advertisement
Honeywell
TH5110DNon-programmable
Thermostat
APPLICATION
The TH511OD Non-programmable Thermostat provides electronic control of 24 Vac, single-stage heating and cooling systems or 750 mV heating systems. See Table 1 for a description.
Table 1, TH5110D Thermostat description.
Feature
Powering Methods
Description
•
Battery only
• Common wire only
• Common wire with battery backup
System Types (Up to 1 Heat, 1 Cool)
Changeover
System Setting
Fan Setting
Gas, oil or electric heat with air conditioning
Warm air, hot water, high efficiency furnaces, heat pumps, steam and gravity
Heat only-includes power to open and power to close zone valves
(Series 20) and normally-open zone valves
Heat only with fan
Cool only
750 mV heating systems
Manual or auto changeover selectable
Heat-Off-Cool-Auto
Auto-On
MERCURYNOTICE
tf this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash.
Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat.
¢_)U.S. Registered Trademark
Copyright © 2004 Honeywell International inc.
° _ • AN Rights Reserved 69-171211
TH5f10D NON-PROGRAMMABLE
INSTALLATION
THERMOSTAT
When installing this product...
1.
Read these instructions carefufly. Failure to follow these instructions can damage the product or cause a hazardous condition.
2.
Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3.
Installer must be a trained, experienced service technician.
4.
After completing installation, use these instructions to check out the product operation.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before beginning installation.
Select Thermostat Location
Select a _ocation for the thermostat about 5ft (1.5m) above the floor in an area with good air circulation at average temperature.
See Fig. 1.
YES
FEET
[1 5 METER'S] l
Separate Wallplate from Thermostat
1.
Separate the wallplate from the thermostat.
See
Fig. 2.
THERMOSTAT
Fig.
2. Separate wallplate from thermostat.
Install Wallplate (See Fig. 3.)
Mount the thermostat hofizontafly on the wall:
1.
Pull the wires through the wire hole on the
wallplate.
2.
Position the waIIplate on the wall with the arrow pointing up. Level the waflplate for appearance only.
3.
Use a pencil to mark the mounting holes.
4.
Remove the wallplate from the wall and drill two 3/16-in. holes in the wall (if drywall) as marked.
For firmer material such as plaster, drill two 7/32-in.
holes. Tap the wall anchors (provided) into the drilled holes until flush with the wall.
5.
Pull the wires through the wire hole on the
wallplate
and position the wallplate over the wall anchors.
6.
insert the mounting screws into the watl anchors and tighten.
Fig.
1. Select thermostat location.
Do not install the thermostat where it can be affected by:
-Drafts or dead spots behind doors and in corners.
-Hot or cold air from ducts.
-Radiant heat from sun or appliances.
-- Concealed pipes and chimneys.
-Unheated (uncooled) areas such as an outside wall behind the thermostat.
SCREWS (2) M22!40
Fig.
3. Install watlplate.
69-1712--1 2
TH51 f OD NON-PROGRAMMABLE THERMOSTAT
WIRING
All wiring must comply with local electrical codes and ordinances.
Refer to Table 2 for descriptions of terminal designations.
See Fig. 6-13 for wiring diagrams for specific equipment applications.
CAUTION
Electrical Hazard.
Can cause electrical shock or equipment damage.
Disconnect power before wiring.
IMPORTANT
Use f8-22 gauge thermostat wire. Shielded
cable is not required.
1, Loosen the screw terminals that are used for the application, insert the wires into the terminal block and tighten each screw terminal. See Fig. 4.
TERMINAL BL
LETTER
2.
Push excess wire back into the wall opening and restrict wires to the shaded area. See Fig. 5.
WALLPLATE WALL OP ENING
WIRE
M22!42
Fig. 5. Restrict wires to shaded area of wire hole.
3.
Plug the wail opening with nonflammable insulation to prevent drafts from affecting the thermostat.
Fig.
4. Insert
wires into terminal block.
Table 2. Terminal designation descriptions.
Terminal
Designation
Rc (see Note t)
R (see Note 1)
Y
C (see Note 2)
O/B W (see Note 3)
G
Description
Power for cooling--connect to secondary side of cooling system transformer
Power for heating--connect to secondary side of heating system transformer
Compressor contactor
Common wire from secondary side of cooling system transformer
Heat relay or changeover
Fan relay valve terminal for heat pumps
NOTES:
1.
When used in a single-transformer system, leave metal jumper in place between Rc and R. If used on a two-transformer system, remove metal jumper between Rc and R.
Common wire is optional when thermostat is used with batteries.
If thermostat is configured for a heat pump in the Installer Setup, configure changeover valve for cool (O-factory setting) or heat (B).
3 69-1712--I
TH5f10D NON-PROGRAMMABLE
WIRING DIAGRAMS
THERMOSTAT
H]ERMOS[A[ WRNG TERM NALS
C
Z_
POWER SU;_Y ;ROV_DE D SCONNEC[ MEANS AND OVERLOAD
(HOT}
Z_ >OWER SUPPLY PROV DE O SCONNECF MEANS AND
M220_S
Fig.
6. Typical
hookup of conventional
with one transformer.
1H/1C system
Z_
CONf GURE SYST_:M [YPE FO dEAF PUMPAND CHANGEOVER
VALVE TO E_THER O OR 8 _N THE _NSTALLER SETUP¸ M220_0
Fig. 8. Typical hookup of 1H/1C heat pump.
IA
_ POWER SUPPLY PROV DE D_SCONNEC[ MEANS AND
A POWER SUP _LY PROV DE D SCONNEC]" MEANS AND OVERLOAD
Fig. 7. Typical hookup of conventional
1H/1C system with two transformers.
Fig.
9. Typical hookup of heat only system.
69-1712--1 4
TH5110D NON-PROGRAMMABLE THERMOSTAT
Z_
POWER SUPPLY
PROV
DE DISCONNECT MEANS AND
r,422o/2
Fig.
10. Typical hookup of heat only system with fan.
THERMOSTAt WRNG TERM NALS
Z_
POWER SUPPLY PROV DE DISCONNECT MEANS AND
Fig.
12. Typical hookup of cool
only system.
THERMOSTAT WRNG TERM NALS
r,422o/4
Z_
sOWER SUPPLY
PROV
DE DISCONNEC r MEANS AND
L1
(Hor)
L2
R
C
Z_
_OWE}_
OVERLOAD
SUPI>LY _/_OV
PROTECTION
DE OISCONNECT
AS REQU RED
MEANS AND
A OPTIONAL 24 VAC COMMON CONNECT ON
L1
04or}
Z_ CON[ GURE SYSTEM TYPE TO HEAr ONLY N THE NSTALLER SE TUP
t,4220/:_
Fig.
11. Typical hookup of heat only Series
system.
20
Fig.
13. Typical hookup normally of a heat only system open zone valve.
with a
5 69-1712--I
TH5flOD NON-PROGRAMMABLE THERMOSTAT
POWER THE THERMOSTAT
You can choose from three methods to power the thermostat:
•
Batteries only (AAA alkaline).
• 24 Vac common wire only.
• 24 Vac common wire with battery backup (AAA alkaline).
NOTE: Battery backup prevents blank displays during power interruptions.
Wiring 24 Vac Common
• Single-Transformer System--Connect the common side of the transformer to the C screw terminal of the thermostat wallplate. Leave the metal jumper in place between Rc and R.
• T\,vo-Transformer System--Connect the common side of the cooling transformer to the C screw terminal of the thermostat waltplate. Remove the metal jumper between Rc and R.
Installing Batteries
Install two AAA alkaline batteries on the back of the thermostat as marked on the battery holder. See Fig. 14.
NOTE: After the thermostat is mounted on the wallplate, the thermostat does not require removal from the wallptate to replace the batteries. Refer to the enctosed Operating
Instructions, 69-1713, for more information on the removable battery holder.
MountThermostat to Wallplate
1.
Align the four tabs on the wallplate with the four slots on the back of the thermostat. Push the thermostat straight onto the wallplate until it snaps into place. See Fig 15.
M22o_s
Fig. 15. Mount thermostat to waltplate.
-BATTERY
BATTERIES
HOLDER
Fig. 14. Installing
batteries.
k422°56
69-1712--1 6
INSTALLER SETUP
Configure Installer Setup
1.
Enter Installer Setup by pressing and holding the
Up and Fan buttons, at the same time, for approximately five seconds, until the screen changes.
See Fig. 16.
TH5110D NON-PROGRAMMABLE THERMOSTAT
Fig. 16. Enter Installer
setup.
Release the Up and Fan buttons when the display on the thermostat matches the display in Fig. t7.
Fig.
17. Configure Installer
Setup.
3.
See Fig. 18 to review how the thermostat buttons are used during Installer Setup. See Table 3 for the
Installer Setup Numbers and Settings.
NS FALLER SE [U] >
AND SAVES YOUR SErViNGS
NSFALLER SE[U >
NUMBER
M22!44
Fig.
18. Review thermostat buttons
Setup.
used for Installer
7 69-1712--I
TH5f10D NON-PROGRAMMABLE THERMOSTAT
Installer Setup Numbers and Settings
Table 3. Installer setup numbers and settings.
Installer Setup
Number
1
2
May
not appear.
See Note a
3
May
not appear.
See Note b
5
May
not appear,
See Note c
9
May not appear,
See Note d
Installer Setup Name
System Type
Changeover
Terminal
Valve-O/B
Energized in
Heating or Cooling
(Heat Pumps only)
Fan Control in Heating
Heating Cycle Rate in cycles per hour (cph)
Compressor Cycle Rate in cycles per hour (cph)
Settings
0--gas, eit or electric heat with air conditioning (Factory Setting)
1--Heat pump
2--Heat only (two-wire systems or power to open and power to close zone valves or normally-open zone valves)
3--Heat only with fan
4--Cool only
0--Changeover valve--O/B terminal energized in cooling
(Factory Setting)
1--Changeover valve--O/B terminal energized in heating
0-- Gas or oil furnace-equipment controls fan in heating
(Factory Setting)
1-- Electric furnace-thermostat controls fan in heating
5--5 cph used for gas or oil furnaces (less than 90% efficient)
(Factory Setting)
1--1 cph used for steam and gravity
3 --3 cph used for hot water and high efficiency furnaces (90%+)
9--9 cph used for electric furnaces
2, 4, 6, 7, 8, 10, 11, 12--Other cycle rate settings
3--3 cph recommended for compressors (Factory Setting)
1, 2, 4, 5, 6--Other cycle rate settings
12
May not appear.
See Note e
14
System Setting
Adjustment
Temperature Display
0--Manual changeover (Factory Setting) (Heat, Off, Cool)
1--Auto changeover (Heat, Off, Cool, Auto)
2--Auto changeover only (Auto)
0--Fahrenheit temperature display (Factory Setting)
1--Celsius temperature display
15
May not appear.
See Note f
Compressor
Protection--
Minimum-Off Timer in minutes
5--Five-minute compressor off-time setting (Factory
0, 1, 2, 3, 4--Other compressor off-time settings
Setting)
Press the Next button to go to the beginning of the Installer Setup or press the Done button to exit the
Installer Setup and save your settings.
Installer Setup Notes: a--Installer Setup Number 2 does not appear if Installer Setup Number 1 is set to 0, 2, 3 or 4.
b--Installer Setup Number 3 does not appear if installer Setup Number 1 is set to 1, 2 or 4.
c--Installer Setup Number 5 does not appear if Installer Setup Number 1 is set to 1 or 4.
d--Installer Setup Number 9 does not appear if Installer Setup Number 1 is set to 2 or 3.
e--Installer Setup Number 12 does not appear if Installer Setup Number 1 is set to 2, 3 or 4.
f-Installer Setup Number 15 does not appear if Installer Setup Number 1 is set to 2 or 3.
69-1712--1 8
TH51 f OD NON-PROGRAMMABLE THERMOSTAT
INSTALLER SYSTEM TEST
Use the Installer System Test to test the heating, cooling and fan.
CAUTION
Equipment Damage Hazard.
Minimum compressor off time is bypassed during installer System Test
Avoid cycling compressor quickly.
How to Use the Installer System Test
1.
Enter the Installer System Test by pressing and holding down the Up and Down buttons at the same time for approximately five seconds, until the screen changes.
See Fig. 19.
ADVANCES
SYSTEM
TO
TEST
NEX [
NUMBER M22!4(_
@ ®
Fig. 20. Review thermostat buttons used during
Installer System Test.
Installer System Tests
IMPORTANT
Use the Instafler System Test to test the heating, cooling and fan. The setting you choose for System Type (Instafler Setup
Number 1) may prevent some System Test
Numbers from appeanng.
Fig. 19. Enter Installer
System Test.
See Fig. 20 to review how the thermostat buttons are used during the Installer System Test. See
Table 4 for available Installer System Tests.
System Test Number
10
Table 4. Installer System Tests.
Test Type
Heating System Test
System Status Number
and Description
1--Heat turns on. When installer Setup Number
1 is set to 1 or Installer Setup Number 3 is set to
1, the fan turns on immediately.
0--Heat and fan turns off.
30 Cooling System Test 1--Compressor and fan turns on.
40 Fan System Test
0--Compressor and fan turns off.
1--Fan turns on.
0--Fan turns off.
70 Thermostat information
(For reference only)
71--Software revision number (Major)
72--Software revision number (Minor)
73--Configuration identification code (Major)
74--Configuration identification code (Minor)
75--Production configuration date code (Week)
76--Production configuration date code (Year)
Press the Next button to go to the beginning of the Installer System Test or press the Done button to exit the installer System Test.
9 69-1712--I
TH5flOD NON-PROGRAMMABLE THERMOSTAT
THERMOSTAT OPERATION
Thermostat Buttons and Battery Holder
See Fig. 21 for description of thermostat buttons and battery holder.
,_ DIGITAL
DISpLAy
_
_
BATTERY
Pq SS OREL
HOLDER
AS
LAT
CH
Minimum-OffTimer Compressor
Protection
The TH5110 has an adjustable Minimum-Off Timer that can be set from zero to five minutes (Factory Setting-five minutes). The Minimum-Off Timer can be bypassed through the Installer System Test or it can be bypassed permanently by setting the Minimum-Off Timer to 0 minutes in the installer Setup.
The Minimum-Off Timer is activated after the compressor turns off.
If the thermostat is system powered (common wire), the
Minimum-Off Timer is also activated upon initial startup and after power interruptions.
If there is a call for cooling or heating during the
Minimum-Off Time, the thermostat flashes "Cool On" or
"Heat On "a. When the Minimum Off Timer expires, "Cool
On" or "Heat On" a appears solid in the display and the compressor and fan turn on.
Fig. 21.
Review
thermostat button description.
Display
See Fig. 22 for description of display.
_ L_ WL:A_NTE SM_As [TFE_biE S p/_ E D 'DI,_ERA
tl'lm_ ih'wl| o Setting iuo
I Ii I c
,_w,,m==_,
_f
HeatOn
_ NDIcArEs
Cool Orl T IERMOSrAr S
_ i _A_.O,o,_
// He°tC°°'l'
AutoOff
CURRENF
[AN SL:[ [ NG
CURREN r
SYS[EM SL:[ [ NG
M22@_
Fig. 22. Review display description.
System and Fan Settings
System
Heat--Thermostat controls the heating system.
Off--Both heating and cooling systems are off.
Cool--Thermostat controls the cooling system.
Auto--Thermostat automatically changes between heating and cooling operation, depending on indoor temperature.
Fan
Auto --Fan runs only when the heating or cooling system is on.
On--Fan runs continuously.
aHeat Pumps only.
AccessoriestReplacementParts
1.
Cover Plates (see Fig. 23):
50001137-001 (Small) Cover Plate--
4-5/16 in. (109 ram) high x
5-1/2 in. (140 ram) wide.
50002883-001(Large) Cover Plate-
6 in. (152 ram) high x
8-5/16 in. (211 ram)wide.
Fig. 23. Cover plate.
2.
Replacement Battery Holder (see Fig. 24):
50000951-001 Battery Holder.
BATTERYHOLDER
BATTERY HOLDER
LATCH
Fig. 24.
Battery
holder.
69-1712--1 10
TH51 f OD NON-PROGRAMMABLE THERMOSTAT
TROUBLESHOOTING
Symptom
Display is blank.
Temperature settings do not change,
Heat does not turn on
(Heat On is solid in the display).
Cooling does not turn on
(Coot On is solid in the display).
Fan does not turn on in a call for heat (electric furnace).
Heat pump puts out cool air in the heat mode and warm air in the cool mode.
Both the heating and cooling equipment are running at the same time.
Thermostat
Table 5. Troubleshooting
Possible Cause is not powered.
The highest or lowest temperature setting was reached.
Heating equipment failure.
Loose or broken wire connection between thermostat and heating equipment.
Cooling equipment failure.
Loose or broken wire connection between thermostat and cooling equipment,
Action
Check for 24 Vac between Rc and C.
Check that fresh AAA alkaline batteries are installed as marked on the battery holder.
Temperature setting range:
Heating:4O ° Fto 90 °F(4.5 °C to32 °C)
Cooling: 50 ° F to 99°F (10°C to 37°C)
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If 24 Vac is present, the thermostat is functional.
Check the heating equipment to find the cause of the problem.
Check for 24 Vac between the heat terminal
(W) and transformer common. If voltage is not present, check wire connection (loose or broken) between the thermostat and the heating equipment.
Check for 24 Vac at the equipment on the secondary side of the transformer between power and common. If voltage is not present, check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If 24 Vac is present, the thermostat is functional.
Check the cooling equipment to find the cause of the problem.
Check for 24 Vac between the cool terminal
(Y) and transformer common. If voltage is not present, check the wire connection
(loose or broken) between the thermostat and the cooling equipment.
Set Fan Control in Heating (Installer Setup
Number 3) to Electric Furnace (Setting 1).
Fan Control in Heating (Installer Setup
Number 3) is set to Gas or Oil Furnace
(Setting 0).
Changeover Valve (Installer Setup
Number 2) is not configured to match the changeover required by the installed heat pump.
The heating equipment is not a heat pump but the System Type (installer
Setup Number 1) is set to Heat Pump
(Setting 1).
Heating and cooling wires are shorted together,
Set Changeover Valve (installer Setup
Number 2) to match the changeover required by the installed heat pump.
Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.
Separate the shorted heating and cooling wires.
II 69-1712--I
TH5110D NON-PROGRAMMABLE THERMOSTAT
Symptom
Heating equipment is running in the cool mode.
Table 5. Troubleshooting
Possible Cause
Heating equipment is not a heat pump but System Type (installer Setup
Number 1) is set to Heat Pump
(Setting 1).
Heating equipment is not a heat pump but System Type (installer Setup
Number 1) is set to Heat Pump
(Setting 1).
Set System Type dnstaller Setup Number 1) to match the installed heating and/or cooling equipment.
Action
Heating equipment does not turn off and the heat temperature setting is set below the room temperature (Heat On is not in the display).
Cannot set the system setting to Heat.
Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.
Cannot set the system setting to Cool.
Heat On is not in the display,
Cool On is not in the display,
System Type (installer Setup Number 1 ) is set to Cool Only (Setting 4).
System Setting Adjustment (Installer
Setup Number 12) is set to Auto
Changeover Only (Setting 2).
System Type (installer Setup Number 1 ) is set to Heat Only (Setting 2) or Heat
Only with Fan (Setting 3).
System Setting Adjustment (Installer
Setup Number 12) is set to Auto
Changeover Only (Setting 2).
System setting is not set to Heat and/or the temperature setting is not set above the room temperature,
System setting is not set to Cool and/or the temperature setting is not set below the room temperature,
Compressor minimum off timer is active.
Heat On is flashing in the display (Heat pumps only).
Cool On is flashing in the display,
Compressor minimum off timer is active.
Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.
Set System Setting Adjustment (Installer
Setup Number 12) to Manual Changeover
(Setting 0) or Auto Changeover (Setting 1).
Set System Type (installer Setup Number 1) to match the installed heating and/or cooling equipment.
Set System Setting Adjustment (Installer
Setup Number 12) to Manual Changeover
(Setting 0) or Auto Changeover (Setting 1).
Set the system setting to Heat and set the temperature setting above the room temperature.
Set the system setting to Cool and set the temperature setting below the room temperature.
Wait up to five minutes for the heating equipment to turn on.
Wait up to five minutes for the cooling equipment to turn on.
SPECIFICATIONS
Electrical Ratings:
Terminal
W Heating
W Heating
(Powerpile)
Y Cooling
G Fan
Voltage
(50/60 Hz)
20 - 30 Vac
750 mV dc
20 - 30 Vac
20 - 30 Vac
Running Current
.02 - 1.0A
100 mA dc
.02 - 1.0A
.02 - .60A
Temperature Setting Range:
Heating: 40°F to 90°F (4.5°C to 32°C).
Cooling: 50°F to 99°F (10°C to 37°C).
Operating Ambient
(2.8°C to 38.9°C).
Temperature: 37°F to 102°F
Shipping Temperature: -30°F to t50°F
(-34.4°C to 65.6°C).
Operating
5% to 90%.
Relative Humidity (Non-condensing):
Thermostat Dimensions: 3-7/16 in (86 ram) high x
4-1/2 in. (114 ram) wide x 1-5/16 in. (33 mm) deep.
Hone) well
Automation and Control
Honeywetl International Inc
1985 Douglas Drive North
Golden Valley, MN 55422
Solutions
Honey_vell
35 Dynamic
Scarborough,
Mrv 4Z9
Limited-Honeywell
Drive
Ontario
Lira[tee
69-1712--1 JS Rev.
6-04
_ papefconlalnflgatleastlo% post-consumer paper fibers.
ww,_v.honeyvvelLoom/yourhome
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project