Please read this document carefully before using this product. The guarantee will be invalidated if the device is damaged by not following instructions detailed in the manual. Cal Controls shall not be responsible for any damage or losses however caused, which may be experienced as a result of the installation or use of this product.
CAL EDT1423 TEMPERATURE CONTROLLER
Thank you for choosing CAL EDT1423 temperature controller.
* 34 x 77mm sized.
* On-Off control.
* 3 contact outputs for cooling, defrost and fan controls.
* 2 NTC probe inputs for cooling and defrost control.
* Offset value can be entered for NTC probe.
* Compressor protection parameters can be entered.
* In the case of probe failure, output state can be
selected on, off or periodical running.
* Upper and lower limits of the setpoint can be adjusted.
°F
R
Pb
HS
Compliant
°C
SET
* Defrosting duration and interval can be adjusted.
* Time and evaporator temperature dependent or manual
defrosting is possible.
* Fan may be operated depending on defrost and compressor.
CAL EDT1423
* Temperature unit can be selected °C or °F.
* Upper and lower limits of the alarm value can be adjusted depending on the setpoint value.
* CE marked according to European Norms.
Order Code : EDT2423-NTC-
1
Supply Voltage
230VAC...230V AC
24............24V AC/DC
12............12V AC/DC
Connection Diagram
ENDA EDT2423 is intended for installation in control panels. Make sure that the device is used only for intended purpose. The electrical connections must be carried out by a qualified staff and must be according to the relevant locally applicable regulations. During an installation, all of the cables that are connected to the device must be free of electrical power. The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not exceeded. The cables should not be close to the power cables or components. www.cal-controls.com
EDT1423-NTC-230
DIGITAL DEFROST THERMOSTAT
SN: XXXXXXXXX www.cal-controls.com
EDT1423-NTC-12
DIGITAL DEFROST THERMOSTAT
SN: XXXXXXXXX www.cal-controls.com
EDT1423-NTC-24
DIGITAL DEFROST THERMOSTAT
SN: XXXXXXXXX
1 2 3 4 5 6 7 8 9 10 11 12
NOTE:
SUPPLY:
184-253V AC
50/60Hz 4.5VA
7
8
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
Line
Neutral
Holding screw
0.4-0.5Nm.
Equipment is protected throughout by DOUBLE INSULATION
Fuse
F 100 mA
250V AC
Switch
230V AC
Supply
Fuse should be connected
Cable size: 1,5mm²
Note:
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
1/3
Technical Specifications
ENVIRONMENTAL CONDITIONS
Ambient/storage
temperature
0 ... +50°C/-25 ... 70°C (with no icing)
Max. relative humidity
Rated pollution degree
Height
80 , up to 31°C decreasing linearly 50% at 40 °C
According to EN 60529 Front panel : IP60
Rear panel : IP20
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gasses.
ELECTRICAL CHARACTERISTICS
Supply voltage 230V AC +10% -20%, 50/60Hz or 24V AC/DC ±10%, 50/60Hz or 12V AC/DC ±10%, 50/60Hz
Power consumption
Wiring
Scale
Sensitivity/Accuracy
Max. 4.5VA
2.5mm² screw-terminal connections.
-50.0 ... +110.0°C (-58.0 ... +230.0°F)
0.1°C / ±1°C
Time Accuracy
Indicator
EMC
Safety requirements
(±1%-15sec) for hour unit, (±1%-1sec) for minute unit
4 digits, 12.5mm, 7 segment yellow LED
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
OUTPUTS
Compressor
Defrost
Fan
Life expectancy for relay
Relay: 250VAC, 8A ( for resistive load) ,NO+NC; 1/2 HP 240VAC
Relay : 250VAC, 8A ( for resistive load) ,NO; 1/2 HP 240VAC
Relay : 250VAC, 8A ( for resistive load) ,NO; 1/2 HP 240VAC
Mechanical 30.000.000; Electrical 100.000 operation.
CONTROL
Control type
Control algorithm
Hysteresis
Single-setpoint, alarm and fan control
On-Off control
Adjustable between 0.1 ... 20.0°C.
)
)
HOUSING
Housing type
Dimensions
Weight
Enclosure material
Suitable for flush-panel mounting.
W77xH34xD70mm
Approx. 223g ( after packing )
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
)
Dimensions
85mm
°F
°C
SET
CAL EDT1423
12 11 10 9 8 7 6 5 4 3 2 1
T TA om .c
OS ols
RM ntr co
HE
C
T
VA
ST
30 alw.c
RO
-2
EF
TC
XX XX
D
3-N
XX
AL
42
XX
IT
T1
: X ww
DIG
ED
SN
Depth
70mm
8mm
For removing mounting clamps:
Push out the mounting clamp in direction 1 as shown in the figure below. Then, pull out the clamp in direction 2.
Mounting clamp
1
Panel cut-out
71mm
Mounting clamp
2
Panel Rubber gasket
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the
panel
CAL CONTROLS LTD
Bury Mead Road, Hitchin, Herts, SG5 1RT, UK.
Tel : +44 (0) 1462 436161 Fax : +44 (0) 1462 451801 e-mail: [email protected] Web : www.cal-controls.com
EDT1423-E-04
FAHRENHEIT
LED
FAN
LED
DEFROST
LED
COMPRESSOR
LED
°F
°C
SET
CAL EDT1423
Displayed process value in the run mode, parameter name or value in programming mode.
When held down for 3 second in the run mode, manual defrost starts. After the specified time with D.dur parameter manual defrost finishes. When held down for 3 second manual defrost finishes before the specified time ends. Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few seconds, the change rate accelerates.
SET
Used for adjusting the value of the setpoint and displaying the value measured by defrost probe in the run mode and for adjusting the selected parameter in the programming mode. While holding key, setpoint value of the selected parameter appears and by using and keys the value can be adjusted.
Run Mode
SET SET
Process
Value
-30.0
-29.9
-30.0
SET
While holding key COMPRESSOR setpoint value appears and by using and keys the value can be adjusted.
Error Messages
Means, thermostat probe is short circuit.
P2.sC
Means, defrost probe is short circuit.
Means, thermostat probe is broken.
Temperature value is higher than the scale.
P2.fa
Means, defrost probe is broken.
Temperature value is lower than the scale.
If both keys are pressed and held for 3 seconds,
programming mode is entered.
RE
If both keys are pressed,
run mode is entered.
Programming Mode
CP DE
R.LoL
The lower limit of the setpoint.
R.uPL
The upper limit of the setpoint.
C.Pon
Delay time for the compressor after power is on.
C.ssC
Delay time required between successive restarts of the compressor.
D.typ
Defrosting type.
D.dur
Defrosting duration
23.5
If process value flashes and warning tone sounds, means, measured value exceeds the adjusted alarm limit.
AL
A.lol
Limit for lower alarm level.
A.upl
Limit for upper alarm level.
Fn SE
F.Con
Fan is controlled depending on temperature.
F.stp
Fan stoping temperature.
S.Cod
Access code for security menu.
This parameter should be
321 .
A.-re
Security parameter for refrigeration menu
drES
Decimal place
C.PPF
Off time for the compressor output in the case of probe failure.
D.tbs
Defrosting time unit.
NOTE:
-30.0
9.9
If key is pressed in the run mode, the measurement value of defrost probe appears.
A.dpo
Delay time to display alarm message after power is on.
F.Ctr
Fan is controlled depending on cold room temperature.
A.res
Security parameter for refrigeration setpoint value
2/3
EDT1423-E-04
D.dCP
EDT1423 PARAMETER TABLE
A.dpo
Fn
F.Con
F.stp
F.Hys
F.Cst
F.dst
F.Pon
F.Std
RE
R.LoL
R.uPL
R.oFF
R.HYS
Unit
DrES
CP
C.pon
C.SSC
C.FoS
C.dly
C.PPn
C.PPF
DE
D.tYP
D.dur
D.int
D.Stp
D.dSP
Menu of Refrigeration control parameters
The lower limit of the setpoint.
The upper limit of the setpoint.
The offset value for the refrigeration.
Switch hysteresis for compressor.
Temperature unit
Decimal place (no= no decimal point 22°C, yes= with decimal point 22.3°C .)
Menu of Compressor protection parameters
Delay time for the compressor after power is on.
Delay time required between successive restarts of the compressor.
Delay time required for the compressor to restart following a stop.
Compressor protection delay (no= no delay, yes= 3sec. delay)
On time for the compressor output in the case of probe failure.
Off time for the compressor output in the case of probe failure.
Menu of Defrost protection parameters
Defrosting type (ElC= Electrical defrost, GAS= hot gas defrost )
Defrosting duration.(If d.dur=0, then defrost is disable.)
Interval between defrost cycles.
Defrosting temperature. If evaporator temperature is higher than this value, defrosting is disabled.
Display configuration during defrost
0
0
0
No
0
0
MIN MAX UNIT DEF.SET
-50.0
R.uPL
°C -50
R.LoL
110.0
°C 110
-20.0
20.0
°C 0
°C 0.1
°C
No
20.0
°F
Yes
2
°C
No
255 min.
1
255 min.
1
255 min.
0
Yes No
255 min.
255 min.
0
1
ElC Gas
0
1 min.
sec.
120 h.
min.
-50.0 110.0
°C
ElC
1
1
2
REal LoC LoC
(rEAL= Real temperature is displayed during defrost.
LoC= The temperature which is measured before defrost is displayed during defrost.)
D.drE
D.Pon
D.dPo
D.drt
D.AAc
D.dCP
Delay time for display real temperature after defrost is over.
Defrosting after power is on.(yes=Defrosting begins when power is on, no=Defrosting doesn’t begin when power is on.)
Delay time for defrosting after power is on.
Drop (Drainage) time
Time interval required for alarm activation after completing defrosting
Delay time for the compressor at hot gas defrosting ( Delay time is adjusted by using Cpon ,CssC and Cfos)
D.tbs
Defrosting time unit (Hour= Hour, minute SEC=Minute,second)
Al
Menu of Alarm control parameters
A.LoL
A.uPL
A.dFL
A.HYS
Limit for lower alarm level. When A.typ is changed, A.Lol should be readjusted.
Limit for upper alarm level. When A.typ is changed, A.upl should be readjusted.
Time delay to display alarm message after alarm is on.
Switch hysteresis for alarm.
0
No
0 30
0 15 min.
min.
0 15 h.
sec.
min.
No Yes
Hour SeC
-50.0
a.LoL
0
0 min.
255 sec.
Yes a.uPL °C
110.0
1
No
2
No
255 min.
0
15.0
1
2
Hour
-50
°C 110
°C 2
A.typ
Alarm configuration (A.Abs = Absolute alarm. Alarm values are A.LoL and A.uPL.
A.rEF = Relative alarm. Alarm values are SET-A.LoL and SET+A.uPL.)
A.abs a.ref
a.abs
F.Ctr
Time delay to display alarm message after power is on.
0 24.0
h.
0.1
Menu of Fan control parameters
Fan is controlled depending on temperature (no= independent on temperature, yes= dependent on temperature.)
Fan stopping temperature. If evaporator temperature is above this parameter, fan stops
Switch hysteresis for fan
Does fan stop when compressor stops? (No=Fan status doesn’t change, YEs= Fan stops with compressor.)
Does fan stop during defrosting? (No=Fan status doesn’t change, Yes= Fan stops during the defrosting.)
Delay time for the fan after power is on.
Delay time for the fan after defrosting is over.
Does the fan control depend on the temperature of cold room?
If (no) is selected, fan stops while evaporator temperature is above the value of F.STp parameter, If (YES) is selected, fan stops while the difference between cold room and the evaporator temperature is lower than the value of
the F.STP parameter. Fan restarts again, if the difference between cold room and the evaporator temperature becomes
higher than the total of the values of F.STP and F.HYS parameters.
No Yes
-50.0 110.0
°C
°C 0 15.0
No Yes
No Yes
0
0
No
255 min.
Yes min.
255 sec.
yes
1
2 yes yes
1
2 no
SE
A.rE.S.
Menu of Parameter security
Security parameter for refrigeration menu.
NonE = Menu is invisible
Security parameter for menu of compressor control.
Security parameter for menu of defrost control.
P.yes
= Parameters of menu are changeable
Security parameter for menu of alarm control.
P.no
= Parameters of menu are only visible.
Security parameter for menu of fan control.
Security parameter for refrigeration setpoint value ( P.yes= Setpoint value is changeable.,P.no= Setpoint value is only visible.)
3/3
EDT1423-E-04