ELPRO 105U-G is a wireless gateway designed for industrial applications, offering reliable data transmission and remote monitoring capabilities. It supports various communication protocols, including Ethernet, serial, and radio, enabling seamless integration with existing systems. The device features multiple digital input/output channels for connecting sensors, actuators, and other devices, allowing for automation and control functions. Additionally, it supports a backup battery for uninterrupted operation during power outages.
advertisement
Instruction Leaflet IL032009EN
Effective December 2015
105U-G wireless gateway installation guide
Figure 1. Antenna Installation
Version 2.0
Antenna* 1 Wavelength
(minimum)
Wavelengths:
360 MHz = 32.7" (83 cm)
512 MHz = 22.8" (58 cm)
869 MHz = 13.4" (34 cm)
Stress
Relief
Loop
Weatherproof
Connections
(recommended:
3M ™ 23 selfbonding tape)
CAUTION
For continued protection against risk of fire, replace the module fuse only with the same type and rating.
Statutory requirements
EC: Unlicensed operation limits the radio power. High gain aerials may only be used to compensate for cable losses.
Antenna installation
Use Figure 1 as a guide for installing an antenna and attaching it to the module.
105U-G
ELPRO
Wireless Gateway
105U-G
Ethernet
RX
Serial
TX
RX
Radio
TX
ACT OK
Surge Arrestor
(optional)
GND at least 11 AWG (4 mm 2 )
Provide good ground connection to mast, module, and surge arrestor.
If ground conditions are poor, use more than one stake.
Coaxial Cable
Mast
Earth Stake
Earth Conductor at least 5 AWG
(16 mm 2 )
* For maximum range, install above local obstructions.
Instruction Leaflet IL032009EN
Effective December 2015
Version 2.0
Installation
Choose a power supply option:
•
•
•
•
12–24 Vac, 1.5A CSA certified
Class 2
15–30 Vdc, 1.5A CSA certified
Class 2
11–15 Vdc, 1.5A
Solar panel with battery
Figure 2. Wiring Diagram
After choosing a power supply option, wire the module as shown in Figure 2.
N otee: All I/O must be SELV.
DIO channels can be wired as inputs or outputs.
When the wiring is completed, connect the module to a computer (PC) and configure it using the configuration software. For details, refer to the user manual.
Before operating the module, read the sections on operation and configuration in the user manual to take advantage of all product features.
WARNING
EXPLOSION HAZARD
Do not disconnect while circuit is live unless area is known to be non-hazardous.
105U-G wireless gateway installation guide
EATON_105U-G Install Guide
Host Protocol
Connection
ELPRO
Wireless Gateway
105U-G-ET1
Ethernet
RX
Serial
TX
RX
TX
Radio
ACT OK
– +
DC Supply
9–30 Vdc, 16 Vac
– +
AC Supply 12–24 Vac
Do not earth
SUP1 or SUP2 connection.
To Earth
Connection
2A
Digital Input
Voltage-Free
Contact or
Transistor
Device
To Earth
Connection
+ –
Digital Output
Max. 30 Vdc, 500 mA
DC Relay Supply
– +
12V Backup Battery
(optional; up to 100 Ah)
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s wireless business www.eaton.com/wireless
© 2014 Eaton
All Rights Reserved
Printed in USA
Publication No. IL032009EN
December 2015
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project