TH5110DNon-programmable Thermostat

Add to my manuals
12 Pages

advertisement

TH5110DNon-programmable Thermostat | Manualzz

Honeywell

TH5110DNon-programmable

Thermostat

APPLICATION

The TH511OD Non-programmable Thermostat provides electronic control of 24 Vac, single-stage heating and cooling systems or 750 mV heating systems. See Table 1 for a description.

Table 1, TH5110D Thermostat description.

Feature

Powering Methods

Description

Battery only

• Common wire only

• Common wire with battery backup

System Types (Up to 1 Heat, 1 Cool)

Changeover

System Setting

Fan Setting

Gas, oil or electric heat with air conditioning

Warm air, hot water, high efficiency furnaces, heat pumps, steam and gravity

Heat only-includes power to open and power to close zone valves

(Series 20) and normally-open zone valves

Heat only with fan

Cool only

750 mV heating systems

Manual or auto changeover selectable

Heat-Off-Cool-Auto

Auto-On

MERCURYNOTICE

tf this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.

¢_)U.S. Registered Trademark

Copyright © 2004 Honeywell International inc.

° _ • AN Rights Reserved 69-171211

TH5f10D NON-PROGRAMMABLE

INSTALLATION

THERMOSTAT

When installing this product...

1.

Read these instructions carefufly. Failure to follow these instructions can damage the product or cause a hazardous condition.

2.

Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.

Installer must be a trained, experienced service technician.

4.

After completing installation, use these instructions to check out the product operation.

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before beginning installation.

Select Thermostat Location

Select a _ocation for the thermostat about 5ft (1.5m) above the floor in an area with good air circulation at average temperature.

See Fig. 1.

YES

FEET

[1 5 METER'S] l

Separate Wallplate from Thermostat

1.

Separate the wallplate from the thermostat.

See

Fig. 2.

THERMOSTAT

Fig.

2. Separate wallplate from thermostat.

Install Wallplate (See Fig. 3.)

Mount the thermostat hofizontafly on the wall:

1.

Pull the wires through the wire hole on the

wallplate.

2.

Position the waIIplate on the wall with the arrow pointing up. Level the waflplate for appearance only.

3.

Use a pencil to mark the mounting holes.

4.

Remove the wallplate from the wall and drill two 3/16-in. holes in the wall (if drywall) as marked.

For firmer material such as plaster, drill two 7/32-in.

holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.

5.

Pull the wires through the wire hole on the

wallplate

and position the wallplate over the wall anchors.

6.

insert the mounting screws into the watl anchors and tighten.

Fig.

1. Select thermostat location.

Do not install the thermostat where it can be affected by:

-Drafts or dead spots behind doors and in corners.

-Hot or cold air from ducts.

-Radiant heat from sun or appliances.

-- Concealed pipes and chimneys.

-Unheated (uncooled) areas such as an outside wall behind the thermostat.

SCREWS (2) M22!40

Fig.

3. Install watlplate.

69-1712--1 2

TH51 f OD NON-PROGRAMMABLE THERMOSTAT

WIRING

All wiring must comply with local electrical codes and ordinances.

Refer to Table 2 for descriptions of terminal designations.

See Fig. 6-13 for wiring diagrams for specific equipment applications.

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

IMPORTANT

Use f8-22 gauge thermostat wire. Shielded

cable is not required.

1, Loosen the screw terminals that are used for the application, insert the wires into the terminal block and tighten each screw terminal. See Fig. 4.

TERMINAL BL

LETTER

2.

Push excess wire back into the wall opening and restrict wires to the shaded area. See Fig. 5.

WALLPLATE WALL OP ENING

WIRE

M22!42

Fig. 5. Restrict wires to shaded area of wire hole.

3.

Plug the wail opening with nonflammable insulation to prevent drafts from affecting the thermostat.

Fig.

4. Insert

wires into terminal block.

Table 2. Terminal designation descriptions.

Terminal

Designation

Rc (see Note t)

R (see Note 1)

Y

C (see Note 2)

O/B W (see Note 3)

G

Description

Power for cooling--connect to secondary side of cooling system transformer

Power for heating--connect to secondary side of heating system transformer

Compressor contactor

Common wire from secondary side of cooling system transformer

Heat relay or changeover

Fan relay valve terminal for heat pumps

NOTES:

1.

When used in a single-transformer system, leave metal jumper in place between Rc and R. If used on a two-transformer system, remove metal jumper between Rc and R.

Common wire is optional when thermostat is used with batteries.

If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).

3 69-1712--I

TH5f10D NON-PROGRAMMABLE

WIRING DIAGRAMS

THERMOSTAT

H]ERMOS[A[ WRNG TERM NALS

C

Z_

POWER SU;_Y ;ROV_DE D SCONNEC[ MEANS AND OVERLOAD

(HOT}

Z_ >OWER SUPPLY PROV DE O SCONNECF MEANS AND

M220_S

Fig.

6. Typical

hookup of conventional

with one transformer.

1H/1C system

Z_

CONf GURE SYST_:M [YPE FO dEAF PUMPAND CHANGEOVER

VALVE TO E_THER O OR 8 _N THE _NSTALLER SETUP¸ M220_0

Fig. 8. Typical hookup of 1H/1C heat pump.

IA

_ POWER SUPPLY PROV DE D_SCONNEC[ MEANS AND

A POWER SUP _LY PROV DE D SCONNEC]" MEANS AND OVERLOAD

Fig. 7. Typical hookup of conventional

1H/1C system with two transformers.

Fig.

9. Typical hookup of heat only system.

69-1712--1 4

TH5110D NON-PROGRAMMABLE THERMOSTAT

Z_

POWER SUPPLY

PROV

DE DISCONNECT MEANS AND

r,422o/2

Fig.

10. Typical hookup of heat only system with fan.

THERMOSTAt WRNG TERM NALS

Z_

POWER SUPPLY PROV DE DISCONNECT MEANS AND

Fig.

12. Typical hookup of cool

only system.

THERMOSTAT WRNG TERM NALS

r,422o/4

Z_

sOWER SUPPLY

PROV

DE DISCONNEC r MEANS AND

L1

(Hor)

L2

R

C

Z_

_OWE}_

OVERLOAD

SUPI>LY _/_OV

PROTECTION

DE OISCONNECT

AS REQU RED

MEANS AND

A OPTIONAL 24 VAC COMMON CONNECT ON

L1

04or}

Z_ CON[ GURE SYSTEM TYPE TO HEAr ONLY N THE NSTALLER SE TUP

t,4220/:_

Fig.

11. Typical hookup of heat only Series

system.

20

Fig.

13. Typical hookup normally of a heat only system open zone valve.

with a

5 69-1712--I

TH5flOD NON-PROGRAMMABLE THERMOSTAT

POWER THE THERMOSTAT

You can choose from three methods to power the thermostat:

Batteries only (AAA alkaline).

• 24 Vac common wire only.

• 24 Vac common wire with battery backup (AAA alkaline).

NOTE: Battery backup prevents blank displays during power interruptions.

Wiring 24 Vac Common

• Single-Transformer System--Connect the common side of the transformer to the C screw terminal of the thermostat wallplate. Leave the metal jumper in place between Rc and R.

• T\,vo-Transformer System--Connect the common side of the cooling transformer to the C screw terminal of the thermostat waltplate. Remove the metal jumper between Rc and R.

Installing Batteries

Install two AAA alkaline batteries on the back of the thermostat as marked on the battery holder. See Fig. 14.

NOTE: After the thermostat is mounted on the wallplate, the thermostat does not require removal from the wallptate to replace the batteries. Refer to the enctosed Operating

Instructions, 69-1713, for more information on the removable battery holder.

MountThermostat to Wallplate

1.

Align the four tabs on the wallplate with the four slots on the back of the thermostat. Push the thermostat straight onto the wallplate until it snaps into place. See Fig 15.

M22o_s

Fig. 15. Mount thermostat to waltplate.

-BATTERY

BATTERIES

HOLDER

Fig. 14. Installing

batteries.

k422°56

69-1712--1 6

INSTALLER SETUP

Configure Installer Setup

1.

Enter Installer Setup by pressing and holding the

Up and Fan buttons, at the same time, for approximately five seconds, until the screen changes.

See Fig. 16.

TH5110D NON-PROGRAMMABLE THERMOSTAT

Fig. 16. Enter Installer

setup.

Release the Up and Fan buttons when the display on the thermostat matches the display in Fig. t7.

Fig.

17. Configure Installer

Setup.

3.

See Fig. 18 to review how the thermostat buttons are used during Installer Setup. See Table 3 for the

Installer Setup Numbers and Settings.

NS FALLER SE [U] >

AND SAVES YOUR SErViNGS

NSFALLER SE[U >

NUMBER

M22!44

Fig.

18. Review thermostat buttons

Setup.

used for Installer

7 69-1712--I

TH5f10D NON-PROGRAMMABLE THERMOSTAT

Installer Setup Numbers and Settings

Table 3. Installer setup numbers and settings.

Installer Setup

Number

1

2

May

not appear.

See Note a

3

May

not appear.

See Note b

5

May

not appear,

See Note c

9

May not appear,

See Note d

Installer Setup Name

System Type

Changeover

Terminal

Valve-O/B

Energized in

Heating or Cooling

(Heat Pumps only)

Fan Control in Heating

Heating Cycle Rate in cycles per hour (cph)

Compressor Cycle Rate in cycles per hour (cph)

Settings

0--gas, eit or electric heat with air conditioning (Factory Setting)

1--Heat pump

2--Heat only (two-wire systems or power to open and power to close zone valves or normally-open zone valves)

3--Heat only with fan

4--Cool only

0--Changeover valve--O/B terminal energized in cooling

(Factory Setting)

1--Changeover valve--O/B terminal energized in heating

0-- Gas or oil furnace-equipment controls fan in heating

(Factory Setting)

1-- Electric furnace-thermostat controls fan in heating

5--5 cph used for gas or oil furnaces (less than 90% efficient)

(Factory Setting)

1--1 cph used for steam and gravity

3 --3 cph used for hot water and high efficiency furnaces (90%+)

9--9 cph used for electric furnaces

2, 4, 6, 7, 8, 10, 11, 12--Other cycle rate settings

3--3 cph recommended for compressors (Factory Setting)

1, 2, 4, 5, 6--Other cycle rate settings

12

May not appear.

See Note e

14

System Setting

Adjustment

Temperature Display

0--Manual changeover (Factory Setting) (Heat, Off, Cool)

1--Auto changeover (Heat, Off, Cool, Auto)

2--Auto changeover only (Auto)

0--Fahrenheit temperature display (Factory Setting)

1--Celsius temperature display

15

May not appear.

See Note f

Compressor

Protection--

Minimum-Off Timer in minutes

5--Five-minute compressor off-time setting (Factory

0, 1, 2, 3, 4--Other compressor off-time settings

Setting)

Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the

Installer Setup and save your settings.

Installer Setup Notes: a--Installer Setup Number 2 does not appear if Installer Setup Number 1 is set to 0, 2, 3 or 4.

b--Installer Setup Number 3 does not appear if installer Setup Number 1 is set to 1, 2 or 4.

c--Installer Setup Number 5 does not appear if Installer Setup Number 1 is set to 1 or 4.

d--Installer Setup Number 9 does not appear if Installer Setup Number 1 is set to 2 or 3.

e--Installer Setup Number 12 does not appear if Installer Setup Number 1 is set to 2, 3 or 4.

f-Installer Setup Number 15 does not appear if Installer Setup Number 1 is set to 2 or 3.

69-1712--1 8

TH51 f OD NON-PROGRAMMABLE THERMOSTAT

INSTALLER SYSTEM TEST

Use the Installer System Test to test the heating, cooling and fan.

CAUTION

Equipment Damage Hazard.

Minimum compressor off time is bypassed during installer System Test

Avoid cycling compressor quickly.

How to Use the Installer System Test

1.

Enter the Installer System Test by pressing and holding down the Up and Down buttons at the same time for approximately five seconds, until the screen changes.

See Fig. 19.

ADVANCES

SYSTEM

TO

TEST

NEX [

NUMBER M22!4(_

@ ®

Fig. 20. Review thermostat buttons used during

Installer System Test.

Installer System Tests

IMPORTANT

Use the Instafler System Test to test the heating, cooling and fan. The setting you choose for System Type (Instafler Setup

Number 1) may prevent some System Test

Numbers from appeanng.

Fig. 19. Enter Installer

System Test.

See Fig. 20 to review how the thermostat buttons are used during the Installer System Test. See

Table 4 for available Installer System Tests.

System Test Number

10

Table 4. Installer System Tests.

Test Type

Heating System Test

System Status Number

and Description

1--Heat turns on. When installer Setup Number

1 is set to 1 or Installer Setup Number 3 is set to

1, the fan turns on immediately.

0--Heat and fan turns off.

30 Cooling System Test 1--Compressor and fan turns on.

40 Fan System Test

0--Compressor and fan turns off.

1--Fan turns on.

0--Fan turns off.

70 Thermostat information

(For reference only)

71--Software revision number (Major)

72--Software revision number (Minor)

73--Configuration identification code (Major)

74--Configuration identification code (Minor)

75--Production configuration date code (Week)

76--Production configuration date code (Year)

Press the Next button to go to the beginning of the Installer System Test or press the Done button to exit the installer System Test.

9 69-1712--I

TH5flOD NON-PROGRAMMABLE THERMOSTAT

THERMOSTAT OPERATION

Thermostat Buttons and Battery Holder

See Fig. 21 for description of thermostat buttons and battery holder.

,_ DIGITAL

DISpLAy

_

_

BATTERY

Pq SS OREL

HOLDER

AS

LAT

CH

Minimum-OffTimer Compressor

Protection

The TH5110 has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting-five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the installer Setup.

The Minimum-Off Timer is activated after the compressor turns off.

If the thermostat is system powered (common wire), the

Minimum-Off Timer is also activated upon initial startup and after power interruptions.

If there is a call for cooling or heating during the

Minimum-Off Time, the thermostat flashes "Cool On" or

"Heat On "a. When the Minimum Off Timer expires, "Cool

On" or "Heat On" a appears solid in the display and the compressor and fan turn on.

Fig. 21.

Review

thermostat button description.

Display

See Fig. 22 for description of display.

_ L_ WL:A_NTE SM_As [TFE_biE S p/_ E D 'DI,_ERA

tl'lm_ ih'wl| o Setting iuo

I Ii I c

,_w,,m==_,

_f

HeatOn

_ NDIcArEs

Cool Orl T IERMOSrAr S

_ i _A_.O,o,_

// He°tC°°'l'

AutoOff

CURRENF

[AN SL:[ [ NG

CURREN r

SYS[EM SL:[ [ NG

M22@_

Fig. 22. Review display description.

System and Fan Settings

System

Heat--Thermostat controls the heating system.

Off--Both heating and cooling systems are off.

Cool--Thermostat controls the cooling system.

Auto--Thermostat automatically changes between heating and cooling operation, depending on indoor temperature.

Fan

Auto --Fan runs only when the heating or cooling system is on.

On--Fan runs continuously.

aHeat Pumps only.

AccessoriestReplacementParts

1.

Cover Plates (see Fig. 23):

50001137-001 (Small) Cover Plate--

4-5/16 in. (109 ram) high x

5-1/2 in. (140 ram) wide.

50002883-001(Large) Cover Plate-

6 in. (152 ram) high x

8-5/16 in. (211 ram)wide.

Fig. 23. Cover plate.

2.

Replacement Battery Holder (see Fig. 24):

50000951-001 Battery Holder.

BATTERYHOLDER

BATTERY HOLDER

LATCH

Fig. 24.

Battery

holder.

69-1712--1 10

TH51 f OD NON-PROGRAMMABLE THERMOSTAT

TROUBLESHOOTING

Symptom

Display is blank.

Temperature settings do not change,

Heat does not turn on

(Heat On is solid in the display).

Cooling does not turn on

(Coot On is solid in the display).

Fan does not turn on in a call for heat (electric furnace).

Heat pump puts out cool air in the heat mode and warm air in the cool mode.

Both the heating and cooling equipment are running at the same time.

Thermostat

Table 5. Troubleshooting

Possible Cause is not powered.

The highest or lowest temperature setting was reached.

Heating equipment failure.

Loose or broken wire connection between thermostat and heating equipment.

Cooling equipment failure.

Loose or broken wire connection between thermostat and cooling equipment,

Action

Check for 24 Vac between Rc and C.

Check that fresh AAA alkaline batteries are installed as marked on the battery holder.

Temperature setting range:

Heating:4O ° Fto 90 °F(4.5 °C to32 °C)

Cooling: 50 ° F to 99°F (10°C to 37°C)

Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.

Check for 24 Vac between the heat terminal

(W) and transformer common. If 24 Vac is present, the thermostat is functional.

Check the heating equipment to find the cause of the problem.

Check for 24 Vac between the heat terminal

(W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment.

Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem.

Check for 24 Vac between the cool terminal

(Y) and transformer common. If 24 Vac is present, the thermostat is functional.

Check the cooling equipment to find the cause of the problem.

Check for 24 Vac between the cool terminal

(Y) and transformer common. If voltage is not present, check the wire connection

(loose or broken) between the thermostat and the cooling equipment.

Set Fan Control in Heating (Installer Setup

Number 3) to Electric Furnace (Setting 1).

Fan Control in Heating (Installer Setup

Number 3) is set to Gas or Oil Furnace

(Setting 0).

Changeover Valve (Installer Setup

Number 2) is not configured to match the changeover required by the installed heat pump.

The heating equipment is not a heat pump but the System Type (installer

Setup Number 1) is set to Heat Pump

(Setting 1).

Heating and cooling wires are shorted together,

Set Changeover Valve (installer Setup

Number 2) to match the changeover required by the installed heat pump.

Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.

Separate the shorted heating and cooling wires.

II 69-1712--I

TH5110D NON-PROGRAMMABLE THERMOSTAT

Symptom

Heating equipment is running in the cool mode.

Table 5. Troubleshooting

Possible Cause

Heating equipment is not a heat pump but System Type (installer Setup

Number 1) is set to Heat Pump

(Setting 1).

Heating equipment is not a heat pump but System Type (installer Setup

Number 1) is set to Heat Pump

(Setting 1).

Set System Type dnstaller Setup Number 1) to match the installed heating and/or cooling equipment.

Action

Heating equipment does not turn off and the heat temperature setting is set below the room temperature (Heat On is not in the display).

Cannot set the system setting to Heat.

Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.

Cannot set the system setting to Cool.

Heat On is not in the display,

Cool On is not in the display,

System Type (installer Setup Number 1 ) is set to Cool Only (Setting 4).

System Setting Adjustment (Installer

Setup Number 12) is set to Auto

Changeover Only (Setting 2).

System Type (installer Setup Number 1 ) is set to Heat Only (Setting 2) or Heat

Only with Fan (Setting 3).

System Setting Adjustment (Installer

Setup Number 12) is set to Auto

Changeover Only (Setting 2).

System setting is not set to Heat and/or the temperature setting is not set above the room temperature,

System setting is not set to Cool and/or the temperature setting is not set below the room temperature,

Compressor minimum off timer is active.

Heat On is flashing in the display (Heat pumps only).

Cool On is flashing in the display,

Compressor minimum off timer is active.

Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.

Set System Setting Adjustment (Installer

Setup Number 12) to Manual Changeover

(Setting 0) or Auto Changeover (Setting 1).

Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.

Set System Setting Adjustment (Installer

Setup Number 12) to Manual Changeover

(Setting 0) or Auto Changeover (Setting 1).

Set the system setting to Heat and set the temperature setting above the room temperature.

Set the system setting to Cool and set the temperature setting below the room temperature.

Wait up to five minutes for the heating equipment to turn on.

Wait up to five minutes for the cooling equipment to turn on.

SPECIFICATIONS

Electrical Ratings:

Terminal

W Heating

W Heating

(Powerpile)

Y Cooling

G Fan

Voltage

(50/60 Hz)

20 - 30 Vac

750 mV dc

20 - 30 Vac

20 - 30 Vac

Running Current

.02 - 1.0A

100 mA dc

.02 - 1.0A

.02 - .60A

Temperature Setting Range:

Heating: 40°F to 90°F (4.5°C to 32°C).

Cooling: 50°F to 99°F (10°C to 37°C).

Operating Ambient

(2.8°C to 38.9°C).

Temperature: 37°F to 102°F

Shipping Temperature: -30°F to t50°F

(-34.4°C to 65.6°C).

Operating

5% to 90%.

Relative Humidity (Non-condensing):

Thermostat Dimensions: 3-7/16 in (86 ram) high x

4-1/2 in. (114 ram) wide x 1-5/16 in. (33 mm) deep.

Hone) well

Automation and Control

Honeywetl International Inc

1985 Douglas Drive North

Golden Valley, MN 55422

Solutions

Honey_vell

35 Dynamic

Scarborough,

Mrv 4Z9

Limited-Honeywell

Drive

Ontario

Lira[tee

69-1712--1 JS Rev.

6-04

_ papefconlalnflgatleastlo% post-consumer paper fibers.

ww,_v.honeyvvelLoom/yourhome

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement