERATURE
-20° to +90°C (non condensing
or icing)
MAX. WIND SPEED
Not affected
REMOTE OUTPUT CHARACTERISTICS
COMPATIBLE BASES
Current Sink to -ve line (17mA
max)
FE-CB Fyreye Common Base
FE-DB Fyreye Diode Base
FE-RB Fyreye Relay Base
FE-SB Sounder Base
FE-SFB Sounder Flasher Base
FE-RB/AR 12V Auto Relay Base
DETECTOR SIZE (WITHOUT BASE)
100mm diameter x 40mm deep
WEIGHT (WITHOUT BASE)
77g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
49
FEOE2000
Fyreye-Extra Conventional Optical Smoke Detector
APPROVED
The Fyreye “Extra” range of conventional detectors
have an extra LED to improve detector identification
in an alarm condition. The 2 LEDs allow an alarm to be
observed from all angles.
The Detector uses a pulsing IR LED & Photodiode to
detect IR scatter caused by smoke entering the chamber
The detector will work with most modern fire alarm
control panels, and comes supplied with a locking grub
screw to prevent unauthorised head removal.
The FEOE2000 is particularly suitable for detecting optically dense smoke, involving materials such as soft
furnishings, PVC, plastic, foam, and all similar materials which produce small visible particles (0.5 to 10
μm)
50
MODEL
FEOE2000
PART NO
80-022
DETECTOR CLASS
Optical Smoke
DESIGN STANDARD
EN54 Pt 7
APPROVAL
DIFT
OPERATING VOLTAGE
9-33V DC
QUIESCENT CURRENT
65μA
ALARM CURRENT @ 24V DC
53mA MAX
OPERATING TEMPERATURE
-10°C to +50°C
MINIMUM CONTINUOUS TEMP.
0°C
MAX. HUMIDITY
95% RH Non Condensing
ALARM CONDITION
2.4% Obscuration per metre
COMPATIBLE BASES
FE-SB Sounder Base
FE-SFB Sounder Flasher Base
COVERAGE
100m2
IP PROTECTION RATING
IP 43
START-UP TIME
10 Seconds
SIZE, DIAMETER x HEIGHT (WITH
BASE)
100 x 37 mm (101 x 53 mm)
WEIGHT (WITH BASE)
95g (153g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
FEHE2000, FEFHE2000 Fyreye Extra
Conventional Rate of Rise and Fixed Heat Detectors
APPROVED
The Fyreye “Extra” range of conventional
detectors have an extra LED to improve detector
identification in an alarm condition. The 2 LEDs
allow an alarm to be observed from all angles.
The rate of rise detector uses a thermistor
arrangement to sense a quick rise in temperature,
and also a final threshold temperature of 57°C.
The fixed heat detector has a single thermistor
arrangement that gives an alarm at a temperature
of 90°C
The detector will work with most modern fire
alarm control panels, and comes supplied with a
locking grub screw to prevent unauthorised head
removal.
24.5
17
48
65
100
MODEL
FEHE2000
FEFHE2000
PART NO
80-038
80-039
DETECTOR CLASS
RATE OF RISE &
FIXED HEAT
FIXED HEAT ONLY
DESIGN STANDARD
EN54 part 5
APPROVAL
DIFT
OPERATING VOLTAGE
9 to 33V DC
QUIESCENT CURRENT
40 μA
ALARM CURRENT @ 24V DC
34mA
OPERATING TEMPERATURE
-10°C to 50°C
MINIMUM CONTINUOUS TEMP.
0°C
MAX HUMIDITY
ALARM CONDITION
95% RH non condensing
Rate of Rise or
Fixed Heat trigger
@ 57 °C
Fixed Heat trigger
@ 90 °C
COMPATIBLE BASES
FE-CB – Common Base
FE-DB – Diode Base
FE-SB – Sounder Base
FE-SFB – Sounder Flasher Base
COVERAGE
50m2
IP PROTECTION RATING
IP43
START UP TIME
10 seconds
SIZE, DIAMETER X HEIGHT
(WITH BASE)
100 x 48 mm (101 x 64 mm)
WEIGHT (WITH BASE)
75g (133g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
51
FEOH2000
Fyreye-Extra Conventional Opto-Heat Multi-Point Detector
APPROVED
The FEOH2000 is the latest addition to the Fyreye
range of detectors which incorporates both an optical
chamber and heat sensing element with advanced
detection technology and discrimination algorithms.
This dual optical multisensor is the perfect replacement
to ionisation detectors.
• Advanced electronic technology used to
minimise false alarms
• 17-30 Vdc
• Designed to meet EN54 requirement
• Compatible with all Fyreye bases
• Attractive design
• Remote LED output
• Lockable to base to stop unauthorised removal
• IP43
• Dual LEDs for 360° visibility
• Built-in 10 seconds alarm verification
• Alarm on heat only is 57°C
MODEL
FEOH2000
PART NO
80-025
SUPPLY VOLTAGE
17-20V dc
AVERAGE QUIESCENT CURRENT AT
24V
100uA
ALARM INDICATION
Dual Clear LED, Red in alarm
ALARM CURRENT AT 9V
17mA
ALARM CURRENT AT 24V
ALARM TRIGGER CONDICTION
OPERATING TEMPERATURE
MAX. WIND SPEED
REMOTE OUTPUT CHRACTERISTICS
COMPATIBLE BASES
52
70mA Max
3% per Metre smoke
obscuration
-20 to +60°C (non condensing
or icing)
Not affected
Current Sink to –ve line
(17mA max)
FE-CB Fyreye Common Base
FE-DB Fyreye Diode Base
FE-RB Fyreye Relay Base
FE-SB Sounder Base
FE-SFB Sounder Flasher Base
COVERAGE
100m2
DETECTOR SIZE (WITHOUT BASE)
100mm diameter x 50mm
deep
WEIGHT (WITHOUT BASE)
95g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
FEUV 2000
Fyreye Ultra-violet Flame Detector
4
to EN5
pt. 10
The FEUV2000 is the replacement for the ZTFD101
flame detector, that fits the standard fyreye
bases.
The detector is particularly suited in applications
where flames can be expected to develop
initially rather than smoke, due to the nature of
the materials being protected. EG Camera film,
computer/audio/video tapes/disks
The detector is for indoor use only, and should
not be exposed to spurious sources of UV, such as
sparks, uncovered halogen lights, lightening etc,
because these could give a false alarm.
Because of the nature of operation of flame
detectors, it is generally recommended to fit just
one detector per zone.
HORIZONTAL & VERTICAL DETECTOR FIELD
OF VIEW
30°
30°
60°
VERTICAL VIEWING
(top fig.)
60°
90°
90°
ANODE
CATHODE
30°
60°
30°
60°
90°
90°
ANODE
CATHODE
UV EMISSION
POINT
HORIZONTAL
VIEWING
(bottom fig.)
MODEL
FEUV2000
PART NO
80-045
INPUT VOLTAGE
12-28 V DC
QUIESCENT CURRENT
320 цA
OPERATING TEMPERATURE
0°C to 45°C
MAX WIND SPEED
NOT AFFECTED
STORAGE TEMPERATURE
-25°C to 80°C
ALARM CURRENT
45-50 mA
DETECTION ANGLE
120°
UV SENSITIVITY
185 – 260 nm
RESPONSE TIME
10 sec for 30mm flame @ 4 metres
SIZE (WxHxD mm)
98 X 98 X 36
WEIGHT
85 g
BASE
FE-CB, FE-DB, FE-RB, FE-SB, FE-SFB
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
53
FE-CB, FE-DB & FE-RB
Fyreye Conventional Detector Bases
LPCB
ed
Approv
4
to EN5
000
pt. 7.2
There are 6 different Fyreye detector bases
available for the conventional range of detectors,
namely , common base, diode base, relay base,
and the 6” versions of these three bases.The
common base is used on systems that don’t need
to keep line integrity on head removal, and also on
addressable systems.
The Diode base is used on systems that do need
line integrity on head removal. This would include
all conventional systems that mix detectors & call
points on the same line. (Note that the Premier M,
MZ & L will need an active end of line to work with
diode bases).
The Relay base is mainly used on 12V security
systems to signal detector operation to the panel.
They can also be used on 24V fire systems where
the activation of a particular detector requires
a signal to nearby equipment (door holders for
example). When using a relay base, DO NOT
CONNECT A REMOTE LED. The detector cannot sink
enough current to operate both.
MODEL
FE-CB
FE-DB
PART NO
45681-200 45681-201
80-054
SUPPLY VOLTAGE
9-33V DC
24V DC
AVERAGE QUIESCENT CURRENT
AT 24V
FE-RB relay base
0µA
ALARM CURRENT AT 24V
0mA
15mA
RELAY MAX SWITCHING POWER
N/A
30W, 50VA
RELAY MAX SWITCHING CURRENT
N/A
1A
Resistive
RELAY MAX SWITCHING VOLTAGE
N/A
50V AC
RELAY MINIMUM CAPABILITY
N/A
10µA,
10mV
RELAY DROPOUT VOLTAGE
N/A
<6v
OPERATING TEMPERATURE
-20 to +90°C (non condensing or
icing)
MAX WIND SPEED
Not affected
CONNECTIONS
L1in, L1out, L2, -R, Earth
BASE SIZE
100mm diameter x 15mm deep
WEIGHT
54
FE-RB
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
50g
50.2g
171.4g
FE-SB , FE-SFB Fyreye Conventional
Sounder Base & Sounder Flasher Base
Fyreye conventional sounder and sounder-flasher
bases are designed to meet the increasing demand
of having a sounder or flasher in each room that
has a detector fitted.
Each model has 8 selectable tones (configured by
a dip switch during commissioning) to give a wide
range of site compatibility.
The Sounder-flasher version has a red LED flasher
incorporated into the base.
MODEL
FE-SB
FE-SFB
PART NO
80-058
80-059
SUPPLY VOLTAGE
9-33V DC
18 – 33 V DC
SYSTEM VOLTAGE
24V DC (Nominal)
24V DC (Nominal)
SOUND OUTPUT @ 1m
90dB(A)
90dB(A)
OPERATING CURRENT
25mA
30mA
NUMBER OF TONES
8
8
SOUND FREQUENCY
440 – 1200 Hz
440 – 1200 Hz
FLASH COLOUR
N/A
RED
FLASH RATE
N/A
1 per Second
CONNECTIONS
Detector +VE = L1 IN
& L1 OUT
Detector -VE = L2
Sounder +VE = +
Terminal on PCB
Sounder -VE = Terminal on PCB
Detector +VE = L1 IN
& L1 OUT
Detector -VE = L2
Sounder +VE = +
Terminal on PCB
Sounder -VE = Terminal on PCB
OPERATING
TEMPERATURE
-0°C to 50°C
-0°C to 50°C
IP RATING
IP43
IP43
ENCLOSURE SIZE
101mm Diameter,
34mm Deep
105mm Diameter,
34mm Deep
WEIGHT
115g
130g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
55
ZT-LE8
Remote Indicator LED
The ZT- LE8 is the new-look remote indicator
LED from Zeta Alarm Systems.
Remote LEDs are used in installations where
a detector going to alarm is likely to occur
behind a locked door, or in a ceiling void. The
Indicator will then show the location of the
alarm.
The ZT-LE8 is designed to work
CONVENTIONAL Fyreye detectors only.
56
MODEL
ZT-LE8
PART NO
48-022
with
INPUT VOLTAGE
9 -33V DC
QUIESCENT CURRENT
0mA
ALARM CURRENT
LIMITED BY DETECTOR (TYPICAL 10mA)
COLOUR
WHITE PLASTIC, RED LENS
OPERATION COLOUR
RED
OPERATING TEMP.
0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
90 x 90 x 38
WEIGHT
56 g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZT-50RZ, ZT-100RZ, ZT-50RV & ZT-100RV
Fyreye 50/100 Reflective Beam Smoke Detector
Vds
ed
p
Ap rov
4
to EN5
pt. 12
The Fyreye Reflective Beam
Detector comprises a single
unit incorporating an Infrared transmitter and receiver.
The signal is reflected by
a prism and analysed for
smoke presence. Should
a predetermined level be
reached, the detector will
signal an alarm.
generally used for 2 reasons;
to cover a wide-open space,
or in places where several
regular smoke dete tors
would
be
aesthetically
unacceptable.
Available types:
2 wire models (ZT-50RZ
/ ZT-100RZ). These are
zone powered, but will
only work on Premier SX &
Premier M+ panels
4 wire models (ZT-50RV
/ ZT-100RV). Requires
an external 24V supply.
Has a fire relay and fault
relay output for wide
compatibility.
The system is designed to be
mounted so that the beam
will project between 0.3 and
0.6 metres below the ceiling,
and parallel to it. Lateral
detection may be up to 7.5
metres either side of the
beam. Beam detectors are
117mm
MODEL
ZT-50RZ
ZT-100RZ
ZT-50RV
ZT-100RV
PART NO
47-050
47-051
47-050A
47-051A
RANGE
5-50m
50–100m
5-50m
50–100m
NUMBER OF WIRES
2
4
SUPPLY VOLTAGE
10.2Vdc to 30Vdc
10.2Vdc to 30Vdc
QUIESCENT CURRENT
<4mA
<4mA
OPERATING
TEMPERATURE
-30°C to 55°C
-30°C to 55°C
MAX HUMIDITY
95% RH N/C
MAX WIND SPEED
ALARM CURRENT
210mm
FIRE OUTPUT
FAULT OUTPUT
POWER DOWN RESET
Not affected
35 mA (Typical)
<15 mA
470 ohm resistor
placed across zone
internally
Schottky Diode
introduced between
–VE in & -VE out
Fire relay closing
(relay contact is
normally open)
Fault relay opening
(relay contact is
normally closed).
<2 seconds
>5 seconds
BEAM MISALIGNMENT
TOLERANCE AT 35%
Detector ± 0.8°
Prism ± 5.0°
ALARM THRESHOLDS
2.50dB (25%), 3.74dB (35%), 6.02dB (50%)
OPTICAL WAVELENGTH
880nm
CONSTRUCTION
Flame Retardant ABS (Grey /Black) IP50
DETECTOR SIZE
130mm (W) x 210mm (H) x 120mm (D)
WEIGHT
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
0.75 kg
0.7 kg
57
ZT-5000/R
Auto-Aligning Reflective Beam Smoke Detector
Based on the proven technology of the standard Fyreye
reflective beam detector, the Fyreye 5000 Auto-Aligning
beam detector has been designed to help improve ease
of installation.
The detector now consists of 2 parts, the beam detector
itself, and a low level control unit. All connections are
made at the control unit, as well as all the alignment
functions. The unit can be configured as 50m or 100m
from the control unit, and can also be set into a low
current mode (at the expense of alignment motor
speed).
The beam detector has a built in laser sight to assist in
the initial mounting of the reflector plate.
Up to 4 beam detectors can be controlled from a single
control unit.
MODEL
BEAM 1
BEAM 2
BEAM 3
BEAM 4
24 V SUPPLY
X
TO FIRE ALARM PANEL ZONE
58
ZT-5000R
PART NO
47-058
RANGE
5-100 m
NUMBER OF WIRES
4
SUPPLY VOLTAGE
14Vdc to 28Vdc
OPERATING CURRENT
8-12 mA (low current mode)
48-52 mA (high current mode)
OPERATING TEMPERATURE
-20°C to 55°C
STORAGE TEMPERATURE
-40°C to 85°C
MAX HUMIDITY
85% RH N/C
MAX WIND SPEED
Not affected
ALARM CURRENT
35 mA (Typical)
FIRE OUTPUT
VOLT FREE RELAY CONTACT
FAULT OUTPUT
VOLT FREE RELAY CONTACT
BEAM MISALIGNMENT
TOLERANCE AT 35%
Detector ± 0.8°
Prism ± 5.0°
ALARM THRESHOLDS
2.50dB (25%), 3.74dB (35%),
6.02dB (50%)
OPTICAL WAVELENGTH
850nm
CONSTRUCTION
Flame Retardant ABS (Grey
/Black) IP54
DETECTOR SIZE
134mm (W) x 135mm (H) x
134mm (D)
DETECTOR WEIGHT
0.5 kg
CONTROLLER SIZE
200mm (W) x 235mm (H) x
71mm (D)
CONTROLLER WEIGHT
0.9 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
UV/IR Optical Flame Detectors
VS-200P and VS200EX (Explosion proof)
Non-Explosion Proof
(Polycarbonate
enclosure)
VS-200EX Explosion
Proof (Aluminium
enclosure)
VS-200P, an intelligent UV/IR flame detector,
this detector is well protected against the
versatile false alarms, such as ARC welding,
artificial light sources, etc.
•
•
•
•
•
•
Non-Explosion Proof (in ABS enclosure)
Explosion Proof (Aluminium enclosure) VS-200EX
UV/IR Dual-Sensor
High Immunity to False Alarms
User-Programmable Configuration
4-20mA Output
MODEL
VS-200P / VS200EX
SPECTRAL RESPONSE
UV : 0.185-0.260 microns
DETECTION RANGE
(HIGHEST SENSITIVITY
RANGE)
1sq.ft. N-Heptane fire at 65ft(20m)
RESONSE TIME
Typical 3 seconds for a 1 sq. ft. N-heptane
pan fire
TIME DELAY
Adjustable time delay up to 10 seconds
FIELD OF VIEW
100° hori./100° verti.
TEMPERATURE RANGE
-40°C to +85°C
HUMIDITY
Up to 95% RH
POWER SUPPLY
24VDC (9 to 35V)
POWER CONSUMPTION
Max. 20mA in standby / Max. 40mA in alarm
ELECTRICAL
CONNECTION
Standard 3/4” NPT gland or on request
DIMENSIONS:
DETECTOT UNIT
110 x 110 x 75 mm / Swivel #B (ball-jointed)
D=16/L=100mm
WEIGHT
Swivel #B : (OPTION) -“ball-jointed” :0.15kg
ELECTRICAL INPUT
PROTECTION
Complete electrical interface protection
against reversed polarity voltage, surges, and
spikes according to MIL-STD-1275
ELECTRMAGNET
COMPATIBILITY
The detector is designed to meet the
following EMC requirements:
Electrostatic Discharge (ESD) IEC801-2
Conducted Emission EN55022
Class A Radiated Emission:EN55022
Class A Radiated Immunity IEC801-3
Dry Contact Relays:
Alarm: 2A at 30VDC 0.6A at at 125VAC
Fault: 2A at 30VDC 0.6A at at 125VAC
Accessory: 2A at 30VDC 0.6A at at 125VAC
OUTPUTS
Applications
•
•
•
•
Chemical Processing & Storage Facilities
Fuel Loading Facilities
Warehouses
Public buildings/Others
4-20mA Current Output
Fault: 0 ± 0.5mA
Normal(Stand-by): 4mA ± 5%
IR Detection: 8mA ± 5%
UV Detection: 12mA ± 5%
Warning:20mA ± 5%
Alarm: 20mA ± 5%
Resistance Loop: 100-600 ohms
ENCLOSURE
ABS
WATER
IP65
PROTECTION
CERTIFICATION
Designed to meet EN54-10
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
59
ZT-CP2
Conventional Call Point
Complies
with EN54
Part 11
The ZT-CP2 is the latest conventional call point
from Zeta Alarm Systems. It has a modern
design, and has been built to EN54 part 11.
It is a resettable call point that signals an alarm
with a yellow flag entering the window area,
and a red alarm LED.
It is available in 2 versions The CP1 version
does not have the Perspex protective cover.
The CP2 version has the protective Perspex
cover as well as a “SNAPLATCH” catch that
needs to be broken off before the call point
cover can be lifted. This acts as a deterrent to
malicious activations, and allows double action
activation
Red is the recommended colour, but white is
available for when architectural requirements
demand.
MODEL
ZT-CP2
ZT-CP2/W
ZT-CP1
PART NO
43-300
43-314
43-301
INPUT VOLTAGE
9 -33V DC
ELEMENT TYPE
RESETTABLE
QUIESCENT CURRENT
0 mA
ALARM CURRENT
Typical 35 mA (Max 51 mA)
ALARM LOAD
ALARM ACTIVATION
PRESS
ELEMENT
COLOUR
RED
WHITE
RED
ALARM FLAG COLOUR
YELLOW
RED
YELLOW
OPERATING TEMP.
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (WxHxD mm)
WEIGHT
60
470 OHM RESISTOR
BREAK SNAPLATCH, LIFT
PERSPEX, PRESS ELEMENT
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
111 X 100 X 67
198 g
198 g
105 X 100
X 58
175 g
ZT-BGU/WP
Weather Proof Break Glass Unit
s
Complie
4
to EN5
pt. 11
The new ZT-BGU/WP is manufactured from
aluminium with built-in push button activator.
Finished with Red anti corrosive epoxy powder
coating with 2 x 20mm cable entries. This unit
is equipped with a stainless steel hammer and
chain.
Two models are available, ZT-BGU/WP/R
with 470Ω built-in resistor for connection to a
standard fire alarm system and ZTBGU/WP for
mains connection.
MODEL
ZT-BGU/WP/R
PART NO
43 - 300/WP
ZT-BGU/WP
43 - 305/WP
CONTACT RATING
10 Amps
VOLTAGE RATING
500V AC
IP RATING
IP65
BUILT-IN RESISTOR
470Ω
WEIGHT
1.5kg
EARTHING
2No M6 External & 1No M5 Internal
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
61
ZTBG-EXD
Explosion Proof Manual Break Glass Unit
The ZTBG/EXD explosion proof fire alarm control
is a station with an integral terminal chamber.
A push button actuator with a mushroom head
is provided in the main chamber.
This actuator is in constant contact with a glass
cover which when broken activates the alarm.
A single contact element in the main chamber
is wired to terminals in the terminal chamber
through sealed explosion proof bushings.
The alarm station is provided with gaskets for
weather proof protection.
62
MODEL NO.
ZTBG/EXD
PART NO.
43-310/EXD
Type of protection
Flame proof
Area classification
Zone 1 & 2
Gas Groups
Group I, II A, II B
Apparatus Standard
IS – 2148 / 81
CMRI Certificate No.
CMRS / TC / H167
Approvals
CCE
Material
Aluminium LM6
Weight
3.0kg (Approx)
IP Protection
IP 65
Finish
Anti corrosive epoxy powder
coated
Cable Entry
2 x ¾” ET
Gasket
Neoprene
Hardware
Stainless Steel (SS-304)
Contact element
INC
Rating Voltage
500 V, 50Hz AC
Terminals
4 x 2.5 mm²
Earthing
External : 2 Nos – M6
Internal : No - M5
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
ZMDD/8R
Midi-Tone Conventional Electronic sounder
s
Complie
4
to EN5
pt. 3
The miditone sounder is a small, high output
conventional sounder from Zeta Alarm Systems.
It is available in red or white.
It is a compact unit that fits a standard European
back box, and can be either surface or flush
mounted.
It has a choice of 8 tone patterns, selectable by
an internal dip switch, and a sound output of 95
dBA @ 1m with volume control.
This product is designed to meet the requirements
of EN54 part 3 and is CE marked.
MODEL
ZMDD/8R
ZMDD/8W
PART NO
42-040
42-040A
Lens Colour
Red
White
Operating Voltage
9-30V DC
Quiescent Current
0mA
Sound Output
95 dBA @ 1m
Alarm Current @ 24V dc
35mA MAX
Operating Temperature
-10°C to +50°C
Minimum Continuous Temp
0°C
Max Humidity
95% RH Non Condensing
IP Protection Rating
IP 43
SIZE (WxHxD mm)
(With Back box)
85 x 85 x 35
(85 x 85 x 67)
WEIGHT
(With Back box)
100 g
(150g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
63
ZMDF/8R
Midi-Tone Electronic sounder & LED Flasher
s
Complie
4
to EN5
pt. 3
The miditone sounder-flasher is the latest
combined sounder flasher from Zeta Alarm
Systems.
It is a compact unit that fits a standard
European back box, and can be either surface
or flush mounted.
It is an ideal way to upgrade an existing sounder
to a sounder-flasher unit.
It has a choice of 8 tone patterns, selectable
by an internal dip switch, and a sound output
of 95 dBA @ 1m.
64
MODEL
ZMDF/
8R
ZMDF/
8A
ZMDF/
8B
ZMDF/
8C
PART NO
42-042
42-042A
42-042B
42-042C
LENS COLOUR
Red
Amber
Blue
Clear
OPERATING VOLTAGE
17-30V DC
QUIESCENT CURRENT
0mA
SOUND OUTPUT
95 dBA @ 1m
ALARM CURRENT @
24V DC
40mA MAX
OPERATING TEMP.
-10°C to +50°C
MIN CONTINUOUS TEMP.
0°C
MAX. HUMIDITY
95% RH Non Condensing
IP PROTECTION RATING
IP 43
SIZE WxHxD
(WITH BLACK BOX)
85 x 85 x 35 mm
(85 x 85 x 67 mm)
WEIGHT
(WITH BLACK BOX)
112 g
(162g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZMDF-XL
Midi Xenon Flasher
The Midi Xenon flasher is a compact xenon flasher
designed to fit a 1 gang backbox.
It comes supplied with a backbox for surface
mounting, but it can be flush mounted to the
wall.
It has a 1 watt tube and a flash rate of 2 per
second.
Available in Red, Amber, Green, Clear & Blue.
This product is CE marked.
FRONT VIEW - LENS ONLY
MODEL
PART NO
COLOUR
85mm
3.8mm
7mm
85mm
SIDE VIEW - LENS & BACK PLATE
10mm
23mm
30mm
ZMDF/
XL
ZMDF/
XLA
ZMDF/
XLB
ZMDF/
XLC
ZMDF/
XLG
42-044
42044A
42044B
42044C
42044G
RED
AMBER
BLUE
CLEAR
GREEN
INPUT VOLTAGE
18 – 30V DC
QUIESCENT CURRENT
0 mA
ALARM CURRENT
80mA @ 24V DC
FLASH RATE
2 PER SECOND
POWER
1 WATT
LINE MONITORING
POLARISED
OPERATING TEMP.
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE (inc b/box)
WxHxD mm
85 x 85 x 30 (62)
WEIGHT (inc b/box)
93 g (144g)
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
65
ZST/8R
Securetone Conventional Electronic Sounder
s
Complie
4
to EN5
pt. 3
The Securetone sounder is designed to be
aesthetically pleasing and unobtrusive.
It has an elegant round design, and fits to its
supplied mounting plate with a bayonet action
to avoid unsightly screws.
It has 8 selectable tones, and has a volume
adjust screw to set the required sound level,
with volume control.
This product is designed to meet the
requirements of EN54 part 3 and is CE
marked.
90mm
100mm
66
MODEL
ZST/8R
ZST/8W
PART NO
42-004
42-004A
COLOUR
RED
WHITE
INPUT VOLTAGE
10 – 30V DC
QUIESCENT CURRENT
0 mA
ALARM CURRENT
35mA MAX
SOUND OUTPUT
100dBA @ 24V @ 1m
LINE MONITORING
POLARISED
OPERATING TEMPERATURE
-0°C to 50°C
MAX. HUMIDITY
95% RH N/C
IP RATING
IP 43
SIZE WxHxD mm
(inc PLATE)
100 x 100 x 75
(100 x 100 x 85)
WEIGHT (inc PLATE)
230 g (260g)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZTSL6
Zeta Secure Light Xenon Flasher
The ZTSL6 range are latest products designed to
provide a visual warning at alarm condition.
Lenses constructed of high-Impact and heat
resistant ACRYREX available in clear, amber, red
or blue.
The case is made of high-impact resistant ABS
plastic.
71 mm
93.2mm
Note: Requires two mounting screws Ø3 x 46 TP2
(included). This can be mounted directly to a
standard outlet box.
14mm
76mm
62mm
Requires two mounting screws Ø3 x 46 TP2 (included). This can be mounted
directly to a standard outlet box.
30.5mm
Ø2.3mm
MODEL
ZTSL6/R
ZTSL6/B
ZTSL6/C
ZTSL6/A
PART NO
42-035
42-036
42-037
42-038
COLOUR
Red
Blue
Clear
Amber
OPERATING VOLTAGE
20-30V dc
OPERATING CURRENT
100mA
FLASH ENERGY
3 Watt
FLASH FREQUENCY
60 times per minute
OPERATING
TEMPERATURE
-30°C to 60°C
INGRESS PROTECTION
IP54
LIVE MONITORING
Polarised
DIMENSIONS
150mm(dia) x 76mm (h)
WEIGHT
150g
71mm
Mounting Template
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
67
ZMT/8
Maxitone & Megatone Electronic Sounders
s
Complie
4
to EN5
pt. 3
Zeta electronic sounders are ideal alternatives
to fire bells. The electronic sounders produce
a high sound level at a lower current
consumption, making them ideal for reducing
the battery standby capacity for a system.
The Maxitone sounder ZMT has 8 selectable
tones (selectable via dip switch combinations),
and an adjustable volume control (for small
rooms).
The Megatone ZIDC (formerly known as an
Industrial sounder) is ideal for warehouses
or industrial use, as it generates an output
of up to 120 dBA @ 1 metre. It has 2 sets of
negative contacts, each producing a different
tone, making this sounder ideal for a 2 stage
evacuation. (If power is applied to both
negatives, the selectable terminal will have
priority).
MODEL
ZMT/8R
ZMT/8W
ZIDC/
10R
ZIDC/
10W
42-001
42001A
42-005
42005A
COLOUR
Red
White
Red
White
NO. OF TONES
8
PART NO
120mm
10 (& 2nd Stage)
OPERATING VOLTAGE
SOUND OUTPUT
103dBA @ 24V
@ 1m
120dBA @ 24V
@ 1m
OPERATING CURRENT
<16mA @ 24V dc
250mA*
126mm
107mm
10-50V dc
OPERATING TEMPERATURE
-30°C to 80°C
INGRESS PROTECTION
IP65
LINE MONITORING
Polarised
DIMENSIONS
124 x 130 x 100 mm
WEIGHT
357g
372g
* Take Care not to overload the sounder circuit when using these
devices.
68
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZTSR/EXD
Flame Proof Siren
The ZTSR/EXD is an explosion proof siren.
In the main chamber Intrinsically safe circuit
is housed and it is duly wired up to terminal
chamber through sealed bushes.
The horn unit is placed on the main chamber
cover and the output signals are taken through
sealed coils. Neoprene ‘0’ rings are provided for
the weather proof protection.
MODEL NO.
ZTSR/EXd24
ZTSR EXd230
PART NO.
42-100/24
42-105/230
TYPE OF PROTECTION
Flame proof – Exd T6 IP 65
AREA CLASSIFICATION
Zone 1 & 2
GAS GROUPS
Group I, II A, II B, II C
APPARATUS STANDARD
IS - 2148
CMRI CERTIFICATE
CMRI / TC / S / H388
APPROVALS
CCE, DGFAS
MATERIALS
Cast Aluminium LM 6
WEIGHT
5 Kg (approx.)
IP PROTECTION
IP 65 to IS 13947 / 93
FINISH
Anti corrosive Epoxy – Powder Coated
CABLE ENTRY
2 x ¾” ET
GASKET
Neoprene
HARDWARE
Stainless Steel
TERMINALS
4 x 2.5 sq. mm (standard) 6 x 2.5 sq. mm (for
looping)
VOLTAGE
24 V DC
230 V AC – 50 Hz
OUTPUT CURRENT
600mA Peak. Galvanically Isolated
POWER RATING
18 Watts
SOUND OUTPUT
106 db 900 Hz On & OFF alternatively at 1C/s
EARTHING
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
External: 2 Nos. - M6
Internal: 1 No. - M5
69
ZTB6B, ZTB8B & ZTB8B/WP
Fire Alarm Bells
s
Complie
4
5
N
E
with
Pt 3
The Zeta motorised fire alarm bells combine
styling and functional efficiency. They
incorporate a low power rotary centrifugal
mechanism, which gives a high sound output
with low current consumption at 24V dc.
The bells are available in 2 sizes;6” (152mm)
and 8” (203mm). These sizes suit a wide variety
of installations.
There is a 230V ac version of the 6” bell, and a
24V dc Weatherproof version of the 8” bell.
• Low current
• Universally accepted fire evacuation signal
152mm
55mm
40mm
10mm
MODEL
ZTB6B
ZTB6B/230
ZTB8B
ZTB8B/WP
PART NO
41-003
41-004
41-005
41-006
SUPPLY
VOLTAGE
18-30V dc
200-250V
AC
DIAMETER
6” (152mm)
8” (203mm)
QUIESCENT
CURRENT
25mA
28mA
NOMINAL
OUTPUT @ 1m
95dB(A)
97dB(A)
DIMENSIONS
152 x 152 x 55 mm
203 x 203 x 55 mm
860g
1700g
WEIGHT
70
18-30V dc
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
960g
1800g
ZTB8B/EXD
Flame Proof Gong Bell
The ZTB8B/EXD is an explosion proof gong bell
with a terminal chamber.
A highly reliable electric circuit is housed inside
to control the frequency of the gong operating
spindle. The operating spindle and dish are made
out of stainless steel thereby ensuring a long
life.
The electric circuits are connected to terminals
in the terminal chamber through nipple. The
covers are provided with neoprene gaskets for
weatherproof protection.
MODEL NO.
ZTB8B/EXD
PART NO.
41-075
TYPE OF PROTECTION
Flame proof – Exd T6 IP 65
AREA CLASSIFICATION
Zone 1 & 2
APPARATUS STANDARD
IS - 2148
MATERIAL
Cast Aluminium LM 6
WEIGHT
3 Kg (approx.)
IP PROTECTION
IP 65 to IS 13947 / 93
FINISH
Anti Corrosive Epoxy – Powder
coated
CABLE ENTRY
1 X 3/4” ET
GASKET
Neoprene
HARDWARE
Stainless steel
VOLTAGE
24V DC or 110V / 230V AC – 50 Hz
POWER RATING
12 Watt
SOUND OUTPUT
112db
TERMINALS
4 x 4 mm²
EARTHING
External: 2 Nos – M6 Internal: 1
No. - M5
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
71
ZT-DR240
Magnetic Door Holders
The Zeta magnetic door holder is designed to
retain a fire door open, against the force of its
own closing device.
In the event of a fire, the door holder magnet
can be turned off by the fire alarm, allowing
the door to shut.
An optional Floor mounting bracket is also
available.
There are 2 versions, 24V dc and 240V ac.
The 24v DC door holder requires either a panel
with a 24v DC output, or a separate 24V PSU.
This can be switched through the FACP aux
relay, but it might need back EMF diodes fitted
to the Door Holder (1N4002 or similar, stripe to
+, non-stripe to -).
SND+ IN
SND+ OUT
RELAY
NC
CM
NO
SND- IN
72
SND- OUT
MODEL
ZT-DR24
ZT-DR240
PART NO
50-001
50-002
RATED VOLTAGE
24V DC
240V AC
RATED CURRENT
35mA
6mA
SWITCH THROUGH AUX
Yes (with Diode)
No
NEEDS BACK EMF DIODE
Yes
No
HOLDING FORCE
200 Newton
DIMENSIONS (MAIN
UNIT)
70 x 90 x 45 mm
DIMENSIONS (KEEPER
PLATE)
56 x 56 x 52 mm
FIXING CENTRES
50 mm
WEIGHT
570g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
CO Monitoring & Control
System
The AirCOn 8 system has been designed
to be a simple to use addressable carbon
monoxide detection and alarm system,
capable of detecting low concentrations
of CO, and automatically starting the
building’s ventilation fans.
Its features include:• True analogue addressable system
• Economical 2 wire installation
• Can view the PPM reading of every detector
• Each detector can be given a 20 character
label to ease device identification (optional).
• Loop of 126 devices divided into 8 zones
• Continuously displays the maximum reading in
each zone
• Option for 2 ventilation relays per zone, for
systems with 2 speed fans
• Zonal or common ventilation options
• Easy to use ventilation level selection
• Battery backup enables the system to give an
alarm warning in the case of mains power failure
• System “programming” is determined by
detector & relay address settings
• Suitable for small and large installations
• Designed & Manufactured in the UK
• Meets latest low voltage directive
• CE marked
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
73
AirCOn8 Addressable Carbon Monoxide
Monitoring & Control System
The AirCOn 8 system is a self conditioned controller
with a capacity to handle up to 110 CO monitors
which are divided to 8 monitoring zones. Each
Zone will permanently display on the Liquid Crystal
Display (LCD) the highest concentration of CO in that
zone in PPM (Particles Per Million). This monitored
value is updated every minute. The system will
allow up to 2 interface modules (ZIOU) which are
programmed to initiate a signal to Ventilation
equipments to operate at pre-determined levels of
concentration. Should the CO concentration keep
rising while the Ventilation is still on, an alarm is
raised at a pre-determined level.
The AirCOn 8 system is idea for...
• Underground car parking facilities
• Warehouses where non-electric fork lift &
vehicles are used
• Tunnels
• Factories
• Boiler Rooms etc.
Device Address Allocation
ZONE
DETECTOR
ADDRESSES
FIRST
VENTILATION
ZIOU ADDRESS
SECOND VENTILATION
ZIOU ADDRESS
MODEL
AirCOn8
37-166
1
1 TO 14
15
16
PART NO
2
17 TO 30
31
32
MAINS VOLTAGE
230 ± 10% VAC, 50/60 Hz
3
33 TO 46
47
48
SYSTEM VOLTAGE
24 VDC + 9V Communication
4
49 TO 62
63
64
POWER SUPPLY
5
65 TO 78
79
80
1.0 Amp PSU
6
81 TO 94
95
96
WIRING
1 Loop, 2000 metres
7
97 TO 110
111
112
PANEL SIZE
335L x 275H x 100D (mm)
8
113 TO 124
125
126
SPACE FOR BATTERIES
Up to 2 x 7.0 AH SLA Batteries
INGRESS PROTECTION
IP43
Note: if Addressable alarm sounders are to be
used they can be fitted to any empty detector
address.
74
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
CO800
Addressable Carbon Monoxide Detector
The CO800 is an analogue addressable Carbon
Monoxide detector specifically designed for use
with the Aircon 8 addressable carbon monoxide
monitoring & ventilation panel.
The detector uses an electro-chemical sensor
with the detection range of 0 to 600 ppm of
carbon monoxide. The detectors address is
set via a binary dipswitch on the rear of the
detector.
The optimum mounting height for this detector
is between 1.5 & 2m from the floor
T
T PAIN
NO
DO
99 mm
36 mm
20 mm
MODEL
CO800
PART NO
47-015
OPERATING VOLTAGE
17 – 28 Vdc
STANDBY CURRENT
500µA @ 24Vdc
OPERATING TEMPERATURES
-20°C to +60°C
MAX. HUMIDITY
95% RH no condensation
MAX. WIND SPEED
Not Effected
INGRESS PROTECTION
IP43
COVERAGE
300m²
SENSOR / RANGE
Electro-chemical / 0-600ppm
SENSOR LIFETIME
5 years maximum
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
75
CO200
Stand Alone Carbon Monoxide Detector
The CO-200 is the new stand alone CO
detector from Zeta Alarm Systems. It has
been designed with the same dimensions as
a standard 2 gang fitting, so can be installed
either Surface mounted with it’s own backbox,
or with a standard recessed box for semi-flush
mounting.
It can be powered either from 230V AC mains,
or from a DC supply (9-28V DC).
It has a built in bar graph display to show the
current CO level reading, and has a 2 stage
relay output which operates at first alarm level
(100ppm) & second alarm level (200ppm).
There is also a 5 volt alarm output capable of
supplying 200mA.
It has power, fault & alarm indications, as well
as a control button for mute (press) and reset
(Press & hold for 5 seconds).
76
MODEL
CO-200
PART NO
47-400
SUPPLY VOLTAGE
230V @50/60Hz AC or 9 -28V DC
QUIESCENT CURRENT
20 mA
START-UP CURRENT
40 mA
ALARM CURRENT
300mA (excluding Alarm output)
BUZZER OUTPUT
85dB@ 3m
OPERATING TEMPERATURE
0°C to 50°C
MAX. HUMIDITY
95% RH N/C
RESPONSE TIME
<30 SECONDS
SENSITIVITY
50 ppm within 90 minutes
100 ppm within 30 minutes
300 ppm within 3 minutes
SIZE (WxHxD mm)
150mm x 90mm x 70mm
WEIGHT
1 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Combustible Gas
Detection Introduction
There are many factors to take into account
when designing a combustible gas detection
system, but the main ones to consider are:-
30cm from the ceiling. LPG is heavier than
air, so these detectors should be installed
approximately 30cm from the floor.
• What is the gas to be monitored
• What concentration is going to report an
alarm?
• Is it lighter or heavier than air?
• Is there anything present that can
contaminate the sensor?
• What do you want the panel to do in the
alarm condition?
Sensor can loose their sensitivity through
contamination or poisoning. This can be caused
by several factors, mainly environmental. If
the sensor element itself is exposed to paint,
lacquer, oil or grease, a loss of sensitivity can
occur through contamination. If the sensor
element is exposed to heavy metal compounds
or Silicon compounds, the catalyst in the sensor
can absorb these poisons and permanently
damage the sensor. If the detector is likely to
be exposed to anything that can contaminate
or poison it, it should be tested at regular
intervals.
GLT Exports supply detectors to detect
Natural gas, or LPG.
The Gasguard 2000 system has 3 programmable
levels that will each operate a separate relay
output. The levels are set as a percentage of
the LEL (Lower Explosion Level).
Natural gas is lighter than air, so these
detectors should be installed approximately
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
77
GG2000
Gas Guard 2000 Addressable Gas Alarm Panel
The Gas Guard 2000 has been designed to monitor
up to 30 addressable combustible gas detectors
which can be used in academic, domestic,
commercial or industrial applications
It has 3 user programmable outputs for
Ventilation, Lower LEL% warning and Higher
LEL% warning.
It connects to the detectors by 4 wires, 2 for
power, 2 for data
The Gas Guard 2000 is available with or without
a panel mounted printer.
MODEL
PART NO
PCB CONNECTIONS
COMMS TO
24V TO
DETECTORS DETECTOR
FAULT
RELAY
HIGH ALARM HIGH ALARM LOWER ALARM
RELAY 1
RELAY 1
RELAY
VENTILATION
RELAY
MAINS IN
47-300
47-300P
COMBUSTIBLE GAS (HYDROCARBON)
SUPPLY VOLTAGE
230V AC +/- 10% @ 50/60 Hz
NO
YES
MAX DETECTORS
30
MAX WIRING DISTANCE
1000 METRES WITH 2.5mm2 CABLE
DETECTION RANGE
0-100% LEL
RESPONSE TIME
<30 SEC
POWER-UP TIME
<60 SEC
OUTPUTS
FAULT – 1 X RELAY SELV @ 1A
VENTILATION – 1 X RELAY SELV @ 1A
LOWER ALARM – 1 X RELAY SELV @ 1A
HIGHER ALARM – 2 X RELAY SELV @ 1A
OPERATING
TEMPERATURE
-10°C to 50°C
HUMIDITY
<90% RH – NON CONDENSING
ENCLOSURE SIZE
(WxHxD)
250 x 450 x 100 mm
WEIGHT
78
GG2000-P
TYPE OF GAS
BUILT IN PRINTER
TO P.S.U.
GG2000
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
9.5 kg
10 kg
FECG2000, TC100
Addressable Combustible Gas Detectors
FECG2000
The addressable combustible gas detectors
suitable for use with the gas guard panel are
available in 2 different housing styles. The
FECG2000 is suitable for domestic, academic,
commercial or light industrial use. The TC100 is
suitable for heavy industrial usage.
Both styles of detector are available for natural
gas detection (methane), or for LPG detection
(Propane or Butane).
All detector combinations can be mixed on the
same wiring.
TC100
MODEL
FECG
2000N
FECG
2000L
TC100N
TC100L
PART NO
47-305
47-310
47-325
47-330
OPERATING
VOLTAGE
24V DC
TARGET GAS
NATURAL
GAS
L.P.G.
NATURAL
GAS
L.P.G.
POSITIONING
30cm
BELOW
CEILING
30cm
ABOVE
FLOOR
LEVEL
30cm
BELOW
CEILING
30cm
ABOVE
FLOOR
LEVEL
SENSOR TYPE
CATALYTIC
WORKING LIFE
3 YEARS
COVERAGE
20m RADIUS
MEASUREMENT
RANGE
0-100% LEL
WORKING TEMP
0°C TO 50°C
MAX HUMIDITY
0°C TO 60°C
<95% RH N/C
IP RATING
IP43
IP54
SIZE
100 x 100 x 39 mm
150 X 155 X 60 mm
WEIGHT
90g
860g
Issue N u m b e r : 2 . L a s t U p d a t e : 1 3 / 0 6 / 2 0 0 7 .
79
ZG-100
Stand Alone Combustible Gas Detector
The ZG-100 is the new stand alone Combustible
Gas detector from Zeta Alarm Systems. It has been
designed with the same dimensions as a standard
2 gang fitting, so can be installed either Surface
mounted with it’s own backbox, or with a standard
recessed box for semi-flush mounting.
There are two versions available. One calibrated
for Natural gas, one calibrated for LPG. They can
be powered either from 230V AC mains, or from a
DC supply (9-28V DC).
They have a built in bar graph display to show the
current Gas level as a %LEL reading, and has a 2
stage relay output which operates at first alarm
level (10%LEL) & second alarm level (25%LEL).
There is also a 5 volt alarm output capable of
supplying 200mA.
They have power, fault & alarm indications, as
well as a control button for mute (press) and reset
(Press & hold for 5 seconds).
BACK BOX for GAS DETECTOR
MODEL
90mm
35mm
PART NO
20mm
121mm
150mm
20mm Knockout
Hollow screw hole with threaded insert
80
47-405
47-410
230V @50/60Hz AC or 9-28V DC
QUIESCENT CURRENT
140 mA
START-UP CURRENT
220mA
ALARM CURRENT
500mA (excluding Alarm output)
BUZZER OUTPUT
85dB@ 3m
OPERATING
TEMPERATURE
0°C to 50°C
MAX. HUMIDITY
95% RH N/C
SENSITIVITY
screw fixing location
ZG-100L
SUPPLY VOLTAGE
RESPONSE TIME
KEY
ZG-100N
<30 SECONDS
4400ppm
1700ppm
SIZE (WxHxD mm)
150mm x 90mm x 70mm
WEIGHT
1 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Extinguishing System
Introduction
Extinguishing systems are primarily used
for the automatic protection of expensive
electronic equipment, such as network
servers, etc. which may be left unmanned
for long periods of time.
They work on the principle that 2 detection
zones are fitted to the area to be protected,
and that both zones should detect a fire
before the extinguishing agent is released.
(This is to avoid the possibility of releasing
the expensive gas in the event of a false
alarm).
When one zone detects an alarm, the control
panel will indicate this, and start the first
stage sounders. When the second zone goes
into alarm, the control panel will indicate
this. It will then stop the first stage sounders,
and start the second stage sounders, which
will have a different tone. The panel will also
start the bottle release timer. This is the delay
between the start of the second stage alarm,
and the extinguishing gas being released. When
the timer ends, the bottle output activates,
and the gas is released.
Most extinguishing panels will also have inputs
to initiate a manual release of the gas, or to
hold or abort the release of the gas. They
may also have the option to be switched to a
Manual only mode, so that the detectors will
not initiate a release.
E.O.L.
E.O.L. E.O.L.
S
S
S
E.O.L.
S
S
S
E.O.L.
E.O.L.
SC
E.O.L.
S1
E.O.L.
S2
E.O.L.
AUTO
MAN
E.O.L.
E.O.L.
AUX
CONTROL
CROSSED
ZONES
OUTPUTS
MONITORING
E.O.L.
EXTINGUISHING CONTROL PANEL
S
230V AC
2x12V DC
(INTERNAL)
REPEATER PANEL
S
E.O.L.
AUTO
MAN
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
SMOKE DETECTOR
MANUAL RELEASE CALL POINT
GAS ABORT CALL POINT
GAS HOLD PUSH BUTTON
COMBINED SOUNDER/FLASHER
END OF LINE DEVICE
AUTO/MANUAL SELECT SWITCH
GAS RELEASE PIPES
GAS CYLENDER
81
PEX8
Premier EX8 Combined extinguishing and Fire Alarm Panel
4-1
EN1209
5
N
&E 4
Pt 2, 4
The Premier EX8 has been designed to BS EN
12094-1:2003 & EN54 parts 2 & 4 standards.
It has 2 “crossed zones” for co-incidence
detection for the extinguishing circuit, and
4 conventional zones for standard fire alarm
detection for the rest of the installation (nonprotected area).
The panel has a large variety of inputs &
outputs, allowing it to connect to a wide
variety of equipment.
The panel has a built in manual release call
point with 2 stage operation to initiate the gas
release.
The panel also has a serial output to an optional
4 wire repeater panel.
MODEL
Panel Inputs & Outputs
SOUNDER OUTPUT
FIELD STATUS INPUTS
RELAY OUTPUTS
REPEAT OUTPUTS
82
1 X COMMON SOUNDER 400mA @ 28V DC
1 X 1ST STAGE SOUNDER 400mA @ 28V DC
1 X 2ND STAGE SOUNDER 400mA @ 28V DC
GAS FIRED
MANUAL RELEASE
EMERGENCY HOLD
EMERGENCY ABORT
AUTOMATIC/MANUAL MODE
LOW PRESSURE
BOTTLE SCALES
FIRST STAGE ALARM
SECOND STAGE ALARM
GAS RELEASED
FAULT
ABORT ACTIVE
HOLD ACTIVE
MANUAL RELEASE OPERATED
BOTTLE OPERATED
MANUAL MODE
AUTOMATIC MODE
GENERAL FAULT
PEX8
PART NO
37-091
SUPPLY VOLTAGE
230V AC +/- 10%
SYSTEM VOLTAGE
24V DC (NOMINAL)
DETECTION ZONES
2 x CROSSED ZONES, 4 PERIPHERAL ZONES
ZONE VOLTAGE
22V DC (OFF LOAD)
CROSSED ZONE EOL
10 K RESISTOR
PERIPHERAL ZONE EOL
100uF CAPACITOR
SOUNDER OUTPUT
1 X COMMON SOUNDER 400mA @ 28V DC
1 X 1ST STAGE SOUNDER 400mA @ 28V DC
1 X 2ND STAGE SOUNDER 400mA @ 28V DC
SOUNDER EOL
10 K RESISTOR
BOTTLE OUTPUT
2 AMP , 28V DC
BOTTLE EOL
10 K RESISTOR
FIELD STATUS INPUTS
EOL
10 K RESISTOR
SERIAL REPEATER
OUTPUT
4 WIRE (2 POWER, 2 DATA)
OPERATING
TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
485 X 395 X 130mm
WEIGHT
8 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 5 / 0 6 / 2 0 0 7 .
REP-EX8
Premier EX8 Repeater Panel
The Premier EX8 repeater panel is a serial (4
wire) repeater panel for use with the Premier
EX8 extinguishing control panel.
It is used where a protected area has more than
one entrance, and some control functions are
required at each entrance.
It has a built in manual release call point, and
has controls to allow the main panel to be set
into manual or automatic mode.
MODEL
REP-EX8
PART NO
37-092
SUPPLY VOLTAGE
28 V DC (FROM MAIN PANEL)
SYSTEM VOLTAGE
24V DC (NOMINAL)
CONTROLS
MANUAL RELEASE
AUTOMATIC / MANUAL MODE SELECT
INDICATIONS
POWER
SUPPLY FAULT
AUTOMATIC MODE
MANUAL MODE
BOTTLE DISABLED
HOLD ACTIVE
ABORT ACTIVE
MANUAL RELEASE
FIRE
GAS IMMINENT
GAS RELEASED
CONNECTION TO
PANEL
4 WIRE (2 POWER, 2 DATA)
OPERATING
TEMPERATURE
-0°C to 50°C
ENCLOSURE SIZE
355 X 375 X 100mm
WEIGHT
3 KG
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
83
ZT-CP2/Y, ZT-CP2/B
Manual Release Call point & Gas Abort Call point
Complies
with EN54
Part 11
The ZT-CP2/Y, and ZT-CP2/B are the latest
Manual Release and Gas Abort call points from
Zeta Alarm Systems. They have a modern
design, and have been built to EN54 part 11.
They can be used with most extinguishing
control panels. The yellow call point is used to
initiate a manual release of the extinguishing
gas. The blue call point is used to stop the
release of the extinguishing gas, for example
if the room is occupied.
They are both resettable call points that
signal an operation with a different colour flag
entering the window area.
They have a protective Perspex cover as well as
a “SNAPLATCH” catch that needs to be broken
off before the call point cover can be lifted. This
acts as a deterrent to malicious activations,
and allows double action activation
MODEL
Insert Key into Reset
Barrel
Turn Key Clockwise.
The Flag retracts and
Operating Element
springs forward.
Unit is now reset
84
ZT-CP2/B
ZT-CP2/Y
PART NO
43-312
43-310
INPUT VOLTAGE
9 -33V DC
9 -33V DC
ELEMENT TYPE
RESETTABLE
RESETTABLE
QUIESCENT CURRENT
0 mA
0 mA
ALARM CURRENT
DEPENDS ON
CONTROL PANEL
DEPENDS ON
CONTROL PANEL
ALARM LOAD
NORMALLY OPEN
CONTACT, CLOSES
ON ACTIVATION
NORMALLY OPEN
CONTACT, CLOSES
ON ACTIVATION
ALARM ACTIVATION
BREAK SNAPLATCH
LIFT PERSPEX
PRESS ELEMENT
BREAK SNAPLATCH
LIFT PERSPEX
PRESS ELEMENT
COLOUR
BLUE
YELLOW
OPERATION FLAG
COLOUR
YELLOW
RED
OPERATING
TEMPERATURE
-20°C to 50°C
-20°C to 50°C
MAX. HUMIDITY
95% RH N/C
95% RH N/C
IP RATING
IP 43
IP 43
SIZE (WxHxD mm)
111 X 100 X 67
111 X 100 X 67
WEIGHT
198 g
198 g
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Aspiration Detection
Introduction
In an aspirated detection system, air is
sampled from the protected area through a
network of pipes or tubes, actively drawing
the air towards the detection system using a
high pressure aspirator fan.
accessibility of point detectors within a sampling
system.
There are 2 main considerations for choosing
an aspirating system.
As an intermediate system, this solution offers
sensitivity far higher than a standard smoke
detector, but at a fraction of the cost of a full
dedicated aspirating system.
The first is that the sampling pipework used
in aspirating systems is more resilient to
harsh environments than a standard point
smoke detector.
The second is that aspirating systems can
often give a much higher sensitivity than a
standard smoke detector.
Because of the range of requirements, GLT
Exports offer a range of equipment to suit
all budgets.
O ption 1: Aspirating Uni t &
s t andard smoke detecto r
Option 2: Aspirating unit &
Laser smoke detector
Option 3: Dedicated aspiration
system
This high-sensitivity smoke detector is an
instrument quality nephelometer collecting
scattered laser light from smoke particles over a
full 360 degree sweep. The resultant sensitivity
is an astonishing 0.001% obscuration/metre some
2000 times more sensitive than conventional
smoke detectors.
This is an ideal solution for systems that
require
the ruggedness, security and
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
85
ASD1 & ASD2 Fyreye Aspirated Smoke Detection System
For Standard Smoke Detectors
Vds
ed
p
A prov
The ASD1 and ASD2 aspiration systems actively
draw air from the protected area through
a network of 25mm pipes perforated with
sampling holes. The system incorporates one
or two conventional or analogue point smoke
detectors, allowing for redundancy or mixed
detection strategies.
Each model utilises a high performance
aspirator and flow monitoring circuitry, with
the flow level indicated on a bar graph.
Each panel can have up to 100m of pipe per
channel.
MODEL
ASD1
ASD2
PART NO
82-005
82-010
SUPPLY VOLTAGE
NOMINAL 24V DC (18 TO 30V DC)
CURRENT
300mA MAX
NUMBER OF
DETECTORS
1 OR 2
NUMBER OF INLET
PIPES
1
2
CONFIGURATION
OPTIONS (2
DETECTORS)
REDUNDANT,
DOUBLE KNOCK
REDUNDANT,
DOUBLE KNOCK,
DOUBLE AREA
PIPE DIAMETER
86
25mm
PIPE LENGTH
100m MAX
SENSITIVITY
DEPENDS ON DETECTOR USED
ALARM INDICATION
VIA DETECTOR
OTHER CONNECTIONS
1 X FAULT RELAY
IP RATING
IP65
OPERATING
TEMPERATURE
-10°C to 60°C
ENCLOSURE SIZE
259 X 183 X 166 mm
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
LASD1 & LASD2
Aspirated Smoke Detection System For Laser Smoke Detectors
Vds
ed
p
A prov
The LASD1 and LASD2 aspiration systems actively
draw air from the protected area through a
network of 25mm pipes perforated with sampling
holes. The system incorporates one or two Laser
point smoke detectors, allowing for redundancy
or mixed detection strategies.
Each model utilises a high performance aspirator
and flow monitoring circuitry, with the flow level
indicated on a bar graph.
Each panel can have up to 100m of pipe per
channel.
MODEL
PART NO
LASD1
LASD2
82-105
82-110
SUPPLY VOLTAGE
NOMINAL 24V DC (18 TO 30V DC)
CURRENT
300mA MAX
NUMBER OF
DETECTORS
1 OR 2
NUMBER OF INLET
PIPES
1
2
CONFIGURATION
OPTIONS (2
DETECTORS)
REDUNDANT,
DOUBLE KNOCK
REDUNDANT,
DOUBLE KNOCK,
DOUBLE AREA
PIPE DIAMETER
25mm
PIPE LENGTH
100m MAX
SENSITIVITY
0.03 TO 3.33%/m ADJUSTABLE
ALARM INDICATION
VIA RELAY
OTHER CONNECTIONS
1 X FIRE LEVEL 1
1 X FIRE LEVEL 2
1 X FAULT
IP RATING
IP 65
OPERATING
TEMPERATURE
-10°C to 60°C
ENCLOSURE SIZE
259 X 183 X 166 mm
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
87
LAZ-R 1, LAZ-R 4, LAZ-R 6, LAZ-R 8 & LAZ-R 15
High Sensitivity Laser Aspirated Smoke Detection System
Vds
ed
p
A prov
The Zeta LAZ-R range of detectors provide the earliest
possible warning to any potential fire threat. They can
detect smoke down to levels of 0.001%
They are ideal for many applications, including power
stations, telecom centres, IT facilities, LCD fab`s, semi
conductor clean rooms, logistic centres, cold storage,
prisons, historic buildings, museums, mines and other
harsh and hazardous areas.
The LAZ-R aspiration system is available in 1,4,6,8 or 15
channel versions. The 1, 4 and 6 versions use standard
25mm diameter tube. The 8 & 15 channel versions use
microbore pipes (6mm O/D, 4mm I/D).
MODEL
LAZ-R1
LAZ-R4
LAZ-R6
LAZ-R8
LAZ-R15
PART NO
82-205
82-210
82-215
82-220
82-225
SUPPLY
VOLTAGE
QUIESCENT
CURRENT
500mA
600mA
MAX CURRENT
1.2A
1.5A
NUMBER OF
INLET PIPES
Up to 4
4
6
8
15
ALARM
INDICATIONS
1
4
6
8
15
PIPE
DIAMETER
25mm
6mm
PIPE LENGTH
100m
50m
ASPIRATOR
TYPE
1400Pa CENTRFUGAL AIR
PUMP
0.8 BAR ROTARY
VANE VACUUM
PUMP
SENSITIVITY
88
NOMINAL 24V DC (18 TO 30V DC)
0.001 to 20% obscuration / metre
ALARM LEVELS
ALERT , ACTION , FIRE 1 , FIRE 2
OTHER
CONNECTIONS
4 X ALARM RELAYS (PROGRAMMABLE)
1 X FAULT RELAY
RS232
RS485
TCP/IP (OPTION)
IP RATING
IP30
OPERATING
TEMPERATURE
-10°C to 60°C
ENCLOSURE
SIZE
490 X 355 X 204 mm
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
Premier Fire Telephone
System Introduction
The Premier Fire Telephone System is an
emergency telephone system which has been
developed in accordance with BS5839 part ll
and BS5839 parts 8 &9. This system is a fully
monitored/battery backed communicator
which enables fire officers / building
management personnel to report the status of
any emergency within a building quickly and
efficiently to the main control centre. This
ensures that the occupants are evacuated
with ease and less panic. The whole system
is simple to operate, and install and will
work independently to any other emergency
fire system within a building.
remote fire telephone. The control panel is
wall mounted within the permanently manned
main control room. There are various types
of telephone remote units available, which are
wall mounted in areas of risk such as stairways,
corridors and “gathering” areas. Operation of
these remote units are extremely simple – just
lift the handset to contact the main control
room.
The system comprises of two main components
these being the main control panel and the
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
89
Premier
Fire Telephone Control Panel
The Premier Fire Telephone Control Panel is
housed in epoxy painted metal boxed with a
perspex door.
The PFT comes with a 10 Amp integral power
supply and telephone set. All controls and
indications have been incorporated with a
large LCD screen for ease and clarity during
emergency operation.
The PFT has a capacity of handling 99
addressable remote emergency devices
such as a ZATT (telephone handset) , ZATS
(Addressable telephone jack sock) and ZATIU
(Addressable telephone interface unit).
Unlimited number of non-addressable sub
telephone and jack socket can be connected
to the control panel.
Features
• Automatic sound recording
• Facility to connect extend land telephone line
with Automatic
• Auto-Dialing in emergency condition
• Real time clock display
• Emergency recording up to 2 minutes
• Manual dial-up of land line
telephone (when connected)
90
MODEL
PFT
PART NO
195-001
System Voltage
24 Vdc
Frequency Response
300-3400Hz(+- 3db)
Bus Load
1.oA Maximum
Bus Length
1.5km (2.5mm² Cable)
Mode of Signal
DTMF
Power Supply
10A
Back-up Batteries
2 x 12AH -12Vdc
IP Rating
IP43
Dimensions
480L x 410W x 140mmD
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZATT & ZTT
Fire Telephone Handset
There are two types of fire telephone available
and a wide variety of enclosures depending on
the location and architectural requirements.
The ZATT is an addressable unit, ZTT is a
conventional (sub unit).
Both are made of impact resistance flame
proof polycarbonate casing and manufactured
specifically for use with our Premier Fire
Telephone Control Panel.
MODEL
ZATT
ZTT
PART NO
195-010
195-0
BUS VOLTAGE
13 – 28 Vdc
SOUND LEVEL OF RING
65dB
STANDBY CURRENT
≤7mA
RATED CURRENT
≤50mA (During Call)
FREQUENCY RESPONSE
300 – 3400Hz +- 3dB
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
91
ZATS
Fire Telephone Socket
The ZATS fire telephone extension plug-whole
socket is an addressable socket to be used
with the Premier Socket to be used with the
Premier Fire Telephone Control Panel.
The ZTS conventional sockets can be
spurred off the ZATS in unlimited number.
The ZHS portable jack handset will connect
directly to the main Fire Telephone Control
Panel.
92
MODEL
ZATS
ZTS
PART NO
195-020
195-021
VOLTAGE
13 - 28Vdc
LINE SIGNAL SENDING
0-5db
LINE SIGNAL RECEIVING
0-15db
STANDBY CURRENT
≤7mA
RATED CURRENT
≤50mA (During Call)
FREQUENCY RATING
300-3400Hz +- 3db
Issue N u m b e r : 2 . L a s t U p d a t e : 2 6 / 0 6 / 2 0 0 7 .
ZATIU
Telephone Interface Unit
The ZATIU telephone interface unit is an
addressable unit can be connected directly to the
bus and it will provide a wide range of options.
Up to four ZTT or ZTS’s can be connected to each
ZATIU where required (typically in long corridors
where all units can have one address).
The ZATIU when placed far from the control
panel (more than 50m) must have the auxiliary
24Vdc (provided in the panel) in order to make
sure that the ring tone level is not jeopardized.
MODEL
ZATIU
PART NO
195-030
VOLTAGE
13-28Vdc
LINE SIGNAL SENDING
0 - 5dB
LINE SIGNAL RECEIVING
0 - 15dB
STANDBY CURRENT
≤18mA
RATED CURRENT
≤180mA (ringing), ≤50mA talking
FREQUENCY
300 – 3400Hz +-3dB
Issue N u m b e r : 2 . L a s t U p d a t e : 0 2 / 0 7 / 2 0 0 7 .
93
ZTS-PB
Fireman Telephone Enclosures
The enclosures for the fi reman’s telephone
are available in a variety of styles to suit a
wide range of locations.
They are
options:-
available
with
the
following
• Colour – Epoxy Painted Signal Red or Brushed
Silver Steel
• Mounting options – Surface mounting, or flush
mounting.
• Access – Pull handle, or Locked enclosure for
restricted access
• These enclosures are sold separately.
130mm
102mm
5mm
MODEL
265mm
255mm
100mm
5mm
330mm
94
ZTS-PB/RSL
ZTS-PB/
RSH
ZTS-PB/RFL
ZTS-PB/
RFH
PART NO
195-100
195-105
195-110
195-115
COLOUR
Signal Red
Signal Red
Signal Red
Signal Red
MOUNTING
Surface
Surface
Flush
Flush
ACCESS
Key Lock
Handle
Key Lock
Handle
MODEL
ZTS-PB/SSL
ZTS-PB/SSH
ZTS-PB/SFL
ZTS-PB/
SFH
PART NO
195-120
195-125
195-130
195-135
COLOUR
Stainless
Steel
Stainless
Steel
Stainless
Steel
Stainless
Steel
MOUNTING
Surface
Surface
Flush
Flush
ACCESS
Key Lock
Handle
Key Lock
HANDLE
Issue N u m b e r : 2 . L a s t U p d a t e : 2 6 / 0 6 / 2 0 0 7 .
Voice Evacuation
Introduction
Studies have consistently shown that people respond more readily and with
less panic in a fire or other emergency situations, to spoken instructions
than to loud electronic sounders or bells.
The Premier Voice evacuation solution has been designed and developed
as a stand alone system that will compliment any Zeta Fire Detection
System.
The System will handle 300W total load (up to 100 x 3W speakers)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
95
PEBS2000
Voice Evacuation Control Panel
The Premier Emergency Broadcast System
is the latest control panel designed in full
compliance with BSEN542000 Part 8 & 9 to
provide a simple voice evacuation system in a
fire or other emergency situation.
The control panel is designed to match the
Premier AL range of fire alarm panels. It has
a glazed enclosure, and is equipped with an
integral microphone for live broadcasting, and
an internal monitoring speaker with volume
control.
Features include:• 4 selectable audio channels
• Lines monitored for open and short circuit
• Monitored input for a remote microphone
• Automatic alert and evacuate inputs
• Amplifier output overload protection and indication
• Up to 2 minute message recording via integral
microphone
• Integral power supply and battery charger
Other Features include:• Each circuit is terminated with a ESEOL end of line
unit.
• The end of line device will have a power
consumption of about 1 Watt.
• Any channel can have more than 75W load,
PROVIDED the total system load does not exceed
300W
• Using 3W speakers, an average of 25 per line can
be connected, giving a system maximum of 100
speakers.
• Cable length can be up to 1 km, when using 1mm2
cable.
• Any unused circuits have an ESEOL unit fitted.
96
MODEL
PEBS2000
PART NO
180-001
NO. OF CHANNELS
4
CHANNEL OUTPUT
75W per Channel (300W Total)
OUTPUT POWER
300W / 120V
OUTPUT POWER MONITOR
>0.25W
SIGNAL TO NOISE
>55dB
HARMONIC DISTOTION OF
POWER AMPLIFIER
63Hz – 16kHz <5%
FREQUENCY CHARACTARISTIC OF
POWER AMPLIFIER
63Hz – 16kHz <1dB
MESSAGE SOURCE
Remote microphone local
microphone alert message
evacuation message
MAINS VOLTAGE
230V AC+10% / -15%
DIMENSIONS (W x H x D)
530 x 720 x230mm
WEIGHT
34Kg
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
CS3 / WS3 / ESEOL
Ceiling Mounted Speaker / Wall Mounted Speaker / End of Line Module
CS3
ESEOL
CS3
WS3
equipment assembled
The CS3 is a 3 Watt 120V with constant-voltage
Ceiling mounted speaker audio power amplifier.
for use on the Premier Input
by
constant
Emergency Broadcast voltage
120V.5-inch
System.Loudspeaker loudspeaker box, wall
equipment assembled or ceiling installation.
with constant-voltage ESEOL
audio power amplifier.
Input
by
constant The ESEOL Emergency
voltage
120V.Ceiling System End of line unit is
used with the PEBS2000
installation.
control panel.It is used
WS3
to monitor the speaker
The WS3 is a 3 Watt 120V lines for a break in the
wall mount speaker cable (open circuit).
for use on the Premier
Emergency Broadcast
System.Loudspeaker
MODEL
CS3
WS3
ESEOL
PART NO
180-002
180-005
180-004
RATED OUTPUT
3W
N/A
INPUT AUDIO
VOLTAGE
120V
20-30V
FREQUENCY
RESPONSE
120Hz – 11 kHz
N/A
SENSITIVITY
90dB
92dB
N/A
DIMENSIONS
178mm DIA X
135mm
220mm x
180mm x
78mm
103mm x
66mm x 27mm
WEIGHT
1.3kg
1.1kg
0.1 Kg
MONITORING
CURRENT
N/A
N/A
2-10mA DC
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
97
RMM2000
Remote Emergency Microphone in Box
The RMM2000 is a remote emergency
microphone in IP65 enclosure, usually mounted
on an external wall allowing live evacuation
from a safe location.
The hand-held microphone is optically and
acoustically monitored.
98
MODEL
RMM2000
PART NO
180-003
CONNECTION
2 Core Shielded Cable
MAX WIRING DISTANCE
1000 Metres
RATED OUTPUT LEVEL
0dBm Balanced
FREQUENCY CHARACTERISTICS
300Hz TO 3400Hz
INPUT OF MICROPHONE
1mV
SIGNAL GAIN
50dB
WEIGHT
10Kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Linear Heat Detection
Introduction
The “Heat Tracer” linear heat detection
cable is ideal for these situations, and is
available in standard, and hot-spot locating
versions.
Principle of operation.
g
Co
lin
and
nv
eyo
r
sH
od
Be
Cable Trays
Ca
ing
elv
bin
Sh
ets
gh
Hi
The Primary mechanism of
heat (fire) detection is that
the dielectric between the
2 NTC cores is monitored for
any change, and compared to
the 2 PVC cores.
• Cable tunnels & ducts
• Road & rail Tunnels
• Petro-chemical storage tank rim seals
• Conveyor belts
• Electric rooms
• High rise warehouse stacking
• Escalators and moving walkways
• Paint shops & spray booths
• Ceiling voids & attic spaces
• Marine engine rooms
• Electrical switchgear cabinets
• Oil rig & off shore systems
• Steam pipe leaks & trace heating faults
• Aircraft hangers
• Computer room under voids
Go
The Zeta Heat tracer system consists of a
control module, and a special 4 core heat
tracer cable. The cable has 4 cores, 2
are covered with negative
temperature
co-efficient
(NTC) material, the other 2
have normal PVC insulation.
The cores are twisted
together
and
protected
by an outer sheath of high
temperature flame retardent
PVC insulation.
Ty p i c a l A p p l i c a t i o n s :
lts
There are many situations when conventional
heat or smoke fire detectors only work to a
limited degree, if at all. For example; dusty
or dirty areas, areas with exhaust fumes,
areas with high humidity, freezing fog, or
areas subjected to high vibration. Also, if
there is no access to the detectors after
installation, a maintenance-free sensor
would be desirable.
Motors, Pumps
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
99
HDC System
Analogue Fixed Temperature Linear Heat Detection System
The combination of LDM92198/
F control module and TC9208/
F heat tracer cable can adapt
to a variety of environmental
conditions due to built in “self
adapting
compensation”.
This compensation assures
the integrity of the alarm
temperature
set
points
throughout the entire length
of the cable. This feature
virtually eliminates false
alarms and greatly enhances
reliability of compensation
for external temperature
variation.
• Open and short circuit
monitoring.
• All alarm parameters are
set on site via special
software
• Equivalent temperature
display
• Rugged construction for
use in harsh environments.
• Recoverable, resettable
and testable system
• Pre-alarm and alarm
outputs (programmable)
• Fault relay output
• RS485 or RS232
communication
Other features include:• Early detection of hazards
at temperatures well
below flame point.
MODEL
TC9208/F
TC9208/F/
NC
PART NO
81-010
81-012
81-014
Poly Tetra
Flouro
Ethane
Bronze
Braid for
explosion &
EM proof
CABLE SPECS
High Temp
PVC
MAX. CABLE LENGTH
CABLE IDENTIFICATION
COLOUR
TO FIRE ALARM PANEL
OR ADDRESSABLE INFERFACE
X
JUNCTION BOX
JB92198
Distance - 537 ft
100
200m
RED
PACKAGE SIZE
537
END OF LINE BOX
EOL92198
TC9208/
F/BB
ORANGE
BRONZE
400, 600 OR 800 m
OPERATING TEMP
-20°C to
100°C
-40°C to
160°C
-40°C to
100°C
EXT DIAMETER
3.2 mm
3.2 mm
3.8 mm
MINIMUM TENSILE
STRENGTH
100N
100N
120N
ALARM SETTING
68 TO 158°C (programmable)
ALARM INDICATION
Common Alarm Indication
CONTROLLER MODEL
LDM92198/F
CONTROLLER PART
NUMBER
81-005
CONTROLLER SUPPLY
VOLTAGE
24V DC
CONTROLLER OUTPUTS
Fault relay / Pre-alarm relay / Alarm
Relay
ENCLOSURE SIZE
138 X 200 X 100mm
WEIGHT
2.5 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
LHDC Hot-Spot Locating
Analogue Fixed Temperature Linear Heat Detection System
The combination of LDM92198/F/L control module
and TC9208/F/L heat tracer cable has all the
functions and characteristics of the HDC System,
with the added feature of giving the distance of
the “hot-spot” from the controller.
In the event of a pre-alarm, the control module
will show the distance along the cable of the
heat source from the controller. This will allow
the responsible person to investigate the cause
of the alarm, hopefully before combustion has
started
MODEL
TC9208/F/L
TC9208/F/
L/NC
TC9208/F/
L/BB
PART NO
81-110
81-112
81-114
CABLE SPECS
High Temp
PVC
Poly Tetre
Fluoro Ethane
Bronze braid
for explosion
& EM proof
MAX. CABLE LENGTH
537
TO FIRE ALARM PANEL
OR ADDRESSABLE INFERFACE
X
JUNCTION BOX
JB92198
Distance - 537 ft
END OF LINE BOX
EOL92198
200m
CABLE IDENTIFICATION
COLOUR
Red
Orange
Bronze
PACKAGE SIZE
400, 600 or
800m
400, 600 or
800m
400, 600 or
800m
OPERATING TEMP
-20 °C to
100°C
-40 °C to
160°C
-40 °C to
100°C
EXT DIAMETER
3.2 mm
3.2 mm
3.8 mm
MINIMUM TENSILE
STRENGTH
100N
100N
120N
ALARM SETTING
68 TO 158°C (programmable)
ALARM INDICATION
Distance From Controller
CONTROLLER MODEL
LDM92198/F/L
CONTROLLER PART
NUMBER
81-105
CONTROLLER SUPPLY
VOLTAGE
24V DC
CONTROLLER OUTPUTS
Fault Relay / Pre-Alarm Relay / Alarm Relay
ENCLOSURE SIZE
138 x 200 x 100mm
WEIGHT
2.5 KG
Issue N u m b e r : 2 . L a s t U p d a t e : 2 6 / 0 6 / 2 0 0 7 .
101
Fire Defence Cable
GLT Exports Ltd Fire Defence Cable has been
independently tested and approved by LPCB to meet
with BS5839-1:2002 26.2d, BS8434-1:2003 30 minutes &
BS EN 50200:2000 Class PH30.
Fire Defence Cable is manufactured in the UK using
the latest technology, materials and manufacturing
equipment. Materials and processes are recorded and
tracked throughout manufacture to ensure consistent
reliability and quality, all cables are marked with time
& date of manufacture and each reel with a unique
quality assurance batch & test number.
Probably the fastest fire cable to prepare for termination
with no troublesome multiple sheaths to strip, Fire
Defence Cable has superb working flexibility but stays
where you put it, reduced installation time and costs.
Fire Defence Cable cores are designed to provide the
highest level of data protection, ideal for long cable
runs and analogue addressable fire systems.
Polyester Backed
co polymer Aluminium Foil
Solid Copper
Conductor
Tinned Solid Copper
CPC (Circuit Protection
Conductor)
Aluminium Foil bonded
to the Outer Sheath
Low Smoke Zero Halogen
Fire Resistant Silicone Insulation
102
In addition to conventional fire alarm smoke detection
and sounder circuits, Fire Defence Cable is also suitable
for use with emergency lighting, automatic lift doors,
air conditioning and computer control where low smoke,
fume and zero halogen cable is required.
• Easy to Install and Superb Working Flexibility.
• Red, White & Black Outer Sheaths Available
• 500 Metre and Special Lengths Available
• Aluminium / Co-polymer Foil Screen
• Approved and Certified to meet
• BS5839-1 26.2d:2002 Clause 26.2d
• BS8434-1:2003
• BS EN 50200:2000 PH30
• BS 7629-1:1997
• BS6387:1994 Clause 11 CWZ
• BSEN50267-2-1:1999
• BSEN50268-2:2000
• Also suitable for
• BS5266-1 1999
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
The FireDefenceCable is available in a variety
of multiple core combinations all with CPC
Outer Sheathing
Materials
Working Voltage
Types
(circuit protection conductor).
Core Insulation
Fire Resistant Silicone
Conductors
Plain Annealed Copper
CPC (Earth)
Tinned Annealed Copper
Screening
Polyester Backed
Talc
Prevents Cores Adhering
Together
Core to Core
500V
Core to CPC
300V
Outer Sheath
Colours
Red, White or Black
Number of Cores
2, 3 & 4 Core
Inner Cores CSA
Supplied On Robust Plastic Reels
Installer safe and easy handling
Better reeling and damage resistant
Weather and moisture resistant
1.0, 1.5, 2.5 mm CSA
1.0mm - 8.0 Kg/100m
500m reels and other special lengths are
available.
•
•
•
•
Low Halogen Polymer
2 Core with CPC
1.5mm - 9.5 Kg/100m
2.5mm - 14.1 Kg/100m
Approximate
Weights
1.0mm -9.5 Kg/100m
3 Core with CPC
1.5mm -12.9 Kg/100m
2.5mm -19.1 Kg/100m
1.0mm - 10.9 Kg/100m
4 Core with CPC
FD-210-ERH-100
1.5mm - 14.5 Kg/100m
2.5mm - 22.2 Kg/100m
1.0mm/7.2mm
2 Core
1.5mm/7.9mm
2.5mm/9.5mm
Fire Defence
2 = 2 core
3 = 3 core
4 = 4 core
10 = 1mm2
25 = 2.5mm2
40 = 4.0mm2
100 = 100m reel
500 = 500m reel
Approximate
Overall Diameter
1.0mm/7.4mm
3 Core
1.5mm/8.5mm
2.5mm/10.1mm
Common to
all models
1.0mm/9.0mm
4 Core
1.5mm/10.5mm
2.5mm/13.0mm
Model Number
Resistance
Manufacturers Recommended Installation
Guidelines
• Recommended clip spacing: 300mm Horizontal /
400mm Vertical
• Minimum bend radius = 6 x Cable Diameter
• Minimum recommended installation temp 0°C
• Installation methods for current rating in
accordance with BS7671:2001 IEE Wiring
Regulations
• The tabulated ratings are based upon 30°C
ambient temperature and 70°C operating
temperature.
1.0mm CSA
1.81 W/100m
1.5mm CSA
1.21 W/100m
2.5mm CSA
0.74 W/100m
Min. Bending
Radius
Radius = 6 x Diameter
Installation Temp.
Min 0°C
Quiescent
Operating Temp.
-20° to +70°C
Voltage Drop
(DC or single phase
AC)
1.0mm CSA
44 mV / A / m
1.5mm CSA
29 mV / A / m
2.5mm CSA
18 mV / A / m
1.5mm – 19.5A
Enclosed
(DC or Single Phase
AC)
1.5mm – 16.5A
Period Identification
10 years from Date of
Manufacture (Marked on
Cable)
Current Rating
Warranty
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
1.0mm – 15A
Cable Clipped
(DC or Single Phase
AC)
2.5mm – 27A
1.0mm – 13A
2.5mm – 23A
103
ZT-DU2
Zeta Duct Unit
The Zeta Duct unit allows air in a ventilation
duct to be monitored for smoke via a smoke
detector mounted outside the duct - in a
sealed chamber.
The unit comes supplied with 2 sampling
probes, one in, one out, which are mounted
through the duct, in the center of the air flow.
For a reliable smoke detection the air speed in
the duct must be at least 2.5 m/s.
The unit can be powered from either 230V AC
or a separate 24V power supply. The unit has
form C relay outputs for Alarm and for fault.
TEST POINT
DUCT WALL
DIRECTION OF AIRFLOW
104
MODEL
ZT-DU2
PART NO
48-010
SUPPLY VOLTAGE
230V AC OR 24V DC
INDICATIONS
POWER
FAULT
ALARM
OUTPUTS
1 X FAULT RELAY
1 X ALARM RELAY
ENCLOSURE SIZE
230 X 195 X 76
WEIGHT
750G
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
ZTS-BZ4
4 Way Bell Splitter
The ZT-BZ4 is a four way expansion unit designed
to be used with any fire alarm control unit with
reversal type bell monitoring.
The unit monitors both open and circuit faults,
as well as transmitting fault signal to the main
fire control panel.
• Compact design
• Can be used with any control panel
• All sounders/bells must be polarised
• Remotely triggered
MODEL
ZT-BZ4
ZT-BZ4/c-1.5
amp
ZT-BZ4/d-5
amp
PART NO
41-002
41-010
41-010A
RATED INPUT
24-30 VDC
ALARM OUTPUT
1.0 amp fused
BOARD DIMENSIONS
60 x 135mm
Issue N u m b e r : 2 . L a s t U p d a t e : 1 8 / 0 6 / 2 0 0 7 .
105
SSG Power Supply
The SSG is the latest 24 volt power supply
from GLT Exports Ltd. It utilises switch mode
technology and is designed to the following
standards:• EN54 PART 4
• UL1950
• TUV EN 60950
• EMG EN55022
• IEC100-4-2,3,4,5
• IEG 1000-3-2
It is housed in an attractive steel enclosure
with space for up to 2 x 17AH SLA batteries.
It has top & rear cable entries.
It is available in 3 sizes, 1.5 Amp, 2.5 Amp &
5.0 Amp, and has front panel indications for
Power, Mains Fault, Low Battery Fault, and
General Fault. Other indications are shown
internally.
FAULT RELAY
PS01 PS02
MAINS IN
SERVICE
BATTERY FAULT
GENERAL FAULT
SYSTYEM FAULT
106
SSG15
SSG25
SSG50
PART NO
46-200
46-205
46-210
INPUT VOLTAGE
90-264V AC @ 47-440Hz
OUTPUT VOLTAGE
27V DC PROTECTED
POWER RATING
EARTH FAULT
CHARGER FAULT
MODEL
PS01 PS02
FUSE FUSE
BATTERY FUSE
BATTERY
MAINS
LED &
FUSE
45W
65W
EFFICENCY
80%
POWER SUPPLY
OUTPUT
2
MAX CURRENT PER
OUTPUT
630mA
130W
1.0A
2.0A
BATTERY CHARGING
CURRENT
300mA (7Ah) / 600mA(17Ah)
FAULT RELAY RATING
1 AMP @ 24V DC
IP RATING
IP 23
ENCLOSURE SIZE
300W x 410H x 97D (mm)
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Zeta Sealed Lead Acid Batteries
Because fire alarm systems are life safety systems,
they must have a battery backup in order that
they will operate in the event of a mains failure.
All parts of the system, including auxiliary power
supplies must have a battery backup.
All the batteries stocked are 12 Volt batteries,
meaning that 2 batteries are required for a 24
volt system. The standard capacities stocked are
2.2Ah, 7Ah, 12Ah and 17Ah
It is important to choose the correct battery size
for the system load to give the required standby
time (usually 24 or 48 hours).
Battery Size
Conventional System
Addressable System
2.2Ah
Small System
Not suitable
7.0Ah
Medium System
Small system
– extended standby
Small System
12Ah
Large System
Medium system
– extended standby
Medium System
Small system
– extended standby
17Ah
Large system
– extended standby
Large System
Medium system
– extended standby
MODEL
Z20201
Z20651
Z21251
Z21751
PART NO
46-002
46-003
46-105
46-004
TYPE
SEALED LEAD ACID
VOLTAGE
12V DC
CAPACITY
2.2 Ah
7.2 Ah
12 Ah
17 Ah
SIZE
(WxDxH
mm)
178x34x65
151x65x98
150x98x103
178x75x168
WEIGHT
1.0 kg
2.5 kg
3.5 kg
5.8 kg
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
107
SD 630A
Autodialler
The SD-630A autodialler is a 24V powered
PCB suitable for mounting in many fire alarm
panels.
In the event of an alarm it can dial up to 6
different telephone numbers, and report with
a 16 second message.
The unit requires use of a telephone handset
to configure the phone numbers and record
the message. It can be configured for tone or
pulse dialling.
The dialler has a volt free relay that can be
activated via the phone line after the unit has
dialled a number and played it’s message.
A 12V version in a small enclosure is available
for use on security systems.
ALARM
NO
LINE
NC
TEL
COM
MODEL
+
24V
-
FOR PROGRAMMING

NOT ALL PANELS HAVE 24V
AUXILIARY OUTPUT
TO FIRE RELAY
FIRE
DET: 021
RECEPTION
FIRE ALARM CONTROL PANEL
TELEPHONE LINE
108
RELAY OUTPUT CAN BE ACTIVATED
BY THE USER AFTER THE DIALLER HAS
CALLED THEIR NUMBER.
SD-630A
PART NO
47-002
SUPPLY VOLTAGE
24V DC
STANDBY CURRENT
50mA
ACTIVE CURRENT
100mA
MESSAGE TIME
16s
DIALLING TIME
70s
TELEPHONE Nos
6
ACTIVATION TRIGGER
Relay Input
OPERATING TEMPERATURE
-0°C to 50°C
PCB SIZE
90 X 80 X 25mm
WEIGHT
2.5 KG
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Test Accessories
The secret to having a trouble free fire alarm
system is to have the system checked, maintained
and serviced regularly.
GLT Exports supply a range of test equipment
suitable for most requirements, including smoke
detector testing, heat detector testing, and
detector removal tools.
Solo smoke test spray is a high quality detector
test spray that does not leave any residue in
the detectors when they are tested. This means
that the detectors do not re-alarm, when the
test alarm is reset.
Solo carbon monoxide spray is designed for
testing CO detectors. It can be used with the
same test equipment as the solo smoke spray
The Zeta BX168 is a hand-held CO gas detector
ideally suited for investigating causes of CO.
It gives the ppm reading on it’s LCD screen, and
has a built in alarm buzzer that sounds at the
alarm level.
It has built in rechargeable Ni-MH batteries.
The Zeta JL268 is a portable gas leak detector
suitable for industrial uses.
Its flexible “goose-neck” allows the sensor
head to be positioned into difficult to access
locations to investigate for gas leaks.
It detects Natural gas & LPG, but is available
on request for a range of other gasses.
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
109
Battery Calculation
Guide
Standby batteries are used to maintain system
operation in the event of a mains failure. The
size of batteries required will depend on several
factors:• How much current the system takes in the
normal condition
• How much current the system takes in the
alarm condition
• How long the system is required to run in the
event of a mains failure.
The general requirement for battery backup
is that the system is to be able to run for 24
hours, then run in alarm for 30 minutes with
an 80% charge in the batteries. (This is to allow
for batteries not being fully charged, battery
degradation etc.)
If the building is likely to be unmanned for
extended periods, one of the following should
be considered:• Fit standby batteries that will allow the
system to run for 48 or 72 hours instead of
the usual 24 hours
• Transmit the fault to an alarm receiving
centre (via a Redcare box, or similar
autodialler)
In general terms, addressable systems tend
to have a higher quiescent current than
conventional systems, and will usually require
a larger standby battery capacity.
x [(TALM x IALM) + (TSBY x (IQP + IQD))]
Where:
• TALM= Maximum time in hours required
for the alarm [½ hour is most common
time]
• IALM = Total Alarm Current in amps for
all alarm devices connected to the alarm
circuits
• TSBY= Standby time in hours for the
system after mains failure [normally 24,
48 or 72 hr]
• IQP = Quiescent current in amps of
control panel in fault condition [because
of mains failure]
• IQD = Quiescent current in amps of
all devices on the system [detectors,
sounders etc].
Ty p i c a l B a t t e r y U s a g e
Conventional
System
Addressable System
2.2Ah
Small System
Not suitable
7.0Ah
Medium System
Small system
– extended standby
Small System
12Ah
Large System
Medium system
– extended standby
Medium System
Small system
– extended standby
17Ah
Large system
– extended standby
Large System
Medium system
– extended standby
Battery Size
The batteries should be replaced as part of the
maintenance routine approximately every 5
years.
In order to calculate the standby battery size
required, the following formula can be used:Battery Size (Standby time in Amp Hours) = 1.25
110
Issue N u m b e r : 1 . L a s t U p d a t e : 1 7 / 0 5 / 2 0 0 7 .
Product Compatibilty
Chart
REPEATER PANELS
P
R
E
R
E
P
PREMIER ELITE 1-2
X
notes:
PREMIER SX
notes:
PREMIER M+
notes:
PREMIER M48
notes:
PREMIER MX 16
notes:
PREMIER MX 32
notes:
PREMIER EX 8
notes:
SIMPLICITY 64
notes:
SIMPLICITY 126
notes:
PREMIER AD
notes:
PREMIER AL 1-4
notes:
PREMIER AL 5-8
notes:
AIRCON 8
√
notes:
P
M
P
4
8
R
E
P
X
X
X
X
R
E
P
M
X
1
6
R
E
P
M
X
3
2
R
E
P
E
X
8
R
E
P
A
D
R
E
P
A
L
R
E
P
A
L
/
G
X
X
X
X
X
X
M
A
N
A
G
E
R
F
E
O
2
0
0
0
X
√
X
X
X
√
X
X
X
X
X
X
X
X
X
X
X
√
√
√
X
X
X
X
X
X
X
X
X
√
X
X
√
X
X
X
X
X
X
X
X
√
X
X
X
√
X
X
X
X
X
X
X
√
X
X
X
X
√
X
X
X
X
X
X
√
X
X
X
X
X
√
X
X
X
X
X
√
X
X
X
X
X
X
√
X
X
X
X
√
X
X
X
X
X
X
X
√
X
X
X
i
X
X
X
X
X
X
X
√
X
X
X
i
X
X
X
X
X
X
X
√
X
X
X
i
X
X
X
X
X
X
X
X
√
√
√
i
X
X
X
X
X
X
X
X
X
√
√
i
X
X
X
no repeater
available
√
√
√
√
√
V
S
2
0
0
P
V
S
2
0
0
E
X
F
E
A
O
2
0
0
0
F
E
A
H
R
2
0
0
0
F
E
A
F
H
2
0
0
0
F
E
A
O
E
2
0
0
0
√
X
X
√
√
√
√
X
X
X
X
X
X
√
ext. psu
needed
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
1 per
zone
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
X
X
√
√
i
√
X
√
√
√
X
√
√
√
√
√
√
√
√
X
√
√
√
X
√
√
√
√
√
√
√
√
√
√
√
√
√
X
ext.psu
needed
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
i
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
X
X
√
√
√
√
√
i
i
i
X
X
X
X
X
X
X
X
X
X
not
compatible
F
E
A
H
E
2
0
0
0
F
E
A
H
H
E
2
0
0
0
F
E
A
O
H
2
0
0
0
X
X
X
Z
T
C
P
2
/
A
D
Z
T
A
B
G
U
/
W
P
Z
T
5
0
R
A
Z
T
1
0
0
R
A
X
X
X
X
ADDR.
SOUNDERS
CONVENTIONAL SOUNDERS
C
O
8
0
0
F
E
C
G
2
0
0
0
N
F
E
C
G
2
0
0
0
L
T
C
1
0
0
N
X
X
X
X
T
C
1
0
0
L
Z
M
D
D
/
8
R
Z
M
D
F
/
8
R
Z
M
X
/
X
L
Z
S
T
/
8
R
Z
S
L
6
1
2
2
4
A
X
√
√
√
√
√
Z
M
T
/
8
R
Z
I
D
C
/
1
0
R
Z
T
B
6
B
√
√
√
X
X
X
X
X
X
X
X
X
X
√
√
X
X
X
Z
T
B
8
B
Z
T
S
T
/
E
X
D
Z
A
M
D
D
/
R
Z
A
M
D
F
/
R
Z
A
S
T
/
R
Z
A
M
T
/
R
Z
I
U
Z
I
O
U
√
√
√
X
X
X
X
X
X
√
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
i
i
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
i
i
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
i
i
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
i
i
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
X
X
X
X
X
X
X
X
X
X
X
F
E
A
S
F
B
Z
T
L
E
8
Z
T
A
L
E
2
Z
T
A
L
E
3
√
√
√
X
X
X
X
√
X
X
√
√
√
√
X
X
X
X
√
X
X
√
√
√
√
√
X
X
X
X
√
X
X
X
√
√
√
√
√
X
X
X
X
√
X
X
X
X
√
√
√
√
√
X
X
X
X
√
X
X
X
X
X
√
√
√
√
√
X
X
X
X
√
X
X
X
X
X
X
√
√
√
√
√
X
X
X
X
√
X
X
Z
S
C
C
Z
T
Z
M
F
E
C
B
F
E
D
B
F
E
R
B
X
X
X
X
X
√
X
X
X
X
X
X
X
X
X
X
√
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
not
compatible
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
X
X
X
X
X
X
X
X
X
X
√
√
√
√
√
X
X
X
X
√
X
X
√
√
√
√
√
√
√
√
√
X
X
X
X
i
i
i
i
i
i
i
i
i
i
i
√
√
√
√
√
√
√
√
√
√
√
X
X
i
i
√
√
√
√
X
√
P
√
√
√
√
√
√
√
√
X
X
i
i
√
√
√
√
X
√
P
√
√
√
√
√
√
√
√
X
X
√
√
√
√
√
√
X
√
P
√
√
√
√
√
√
√
√
X
X
√
√
√
√
√
√
X
√
√
√
√
√
√
√
√
√
√
X
X
√
√
√
√
√
√
X
√
√
√
X
√
√
√
X
X
X
X
X
X
X
X
X
X
X
X
√
X
X
X
X
X
X
X
X
√
X
X
X
X
X
X
X
X
X
X
X
not
compatible
i
i
√
√
√
i
i
√
√
√
√
√
√
√
√
√
32 max.
/loop
√
√
√
X
X
X
X
i
i
i
i
i
i
i
i
i
i
i
i
i
√
√
√
√
√
√
√
√
√
i
i
√
√
√
√
√
√
√
√
√
i
i
√
√
√
√
√
√
√
√
√
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
√
√
√
32 max.
/loop
√
√
√
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
√
√
√
32 max.
/loop
√
√
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
√
√
√
32 max.
/loop
√
√
X
X
X
X
X
√
√
√
√
√
√
√
√
√
√
√
√
√
√
32 max.
/loop
X
X
√
X
X
X
X
i
i
i
i
i
i
i
i
i
i
i
√
√
√
32 max.
/loop
not compatible
X
F
E
A
S
B
not
compatible
total 126 per loop
(including sounders & interfaces)
X
F
E
A
R
B
not
compatible
total 126 per loop
(including sounders & interfaces)
i
F
E
A
I
B
Z
T
Z
M
/
4
not
compatible
total 126 per loop
(including sounders & interfaces)
i
F
E
S
B
F
E
S
F
B
Z
S
C
C
/
4
not
compatible
total 126 per loop
(including sounders & interfaces)
i
REMOTE
LED
DETECTOR BASES
not
compatible
total 126 per loop
(including sounders & interfaces)
i
If you have any questions
or doubts, contact your
local representitive, or
contact
our
technical
support team via email on :technical@gltexports.com
not
compatible
not
compatible
√
ADDR.
INTERFACE
Z
T
B
8
B
/
E
X
D
not
compatible
not
compatible
X
Compatible but requires some extra
setup.
not
compatible
ext.psu
needed
i
P
not
compatible
ext.psu
needed
√
i
not
compatible
ext.psu
needed
√
Not compatible with this panel
These items can be used indirectly, via an
interface module. Contact your supplier
for further information
not
compatible
ext.psu
needed
1 per
zone
√
√
ext.psu
needed
1 per
zone
√
√
ext.psu
needed
1 per
zone
√
X
not
compatible
conventional detectors can be connected via
a zone monitor unit
no repeater
available
X
√
Z
T
1
0
0
R
V
conventional detectors can be connected via
a zone monitor unit
serial repeater 4 cores
X
√
Z
T
5
0
R
V
conventional detectors can be connected via
a zone monitor unit
serial repeater 4 cores
X
√
Z
T
1
0
0
R
Z
conventional detectors can be connected via
a zone monitor unit
serial repeater 4 cores
X
√
Z
T
5
0
R
Z
conventional detectors can be connected via
a zone monitor unit
serial repeater 4 cores
X
Z
T
C
P
2
Z
T
B
G
U
/
W
P
20 per
zone
serial repeater 4 cores
X
F
E
U
V
2
0
0
0
20 per
zone
serial repeater 4 cores
X
F
E
O
H
2
0
0
0
20 per
zone
serial repeater 4 cores
X
F
E
H
H
E
2
0
0
0
32 per zone
(max.)
serial repeater 4 cores
X
F
E
H
E
2
0
0
0
32 per zone
(max.)
serial repeater 4 cores
X
F
E
O
E
2
0
0
0
32 per zone
(max.)
serial repeater 4 cores
X
F
E
F
H
2
0
0
0
32 per zone
(max.)
hardwired repeater - cables: -5 +1
per zone
X
F
E
H
R
2
0
0
0
Z
T
B
G
U
/
E
X
D
These addressable detectors dividing the circuit rating
have been designed to work by the sounder’s operating
only with the Zeta Alarm current.
Panels in this table.
This chart is meant to assist
The maximum number identification of which
of sounders that can be devices or repeaters will
fitted to a sounder circuit work with each control
can be calculated by panel.
Compatible, and can be connected
directly to the panel
ADDRESSABLE DETECTORS
20 per
zone
hardwired repeater - cables: -5 +1
per zone
notes:
GASGUARD 2000
P
M
P
R
E
P
/
M
A
L
A
R
M
Information
√
CONVENTIONAL DETECTORS
no repeater
available
notes:
PREMIER ELITE 4-8
P
M
P
R
E
P
P
M
P
4
8
R
E
P
/
M
Ke y
X
X
X
X
X
X
X
X
not compatible
Issue Number:1. Last Update: 17/05/2007.
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
X
X
X
not
compatible
Distributor
GLT Exports Ltd
72/78 Morfa Road
Hafod
Swansea
SA1 2EN
United Kingdom
Telephone
Tel: +44 (0) 1792 455175
Fax: +44 (0) 1792 455176
E-Mail
sales@gltexports.com
technical@gltexports.com
Web
www.gltexports.com
www.zeta-alarms.co.uk
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF