quantum typical oneline concept drawing not for construction

quantum typical oneline concept drawing not for construction
LUTRON NOTES:
ALL DIMMING BALLASTS TO BE LUTRON ECOSYSTEM,
ECOSYSTEM H-SERIES, OR HI-LUME 3D TYPE. LUTRON DRIVER
TO BE A-SERIES 3 WIRE UNLESS OTHERWISE NOTED.
E.E. TO CONFIRM ALL CIRCUITING REQUIREMENTS.
ARCHITECT TO VERIFY QUANTITY, LOCATION & FINISH OF ALL
CONTROLS.
ALL FACEPLATES, DIMMERS, SWITCHES, RECEPTACLES
& CABLE/PHONE JACKS TO BE LUTRON NOVA T*
TYPICAL POWER MODULES
LUTRON FIELD SERVICE COMMISSIONING INCLUDED IN
ALL SYSTEMS INITIATES AN 2 YEAR LIMITED WARRANTY. THE
ELECTRICAL
CONTRACTOR
MUST
CONTACT
LUTRON
(800-523-9466) TO SET UP VISIT WITH 10 DAYS NOTICE.
TYPICAL ECOSYSTEM LOOP DETAIL
ZONE:
(SWITCHED POWER)
(0-10V DIM)
120V/277V
INPUT FEED
INPUT FEED
FROM DISTRIBUTION
PANEL
INPUT FEED
FROM DISTRIBUTION PANEL
H3D Txxx x x x xx
IR
OCC
+20
E1
E2
NEU
DH
SH
Daylight
NEU
DH
SH
Common
EC5 Txxxx J UNV x
NEU
DH
SH
NEU
N/C
HOT
E1
E2
E1
E2
E1
E2
H-SERIES BALLAST
HI-LUME 3D BALLAST
ECOSYSTEM BALLAST
Typical EcoSystem Loop
64 Ballasts/Interfaces Max
INPUT FEED
FROM DISTRIBUTION
PANEL
INPUT FEED
FROM DISTRIBUTION
PANEL
EHD Txxx x x x xx
EcoSystem
Compact
Fluorescent
Ballast
TO 0-10V LED
DRIVER
(BY OTHERS)
INPUT FEED
FROM DISTRIBUTION
PANEL
HI-LUME LED
LUTRON A-SERIES LED DRIVER
120V/277V
TVI-LMF-2A
ECOSYSTEM TO
0-10V INTERFACE
DIMENSIONS:
4.2"(W) X 3.0"(H) X 1.0"(D)
LUTRON 5-SERIES LED DRIVER
120V/277V
PHPM-WBX-DV-WH
120 - 277V
PHASE-ADAPTIVE POWER
MODULE WITH
FLUORESCENT INPUT
5.1"(H) X 6.3"(W) X 1.6"(D)
TO NORMAL 3PHASE 4WIRE
DISTRIBUTION PANEL
CONTRACTOR TO PROVIDE (1) 3P BREAKER.
UP TO 10 WIRELESS PER QSM
ZONE #
FLD
120V/277V
INPUT FEED
ECOSYSTEM DIGITAL LOOP #
UL924 EMERGENCY COMPLIANCE
(AS REQUIRED, EE TO VERIFY EMERGENCY REQUIREMENTS)
120V CONTROL
INPUT ONLY
C5-BMJ-16A
ECOSYSTEM DIMMING
POWER MODULE FOR
3-WIRE LUTRON
DIMMING BALLASTS
7.8"(H) X 5"(W) X 2.5"(D)
C5-XPJ-16A
ECOSYSTEM SWITCHING
POWER MODULE FOR
NON-DIM LOADS
7.8"(H) X 5"(W) X 2.5"(D)
HI-LUME LED
120/277V
GRX-TVI
INPUT FEED 0-10V BALLAST
INTERFACE
318mm[12.5"] (H) x 155mm[6.1"] (W) X 84mm[3.3"] (D)
ZONE #
120V/277V
INPUT FEED
INPUT FEED
INPUT FEED
FROM DISTRIBUTION
PANEL
120V
INPUT FEED
TO NON-DIM
LOAD
PHPM-3F-DV-WH
FLUORESCENT POWER MODULE
DIMS 120V OR 277V 3-WIRE FL
ACCEPTS 120V CONTROL SIGNAL ONLY
DIMENSIONS:
5.1"(H) X 6.3"(W) X 1.6"(D)
TO ECOSYSTEM
BALLASTS/MODULES
(64 MAX PER LOOP)
120V CONTROL
INPUT ONLY
UP TO 4 WIRED DEVICES PER QSM
LRF2-VCR2B-P-WH
434MHZ WIRELESS
VACANCY SENSOR
3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
5 #12AWG
LUTRON
ZONE #
120V/277V
INPUT FEED
PHPM-PA-DV-WH
PHASE-ADAPTIVE POWER MODULE
DIMS 120V OR 277V LOADS
ACCEPTS 120V CONTROL SIGNAL ONLY
DIMENSIONS:
5.1"(H) X 6.3"(W) X 1.6"(D)
LUTRON
ALTERNATE FOR QUANTUM LIGHTING
MANAGEMENT SYSTEM CONTROL
RED
RED
NORMAL/EMERGENCY
INPUT POWER
PP-120H
(120 VAC)
POWER SUPPLY
2.33"[59mm] (H) X 3.69"[94mm] (W) X 1.36"[34,5mm] (D)
DEDICATED ETHERNET
ENVIRONMENT
E
PJ2-3BRL-GWG-L01
434 MHZ PICO WIRELESS, LIGHT
3 BUTTON CONTROL WITH RAISE/LOWER
SHOWN WITH CW-1-WH
CLARO WALLPLATE
PICO DIMENSIONS:
2.61"[66,3mm] (H) X 1.28"[32,5mm] (W) X 0.37"[9,4mm] (D)
W/WALLPLATE:
4.69"[119mm] (H) X 2.94"[74,7mm] (W) X 0.37"[9,4mm] (D)
*SEE SPECIFICATION SHEET FOR
MOUNTING INSTRUCTIONS
LOCATION TBD
LUT-ELI-3PH
EMERGENCY LIGHTING
INTERFACE
7.75"[197mm] (H) X 4"[102mm] (W) X 2.5"[63,5mm] (D)
LRF2-DCRB-WH
434MHZ WIRELESS
DAYLIGHT SENSOR
1.6"[40,6mm] (DIA) X 0.7"[17,8mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
LRF2-OCR2B-P-WH
434MHZ WIRELESS
OCCUPANCY/VACANCY SENSOR
3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH
RECESS MOUNT KIT FOR
NON-METALLIC CEILINGS)
LOCATION TBD
(OPTION:WITH L-CRMK-WH
RECESS MOUNT KIT FOR
NON-METALLIC CEILINGS)
PX-3B-GWG-I01
PICO WIRED
3 BUTTON CONTROL
SHOWN WITH CW-1-WH
LOS-xxx-xxxx-WH
CLARO WALLPLATE
CEILING MOUNT
PICO DIMENSIONS:
OCCUPANCY SENSOR
2.61"[66,3mm] (H) X 1.28"[32,5mm] (W) X 0.37"[9,4mm] (D)
4.5"[114mm] (DIA) X 1.4"[35,6mm] (D)
W/WALLPLATE:
LOCATION TBD
4.69"[119mm] (H) X 2.94"[74,7mm] (W) X 0.37"[9,4mm] (D)
*SEE SPECIFICATION SHEET FOR
MOUNTING INSTRUCTIONS
LOCATION TBD
TO QSM
AS REQUIRED
EC-DIR-WH
FIXTURE MOUNTABLE DAYLIGHT
SENSOR W/ IR RECEIVER
(1 MAX PER BALLAST/MODULE)
1.18"[30mm] DIA.
LOCATION TBD
TO QSM
AS REQUIRED
ECOSYSTEM DIGITAL LOOP #
Q
QSGRJ-6E-TWH
(# OF QS ZONES: 6)
FUNCTION: SCENES 1-4 & OFF
WITH (1) ECOSYSTEM BUS
(4 GANG US BACKBOX BY OTHERS)
LOCATION TBD
AS REQUIRED
FOR NON-DIM LIGHTING LOADS
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
TYPICAL WALL CONTROL
(OTHER CONFIGURATIONS AVAILABLE)
Q
QS-A-CMP-L-O
LAPTOP COMPUTER
OPTIONAL GREEN GLANCE
TO ECOSYSTEM
BALLASTS/MODULES
(64 MAX PER LOOP)
QSWS2-5BRLN-WH
FUNCTION: 5-BUTTON SCENE
SELECT WITH RAISE/LOWER
(1 GANG US BACKBOX BY OTHERS)
LOCATION TBD
AS REQUIRED
FOR DIGITALLY ADDRESSABLE LIGHTING LOADS
AS REQUIRED
FOR 0-10V/NON-DIM LIGHTING LOADS
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
TO QUANTUM SERVER OR
LIGHTING MANAGEMENT
NETWORK SWITCH
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
ZONE X
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
DVI DIGITAL SIGNAL
E
ZONE (X)
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
ECOSYSTEM DIGITAL LOOP #1
TO ECOSYSTEM
BALLASTS/MODULES
(64 MAX PER LOOP)
ZONE X
ECOSYSTEM DIGITAL LOOP #2
TO ECOSYSTEM
BALLASTS/MODULES
(64 MAX PER LOOP)
ZONE X
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
TO ECOSYSTEM BALLASTS/MODULES (64 MAX PER LOOP)
ZONE (X)
ECOSYSTEM LOOP #1
64 BALLASTS/INTERFACES MAX
ZONE (X)
ECOSYSTEM LOOP #2
64 BALLASTS/INTERFACES MAX
QS-A-CMP-D-0
GREEN GLANCE CLIENT PC
(CUSTOMER SUPPLIED PC MUST MEET
MINIMUM SPECIFICATION OF MODEL
QS-A-CMP-DB0-0)
LOCATION TBD
ECOSYSTEM LOOP #3
64 BALLASTS/INTERFACES MAX
USER-SUPPLIED
GREEN GLANCE DISPLAY
(MINIMUM RESOLUTION 1024 X 768)
120V/277V INPUT FEED
120V, 20A DEDICATED
NORMAL/EMERGENCY
INPUT FEED
ECOSYSTEM LOOP #4
64 BALLASTS/INTERFACES MAX
ECOSYSTEM LOOP #5
64 BALLASTS/INTERFACES MAX
ECOSYSTEM LOOP #6
64 BALLASTS/INTERFACES MAX
TYPICAL PALLADIOM KEYPAD
(SEE SPEC SUBMITTAL SHEET
FOR ADDITIONAL BUTTON CONFIGURATIONS,
STYLES, AND AVAILABLE FINISHES)
TYPICAL QS SEETOUCH KEYPAD
(SEE SPEC SUBMITTAL SHEET
FOR ADDITIONAL BUTTON CONFIGURATIONS,
STYLES, AND AVAILABLE FINISHES)
TYPICAL QSM
QTY AND LOCATION BASED ON QTY
AND LOCATION OF SENSORS
LINK: B
(CONFIGURABLE LINK)
ECOSYSTEM LOOP #7
64 BALLASTS/INTERFACES MAX
Q
ECOSYSTEM LOOP #8
64 BALLASTS/INTERFACES MAX
TO NEXT PANEL
E
TO NETWORK (QS-EO OR QS-LO)
E
QSWS2-5BRLN-WH
FUNCTION: 5-BUTTON SCENE
SELECT WITH RAISE/LOWER
(1 GANG US BACKBOX BY OTHERS)
LOCATION TBD
P
LINK: D
(PANEL LINK - 32 CIRCUIT SELECTORS MAX)
Q
120V/277V
120V/277V INPUT FEED
120V/277V
120V/277V
POWER FOR ESN
Q
QSM2-4W-C
QUANTUM SENSOR MODULE (QSM)
WITH (4) UNIVERSAL WIRED INPUTS
AND 434MHZ WIRELESS RECEIVER
60'[18.29m] RADIUS RF COVERAGE
(30'[9.14m] THROUGH WALLS)
4.04"[102.6mm] (DIA) X 1.17"[29.7mm] (D)
LOCATION TBD
LOCATION TBD
QP2-2P8CSE-120
QUANTUM LIGHT MANAGEMENT HUB
CONTAINING (8) ECOSYSTEM LOOPS
(2) QUANTUM PROCESSORS
(3) CONFIGURABLE LINKS, AND
(1) 5 PORT ETHERNET SWITCH
31.5"[800mm] (H) X 15.8"[401mm] (W) X 5.8"[147mm] (D)
OPTIONAL IPAD CONTROL
120V/277V
120V/277V INPUT FEED
Q
QWP-U-4W-WH
4-BUTTON
PALLADIOM WALLSTATION
(1 GANG US BACKBOX BY OTHERS)
120V/277V
120V/277V INPUT FEED
LUTRON
LINK: C
(QS LINK - 99 DEVICES MAX)
120/277V
INPUT FEED
ZONE (X)
ESN#
ESN#
#
#
To QS Devices
(Up to 14 PDUs)
To QS Devices
(Up to 30 PDUs)
Q
QSN-4S16-S
ENERGI SAVR NODE QS (ESN)
WITH (4) SWITCHED OUTPUTS AND
(1) QS COMMUNICATION LINK
13.25"[336,7mm] (H) X 9.25"[235mm] (W) X 3.16"[80,3mm] (D)
ZONE X
ESN#
#
120/277V
To QS Devices
(Up to 14 PDUs)
Q
QSN-2ECO-S
ENERGI SAVR NODE QS (ESN)
(2) ECOSYSTEM DIGITAL LINKS
AND (1) QS COMMUNICATION LINK
13.25"[336,7mm] (H) X 9.25"[235mm] (W) X 3.16"[80,3mm] (D)
QSN-4T16-S
ENERGI SAVR NODE QS (ESN)
WITH (4) SWITCHED OUTPUTS,
(4) 0-10V CHANNELS, AND
(1) QS COMMUNICATIONS LINK
DIMENSIONS:
13.25"[336,7mm] (H) X 9.25"[235mm] (W) X 3.16"[80,3mm] (D)
LOCATION TBD
LOCATION TBD
LOCATION TBD
TYPICAL PANELS AS REQUIRED
MODEL NUMBER AND QUANTITY TO BE DETERMINED BASED ON QUANTITY, CONTROL TYPE, AND TOTAL WATTAGE OF INDIVIDUAL ZONES.
LOCATION TBD
REFER TO LOAD
SCHEDULE SHEET FOR
FEEDER INFORMATION
CORPORATE WIRELESS NETWORK
(BY OTHERS)
E
REFER TO LOAD
SCHEDULE SHEET FOR
FEEDER INFORMATION
REFER TO LOAD
SCHEDULE SHEET FOR
FEEDER INFORMATION
QS-EO:
INSTALLING CONTRACTOR TO COORDINATE ALL NETWORK CONNECTIONS
AND COMMUNICATION REQUIREMENTS WITH IT CONTRACTOR AND OWNER
(LUTRON Q-CONTROL+ APPLICATION AVAILABLE FOR CLIENT DOWNLOAD)
QUANTUM LOCAL AREA NETWORK SHARED INTRANET.
THE QUANTUM INTER-PROCESSOR AND COMPUTER
(SERVER / DESKTOP OR LAPTOP) NETWORK MAY BE
CONNECTED THROUGH A SHARED INTRANET. THE
QUANTUM COMPUTER MAY OR MAY NOT BE SUPPLIED BY
LUTRON AND NODES ON LAN ARE NOT LIMITED TO LUTRON
QUANTUM PROCESSOR AND LUTRON QUANTUM
COMPUTER. ALL NETWORK EQUIPMENT INCLUDING
ROUTERS, SWITCHES, AND NETWORK CABLES ARE
SUPPLIED BY OTHERS AND MUST ADHERE TO LUTRON
SPECIFICATIONS. THE SHARED INTRANET MUST BE ABLE
TO PASS UDP MULTICAST TRAFFIC. ALL NETWORK
ARCHITECTURE AND SETUP MUST BE COORDINATED
THROUGH THE END USERS INFORMATION TECHNOLOGY
GROUP OR CONSULTANT AND MAY REQUIRE ADDITIONAL
STARTUP TIME AND EXPENSE.
APPLE IPAD (BY OTHERS)
W/ LUTRON Q-CONTROL + APPLICATION
(AVAILABLE FOR CLIENT DOWNLOAD
FOR FREE AT ITUNES)
AS REQUIRED
QTY & LOCATION OF SHADES TBD BY ARCHITECT AND/OR SHADE DEALER
REFER TO LOAD
SCHEDULE SHEET FOR
FEEDER INFORMATION
CONTROL FEED
REFER TO CONTROL
CKT. NOTE
120-240 V~
INPUT FEED
P
P
X
XP SOFTSWITCH PANEL
STANDARD DIMENSIONS:
59"[1499mm] (H) X 16"[406mm] (W) X 4"[102mm] (D)
LOCATION TBD
X
GP DIMMER PANEL
DIMENSIONS:
37"[940mm] (H) X 28"[711mm] (W) X 12"[305mm] (D)
LOCATION TBD
P
X
LP DIMMER PANEL
DIMENSIONS:
59"[1499mm] (H) X 15"[381mm] (W) X 4"[102mm] (D)
LOCATION TBD
TO QS DEVICES AND/OR
AS REQUIRED
QS SHADES ONLY
(MAXIMUM OF 1/OUTPUT)
(UP TO 10)
S
SIVOIA QS EDU
ELECTRONIC SHADE DRIVE UNIT
LOCATION TBD
P
TO ADDITIONAL QUANTUM PANELS
(MAX OF 32 PANELS / PANEL LINK)
Q
Q
TO QS LINK
SERVICES BELOW ARE TO BE INCLUDED AS PART OF THIS PROJECT'S SCOPE OF WORK
AND SPECIFIED INTO THE WRITTEN SPEC DOCUMENTS.
PRE-STARTUP SERVICES
LOCATION TBD
TO BACNET BUILDING MANAGEMENT
NETWORK (BY OTHERS)
CONTROL CIRCUIT NOTE:
SUPPLIES POWER FOR INTERNAL OPERATION.
LUTRON RECOMMENDS A DEDICATED 120V OR 277V, 20A 1 PHASE 2 WIRE FEED TO
POWER THE CONTROL CIRCUIT IN THE PANEL.
IF THE CONTROL CIRCUIT IS TAPPED FROM A CIRCUIT THAT POWERS A RELAY IN THE
PANEL, IT DRAWS A MAXIMUM OF 1.5A TOWARD THE TOTAL LOAD FOR THAT CIRCUIT.
REQUIRES MOBILE CONTROL AND PROGRAMMING
SOFTWARE LICENSE (QSW-MC-PS-A)
(1) LICENSE REQUIRED PER IPAD
TYPICAL PARTITION CONTROL
120-240 V~
INPUT FEED
TO DUPLEX
RECEPTACLE
BY OTHERS
TO ADDITIONAL
QS DEVICES
(MAX OF 99
DEVICES / QS
LINK)
UPS
UNINTERRUPTIBLE
POWER SUPPLY
BY LUTRON
QS-A-CMP-S/R
QUANTUM LIGHTING MANAGEMENT SYSTEM
DEDICATED SERVER. TOWER CASE OR RACK
MOUNT CAN BE PROVIDED. CUSTOMER
PROVIDED SERVER MUST MEET
SPECIFICATION DETAILED IN QS-A-CMP-BO-0
SPEC. SHEET. TO BE LOCATED IN
CUSTOMERS CORPORATE DATA CENTER.
INSTALLATION TO MEET SPECIFICATIONS AND
REQUIREMENTS IN QS-A-CMP-R-0 SPEC
SHEET.
CAT5 CABLE
Q
QSE-CI-DMX
DMX CONTROL INTERFACE
LOCATION TBD
14 # 18 AWG
MAXIMUM
Q
Q
Q
QSE-CI-NWK-E
ETHERNET TCP/IP
COMMUNICATION INTERFACE
LOCATION TBD
TO EQUIPMENT
BY OTHERS
QSE-IO
CONTACT-CLOSURE INTERFACE
LOCATION TBD
120V
INPUT FEED
24V
TO DMX
EQUIPMENT
BY OTHERS
TO PC OR DIGITAL
AV EQUIPMENT BY OTHERS
OR
TO PC OR DIGITAL
AV EQUIPMENT BY OTHERS
MAXIMUM OF 2 TELNET CONNECTIONS
TO EACH INTERFACE VIA ETHERNET
TO QS DEVICES AND/OR
QS SHADES ONLY
(UP TO 10)
COMMON
RS232 WIRING
E
Q
Q
QSPS-DH-1-75
QS LINK POWER SUPPLY
DIMENSIONS:
3.54" [90mm] (H) X 3.54" [90mm] (W)
X 2.40" [61mm] (D)
Q
QSPS-10PNL
SIVOIA QS SMART PANEL
18"[457mm] (H) X 10.86"[276mm] (W) X 4.16"[106mm] (D)
LOCATION TBD
ALTERNATIVE OCCUPANCY/VACANCY SENSORS FOR SPECIFIC APPLICATIONS
LOCATION TBD
LOCATION TBD
DMX INPUT SOFTWARE LICENSE REQUIRED
QSW-DMX-IN
REQUIRES QUANTUM VERSION 3.1 OR HIGHER
LOCATION TBD
(OPTION:WITH L-CRMK-WH
RECESS MOUNT KIT FOR
NON-METALLIC CEILINGS)
D
NT-DMXJ-IN-WH
DMX-512 INPUT RECEPTACLE
(1 GANG US BACKBOX BY OTHERS)
COM621
QSPS-J-1-50
QS J-BOX MOUNT
LINK POWER SUPPLY
4.3"[109mm] (H) X 3.38"[86mm] (W) X 1.4"[35.5mm] (D)
LOCATION TBD
4.35"[110mm] (H) X 1.8"[46mm] (W) X 1.35"[34mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
LRF2-OWLB-P-WH
434MHZ WIRELESS
WALL MOUNTED
OCCUPANCY/VACANCY SENSOR
4.35"[110mm] (H) X 1.8"[46mm] (W) X 1.35"[34mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
LRF2-DCRB-WH
434MHZ WIRELESS
DAYLIGHT SENSOR
1.6"[40,6mm] (DIA) X 0.7"[17,8mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
INPUT POWER (NORMAL-EMERGENCY)
LRF2-VCR2B-P-WH
434MHZ WIRELESS
VACANCY SENSOR
3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
LOCATION TBD
(OPTION:WITH L-CRMK-WH
RECESS MOUNT KIT FOR
NON-METALLIC CEILINGS)
2
GRX-CBL-346S
OR
GRX-PCBL-346S
DATA (TERMINALS 3&4):
E
POWER (TERMINALS 1&2):
500ft (153 m) TO
2,000ft (600 m)**
GRX-CBL-46L
OR
GRX-PCBL-46L
DATA (TERMINALS 3&4):
3 #12AWG (4 mm )
2-WAY RF COMMUNICATION
0-10V SIGNAL: 2 #18AWG (1.0 mm2)
2 #18AWG (1.0 mm2)
ECOSYSTEM BUS/LOOP:
LUTRON CABLE C-CBL-216-GR-1
(2 #16 CONDUCTOR NON-PLENUM) OR
C-PCBL-216-CL-1 (2 #16 CONDUCTOR
PLENUM RATED). OTHERWISE USE 2 #16
AWG (1.5 mm2) BY OTHERS.
3 #18AWG (1.0 mm2)
LUTRON SENSOR CABLE C-CBL-522S
OTHERWISE USE 3 #22 AWG (1.0 mm2)
LUTRON SENSOR CABLE C-CBL-522S
OTHERWISE USE 4 #22 AWG (1.0 mm2)
CAT5E OR BETTER CABLE FOR LUTRON
NETWORK
TERMINATED
WITH
RJ45
CONNECTORS (TO BE PROVIDED BY
OTHERS). 328 ft (100 m) MAXIMUM RUN.
D
DMX CONTROL
DALI LINK
*ALTERNATE DATA-ONLY CABLE: USE APPROVED
TWISTED/SHIELDED) FROM BELDEN (MODEL # 9461).
DATA
LINK
CABLE
(22
AWG
[0.5
mm ]
P PANEL LINK (SEE WIRE DESCRIPTION BELOW)
LUTRON CABLE GRX-CBL-46L (5 CONDUCTOR NON-PLENUM) OR GRX-PCBL-46L (5 CONDUCTOR
PLENUM RATED). OTHERWISE USE 2 #12 AWG (4
1 BELDEN #9461 AND BETWEEN PANELS
F
TO ADDITIONAL ENERGI SAVR
NODES & SENSOR MODULES
LOCATION TBD
LINK: A
DMX INPUT LINK
LINK: B
(CONFIGURABLE LINK)
LINK: C
QS LINK
TO NETWORK (QS-EO OR QS-LO)
LINK: D
PANEL LINK
E
TO CONFIGURABLE LINK AS REQUIRED
TO QS LINK AS REQUIRED
QSM RULES
4 WIRED DEVICES MAX (OF ANY COMBINATION)
10 WIRELESS OCCUPANCY SENSORS
10 WIRELESS DAYLIGHT SENSORS
10 WIRELESS PICOS
QSM2-4W-C
QUANTUM SENSOR MODULE (QSM)
WITH (4) UNIVERSAL WIRED INPUTS
AND 434MHZ WIRELESS RECEIVER
60'[18.29m] RADIUS RF COVERAGE
(30'[9.14m] THROUGH WALLS)
4.04"[102.6mm] (DIA) X 1.17"[29.7mm] (D)
LOCATION TBD
SHADES + CONTROLS
Q
TO ADDITIONAL ENERGI SAVR
NODES & SENSOR MODULES
QP2-2P0CSE-120
QUANTUM LIGHT MANAGEMENT HUB
CONTAINING (0) ECOSYSTEM LOOPS
(2) QUANTUM PROCESSORS
(4) CONFIGURABLE LINKS, AND
(1) 5 PORT ETHERNET SWITCH
31.5"[800mm] (H) X 15.8"[401mm] (W) X 5.8"[147mm] (D)
LOCATION TBD
12 AWG (4 mm )
QSH-CBL-L-500
QSH-CBLP-L-500
16 AWG (1.5 mm )
QSH-CBL-M-500
QSH-CBLP-M-500
18 AWG (1.0 mm )
GRX-CBL-346S-500
NONE
UP TO 50
POWER DRAW UNITS
1,250 ft (375 m)
500 ft (150 m)
250 ft (75 m)
NONE
UP TO 25
POWER DRAW UNITS
2,000 ft (600 m)
1,000 ft (300 m)
600 ft (175 m)
FIBER OPTIC CABLE FOR LUTRON NETWORK TERMINATED WITH APPROPRIATE FIBER OPTIC
CONNECTORS (TO BE PROVIDED BY OTHERS). NOTE: REQUIRES DEDICATED FIBER OPTIC LINK
(SINGLE-MODE OR MULTI-MODE).
QS INDIVIDUAL POWER SUPPLY (QSPS-PX-1-50 OR QSPS-J-1-50) QS WIRING GUIDE
MAXIMUM DEVICES PER ONE OUTPUT
SHADES + CONTROLS
TO PANEL LINK AS REQUIRED
NONE
SATISFIES DOCUMENTATION REQUIRED FOR SYSTEM
PERFORMANCE-VERIFICATION, INCLUDING LEED.
ONSITE SCENE &
LEVEL TUNING
(LSC-AF-VISIT)
LUTRON FIELD SERVICE ONSITE VISIT WITH THE LIGHTING
DESIGNER TO VERIFY PERFORMANCE AND MAKE REAL-TIME
ADJUSTMENTS.
CUSTOMER SITE
SOLUTION TRAINING
(LSC-TRAINING)
ADDITIONAL TRAINING WITH FACILITY STAFF ON SYSTEM
FEATURES AND FUNCTIONALITY.
SOFTWARE
MAINTENANCE
AGREEMENT
(LSC-SMA)
LUTRON TO PROVIDE COMPATIBILITY TESTING FOR SERVER AND
BROWSER PATCH UPDATES AND UNLIMITED NO-CHARGE
QUANTUM
LICENSE UPGRADES FOR THE DURATION OF THE TERM THE
SOFTWARE MAINTENANCE AGREEMENT IS IN EFFECT.
SILVER ENHANCED
WARRANTY (LSC-E8S)
FIRST 2 YEARS: 100% PARTS/DIAGNOSTIC LABOR COVERAGE AS
PROVIDED UNDER THE COMMERCIAL SYSTEMS LIMITED
WARRANTY, WITH FIRST AVAILABLE RESPONSE TIME. YEARS 3-8:
PRO-RATED PARTS ONLY COVERAGE.
12 AWG (4 mm )
QSH-CBL-L-500
QSH-CBLP-L-500
16 AWG (1.5 mm )
QSH-CBL-M-500
QSH-CBLP-M-500
2,000 ft (600 m)
1,500 ft (450 m)
CONCEPT DRAWING NOTES:
CONTROL SYSTEM DRAWING IS PROVIDED FOR CONCEPTUAL PURPOSES ONLY AND IS NOT
INTENDED FOR
EXACT EQUIPMENT REQUIREMENTS, INCLUDING LOCATIONS AND
QUANTITIES, SHOULD BE VERIFIED IN ACCORDANCE WITH THE MOST UP-TO-DATE
LIGHTING/ELECTRICAL REFLECTED CEILING PLANS, LIGHTING FIXTURE SCHEDULES, PANEL
ACCORDANCE
WITH
SCHEDULES/DETAILS.
S
ARCHITECTURAL
PLANS,
SPECIFICATIONS
AND
WINDOW
QS SMART PANEL POWER SUPPLY (QSPS-PX-10-60) SHADE WIRING GUIDE
MAXIMUM DEVICES PER ONE OUTPUT
SHADES + CONTROLS
1 SIVOIA QS SHADE OR
DRAPERY
UP TO 1
POWER
DRAW UNIT
MAXIMUM DISTANCE PER ONE OUTPUT BASED ON WIRE GUAGE
12 AWG (4 mm )
QSH-CBL-L-500
QSH-CBLP-L-500
16 AWG (1.5 mm )
QSH-CBL-M-500
QSH-CBLP-M-500
18 AWG (1.0 mm )
GRX-CBL-346S-500
500 ft (150 m)
200 ft (60 m)
125 ft (35 m)
200 ft (60 m)
75 ft (20 m)
50 ft (15 m)
QS INDIVIDUAL POWER SUPPLY (QSPS-PX-1-50 OR QSPS-J-1-50) SHADE WIRING GUIDE
MAXIMUM DEVICES PER ONE OUTPUT
SHADES + CONTROLS
UP TO 1
POWER
DRAW UNIT
PANELS ARE DAISY-CHAINED ON ONE OF THE CONFIGURABLE LINKS PER LUTRON'S DRAWING,
HOWEVER THEY DO NOT HAVE TO BE IN THE ORDER SHOWN.
DO NOT HOME-RUN OR T-TAP THIS WIRING LINK. ALL CIRCUITS NEED TO BE LANDED IN THESE
PANELS PER LUTRON'S PANEL SCHEDULES.
THE MAXIMUM WIRE LENGTH OF A PANEL LINK IS 2,000 ft (600 m). A MX-RPTR IS USED TO EXTEND
THE LENGTH OF A LINK ANOTHER 2,000 ft (600 m). A MAXIMUM OF (3) MX-RPTR'S MAY BE USED
PER LINK FOR MAXIMUM LENGTH OF 8,000 ft (2,430 m) PER LINK.
IF A PANEL IS MOVED TO ANOTHER LINK, OR THE LOADS ARE NOT WIRED AS SHOWN IN LUTRON
PANEL SCHEDULES, LUTRON MUST BE NOTIFIED. THIS INFORMATION IS IMPORTANT FOR
PROGRAMMING THE SYSTEM.
UP TO 32 CIRCUIT SELECTORS PER LINK
UP TO 512 SWITCH LEGS OR ZONES PER LINK
LT-1 LINK TERMINATORS NEEDED ON EACH END OF THE LINK
ECOSYSTEM BUS/LOOP RULES
18 AWG (1.0 mm )
GRX-CBL-346S-500
MAXIMUM DISTANCE PER ONE OUTPUT BASED ON WIRE GUAGE
12 AWG (4 mm )
QSH-CBL-L-500
QSH-CBLP-L-500
16 AWG (1.5 mm )
QSH-CBL-M-500
QSH-CBLP-M-500
18 AWG (1.0 mm )
GRX-CBL-346S-500
250 ft (75 m)
100 ft (30 m)
50 ft (15 m)
GOLD ENHANCED
WARRANTY
(LSC-E8G)
PLATINUM ENHANCED
WARRANTY (LSC-E8P)
FIRST 2 YEARS: 100% PARTS/DIAGNOSTIC LABOR COVERAGE AS
PROVIDED UNDER THE COMMERCIAL SYSTEMS LIMITED
WARRANTY; 72-HOUR ONSITE/REMOTE RESPONSE TIME; ONE
ANNUAL PREVENTIVE MAINTENANCE VISIT. YEARS 3-8:
PRO-RATED PARTS ONLY COVERAGE.
FIRST 2 YEARS: 100% PARTS/DIAGNOSTIC LABOR COVERAGE AS
PROVIDED UNDER THE COMMERCIAL SYSTEMS LIMITED
WARRANTY; 24-HR ONSITE/REMOTE RESPONSE TIME; ONE
ANNUAL PREVENTIVE MAINTENANCE VISIT. YEARS 3-8:
PRO-RATED PARTS ONLY COVERAGE.
PLEASE GO TO WWW.LUTRON.COM/SERVICES FOR FURTHER INFORMATION.
QUANTUM TYPICAL ONELINE
THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION:
MAXIMUM DISTANCE PER ONE OUTPUT BASED ON WIRE GUAGE
UP TO 8
POWER DRAW UNITS
1 SIVOIA QS SHADE
OR DRAPERY
SYSTEM
PERFORMANCE
VERIFICATION
DOCUMENTATION
(LSC-SPV-DOC)
PANEL(S) BASED ON _______________________ DATED XX.XX.XX FROM ____________________
(CONNECT WIRES 1, 2, 3 AND 4. DO NOT CONNECT WIRE # 5)
MAXIMUM DISTANCE PER ONE OUTPUT BASED ON WIRE GUAGE
THIS IS A TOPOLOGY-FREE LINK (T-TAP, HOME-RUN, ETC. IS OK); REFER TO TABLE BELOW FOR
WIRE RUN LIMITS.
IF WIRED DIFFERENTLY THAN WHAT IS SHOWN, POWER DRAW UNIT REQUIREMENTS NEED TO
BE CONFIRMED; SEE POWER DRAW UNITS (PDUs) SPECIFICATION SHEET INCLUDED IN THIS
SUBMITTAL.
MAXIMUM OF 512 OUTPUTS (BALLASTS, SHADES, CONTACT CLOSURES, ETC).
MAXIMUM OF 100 OCCUPANCY SENSORS, 100 DAYLIGHT SENSORS/RADIO SHADOW SENSORS
AND 100 KEYPADS.
MAXIMUM OF 100 QS DEVICES (SUCH AS A GRAFIK
QS,
QS KEYPAD, SMART
PANEL POWER SUPPLY [QSPS-Px-10-60], ESN, OR
QS SHADE / DRAPERY DRIVE UNIT).
QUANTUM PROCESSOR COUNTS AS 1 DEVICE PER LINK.
MAXIMUM OF 100 ZONES - SUCH AS A SIVOIA QS SHADE / DRAPERY DRIVE UNIT, OR A LIGHTING
ZONE ON A GRAFIK EYE QS (DOES NOT APPLY TO QUANTUM SYSTEMS).
THE 10 OUTPUTS ON A QSPS-Px-10-60 CANNOT EXCEED A COMBINED LENGTH OF 2,000 ft (600 m).
PANEL LINK RULES
P PANEL LINK (SEE WIRE DESCRIPTION BELOW)
LUTRON
LOCATION TBD
Q
THE FOLLOWING LINK RULES MUST BE OBSERVED FOR PROPER OPERATION:
2 #12AWG (4 mm )
POWER (TERMINALS 1&2):
LESS THAN 500ft
(153 m)
1-WAY RF COMMUNICATION
2
AVAILABLE FROM LUTRON IN ONE
CABLE:
WIRE GUAGE
MAXIMUM DEVICES PER ONE OUTPUT
Q
NT-DMXJ-IN-WH
DMX-512 INPUT RECEPTACLE
(1 GANG US BACKBOX BY OTHERS)
GRX-IRPS-WH
INFRARED PARTITION
SWITCH
ONSITE STARTUP TO TAKE PLACE OUTSIDE OF NORMAL LUTRON
BUSINESS HOURS (8:00 AM-5:00 PM, MON-FRI)
ONSITE PERFORMANCE
LUTRON FIELD SERVICE ONSITE WALKTHROUGH TO
VERIFICATION
DEMONSTRATE THE LUTRON SYSTEM FUNCTIONALITY TO A
WALKTHROUGH
FACILITY REPRESENTATIVE (e.g. COMMISSIONING AGENT OR LEED
(LSC-WALK)
CONSULTANT).
QS LINK RULES
INPUT POWER (NORMAL)
Q QS CONTROL LINK (SEE WIRE DESCRIPTION BELOW)
**TOTAL LENGTH OF THE QS LINK MUST NOT EXCEED 2,000 ft (600 m).
120V, 20A
DEDICATED NORMAL/EMERGENCY
INPUT FEED
NT-DMXJ-IN-WH
DMX-512 INPUT RECEPTACLE
(1 GANG US BACKBOX BY OTHERS)
TRANSMITTER
QSE-IO
CONTACT-CLOSURE INTERFACE
LOCATION TBD
QS SMART PANEL POWER SUPPLY (QSPS-PX-10-60) QS WIRING GUIDE
LOCATION TBD
RECEIVER
AFTER HOURS
STARTUP (LSC-AH-SU)
WIRING NOTES:
Q QS CONTROL LINK (SEE WIRE DESCRIPTION BELOW)
TOTAL CONTROL
LINK LENGTH
LRF2-OKLB-P-WH
434MHZ WIRELESS
CORNER MOUNTED
OCCUPANCY/VACANCY SENSOR
LUTRON TO PROVIDE FINAL DESIGN LAYOUT AND FINE-TUNING
CALIBRATION OF OCCUPANCY AND DAYLIGHT SENSORS.
MAINTENANCE & SUPPORT SERVICES
(CONNECT WIRES 1, 3 AND 4. DO NOT CONNECT WIRE # 2)
LRF2-OCR2B-P-WH
434MHZ WIRELESS
OCCUPANCY/VACANCY SENSOR
3.57"[90,7mm] (DIA) X 1.13"[28,7mm] (D)
MAX 10 PER QSM
*DEVICE IS SURFACE-MOUNTED AND
BATTERY POWERED, DOES NOT
REQUIRE POWER FEED
SENSOR LAYOUT &
TUNING (LSC-SENS-LT)
LUTRON FIELD SERVICE TO REVISIT THE FACILITY TO OPTIMIZE
SYSTEM OPTIMIZATION
AND ENSURE SUSTAINABLE PERFORMANCE AND MAXIMIZE
(LSC-SYSOPT)
ENERGY SAVINGS BY ADJUSTING SETTINGS AND PROGRAMMING.
RECOMMEND SCHEDULING 6-12 MONTHS AFTER STARTUP.
QS WIRING AS REQUIRED BY CONTROL LINK LENGTH
(REFER TO QS SMART PANEL POWER SUPPLY WIRING GUIDE FOR SHADE WIRING NOTES):
NT-DMXJ-IN-WH
DMX-512 INPUT RECEPTACLE
(1 GANG US BACKBOX BY OTHERS)
SINGLE GANG
BACKBOX
Q
WIRING LEGEND:
NT-DMXJ-IN-WH
DMX-512 INPUT RECEPTACLE
(1 GANG US BACKBOX BY OTHERS)
SINGLE GANG
BACKBOX
GRX-12VDC
POWER SUPPLY
(PLUGS INTO DUPLEX
RECEPTACLE)
LUT-8X8-ENC
LUTRON 8X8 ENCLOSURE
DIMENSIONS:
8" [203mm] (H) X 8" [203mm] (W)
X 4" [102mm] (D)
LOCATION TBD
AS REQUIRED
FOR DMX LIGHTING CONTROL
INTEGRATION CONSULTATION FOR 3RD PARTY EQUIPMENT (e.g.
BUILDING AUTOMATION SYSTEMS, ENERGY DASHBOARDS,
NON-LUTRON SHADES, IT NETWORK).
STARTUP SERVICES
TYPICAL POWER SUPPLIES AS REQUIRED
D
SYSTEM & NETWORK
INTEGRATION
CONSULTATION
(LSC-INT-VISIT)
(THESE SERVICES ARE ADDITIONAL TO YOUR SPECIFIED STARTUP BASED ON
YOUR REQUIREMENTS)
TYPICAL GATEWAYS AS REQUIRED
DEDICATED
ETHERNET ENVIRONMENT
SERVICE DESCRIPTION
TO QS LINK
QSPS-10PNL
SIVOIA QS SMART PANEL
18"[457mm] (H) X 10.86"[276mm] (W)
X 4.16"[106mm] (D)
X
CCP DIMMER PANEL
DIMENSIONS:
59"[1499mm] (H) X 15"[381mm] (W) X 4"[102mm] (D)
LOCATION TBD
SERVICE TITLE
(LINE ITEM)
LED DIMMING REQUIRES AN EXACT MATCH BETWEEN THE LED ARRAY, DRIVER AND
LUTRON CANNOT GUARANTEE COMPATIBILITY OR PERFORMANCE WITHOUT TESTING THIS
COMBINATION.
TO CONFIRM WHAT PRODUCTS LUTRON HAS AVAILABLE OR WHAT INTERFACES MAY BE
REQUIRED, CALL 1-877-DIM-LED8 OR CHECK LUTRON'S PRODUCT COMPATIBILITY MATRIX ON-LINE
THE FOLLOWING LOOP RULES MUST BE OBSERVED FOR PROPER OPERATION:
THIS IS TOPOLOGY-FREE AND POLARITY FREE WIRING (T-TAP, HOME-RUN, ETC. IS OK).
KEEP ALL THE BALLASTS/MODULES IN ONE ROOM ON THE SAME LOOP WHENEVER POSSIBLE.
WIRE DAYLIGHT SENSORS, OCCUPANCY SENSORS AND PERSONAL CONTROLS TO THE
CLOSEST ECOSYSTEM BALLAST/SENSOR MODULE IN THE SAME ROOM.
ECOSYSTEM LOOPS ARE SHOWN ON THE LIGHTING PLANS. IF THERE IS A DISCREPANCY, AND
ROOMS ARE WIRED TO A DIFFERENT LOOP THAN THE ONE SHOWN, LUTRON NEEDS TO BE
NOTIFIED. THIS INFORMATION IS IMPORATANT FOR PROGRAMMING THE SYSTEM.
UP TO 65 BALLASTS/MODULES PER ECOSYSTEM LOOP
UP TO 64 IR CONTROLS PER LOOP
UP TO 16 DAYLIGHT SENSORS PER LOOP
UP TO 32 OCCUPANT SENSORS PER LOOP
QUANTUM NETWORK
TO REQUEST THE TESTING OF AN LED PRODUCT BY LUTRON MANUFACTURERS CAN FILL OUT AN
LED EVALUATION REQUEST FORM ON-LINE AT WWW.LUTRON.COM/LED OR CONTACT
WHEN A LIGHTING MANAGEMENT NETWORK (LMN) IS REQUIRED TO ENABLE COMMUNICATIONS
BETWEEN INDIVIDUAL LIGHT MANAGEMENT HUBS (LMH) AND BETWEEN LMH AND THE SYSTEM
SERVER/DESKTOP/LAPTOP
THE LMN REQUIRES A DEDICATED LAN OR
IT IS THE
RESPONSIBILITY OF THE NETWORK PROVIDER TO ENSURE THE RELIABILITY AND SECURITY OF THE
LMN.
LUTRON CAN GUARANTEE COMPATIBILITY AND PERFORMANCE OF LUTRON HI-LUME A-SERIES LED
DRIVERS USED WITH APPROPRIATE LUTRON
THE HI-LUME A-SERIES LED DRIVER CAN
BE USED ON PRODUCTS UNDER 40 WATTS WITH SUITABLE MOUNTING
PLEASE
REFER TO THE SPECIFICATION SUBMITTAL SHEET FOR FURTHER INFORMATION.
CAT5E OR BETTER ETHERNET CABLE TO BE RUN FOR DEDICATED LMN TERMINATED WITH RJ45
CONNECTORS (PROVIDED BY
THE NUMBER OF ETHERNET HOPS/SEGMENTS BETWEEN THE
SERVER/DESKTOP/LAPTOP (Q-MANAGER) AND ANY LMN NODE SHALL NOT EXCEED
TOTAL LENGTH
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING 0-10V CONTROL, PERFORMANCE AND
COMPATIBILITY CANNOT BE GUARANTEED BY
PRODUCTS FOLLOWING THE IEC
STANDARD 60929 ARE MORE LIKELY TO PROVIDE ACCEPTABLE PERFORMANCE
DETERMINATION OF RESULT ACCEPTABILITY IS UP TO THE USER'S DISCRETION.
IF USING UNTESTED, NON-LUTRON LED DRIVERS REQUIRING PHASE CONTROL, PERFORMANCE
AND COMPATIBILITY CANNOT BE GUARANTEED BY
A-SERIES OR ELV PRODUCTS
PROVIDING HIGH END AND LOW END TRIM ADJUSTMENTS ARE MORE LIKELY TO PROVIDE
ACCEPTABLE PERFORMANCE RESULTS. DETERMINATION OF RESULT ACCEPTABILITY IS UP TO
THE USER'S DISCRETION.
CONCEPT DRAWING
NOT FOR CONSTRUCTION
Project Number:
Drawn By:
#######
XXX
Drawing Revision:
Drawing Date:
Sheet:
0
OCTOBER 2016
1 of 1
IF LONGER RUNS ARE REQUIRED, MULTI-MODE FIBER OPTIC CABLE CAN BE USED INSTEAD WITH
APPROPRIATE FIBER OPTIC CONNECTORS (PROVIDED BY
CONSULT WITH NETWORK
PROVIDER FOR STANDARD ETHERNET AND FIBER OPTIC WIRING RULES FOR DISTANCE AND
SEPARATION AS WELL AS FOR PLACEMENT OF SWITCHES, ROUTERS, HUBS, ETC.
FOR MORE INFORMATION REGARDING NETWORK EQUIPMENT REQUIREMENTS AND NETWORK
CONFIGURATION, PLEASE REFER TO THE QUANTUM LIGHTING MANAGEMENT NETWORK
SPECIFICATION SHEET OR CONTACT LUTRON.
Lutron Electronics Co., Inc.
7200 Suter Road | Coopersburg, PA 18036 | USA
(610) 282-3800 | fax: (610) 282-1146