CAL EDT1423 TEMPERATURE CONTROLLER

CAL EDT1423 TEMPERATURE CONTROLLER
Technical Specifications
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. Cal Controls shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
ENVIRONMENTAL CONDITIONS
Ambient/storage
temperature
Max. relative humidity
Rated pollution degree
CAL EDT1423 TEMPERATURE CONTROLLER
0 ... +50°C/-25 ... 70°C (with no icing)
80%, up to 31°C decreasing linearly 50% at 40°C
According to EN 60529
Front panel : IP60
Rear panel : IP20
Max. 2000m
Height
Thank you for choosing CAL EDT1423 temperature controller.
Do not use the device in locations subject to corrosive and flammable gasses.
* 34 x 77mm sized.
R HS
* On-Off control.
Compliant
* 3 contact outputs for cooling, defrost and fan controls.
* 2 NTC probe inputs for cooling and defrost control.
* Offset value can be entered for NTC probe.
°F
* Compressor protection parameters can be entered.
* In the case of probe failure, output state can be
selected on, off or periodical running.
SET
* Upper and lower limits of the setpoint can be adjusted.
* Defrosting duration and interval can be adjusted.
* Time and evaporator temperature dependent or manual
CAL
EDT1423
defrosting is possible.
* Fan may be operated depending on defrost and compressor.
* Temperature unit can be selected °C or °F.
* Upper and lower limits of the alarm value can be adjusted depending on the setpoint value.
* CE marked according to European Norms.
ELECTRICAL CHARACTERISTICS
Pb
Supply voltage
Power consumption
Wiring
Scale
Sensitivity/Accuracy
Time Accuracy
Indicator
EMC
°C
230V AC +10% -20%, 50/60Hz or 24V AC/DC ±10%, 50/60Hz or 12V AC/DC ±10%, 50/60Hz
Max. 4.5VA
2.5mm² screw-terminal connections.
-50.0 ... +110.0°C (-58.0 ... +230.0°F)
0.1°C / ±1°C
(±1%-15sec) for hour unit, (±1%-1sec) for minute unit
4 digits, 12.5mm, 7 segment yellow LED
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
Safety requirements
OUTPUTS
Relay: 250VAC, 8A (for resistive load),NO+NC; 1/2 HP 240VAC CosF
= 0.4 (for inductive load)
Relay: 250VAC, 8A (for resistive load),NO; 1/2 HP 240VAC CosF
= 0.4 (for inductive load)
Relay: 250VAC, 8A (for resistive load),NO; 1/2 HP 240VAC CosF
= 0.4 (for inductive load)
Mechanical 30.000.000; Electrical 100.000 operation.
Compressor
Defrost
Fan
Life expectancy for relay
Order Code : EDT2423-NTC-     
1
Supply Voltage
230VAC...230V AC
24............24V AC/DC
12............12V AC/DC
CONTROL
Single-setpoint, alarm and fan control
On-Off control
Adjustable between 0.1 ... 20.0°C.
Control type
Control algorithm
Hysteresis
HOUSING
Connection Diagram
Suitable for flush-panel mounting.
W77xH34xD70mm
Approx. 223g (after packing)
Self extinguishing plastics
Housing type
Dimensions
Weight
Enclosure material
ENDA EDT2423 is intended for installation in control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation
temperature is not exceeded. The cables should not be close to the power cables or components.
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
Dimensions
Depth
85mm
Line
8
Neutral
1
2
4
5
6
7
8
34mm
THERMOSTAT (NTC)
DEFROST (NTC)
24V AC/DC ±10%
50/60Hz 4.5VA
DEFROST
250V AC 8A
RESISTIVE LOAD
3
FAN
250V AC 8A
RESISTIVE LOAD
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
THERMOSTAT (NTC)
9 10 11 12
9 10 11 12
Note:
Switch
230V AC
Supply
Fuse should
be connected Cable size: 1,5mm²
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
1/3
Panel cut-out
71mm
29mm
8
DEFROST (NTC)
12V AC/DC ±10%
50/60Hz 4.5VA
FAN
250V AC 8A
RESISTIVE LOAD
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
THERMOSTAT (NTC)
DEFROST (NTC)
230V AC +10% -20%
50/60Hz 4.5VA
DEFROST
250V AC 8A
RESISTIVE LOAD
FAN
250V AC 8A
RESISTIVE LOAD
7
7
www.cal-controls.com
184-253V AC
50/60Hz 4.5VA
Fuse
F 100 mA
250V AC
6
SN: XXXXXXXXX
NOTE:
5
Equipment is protected throughout
by DOUBLE INSULATION
Holding screw
0.4-0.5Nm.
SUPPLY:
4
EDT1423-NTC-230VAC
DIGITAL DEFROST THERMOSTAT
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
DEFROST
250V AC 8A
RESISTIVE LOAD
3
9 10 11 12
2
8
1
7
9 10 11 12
6
8
DEFROST
250V AC 8A
RESISTIVE LOAD
7
Panel Rubber
gasket
1
COMPRESSOR
250V AC 8A
RESISTIVE LOAD
6
FAN
250V AC 8A
RESISTIVE LOAD
5
230V AC +10% -20%
50/60Hz 4.5VA
4
2
Mounting
clamp
Mounting
clamp
THERMOSTAT (NTC)
3
EDT1423
DEFROST (NTC)
2
CAL
5
SN: XXXXXXXXX
4
SN: XXXXXXXXX
SET
3
SN: XXXXXXXXX
8mm
Push out the mounting clamp
in direction 1 as shown
in the figure below. Then, pull
out the clamp in direction 2.
°C
2
EDT1423-NTC-24
DIGITAL DEFROST THERMOSTAT
1
°F
www.cal-controls.com
EDT1423-NTC-12
DIGITAL DEFROST THERMOSTAT
1
www.cal-controls.com
www.cal-controls.com
EDT1423-NTC-230
DIGITAL DEFROST THERMOSTAT
70mm
For removing mounting clamps:
CAL CONTROLS LTD
Bury Mead Road, Hitchin, Herts, SG5 1RT, UK.
Tel : +44 (0) 1462 436161 Fax : +44 (0) 1462 451801
e-mail: [email protected] Web : www.cal-controls.com
Note :1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
panel
EDT1423-E-04
FAN
LED
FAHRENHEIT
LED
DEFROST COMPRESSOR
LED
LED
°F
Displayed process value in the run mode, parameter name or value in programming mode.
When held down for 3 second in the run mode, manual defrost starts. After the specified time with D.dur parameter manual defrost finishes. When held down for 3 second manual defrost finishes before the
specified time ends. Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a few
seconds, the change rate accelerates.
°C
SET
Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few seconds, the change rate
accelerates.
CAL
EDT1423
SET
Used for adjusting the value of the setpoint and displaying the value measured by defrost probe in the run mode and for adjusting the selected parameter in the programming mode. While holding
setpoint value of the selected parameter appears and by using
and
keys the value can be adjusted.
Error Messages
Run Mode
-22.0
1000
Process
Value
SET
SET
-29.9
-30.0
-30.0
SET
While holding
key COMPRESSOR setpoint value appears and by using
the value can be adjusted.
If both
key,
keys are pressed and held for 3 seconds,
programming mode is entered.
If both
and
P1.sc
P1.sC
Means, thermostat probe is short circuit.
P2.sC
Means, defrost probe is short circuit.
P1.fa
Means, thermostat probe is broken.
P2.fa
Means, defrost probe is broken.
keys
Temperature value is higher than the scale.
keys are pressed,
run mode is entered.
23.5
Temperature value is lower than the scale.
If process value flashes and warning tone sounds, means,
measured value exceeds the adjusted alarm limit.
Programming Mode
RE
R.LoL
R.uPL
CP
The lower limit
of the setpoint.
The upper limit
of the setpoint.
Delay time for
the compressor
after power is on.
D.typ
C.ssC
Delay time required
between successive
restarts of the compressor.
D.dur
Off time for the compressor
output in the case of
probe failure.
D.tbs
C.PPF
AL
Defrosting type.
C.Pon
Decimal place
drES
DE
A.lol
Defrosting duration
A.upl
Defrosting time unit.
A.dpo
Fn
Limit for
lower alarm level.
Limit for
upper alarm level.
Delay time to display
alarm message after
power is on.
F.Con
F.stp
F.Ctr
SE
Fan is controlled
depending on temperature.
S.Cod
Fan stoping temperature.
A.-re
Fan is controlled
depending on cold room
temperature.
A.res
Access code for security menu.
This parameter should be 321 .
Security parameter
for refrigeration menu
Security parameter
for refrigeration setpoint value
NOTE:
-30.0
9.9
If
key is pressed in the run mode, the measurement value of defrost probe appears.
2/3
EDT1423-E-04
EDT1423 PARAMETER TABLE
RE
R.LoL
R.uPL
R.oFF
R.HYS
Unit
DrES
CP
C.pon
C.SSC
C.FoS
C.dly
C.PPn
C.PPF
DE
D.tYP
D.dur
D.int
D.Stp
D.dSP
Menu of Refrigeration control parameters
MIN
Al
UNIT DEF.SET
-50.0 R.uPL
°C
-50
The upper limit of the setpoint.
R.LoL 110.0
°C
110
The offset value for the refrigeration.
0
-20.0
20.0
°C
Switch hysteresis for compressor.
0.1
20.0
°C
Temperature unit
°C
No
°F
Yes
Delay time for the compressor after power is on.
0
255
min.
1
Delay time required between successive restarts of the compressor.
0
255
min.
1
Delay time required for the compressor to restart following a stop.
0
255
min.
No
Yes
On time for the compressor output in the case of probe failure.
0
255
min.
0
Off time for the compressor output in the case of probe failure.
0
255
min.
1
ElC
Gas
Decimal place (no= no decimal point 22°C, yes= with decimal point 22.3°C .)
2
°C
No
Menu of Compressor protection parameters
Compressor protection delay (no= no delay, yes= 3sec. delay)
0
No
Menu of Defrost protection parameters
Defrosting type (ElC= Electrical defrost, GAS= hot gas defrost )
Defrosting duration.(If d.dur=0, then defrost is disable.)
0
Interval between defrost cycles.
1
Defrosting temperature. If evaporator temperature is higher than this value, defrosting is disabled.
-50.0
ElC
min.
sec.
120 h.min.
110.0 °C
255
1
1
2
Display configuration during defrost
REal
LoC
0
255
No
Yes
Delay time for defrosting after power is on.
0
30
Drop (Drainage) time
0
15
Time interval required for alarm activation after completing defrosting
0
15
No
Yes
(rEAL= Real temperature is displayed during defrost.
LoC= The temperature which is measured before defrost is displayed during defrost.)
D.drE
D.Pon
D.dPo
D.drt
D.AAc
D.dCP
D.tbs
MAX
The lower limit of the setpoint.
Delay time for display real temperature after defrost is over.
Defrosting after power is on.(yes=Defrosting begins when power is on, no=Defrosting doesn’t begin when power is on.)
Delay time for the compressor at hot gas defrosting ( Delay time is adjusted by using Cpon ,CssC and Cfos)
Defrosting time unit (Hour= Hour, minute SEC=Minute,second)
LoC
min.
sec.
1
No
min.
min.
sec.
h.
min.
1
2
2
No
Hour
Hour SeC
Menu of Alarm control parameters
A.LoL
A.uPL
A.dFL
A.HYS
Limit for lower alarm level. When A.typ is changed, A.Lol should be readjusted.
-50.0 a.uPL
°C
-50
Limit for upper alarm level. When A.typ is changed, A.upl should be readjusted.
a.LoL 110.0
°C
110
A.typ
Alarm configuration (A.Abs = Absolute alarm. Alarm values are A.LoL and A.uPL.
A.rEF = Relative alarm. Alarm values are SET-A.LoL and SET+A.uPL.)
A.dpo
Time delay to display alarm message after power is on.
Fn
F.Con
F.stp
F.Hys
F.Cst
F.dst
F.Pon
F.Std
F.Ctr
SE
A.-rE
A.-CP
A.-DE
A.-AL
A.-Fn
A.rE.S.
Time delay to display alarm message after alarm is on.
0
255
min.
0
Switch hysteresis for alarm.
0
15.0
°C
2
A.abs a.ref
a.abs
0
24.0
h.
0.1
No
-50.0
Yes
110.0
°C
yes
1
°C
Menu of Fan control parameters
Fan is controlled depending on temperature (no= independent on temperature, yes= dependent on temperature.)
Fan stopping temperature. If evaporator temperature is above this parameter, fan stops
0
15.0
Does fan stop when compressor stops? (No=Fan status doesn’t change, YEs= Fan stops with compressor.)
No
Yes
Does fan stop during defrosting? (No=Fan status doesn’t change, Yes= Fan stops during the defrosting.)
Switch hysteresis for fan
No
Yes
Delay time for the fan after power is on.
0
255
Delay time for the fan after defrosting is over.
0
255
Does the fan control depend on the temperature of cold room?
If (no) is selected, fan stops while evaporator temperature is above the value of F.STp parameter, If (YES) is selected,
fan stops while the difference between cold room and the evaporator temperature is lower than the value of
the F.STP parameter. Fan restarts again, if the difference between cold room and the evaporator temperature becomes
higher than the total of the values of F.STP and F.HYS parameters.
No
Yes
2
yes
yes
min.
min.
sec.
1
2
no
Menu of Parameter security
Security parameter for refrigeration menu.
Security parameter for menu of compressor control.
Security parameter for menu of defrost control.
Security parameter for menu of alarm control.
NonE
= Menu is invisible
P.yes
= Parameters of menu are changeable
P.no
= Parameters of menu are only visible.
Security parameter for menu of fan control.
Security parameter for refrigeration setpoint value ( P.yes= Setpoint value is changeable.,P.no= Setpoint value is only visible.)
3/3
EDT1423-E-04