- No category
advertisement
▼
Scroll to page 2
of 47
Installation Installation instructions for basic unit 9 9 Installation 9.1 Installation instructions for basic unit Comply with the safety notes during installation. Installation notes for size 6 The MOVIDRIVE® units of size 6 (0900 ... 1320) are equipped with a factory mounted lifting ring [1]. If possible, use crane and lifting ring [1] to install the unit. If a crane is not available, you can push a carrying bar [2] through the rear panel to facilitate installation (included in the delivery scope of size 6). Secure the carrying bar [2] against axial displacement by using the split pin [3]. [3] [2] [1] [3] 54406AXX Figure 153: Installation of MOVIDRIVE® size 6 with factory mounted lifting ring and carrying bar [1] Factory mounted lifting ring [2] Carrying bar (included in the delivery of size 6) [3] Split pin (included in the delivery of size 6) Tightening torques • Only use original connection elements. Note the permitted tightening torques of MOVIDRIVE® power terminals. – – – – – – • 328 size 0 and 1 Sizes 2S and 2 Size 2 Size 3 Sizes 4 and 5 Size 6 → → → → → → 0.6 Nm 1.5 Nm 1.5 Nm 3.5 Nm 14 Nm 20 Nm The permitted tightening torque of the signal terminals is 0.6 Nm. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Installation instructions for basic unit Minimum clearance and Mounting position • 9 Leave 100 mm clearance at the top and bottom for optimum cooling. Make sure air circulation in the clearance is not impaired by cables or other installation material. With sizes 4, 5 and 6, do not install any components which are sensitive to high temperatures within 300 mm of the top of the unit. 1 2 • Ensure an unobstructed cooling air supply and that air heated by other units cannot be drawn in or reused. 3 • There is no need for clearance at the sides. You can line up the units directly next to one another. 4 Only install the units vertically. Do not install them horizontally, tilted or upside down (→ following figure, applies to all sizes). 5 • 6 100 mm 7 8 9 10 11 100 mm 12 51463BXX 13 Figure 154: Minimum clearance and mounting position of the units 14 Separate cable ducts • Input fuses and earth-leakage circuit breakers • Install the input fuses at the beginning of the supply system lead after the supply bus junction (→ Wiring diagram for basic unit, power section and brake). 16 • Earth leakage circuit breaker as sole protection device: Only use earth leakage circuit breakers type B according to EN 50178. 17 Supply system and brake contactors Route power cables and electronics cables in separate cable ducts. 15 • Only use contactors in utilization category AC-3 (IEC 158-1) as supply system and brake contactors. 18 • Only use the supply system contactor K11 (→ Sec. "Wiring diagram for basic unit") to switch the inverter on and off. Do not use it for jog mode. Use the commands "Enable/Rapid stop," "CW/Stop" or "CCW/Stop" for jog mode. 19 Observe a minimum switch-off time of 10 s for the supply system contactor K11. 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 329 Installation Installation instructions for basic unit 9 PE supply system connection (→ EN 50178) Earth-leakage currents ≥ 3.5 mA may occur during normal operation. To meet the requirements of EN 50178 note the following: • With a power supply line < 10 mm2 (AWG 8): Route a second PE conductor with the cross section of the power supply line in parallel to the protective earth via separate terminals or use a copper protective earth conductor with a cross section of 10 mm2 (AWG 8). • With a power supply line ≥ 10 mm2 (AWG 8): Route a copper protective earth conductor with the cross section of the power supply line. IT systems • SEW-EURODRIVE recommends using earth-leakage monitors with pulse-code measurement for power supply systems with a non-grounded star point (IT systems). Use of such devices prevents the earth-leakage monitor mis-tripping due to the earth capacitance of the inverter. Cross sections • Supply system lead: Cross section according to rated input current Imains at rated load. • Motor cable: Cross section according to rated output current Irated. • Electronics cables of basic unit (terminals X10, X11, X12, X13, X16): – One core per terminal 0.20 ... 2.5 mm2 (AWG 24 ... 12) – Two cores per terminal 0.25 ... 1 mm2 (AWG 22 ... 17) • Electronics cables of terminal X17 and DIO11B terminal expansion board (terminals X20, X21, X22): – One core per terminal 0.08 ... 1.5 mm2 (AWG 28 ... 16) – Two cores per terminal 0.25 ... 1 mm2 (AWG 22 ... 17) Unit output • Only connect ohmic/inductive loads (motors). Never connect capacitive loads! 51412AXX Figure 155: Only connect ohmic/inductive loads; do not connect capacitive loads Connecting braking resistors 330 • Use two closely twisted cables or a 2-core shielded power cable. Cross section according to the rated output current of the inverter. • Protect the braking resistor (except for BW90-P52B) using a bimetallic relay (→ wiring diagram for basic unit, power section and brake). Set the trip current according to the technical data of the braking resistor. • For braking resistors of the BW...-T series, the integrated temperature switch can be connected using a 2-core shielded cable as an alternative to a bimetallic relay. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Installation instructions for basic unit • Operating braking resistors 9 Flat-type braking resistors have internal thermal overload protection (fuse which cannot be replaced). Install the flat-type braking resistors together with the appropriate touch guard. 1 • The connection leads to the braking resistors carry a high voltage (ca. DC 900 V) during rated operation. 3 • The surfaces of the braking resistors get very hot when the braking resistors are loaded with Prated. Select a suitable installation position. Braking resistors are usually mounted on the switch cabinet roof. 2 4 5 Binary inputs / binary outputs EMC compliant installation • The binary inputs are electrically isolated by optocouplers. • The binary outputs are short-circuit proof, although they are not protected against external voltage (exception: relay output DOØ1). External voltage can cause irreparable damage to the binary outputs. • All cables except for the power supply line must be shielded. As an alternative to the shielding, the option HD.. (output choke) can be used for the motor cable to achieve the emitted interference limit values. . • When using shielded motor cables, e.g. prefabricated motor cables from SEW-EURODRIVE, you must keep the unshielded conductors between the shield and connection terminal of the inverter as short as possible. • Connect the shield by the shortest possible route and make sure it is earthed over a wide area at both ends. You can ground one end of the shield via a suppression capacitor (220 nF / 50 V) to avoid ground loops. If using double-shielded cables, ground the outer shield on the inverter end and the inner shield on the other end. 6 7 8 9 10 11 12 13 14 15 16 17 18 00755BXX Figure 156: Correct shield connection using metal clamp (shield clamp) or metal cable gland • You can also use earthed sheet-metal ducts or metal pipes to shield the cables. Route the power and control cables separately. • Provide high frequency compatible grounding for the inverter and all additional units (wide area metal-on-metal contact between the unit housing and ground, e.g. unpainted control cabinet mounting panel). 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 331 Installation Installation instructions for basic unit 9 NF.. line filter • This is a product with restricted availability in accordance with IEC 61800-3. It may cause interference in residential environments. In such cases, the operator may need to implement appropriate measures. • For detailed information on EMC compliant installation, refer to the publication "Electromagnetic Compatibility in Drive Engineering" from SEW-EURODRIVE. • The NF.. line filter option can be used to maintain the class B limit for MOVIDRIVE® MDX60B/61B units size 0 to 5. • Install the line filter close to the inverter but outside the minimum clearance for cooling. • Keep the length of the cable between the line filter and inverter to an absolute minimum, and never more than 400 mm. Unshielded, twisted cables are sufficient. Also use unshielded cables as the supply system lead. • No EMC limits are specified for interference emission in voltage supply systems without earthed star point (IT systems). The effectiveness of input filters in IT systems is severely limited. • SEW-EURODRIVE recommends one of the following EMC measures on the motor side to maintain class A and B limits: – Shielded motor cable – HD... output choke option – HF.. output filter option (in operating modes VFC and U/f) HD... output choke • Install the output choke close to the inverter but outside the minimum clearance for cooling. • Route all three phases together through the output choke. Do not route the PE conductor through the output choke! 4 5 6 ® MOVIDRIVE n=5 HD... PE U V W (1) 05003AXX Figure 157: Connecting HD... output chokes (1) = Motor cable 332 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Removing / installing the keypad 9.2 9 Removing / installing the keypad Removing the keypad 1 Proceed in this order: 2 1. 3 2. 3. 4 STOP RUN DEL 5 OK STOP RUN DEL OK 6 7 8 52205AXX Figure 158: Removing the keypad 9 1. Unplug the connection cable from the Xterminal. 2. Carefully push the keypad downward until it comes off the upper fixture on the front cover. 10 3. Remove the keypad forward (not to the side!). 11 Installing the keypad 12 Proceed in this order: 13 3. 2. 14 15 STOP RUN DEL OK 1. 16 STOP RUN DEL OK 17 18 19 51479AXX Figure 159: Installing the keypad 1. Place the keypad with the bottom side onto the lower fixture of the front cover. 2. Push the keypad into the upper fixture of the front cover. 3. Plug the connecting cable into the Xterminal. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 20 21 22 333 Installation Removing / installing the front cover 9 9.3 Removing / installing the front cover Removing the front cover Proceed as follows to remove the front cover: • If a keypad is installed, remove it first (→ page 333). 1. 2. 52948AXX Figure 160: Removing the front cover 1. Press the grooved clip on top of the front cover. 2. Keep the clip pressed down to remove the front cover. 334 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Removing / installing the front cover Installing the front cover 9 Proceed as follows to install the front cover: 1 2 3 4 5 6 7 2. 8 9 BG0 10 3. 11 12 1. 13 14 15 BG1 -6 16 17 18 1. 19 52989AXX Figure 161: Installing the front cover 1. Insert the front cover with the bottom side into the support. 20 21 2. Keep the grooved clip on top of the front cover pressed down. 3. Push the front cover onto the unit. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 22 335 Installation UL compliant installation 9 9.4 UL compliant installation Note the following points for UL compliant installation: • Only use copper cables with the following temperature ranges as connection cables: – for MOVIDRIVE® MDX60B/61B0005 ... 0300 temperature range 60/75°C – for MOVIDRIVE® MDX61B0370 ... 1320 temperature range 75 °C • Permitted tightening torques for MOVIDRIVE® power terminals: – – – – – • Size 0 and 1 Sizes 2S and 2 Size 3 Sizes 4 and 5 Size 6 → → → → → 0.6 Nm 1.5 Nm 3.5 Nm 14 Nm 20 Nm MOVIDRIVE® drive inverters are suitable for operation in voltage power systems with an earthed star point (TN and TT systems), which can supply a max. supply current and a max. supply voltage in accordance with the following table. The fuses listed in the following tables are the maximum permitted fuses for each inverter. Only use melting fuses. 400/500 V units MOVIDRIVE® MDX60B/61B...5_3 Max. supply current Max. supply voltage Fuses 0005/0008/0011/0014 AC 5000 A AC 500 V AC 15 A / 600 V 0015/0022/0030/0040 AC 10000 A AC 500 V AC 35 A / 600 V 0055/0075 AC 5000 A AC 500 V AC 60 A / 600 V 0110 AC 5000 A AC 500 V AC 110 A / 600 V 0150/0220 AC 5000 A AC 500 V AC 175 A / 600 V 0300 AC 5000 A AC 500 V AC 225 A / 600 V 0370/0450 AC 10000 A AC 500 V AC 350 A / 600 V 0550/0750 AC 10000 A AC 500 V AC 500 A / 600 V 0900 AC 10000 A AC 500 V AC 250 A / 600 V 1100 AC 10000 A AC 500 V AC 300 A / 600 V 1320 AC 10000 A AC 500 V AC 400 A / 600 V MOVIDRIVE® MDX61B...2_3 Max. supply current Max. supply voltage Fuses 0015/0022/0037 AC 5000 A AC 240 V AC 30 A / 250 V 0055/0075 AC 5000 A AC 240 V AC 110 A / 250 V 0110 AC 5000 A AC 240 V AC 175 A / 250 V 0150 AC 5000 A AC 240 V AC 225 A / 250 V 0220/0300 AC 10000 A AC 240 V AC 350 A / 250 V 230 V units 336 • Use only tested units with a limited output voltage (Vmax = DC 30 V) and limited output current (I ≤ 8 A) as an external DC 24 V voltage source. • UL certification does not apply to operation in voltage supply systems with a non-earthed star point (IT systems). System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Shield clamps 9.5 9 Shield clamps Power shield clamp for size 0 1 A set of power shield clamps is supplied as standard with size 0. The power shield clamps are not yet installed. MOVIDRIVE® MDX60B/61B 2 Install the power shield clamps as follows: • Secure the contact clips to the shield plates. • Secure the power shield clamps to the top and the bottom of the unit. 3 4 1 5 2 6 3 7 4 8 9 10 11 51465AXX Figure 162: Installing the power shield clamp (size 0) [1] Contact clips [3] Shield plate [2] Retaining screws for contact clips [4] Retaining screw for power shield clamp 12 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 337 Installation Shield clamps 9 Power shield clamp for size 1 A power shield clamp is supplied as standard with MOVIDRIVE® MDX61B size 1. Install this power shield clamp together with the retaining screws of the unit. 1 2 02012BXX Figure 163: Installing the power shield clamp (size 1) [1]Power shield clamp Power shield clamp for sizes 2S and 2 [2] PE connection (y) A power shield clamp with 2 retaining screws is supplied as standard with MOVIDRIVE® MDX61B sizes 2S and 2. Mount this power shield clamp together with the two retaining screws to X6. 01469BXX Figure 164: Installing power shield clamp (sizes 2S and 2) [1] Power shield clamp [2] PE connection (y) Power shield clamps provide you with a very convenient way of installing the shield for the motor and brake cables. Install the shield and PE conductor as shown in the figures. Power shield clamp for sizes 3 to 6 338 No power shield clamps are supplied with MOVIDRIVE® MDX61B sizes 3 to 6. Use commercially available shield clamps for installing the shielding of motor and brake cables. Apply the shield as closely as possible to the inverter. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Shield clamps Electronics shield clamp for size 0 9 Install the electronics shield clamps as follows: 1 • If installed, remove the keypad and the front cover. • Secure the electronics shield clamp to the bottom of the unit directly under the electronic terminal strip X14. 2 3 1 MDX 60B MDX 61B 1 4 2 2 4 4 3 5 3 6 7 8 9 51466AXX Figure 165: Installing the electronics shield clamp (size 0) Electronics shield clamp for sizes 1 to 6 [1] Contact clip [3] Shield plate 10 [2] Retaining screw for contact clip [4] Retaining screw for electronics shield clamp 11 12 Install the electronics shield clamps as follows: • Secure the contact clips to the shield plates. • Secure the electronics shield clamp to the bottom of the unit. 13 1 14 15 3 2 16 4 17 18 19 20 51465AXX 21 Figure 166: Installing the electronics shield clamp (sizes 1 - 6) [1] Contact clips [3] Shield plate 22 [2] Retaining screws for con- [4] Retaining screw for electronics shield clamp tact clips System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 339 Installation Touch guard 9 9.6 Touch guard Sizes 4-6 With MOVIDRIVE® size 4 (AC 500 V unit:MDX61B0370/0450; AC 230 V units; MDX61B0220/0300), size 5 (MDX61B0550/0750) and size 6 (MDX61B0900/1100/1320), 2 touch guards with 6 retaining screws are supplied as standard. Install the touch guard on both covers of the power section terminals. [2] [1] [3] Figure 167: Touch guard for MOVIDRIVE® MDX61B sizes 4, 5 and 6 06624AXX The touch guard consist of the following parts: [1] Cover plate [2] Connection plate [3] Screen (only for sizes 4 and 5) The MOVIDRIVE® MDX61B units sizes 4, 5 and 6 can only achieve enclosure IP10 when the following conditions are met: • Touch guard is fully installed • The shrink tubing is installed on all power terminals (X1, X2, X3, X4) If the above conditions are not met, MOVIDRIVE® units sizes 4, 5 and 6 have enclosure IP00. 340 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Touch guard Size 2S 9 If the touch guard (→ following figure) is attached at the connections X4:-Uz/+Uz and X3:+R/-R, the MOVIDRIVE® MDX61B units size 2S have protection enclosure IP20; without touch guard they have enclosure IP10. 1 2 3 IP10 X4 4 -UZ +UZ PE IP20 5 X4 6 -UZ +UZ PE 7 8 9 1 2 3 4 5 6 7 8 9 +/- 0 . 10 IP10 11 X3 8/+R 9/-R PE 12 IP20 13 X3 14 8/+R 9/-R PE Figure 168: Touch guard for MOVIDRIVE® MDX61B size 2S 54408AXX 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 341 Installation Wiring diagram for basic unit 9 9.7 Wiring diagram for basic unit Wiring the power section and brake L1 L2 L3 PE F11/F12/F13 K11 (AC-3) Protective earth (Shield) L1 L2 UAC UAC F14/F15 F14/F15 L3 Option NF.. line filter L1' L2' L3' UAC 1 F14/F15 2 DC link connection * 3 7 L1 L2 L3 -UZ +UZ PE X4: X1: K11 AC-3) K11 (AC-3) K11 (AC-3) Power section X3: X2: DBØØ DGND DBØØ K12 (AC-3) DBØØ Brake plug ** CM (DY) 3 (3) 4 (2) 5 (1) PE U V W 4 5 6 +R -R PE 8 9 K12 (AC-3) DGND 1 BMK 2 3 4 13 14 15 8 1 BG 2 3 BGE 4 5 ® Section "Connecting the BW... / BW..-T braking resistor DGND white red blue CT/CV/DT/DV/D: Cut-off in the DC and AC circuits 1 BG 2 3 BGE 4 5 white red blue M 3-phase BW CT/CV/DT/DV/D: Cut-off in the AC circuit CT/CV, CM71...112: Cut-off in the DC and AC circuits 55310AEN * With sizes 1 and 2, there is no PE connection next to the supply system connection terminals and motor connection terminals (X1, X2). In this case, use the PE terminal next to the DC link connection (X4). ** Important: It is essential to adhere to the connection sequence of the brake connector. Incorrect connection will lead to irreparable damage to the brake. When connecting the brake via the terminal box → Operating instructions for CM motors! A separate supply system lead is required for connecting the brake rectifier. Powering it from the motor voltage is not permitted! Always switch off the brake on the DC and AC sides with: – All hoist applications – Drives which require a rapid brake response time – CFC and SERVO operating modes Brake rectifier in switch cabinet 342 Route the connection cables between the brake rectifier and the brake separately from other power cables when installing the brake rectifier in the switch cabinet. Joint installation is permitted with shielded power cables only. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Wiring diagram for basic unit 9 Connecting the BW.../ BW...-...-T braking resistor 1 U 4 X2: V W 5 X3: +R -R PE U 8 4 6 2 Power section Power section 9 X2: V W 5 X3: +R -R PE 6 8 3 9 4 F16 5 Has effect on K11 6 BW...-...-T M 3-phase T2 RB1 7 Has effect on K11 8 T1 BW... RB2 When the internal thermostat triggers, K11 must be opened and DIØØ "Controller inhibit" must have a "0" signal. The resistance circuit must not be interrupted! 9 When the external bimetallic relay (F16) triggers, K11 must be opened and DIØØ "controller inhibit" must have a "0" signal. The resistance circuit must not be interrupted! 55414AEN 10 11 12 Overload protection Braking resistor type Design specified Internal thermostat (..T) External bimetallic relay (F16) Required BW... - - BW...-...-T1) - One of the two options (internal thermostat / external bimetallic relay) is required. BW...-003 / BW...-005 Adequate - Permitted BW090-P52B Adequate - - 1) Permitted mounting options: On horizontal or vertical surfaces with brackets at the bottom and perforated sheets at top and bottom. Mounting not permitted: On vertical surfaces with brackets at the top, right or left. 13 14 15 16 17 When connecting and operating the brake resistors, you must read the instructions in the section "Installation instructions for basic unit". 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 343 Installation Wiring diagram for basic unit 9 Connecting the electronics terminals CONTROL Switchover I-Signal <-> U-signal * System bus terminating resistor Xterminal:9.6 kBaud <-> 57.6 kBaud* Frequency input active Xterminal S 11 S 12 S 13 S 14 ON OFF* X12: System bus Ref. System bus High System bus Low DGND SC11 SC12 1 2 3 REF1 AI 11 AI12 AGND REF2 1 2 3 4 5 R11 X11: +10 V DE L + n1 (0...10 V*; +/-10 V) 0...20 mA; 4 ... 20 mA Reference pot. analog signals -10 V OK 1 2 3 4 5 6 7 8 9 10 11 Binary outputs Ref. binary outputs DGND X16: DIØ6 DIØ7 DOØ3 DOØ4 DOØ5 DGND 1 2 3 4 5 6 X10: K12 (AC-3) 24V Connect external 24 V supply depending on the option (MOVIDRIVE® electronics data) 1 2 3 4 X17: 1 TF1 2 DGND 3 DBØØ DOØ1-C 4 DOØ1-NO 5 DOØ1-NC 6 7 DOØ2 8 VO24 VI24 9 DGND 10 Shield plate or shield clamp Reference potential for binary signals +24 V input Reference +24 V input safe stop +24 V input Safe stop Input TF-/TH-KTY+ Ref. pot. binary signals /Brake Relay contact Ready signal* NO contact relay NC contact /Fault* +24 V output +24 V input Reference potent. binary signals DGND VO24 SOV24 SVI24 . DIØØ DIØ1 DIØ2 DIØ3 DIØ4 DIØ5 DCOM* * VO2 4 DGND ST11 ST12 No function* No function* IPOS output* IPOS output* IPOS output* Reference pot. binary signals Option slot Only with MDX61B 0 1 2 3 4 5 6 7 8 9 A b c d E F H t U 7-Segment display operating status Inverter not ready Controller inhibt active No enable Current at standstill VFC mode n-control M-control Hold control Factory setting Limit switch reached Technology option Free IPOS reference travel Flying start Calibrate encoder Fault display Manual operation Timeout active Safe stop active IPOS program running (flashing point) 7-Segment display Socket Sub-D 9-pole /Controller inh. CW/stop* CCW/stop* Enable/Rapid stop* n11/n21* n12/n22* Refer. X13:DIØØ...DIØ5 +24 V output Reference pot. binary signals RS485 + RS485 - Master level controller Binary input X13: RS232 -10V...+10V 0(4)...20mA I U X11:AI11/AI12 Option DBG60B keypad Option UWS21A serial interface 55336AEN Figure 169: Wiring diagram for electronics terminals 344 * Factory setting ** If the binary inputs are connected to the DC 24 V voltage supply X13:8 "VO24", install a jumper between X13:7 (DCOM) and X13:9 (DGND) on MOVIDRIVE®. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Wiring diagram for basic unit 9 Description of terminal functions on the basic unit (power section and control unit) Terminal X1:1/2/3 X2:4/5/6 X3:8/9 X4: Function L1/L2/L3 (PE) U/V/W (PE) +R/-R (PE) +UZ/-UZ (PE) 2 Power supply connection Motor connection Braking resistor connection DC link connection 3 Change I-signal DC(0(4)...20 mA) ↔ V-signal DC(-10 V...0...10 V, 0...10 V), factory setting to V signal. Switching system bus terminating resistor on/off; factory setting: OFF. Set baud rate for the RS485 interface. Either 9.6 or 57.6 kBaud, factory setting: 75.6 kBaud. Switch frequency input on or off, factory setting: switched off. S11: S12: S13: S14: DGND SC11 SC12 Reference potential system bus System bus high System bus low X11:1 X11:2/3 X11:4 X11:5 REF1 AI11/12 AGND REF2 DC+10 V (max. DC 3 mA) for setpoint potentiometer Setpoint input n1 (differential input or input with AGND reference potential), signal form → P11_ / S11 Reference potential for analog signals (REF1, REF2, AI.., AO..) DC–10 V (max. DC 3 mA) for setpoint potentiometer X13:1 X13:2 X13:3 X13:4 X13:5 X13:6 DIØØ DIØ1 DIØ2 DIØ3 DIØ4 DIØ5 Binary input 1, with fixed assignt "/Controller inhibit" Binary input 2, factory setting to "CW/stop" Binary input 3, factory setting to "CCW/stop" Binary input 4, factory setting to "Enable/rapid stop" Binary input 5, factory setting to "n11/n21" Binary input 6, factory setting to "n11/n22" X13:7 DCOM Reference for binary inputs X13:1 to X13:6 (DIØØ ... DIØ5) and X16:1/X16:2 (DIØ6 ... DIØ7) • Switching binary inputs with DC+24 V external voltage: X13:7 (DCOM) must be connected to the reference potential of the external voltage. – Without jumper X13:7-X13:9 (DCOM-DGND) → Isolated binary inputs – With jumper X13:7-X13:9 (DCOM-DGND) → Non-isolated binary inputs • 4 5 X12:1 X12:2 X12:3 • • 6 7 The binary inputs are electrically isolated by optocouplers. Selection options for binary inputs 2 to 6 (DIØ1 ... DIØ5) → Parameter menu P60_ 8 9 The binary inputs must be switched with DC+24 V from X13:8 or X10:8 (VO24) → Jumper required X13:7-X13:9 (DCOM-DGND). X13:8 X13:9 X13:10 X13:11 VO24 DGND ST11 ST12 Auxiliary supply output DC+24 V (max. load X13:8 and X10:8 = 400 mA) for external command switches Reference potential for binary signals RS485+ RS485- X16:1 X16:2 X16:3 X16:4 X16:5 DIØ6 DIØ7 DOØ3 DOØ4 DOØ5 X16:6 DGND Binary input 7, factory setting "no function" Binary input 8, factory setting "no function" Binary output 3, factory setting "IPOS output" Binary output 4, factory setting "IPOS output" Binary output 5, factory setting "IPOS output" Do not connect external voltage to binary outputs X16:3 (DOØ3) and X16:5 (DOØ5)! Reference potential for binary signals X10:1 X10:2 X10:3 X10:4 X10:5 X10:6 X10:7 TF1 DGND DBØØ DOØ1-C DOØ1-NO DOØ1-NC DOØ2 • • • The binary inputs are electrically isolated by optocouplers. Selection options for binary inputs 7 and 8 (DIØ6/DIØ7) → Parameter menu P60_ Selection option for binary inputs 3 to 5 (DOØ3...DOØ5) → Parameter menu P62_ KTY+/TF-/TH connection (connect to X10:2 via TF/TH), factory setting to "No response" (→ P835) Reference potential for binary signals / KTY– Output 0, with assign. "/Brake", max. capacity DC 150 mA (short-circuit proof and protected vs. ext. voltage) Shared contact binary output 1, factory setting "Ready" NO contact binary output 1, max. load of relay contacts DC 30 V and DC 0.8 A NC contact binary output 1 Output 2, setting "/Fault", max. load capacity DC 50 mA (short-circuit proof, protected vs. external voltage) Selection options for binary outputs 1 and 2 (DOØ1 and DOØ2) → Parameter menu P62_ Do not apply an external voltage to binary outputs X10:3 (DBØØ) and X10:7 (DOØ2)! X10:8 X10:9 X10:10 VO24 VI24 DGND Auxiliary supply output DC+24 V (max. load X13:8 and X10:8 = 400 mA) for external command switches Input DC+24 V voltage supply (backup voltage depending on options, unit diagnosis when supply off) Reference potential for binary signals X17:1 X17:2 X17:3 X17:4 DGND VO24 SOV24 SVI24 Reference potential for X17:3 Auxiliary supply voltage DC+24 V, only to supply X17:4 Reference potential for DC+24 V input "Safe stop" (safety contact) DC+24 V input "Safe stop" (safety contact) Xterminal 1 Option slot: DBG60B keypad / UWS21A or USB11A interface converter 10 11 12 13 14 15 16 17 18 19 20 21 3 slots for option cards (size 0: 2 slots for option cards) 22 X17: For safety applications, it is essential to observe the information in the publications "Safe disconnection for MOVIDRIVE® MDX60B/61B – Conditions" and "Safe disconnection for MOVIDRIVE® MDX60B/61B – Applications." System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 345 Installation Assignment of braking resistors, chokes and filters 9 9.8 Assignment of braking resistors, chokes and filters AC 400/500 V units, size 0 MOVIDRIVE® MDX60/61B...-5A3 0005 0008 Size 0011 0014 0 Braking resistors BW... / BW..-..-T Trip current Part number BW... BW090-P52B1) - 824 563 0 BW072-003 IF = 0.6 ARMS 826 058 3 BW072-005 IF = 1.0 ARMS 826 060 5 BW168/BW168-T IF = 2.5 ARMS 820 604 X 1820 133 4 BW100-06/BW100-006-T IF = 1.8 ARMS 821 701 7 1820 419 8 Line chokes Part number BW...-...-T Part number Σ Imains = AC 20 A 826 012 5 NF009-503 Umax = AC 550 V 827 412 6 Output chokes Inside diameter Part number HD001 d = 50 mm (1.97 in) 813 325 5 For cable cross sections 1.5 ... 16 mm2 (AWG 16 ... 6) HD002 d = 23 mm (0.91 in) 813 557 6 For cable cross sections ≤ 1.5 mm2 (AWG 16) ND020-013 Line filter Part number Output filters (only in VFC mode) Part number HF008-503 826 029 X A HF015-503 826 030 3 B HF022-503 826 031 1 A B 1) Internal thermal overload protection, no bimetallic relay required. 346 A In rated operation (100 %) B With variable torque load in VFC mode (125 %) System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Assignment of braking resistors, chokes and filters 9 AC 400/500 V units, sizes 1, 2S, and 2 MOVIDRIVE® 1 MDX61B...-5A3 0015 0022 Size 0030 0040 0055 1 Braking resistors BW... / BW..-..-T Trip current Part no. BW... BW100-005 IF = 0.8 ARMS 826 269 1 BW100-006/ BW100-006-T IF = 1.8 ARMS 821 701 7 BW168/BW168-T IF = 2.5 ARMS 820 604 X 1820 133 4 BW268/BW268-T IF = 3.4 ARMS 820 715 1 1820 417 1 BW147/BW147-T IF = 3.5 ARMS 820 713 5 1820 134 2 BW247/BW247-T IF = 4.9 ARMS 820 714 3 1820 084 2 BW347/BW347-T IF = 7.8 ARMS 820 798 4 1820 135 0 BW039-012/ BW039-012-T IF = 4.2 ARMS 821 689 4 1820 136 9 BW039-026/ BW039-026-T IF = 7.8 ARMS 821 690 8 1820 415 5 BW039-050/ BW039-050-T IF = 11 ARMS 821 691 6 1820 137 7 0075 2S 0110 2 2 Part no. BW...-...-T 3 1820 419 8 4 5 6 7 8 9 Line chokes Part no. ND020-013 Σ Imains = AC 20 A 826 012 5 ND045-013 Σ Imains = AC 45 A 826 013 3 10 11 Line filter Part no. NF009-503 827 412 6 A NF014-503 827 116 X B NF018-503 Umax = AC 550 V NF035-503 12 A 827 413 4 B 13 827 128 3 14 Output chokes Inside diameter Part no. HD001 d = 50 mm (1.97 in) 813 325 5 For cable cross sections 1.5 ... 16 mm2 (AWG 16 ... 6) HD002 d = 23 mm (0.91 in) 813 557 6 For cable cross sections ≤ 1.5 mm2 (AWG 16) HD003 d = 88 mm (4.46 in) 813 558 4 For cable cross sections > 16 mm2 (AWG 6) Output filters (only in VFC mode) Part no. HF015-503 826 030 3 A HF022-503 826 031 1 B HF030-503 826 032 X HF040-503 826 311 6 HF055-503 826 312 4 HF075-503 826 313 2 HF023-403 825 784 1 HF033-403 825 785 X A In rated operation (100 %) B With variable torque load in VFC mode (125 %) 15 16 17 A B 18 A B A B 19 A B A B A 20 B 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 347 Installation Assignment of braking resistors, chokes and filters 9 AC 400/500 V units, sizes 3 to 6 MOVIDRIVE® MDX61B...-503 0150 Size 0300 037 0 3 045 0 4 055 0 075 0 090 0 5 1100 132 0 6 Braking resistors BW... / BW...-...-T Trip current Part no. BW... Part no. BW...-...-T BW018-015/ BW018-015-T IF = 4.0 ARMS 821 684 3 1820 416 3 C C BW018-035/ BW018-035-T IF = 8.1 ARMS 821 685 1 1820 138 5 C C BW018-075/ BW018-075-T IF = 14 ARMS 821 686 X 1820 139 3 C C BW915/ BW915-T IF = 28 ARMS 821 260 0 1820 413 9 BW012-025/ BW012-025-T IF = 10 ARMS 821 680 0 1820 414 7 BW012-050/ BW012-050-T IF = 17 ARMS 821 681 9 1820 140 7 BW012-100/ BW012-100-T IF = 29 ARMS 821 682 7 1820 141 5 BW106/ BW106-T IF = 38 ARMS 821 050 0 1820 083 4 C C C BW206/ BW206-T IF = 42 ARMS 821 051 9 1820 412 0 C C C ND045-013 Σ Imains = AC 45 A 826 013 3 A ND085-013 Σ Imains = AC 85 A 826 014 1 B ND150-013 Σ Imains = AC 150 A 825 548 2 ND300-0053 Σ Imains = AC 300 A 827 721 4 Line chokes A 348 0220 Part no. A B In rated operation (100 %) B With variable torque load in VFC mode (125 %) C Connect two braking resistors in parallel and set twice the trip current on F16 (2 × IF) System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Assignment of braking resistors, chokes and filters 9 1 ® MOVIDRIVE MDX61B...-503 0150 Size 0300 3 Line filter 0370 0450 0550 4 0750 5 0900 1100 827 128 3 A NF048-503 827 117 8 B NF063-503 827 414 2 NF085-503 827 415 0 2 Umax = AC 550 V 3 A B A B 827 416 9 4 A B A 5 NF150-503 827 417 7 NF210-503 827 418 5 A NF300-503 827 419 3 B Output chokes 1320 6 Part no. NF035-503 NF115-503 0220 Inside diameter B 7 Part number 2 HD001 d = 50 mm (1.97 in) 813 325 5 for cable cross sections 1.5...16 mm (AWG 16...6) HD003 d = 88 mm (4.46 in) 813 558 4 For cable cross sections > 16 mm2 (AWG 6) HD004 Connection with M12 bolt 816 885 7 Output filters (only in VFC mode) 8 9 10 Part number 825,785 X A B/D HF047-403 825 786 8 B A HF450-503 826 948 3 HF033-403 6 A/D 11 B A In rated operation (100 %) B With variable torque load in VFC mode (125 %) D Connect two output filters in parallel E In rated operation (100 %): One output filter With variable torque load (125 %): Connect two output filters in parallel E D D 12 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 349 Installation Assignment of braking resistors, chokes and filters 9 AC 230 V units, sizes 1 to 4 MOVIDRIVE® MDX61B...-2_3 0015 Size Braking resistors 0037 0055 1 0075 0110 2 0150 0220 3 0300 4 Trip current Part number BW039-003 IF = 2.0 ARMS 821 687 8 BW039-006 IF = 3.2 ARMS 821 688 6 BW039-012 IF = 4.2 ARMS 821 689 4 BW039-026 IF = 7.8 ARMS 821 690 8 BW027-006 IF = 2.5 ARMS 822 422 6 BW027-012 IF = 4.4 ARMS 822 423 4 BW018-015 IF = 4.0 ARMS 821 684 3 C C C C BW018-035 IF = 8.1 ARMS 821 685 1 C C C C BW018-075 IF = 14 ARMS 821 686 X C C C C BW915 IF = 28 ARMS 821 260 0 C C C C BW012-025 IF = 10 ARMS 821 680 0 BW012-050 IF = 19 ARMS 821 681 9 BW012-100 IF = 27 ARMS 821 682 7 BW106 IF = 38 ARMS 821 050 0 C C BW206 IF = 42 ARMS 821 051 9 C C Σ Imains = AC 20 A 826 012 5 A B Line chokes ND020-013 Part number ND045-013 Σ Imains = AC 45 A 826 013 3 ND085-013 Σ Imains = AC 85 A 826 014 1 ND150-013 Σ Imains = AC 150 A 825 548 2 Line filter B A NF014-503 827 116 X B NF018-503 827 413 4 NF035-503 A B 827 412 6 NF048-503 A Part number NF009-503 Umax = AC 550 V A B 827 128 3 827 117 8 A NF063-503 827 414 2 B NF085-503 827 415 0 A 827 416 9 B NF115-503 Output chokes 350 0022 Internal diameter Part number HD001 d = 50 mm 813 325 5 For cable cross sections 1.5 ... 16 mm2 (AWG 16 ... 6) HD002 d = 23 mm 813 557 6 For cable cross sections ≤ 1.5 mm2 (AWG 16) HD003 d = 88 mm 813 558 4 For cable cross sections > 16 mm2 (AWG 6) A In rated operation (100 %) B With variable torque load in VFC mode (125 %) C Connect two braking resistors in parallel and set twice the trip current on F16 (2 × IF) System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation System bus connection (SBus 1) 9.9 9 System bus connection (SBus 1) 1 Only if P884 "SBus baud rate" = 1000 kbaud: MOVIDRIVE® compact MCH4_A units must not be combined with other MOVIDRIVE® units in the same system bus combination. 2 The units may be combined at baud rates ≠ 1000 kbaud. 3 Max. 64 CAN bus stations can be addressed using the system bus (SBus). Use a repeater after 20 or 30 stations, depending on the length of the cables and the cable capacity. The SBus supports transmission technology compliant with ISO 11898. 4 5 The "Serial Communication" manual contains detailed information about the system bus. This manual can be ordered from SEW-EURODRIVE. 6 SBus wiring diagram Control unit S 11 S 12 S 13 S 14 Systembus Terminating resistor Control unit Systembus Terminating resistor ON OFF Systembus Ref. Systembus High Systembus Low Systembus Ref. Systembus High Systembus Low 1 2 3 S 11 S 12 S 13 S 14 Systembus Terminating resistor 8 ON OFF X12: DGND SC11 SC12 7 Control unit ON OFF X12: DGND SC11 SC12 S 11 S 12 S 13 S 14 1 2 3 Systembus Ref. Systembus High Systembus Low 9 X12: DGND SC11 SC12 1 2 3 10 11 12 54534AEN Figure 170: System bus connection Cable specification • 13 Use a 4-core twisted and shielded copper cable (data transmission cable with braided copper shield). The cable must meet the following specifications: – Core cross section 0.25 ... 0.75 mm2 (AWG 23 ... AWG 18) – Line resistance 120 Ω at 1 MHz – Capacitance per unit length ≤ 40 pF/m at 1 kHz Suitable cables include CAN bus or DeviceNet cables. Shielding • Connect the shield to the electronics shield clamp on the inverter or master controller and make sure it is connected over a wide area at both ends. Cable length • The permitted total cable length depends on the baud rate setting of the SBus (P884): – – – – Terminating resistor 125 kbaud 250 kbaud 500 kbaud 1000 kbaud → → → → 320 m 160 m 80 m 40 m • Switch on the system bus terminating resistor (S12 = ON) at the start and end of the system bus connection. Switch off the terminating resistor on the other units (S12 = OFF). • There must not be any potential displacement between the units connected with the SBus. Take suitable measures to avoid potential displacement, such as connecting the unit ground connectors using a separate line. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 14 15 16 17 18 19 20 21 22 351 Installation Connection of RS485 interface 9 9.10 Connection of RS485 interface The RS485 interface can be used for connecting max. 32 MOVIDRIVE® units, e.g. for master/slave operation, or 31 MOVIDRIVE® units and a master control system (PLC). Wiring diagram RS485 interface X13: RS485+ RS485- X13: DIØØ 1 DIØ1 2 DIØ2 3 DIØ3 4 DIØ4 5 DIØ5 6 DCOM 7 VO24 8 DGND 9 ST11 10 ST12 11 RS485+ RS485- 쵰 X13: DIØØ 1 DIØ1 2 DIØ2 3 DIØ3 4 DIØ4 5 DIØ5 6 DCOM 7 VO24 8 DGND 9 ST11 10 ST12 11 RS485+ RS485- 쵰 DIØØ 1 DIØ1 2 DIØ2 3 DIØ3 4 DIØ4 5 DIØ5 6 DCOM 7 VO24 8 DGND 9 ST11 10 ST12 11 쵰 쵰 54535AXX Figure 171: RS485 connection Cable specification • Use a 4-core twisted and shielded copper cable (data transmission cable with braided copper shield). The cable must meet the following specifications: – Core cross section 0.25 ... 0.75 mm2 (AWG 23 ... 18) – Cable resistance 100 ... 150 Ω at 1 MHz – Capacitance per unit length ≤ 40 pF/m at 1 kHz The following cable is suitable, for example: – BELDEN (www.belden.com), data cable type 3107A Shielding • Connect the shield to the electronics shield clamp on the inverter or higher-level controller and make sure it is connected over a wide area at both ends. Cable length • The permitted total cable length is 200 m. Terminating resistor • Dynamic terminating resistors are installed. Do not connect any external terminating resistors! There must not be any difference of potential between the units connected with the RS485. Take suitable measures to avoid potential displacement, such as connecting the unit ground connectors using a separate line. 352 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connection of interface converter option UWS21A (RS232) 9.11 9 Connection of interface converter option UWS21A (RS232) Part number 1 Interface converter option UWS21A: 823 077 3 2 Connecting MOVIDRIVE® to UWS21A • Use the connection cable supplied to connect the UWS21A option to the MOVIDRIVE® unit. 3 ® • Plug the connection cable into the Xterminal socket of the MOVIDRIVE unit. • Note that the DBG60B keypad and the UWS21A serial interface cannot be connected to the MOVIDRIVE® at the same time. 4 5 MOVIDRIVE® MDX60/61B 6 7 UWS21A 8 9 10 Figure 172: Connection cable between MOVIDRIVE®and 51460AXX UWS21A 11 Connecting UWS21A to PC • Use the connection cable supplied (shielded RS232 standard interface cable) to connect the UWS21A option to the PC. PC COM 1-4 UWS 21A GND 5 3 2 TxD 3 2 15 16 max. 5 m (16.5 ft) R S -232 [1] 13 14 5 RxD 12 [2] 06186AXX 17 Figure 173: UWS21A-PC connection cable (1:1 connection assignment) [1] 9-pin sub D connector [2] 9-pin sub D socket 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 353 Installation Connection of the interface converter option USB11A 9 9.12 Connection of the interface converter option USB11A Part number Interface converter option USB11A: 824 831 1 • The scope of delivery for the USB11A includes: – – – – Connecting MOVIDRIVE®USB11A - PC USB11A interface adapter USB connection cable PC - USB11A (type USB A-B) Connection cable for MOVIDRIVE® MDX60B/61B - USB11A (cable RJ10-RJ10) CD-ROM with drivers and MOVITOOLS® • The USB11A interface converter supports USB 1.1 and USB 2.0. • Use the connection cable [1] (RJ10 - RJ10) supplied to connect the USB11A option to the MOVIDRIVE® unit. • Plug the connection cable [1] into the Xterminal slot of the MOVIDRIVE® MDX60B/61B and into the RS485 slot of the USB11A. • Note that the DBG60B keypad and the USB11A interface converter cannot be connected to the MOVIDRIVE® at the same time. • Use the USB connection cable [2] (type USB A-B) to connect the USB11A to the PC. MOVIDRIVE® MDX60/61B PC COM 1-4 [1] [2] USB11A Figure 174: Connection cable for MOVIDRIVE® MDX60B/61B - USB11A Installation Operation with MOVITOOLS® 54532AXX • Connect the USB11A to a PC and MOVIDRIVE® MDX60B/61B using the connection cables supplied. • Insert the enclosed CD into the CD drive of your PC and install the driver. The first free COM port on the PC will be assigned to the USB11A interface converter . • After installation, the PC recognizes the USB11A interface converter after approximately 5 to 10 s. • Start MOVITOOLS®. If the connection between the PC and USB11A is interrupted, you will have to restart MOVITOOLS®. 354 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Option combinations for MDX61B 9 9.13 Option combinations for MDX61B Configuration of option slots Size 0 (0005 ... 0014) 1 Sizes 1 ... 6 (0015 ... 1320) 2 3 4 2. 5 6 3. 1. 7 8 9 06677AXX Figure 175: Options slots for MOVIDRIVE® MDX61B 10 1. Encoder slot for encoder options 2. Fieldbus slot for communication options 11 3. Expansion slot for communication options (only for sizes 1 to 6) 12 Option card combinations for MDX61B The option cards are different in size and can only be installed in the matching option slots. The following list shows the possible combinations of option cards for MOVIDRIVE® MDX61B. 13 14 ® MOVIDRIVE MDX61B Option card Designation DEH11B Encoder input incr. / Hiperface® Encoder slot Size 0 - size 6 Fieldbus slot Size 0 - size 6 Expansion slot Size 1 - size 6 X ® 16 DER11B Encoder input resolver / Hiperface DFP21B Fieldbus interface Profibus X DFI11B Fieldbus interface Interbus X DFI21B Fieldbus interface Interbus LWL X DFD11B Fieldbus interface DeviceNet X DFC11B Fieldbus interface CAN/CANopen X X 17 18 19 DFE11B Fieldbus interface Ethernet X DIO11B I/O expansion X DRS11B Phase-synchronous operation X DIP11B SSI encoder interface X 1) When fieldbus slot is not available 15 X1) 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 355 9 Installation Installing and removing option cards 9.14 Installing and removing option cards Before you begin 356 • For MOVIDRIVE® MDX61B size 0, only SEW-EURODRIVE can install or remove option cards! • MOVIDRIVE® MDX61B sizes 1 to 6 allow you to install or remove 3 option cards. Observe the following notes before installing or removing an option card: • Disconnect the inverter from power. Switch off the 24 V DC and the supply voltage. • Take appropriate measures to protect the option card from electrostatic charge (use discharge strap, conductive shoes, etc.) before touching it. • Before installing the option card, remove the keypad (→ Sec. "Removing / installing the keypad") and the front cover (→ Sec. "Removing / installing the front cover"). • After having installed the option card, replace the keypad (→ Sec. "Removing / installing the keypad") and the front cover (→ Sec. "Removing / installing the front cover"). • Keep the option card in its original packaging until immediately before you are ready to install it. • Hold the option card by its edges only. Do not touch any components. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Installing and removing option cards 9 Basic procedure for installing/removing an option card 1 2 3 2. 4 1. 5 6 7 3. 8 9 10 11 12 4. 13 14 15 16 17 Figure 176: Installing an option card in MOVIDRIVE® MDX61B sizes 1 to 6 53001AXX 18 1. Remove the retaining screws holding the card retaining bracket. Pull the card retaining bracket out evenly from the slot (do not twist!). 19 2. Remove the retaining screws of the black cover plate on the card retaining bracket. Remove the black cover plate. 20 3. Position the option card onto the retaining bracket so that the retaining screws fit into the corresponding bores on the card retaining bracket. 21 4. Insert the retaining bracket with installed option card into the slot, pressing slightly so it is seated properly. Secure the card retaining bracket with the retaining screws. 22 5. To remove the option card, follow the instructions in reverse order. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 357 Installation Connection of encoder and resolver 9 9.15 Connection of encoder and resolver The following wiring diagrams do not show the view onto the cable end but • with the plugs / sockets: View on motor plugs/sockets • with unit sockets: View on unit socket The core colors specified in the wiring diagrams are in accordance with the IEC 757 color code and correspond to the core colors used in the prefabricated cables from SEW-EURODRIVE. For more details, refer to the "SEW Encoder Systems" manual, which can be obtained from SEW-EURODRIVE. General installation information • Max. line length from inverter - encoder/resolver: 100 m with a capacitance per unit length ≤ 120 nF/km. • Core cross section: 0,20 ... 0.5 mm2 (AWG 24 ... 20) • If you cut a core of the encoder/resolver cable, isolate the cut-off end of the core. • Use shielded cables with twisted pairs of insulated conductors and connect the shield at both ends: – At the encoder in the cable gland or in the encoder plug – At the inverter in the housing of the sub D plug • Route the encoder/resolver cable separately from the power cables. Shielding Connect the shield of the encoder/resolver cable over a large area. On the inverter Connect the shield on the inverter end in the housing of the sub D plug (→ following illustration). 01939BXX 358 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connection of encoder and resolver On the encoder/resolver 9 Connect the shield on the encoder/resolver side at the respective earthing clamps (→ following illustration). If you are using an EMC screwed gland, connect the shield to the cable gland over a large area. For drives with a plug connector, connect the shield on the encoder plug. 1 2 3 4 5 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 6 7 8 55513AXX Prefabricated cables 9 SEW-EURODRIVE offers prefabricated cables for connecting encoders/resolvers. We recommend using these prefabricated cables. 10 11 12 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 359 Installation Connecting the DEH11B (HIPERFACE®) option 9 9.16 Connecting the DEH11B (HIPERFACE®) option HIPERFACE® encoder card type DEH11B option: 824 310 7 Part number The "HIPERFACE® encoder card type DEH11B" option is only possible in conjunction with MOVIDRIVE® MDX61B, not with MDX60B. The DEH11B option must be plugged into the encoder slot. Front view of DEH11B DE H11B 1 15 8 15 8 9 1 X14 9 X15 Description Terminal Function X14: Input of external encoder or output of incremental encoder simulation X14:1 X14:2 X14:3 X14:4 X14:5/6 X14:7 X14:8 X14:9 X14:10 X14:11 X14:12 X14:13/14 X14:15 (COS+) signal track A (K1) (SIN+) signal track B (K2) Signal track C (K0) DATA+ Reserved Switchover Reference potential DGND (COS–) Signal track A (K1) (SIN–) Signal track B (K2) Signal track C (K0) DATAReserved DC+12 V (max. load X14:15 and X15:15 = DC 650 mA) X15:1 X15:2 X15:3 X15:4 X15:5 X15:6 X15:7 X15:8 X15:9 X15:10 X15:11 X15:12 X15:13 X15:14 X15:15 (COS+) signal track A (K1) (SIN+) signal track B (K2) Signal track C (K0) DATA+ Reserved Reference potential TF/TH/KTY– Reserved Reference potential DGND (COS–) Signal track A (K1) (SIN–) Signal track B (K2) Signal track C (K0) DATAReserved TF/TH/KTY+ connection DC+12 V (max. load X14:15 and X15:15 = DC 650 mA) Connection → page 366 topage 369 Pulse count of the incremental encoder simulation: • 1024 pulses/revolution with HIPERFACE® encoder on X15 • as on X15: Motor encoder input with sin/cos encoder or TTL sensor on X15 X15: Motor encoder input 06198AXX Important notes Permitted encoders 360 • The connections on X14 and X15 must not be plugged or removed during operation. De-energize the inverter before plugging or removing the encoder connections. Switch off the supply voltage and the DC 24 V (X10:9). • If X14 is used as an incremental encoder simulation output, the switchover (X14:7) must be jumpered with DGND (X14:8). • The DC 12 V supply voltage from X14 and X15 is sufficient to operate SEW encoders with a DC 24 V supply voltage. With all other encoders, check whether they can be connected to the DC 12 V supply voltage. • Do not connect HTL encoders. The following encoders may be connected to the "HIPERFACE® encoder card type DEH11B" option: • HIPERFACE® encoder type AS1H, ES1H or AV1H • sin/cos encoder type ES1S, ES2S, EV1S or EH1S • DC 5 V TTL sensor with DC 24 V voltage supply type ES1R, ES2R, EV1R or EH1R • DC 5 V TTL sensor with DC 5 V voltage supply type ES1T, ES2T, EV1T or EH1T via option DWI11A System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connecting the DEH11B (HIPERFACE®) option 9 HIPERFACE® encoder connection HIPERFACE® encoders AS1H, ES1H and AV1H are recommended for operation with DEH11B. Depending on the motor type and motor configuration, the encoder is connected via plug connector or terminal box. DT../DV.., DS56, CT../CV.., CM71...112 with plug connector Connect the HIPERFACE® encoder as follows: AS1H / ES1H / AV1H 2 3 max. 100 m DEH11B, X15: 3 RD 4 BU 8 9 1 5 YE 2 10 12 7 6 GN 11 6 DATA- 7 VT 3 5 DATA+ 8 BK 4 TF/TH/KTY+ 9 BN TF/TH/KTY- 10 WH 11 GYPK US 12 RDBU cos+ cossin+ sin- 1 9 2 10 12 4 14 6 8 15 PK GY 쵰 1 4 15 5 8 6 9 7 1 8 쵰 Figure 177: Connecting HIPERFACE® encoder to DEH11B as a motor encoder 9 54439BAXX 10 Important for DT/DV and CT/CV motors: The TF or TH is not connected to the encoder cable but must be connected using an additional 2-core shielded cable. 11 Part numbers of the prefabricated cables: 12 • For fixed routing: 1332 453 5 • For cable carrier routing: 1332 455 1 Part numbers of the prefabricated extension cables: • For fixed routing: 199 539 1 • For cable carrier routing: 199 540 5 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 361 Installation Connecting the DEH11B (HIPERFACE®) option 9 CM71...112 with terminal box Connect the HIPERFACE® encoder as follows: max. 100 m AS1H/ES1H cos+ cossin+ sinDATADATA+ TF/TH/KTY+ TF/TH/KTY- DEH11B, X15: RD 1 BU 2 YE 3 4 GN 5 VT 6 BK 9 BN 10 WH 7 GYPK 8 RDBU 1 9 2 10 12 4 14 6 8 15 PK GY 쵰 15 8 9 1 쵰 54440BXX Figure 178: Connecting HIPERFACE® encoder to DEH11B as a motor encoder Part numbers of the prefabricated cables: Connecting sin/cos encoder to DT../DV.., CT../CV motors • For fixed routing: 1332 457 8 • For cable carrier routing: 1332 454 3 The high resolution sin/cos encoders EH1S, ES1S, ES2S or EV1S can also be connected to DEH11B. Connect the sin/cos encoder as follows: EH1S / ES1S / ES2S / EV1S EH1R / ES1R / ES2R / EV1R max. 100 m DEH11B, X15: YE GN RD BU PK GY 1 9 2 10 3 11 15 8 WH BN BK VT 쵰 15 9 8 1 쵰 54329BXX Figure 179: Connecting the sin/cos encoder to DEH11B as a motor encoder Part numbers of the prefabricated cables: 362 • For fixed routing: 1332 459 4 • For cable carrier routing: 1332 458 6 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connecting the DEH11B (HIPERFACE®) option 9 Connecting TTL sensors to DT../DV.. motors TTL sensors from SEW-EURODRIVE are available with DC 24 V and DC 5 V voltage supply. DC 24 V voltage supply Connect TTL sensors with DC 24 V voltage supply EH1R, ES1R, ES2R or EV1R in the same way as the high-resolution sin/cos encoders (→ Figure 179). DC 5 V voltage supply TTL sensors with a DC 5 V voltage supply ES1T, ES2T, EH1T or EV1T must be connected via the "DC 5 V encoder power supply type DWI11A" option (part number 822 759 4). The sensor cable must also be connected to correct the supply voltage of the encoder. Connect these encoders as follows: 1 2 DEH11B, X15: 1 1 9 2 10 3 11 15 8 5 6 1 6 2 7 3 8 9 5 BK VT 쵰 ES1T / ES2T / EV1T / EH1T max. 100 m 7 6 9 1 8 5 9 10 쵰 YE GN RD BU PK GY WH BN VT* 1 6 2 7 3 8 9 5 4* 쵰 DWI11A X1: MOVIDRIVE 9 8 4 max. 5 m YE GN RD BU PK GY WH BN 11 9 X2: Encoder 15 3 5 12 6 1 13 14 쵰 54330BXX 15 Figure 180: Connecting the TTL sensor via DWI11A to DEH11B as a motor encoder 16 * Connect the sensor cable (VT) on the encoder to UB, do not jumper on the DWI11A! 17 Part numbers of the prefabricated cables: • • HIPERFACE® encoder card type DEH11B X15 option: → DWI11A X1: MOVIDRIVE® 18 – For fixed routing: 19 817 957 3 Encoders ES1T / ES2T / EV1T / EH1T → DWI11A X2: Encoder – For fixed routing: – For cable carrier routing: 198 829 8 198 828 X 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 363 Installation Connecting the DER11B (resolver) option 9 9.17 Connecting the DER11B (resolver) option Part number Resolver card type DER11B option: 824 307 7 The "resolver card type DER11B" option is only possible in conjunction with MOVIDRIVE® MDX61B, not with MDX60B. The DER11B option must be plugged into the encoder slot. Front view of DER11B DE R 11B Terminal Function X14: Input of external encoder or output of incremental encoder simulation X14:1 X14:2 X14:3 X14:4 X14:5/6 X14:7 X14:8 X14:9 X14:10 X14:11 X14:12 X14:13/14 X14:15 (cos) signal track A (K1) (sin) signal track B (K2) Signal track C (K0) DATA+ Reserved Switchover Reference potential DGND (cos–) Signal track A (K1) (sin–) Signal track B (K2) Signal track C (K0) DATAReserved DC+12 V (max. load DC 650 mA) X15:1 X15:2 X15:3 X15:4 X15:5 X15:6 X15:7 X15:8 X15:9 sin+ (S2) cos+ (S1) Ref.+ (R1) Not assigned Reference potential TF/TH/KTY– sin– (S4) cos– (S3) Ref.– (R2) TF/TH/KTY+ connection 9 1 Connection → page 366 topage 369 15 8 The pulse count of the incremental encoder simulation is always 1024 pulses per revolution 9 5 6 1 X14 X15 Description X15: Resolver input 06199AXX Important notes Permitted encoders • The connections on X14 and X15 must not be plugged or removed during operation. De-energize the inverter before plugging or removing the encoder connections. Switch off the supply voltage and the DC 24 V (X10:9). • If X14 is used as an incremental encoder simulation output, the switchover (X14:7) must be jumpered with DGND (X14:8). • The DC 12 V supply voltage from X14 is sufficient to operate SEW encoders with a DC 24 V supply voltage. With all other encoders, check whether they can be connected to the DC 12 V supply voltage. • Do not connect HTL encoders. The following encoders can be connected at X14 (external encoder inputs): • HIPERFACE® encoder type AS1H, ES1H or AV1H • sin/cos encoder type ES1S, ES2S, EV1S or EH1S • DC 5 V TTL sensor with DC 24 V voltage supply type ES1R, ES2R, EV1R or EH1R • DC 5 V TTL sensor with DC 5 V voltage supply type ES1T, ES2T, EV1T or EH1T via option DWI11A 2-pole resolvers, AC 7 Veff, 7 kHz, can be connected at X15 (resolved input). The gear ratio of the resolver amplitudes must be approximately 0.5. The control dynamics decrease if the value is lower; the evaluation may be unstable if the value is higher. 364 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connecting the DER11B (resolver) option Resolver 9 SEW-EURODRIVE offers the following pre-fabricated cables for connecting resolvers to DER11B: 1 2 Part number For motor type DS56 CM71 ... 112 Fixed routing Cable carrier installation With plug connector 199 487 5 199 319 4 Extension cable 199 542 1 199 541 3 CM71 ... 112 With terminal box 199 589 8 199 590 1 DS56 With terminal box 1332 817 4 1332 844 1 3 4 5 Terminal / pin assignment CM motors: The resolver connections are accommodated in a plug connector or on a 10-pin Wago terminal strip. 6 DS motors: The resolver connections in the terminal box are either accommodated on a 10-pin Phoenix terminal strip or in the plug connector. 7 CM plug connector DS56:Intercontec, type ASTA021NN00 10 000 5 000 Terminal / pin Connection Description 1 Ref.+ 2 Ref.- 3 cos + 4 cos- 5 sin+ 6 sin- 9 TF / TH / KTY + 10 TF/TH/KTY– 8 Core color in prefabricated cable Pink (PK) Reference 9 Gray (GY) Red (RD) Cosine signal Blue (BU) 10 Yellow (YE) Sine signal Green (GN) 11 Brown (BN) / violet (VT) Motor protection 12 White (WH) / black (BK) The resolver signals have the same numbering on the 10-pin Phoenix terminal strip and in the plug connectors. 13 Connect the resolver as follows: 14 max. 100 m CM71...112 DS56 9 1 8 12 7 2 10 11 3 4 [1] 6 5 1 Ref.+ 2 Ref.3 cos+ 4 cos5 sin+ 6 sin7 N.C. 8 N.C. 9 TF/TH/KTY+ 10 TF/TH/KTY[2] DER11B, X15: PK GY RD BU YE GN 3 8 2 7 1 6 9 5 4 BN WH 9 5 6 1 16 17 18 VT BK 쵰 15 19 쵰 54331BXX 20 Figure 181: Connecting the resolver 1) Plug connector 21 2) Terminal strip If using the pre-fabricated cable with conductor end sleeves, cut off the violet and black conductor (VT) of the cable in the motor terminal box. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 22 365 Installation External encoder connection 9 9.18 External encoder connection External encoders Voltage supply The following external encoders can be connected to connector X14 of the DEH11B option and the DER11B option. • HIPERFACE® encoder AV1H • High-resolution sin/cos encoders with signal voltage 1 VSS • DC 5 V TTL sensors with signal level to RS422 SEW encoders with DC 24 V voltage supply (max. DC 180 mA) are connected directly to X14. . These SEW encoders are then powered by the inverter. SEW encoders with a DC 5 V voltage supply must be connected via the "DC 5 V encoder power supply type DWI11A" option (part number 822 759 4). Connecting HIPERFACE® encoder AV1H Connect the HIPERFACE® encoder AV1H as follows: 9 1 2 8 12 7 10 11 3 4 DEH11B/DER11B, X14: 1 9 2 1 9 10 4 12 15 8 15 8 max. 100 m AV1H 6 5 COS 3 RD REFCOS 4 BU SIN 5 YE REFSIN 6 GN DATA+ 8 BK DATA- 7 VT US 12 RDBU 11 GYPK GY PK 쵰 쵰 54332BXX Figure 182: Connecting the HIPERFACE® encoder AV1H to DEH11B/DER11B as external encoder Part numbers of the prefabricated cables: • For fixed routing: 818 015 6 • For cable carrier routing: 818 165 9 Part numbers of the prefabricated extension cables: 366 • For fixed routing: 199 539 1 • For cable carrier routing: 199 540 5 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation External encoder connection sin/cos encoder connection 9 Connect the sin/cos encoder as follows: EH1S / EH1R / ES1S / ES1R EV1S / EV1R / ES2R / ES2S 1 DEH11B/DER11B, X14: max. 100 m YE GN RD BU PK GY WH BN 1 9 2 10 3 11 15 8 BK VT 쵰 2 3 1 9 4 5 8 15 6 쵰 54333BXX Figure 183: Connecting the sin/cos encoder to DEH11B/DER11B as an external encoder 7 Part numbers of the prefabricated cables: 8 • For fixed routing: 817 960 3 9 If using the prefabricated cable with conductor end sleeves, cut off the red-blue conductor (RDBU) of the cable. • For cable carrier routing: 818 168 3 10 11 TTL sensor connection TTL sensors from SEW-EURODRIVE are available with DC 24 V and DC 5 V voltage supply. DC 24 V voltage supply Connect TTL sensors with DC 24 V voltage supply EV1R in the same way as the highresolution sin/cos encoders (→ Figure 179). 12 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 367 Installation External encoder connection DC 5 V TTL sensors with a DC 5 V voltage supply EV1T, EH1T, ES1T and ES2T must be connected via the "DC 5 V encoder power supply type DWI11A" option (part number 822 759 4). The sensor cable must also be connected to correct the supply voltage of the encoder. Connect these encoders as follows: DEH11B / DER11B, X14: 9 15 1 8 max. 5 m YE GN RD BU PK GY WH BN 1 9 2 10 3 11 15 8 1 6 2 7 3 8 9 5 BK VT 쵰 EH1T /EV1T ES1T / ES2T max. 100 m 6 9 1 5 쵰 YE GN RD BU PK GY WH BN VT* 1 6 2 7 3 8 9 5 4* 쵰 DWI11A X1: MOVIDRIVE DC 5 V voltage supply 9 X2: Encoder 9 6 5 1 쵰 54335BXX Figure 184: Connecting the TTL sensor EV1T to MDX via DWI11A as an external encoder * Connect the sensor cable (VT) on the encoder to UB, do not jumper on the DWI11A! Part numbers of the prefabricated cables: • HIPERFACE® encoder card type DEH11B X14 option: → DWI11A X1: MOVIDRIVE® – For fixed routing: • 818 164 0 Encoder EV1T → DWI11A X2: Encoder – For fixed routing: – For cable carrier routing: 368 198 829 8 198 828 X System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connection of incremental encoder simulation 9 9.19 Connection of incremental encoder simulation 1 Incremental encoder simulation 2 Connector X14 of the DEH11B or DER11B option can also be used as incremental encoder simulation output. To do so, you have to jumper "switchover" (X14:7) with DGND (X14:8) and disconnect the connection between X14:15 und UB. X14 then delivers the incremental encoder signals with a signal level according to RS422. The number of pulses is as follows: • With DEH11B as on X15 motor encoder input • With DER11B 1024 pulses/revolution 4 YE GN RD BU PK GY 1 9 2 10 3 11 15 8 7 WH BN RDBU 쵰 VT BK 5 DEH11B / DER1B X14: max. 100 m Umschaltung 3 6 9 1 7 15 8 8 9 쵰 54336BXX Figure 185: Incremental encoder simulation connection to DEH11B or DER11B 10 Part number of the prefabricated cable: 11 • Option type DEH/DER11B X14: → incremental encoder simulation – For fixed routing: 817 960 3 If using the prefabricated cable with conductor end sleeves, cut off the white (WH) and black (BK) conductor of the cable. 12 13 14 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 369 Installation Master/slave connection 9 9.20 Master/slave connection Master/slave connection Connector X14 of the DEH11B or DER11B option can also be used for the "internal synchronous operation" application (master/slave connection of several MOVIDRIVE® units). For this purpose, you must jumper "switchover" (X14:7) with DGND (X14:8) on the master end. X14-X14 connection (= master/slave connection) of two MOVIDRIVE® units. max. 10 m 9 15 1 8 1 RD 9 BU 2 YE 10 GN 3 VT 11 BK 15 8 BN 7 WH 1 9 2 10 3 11 15 8 7 9 15 1 8 54390BXX Figure 186: X14-X14 connection (master/slave connection) Part number of the prefabricated cable: 370 • For fixed routing: 817 958 1 • Up to 3 slaves can be connected to the MOVIDRIVE® master. • Please note: X14:7 is not allowed to be connected when connecting the individual MOVIDRIVE® slaves to one another. Connections X14:7 and X14:8 are only allowed to be jumpered between the MOVIDRIVE® master and the first MOVIDRIVE® slave. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connection and terminal description of the DIO11B option 9 9.21 Connection and terminal description of the DIO11B option Part number 1 Terminal expansion board type DIO11B: 824 308 5 2 The "terminal expansion board type DIO11B" option is only possible in conjunction with MOVIDRIVE® MDX61B, not with MDX60B. Front view of DIO11B The DIO11B option must be plugged into the fieldbus slot. If the fieldbus slot is not available, you can plug the DIO11B expansion board in the expansion slot. 3 The extended handle end of the plug connectors (terminals X20, X21, X22, X23) must only be used for removing the plug connectors (not for plugging them in!). 4 Terminal X20:1/2 AI21/22 X20:3 AGND X21:1 X21:4 AOV1 AOV2 X21:2 X21:5 AOC1 AOC2 DIO11B DI1Ø DI11 DI12 DI13 DI14 DI15 DI16 DI17 DCOM DGND 1 2 3 4 5 6 7 8 9 10 DO1Ø DO11 DO12 DO13 DO14 DO15 DO16 DO17 24V IN 1 2 3 4 5 6 7 8 9 X21:3/6 AGND X22:1...8 DI1Ø...17 X22:9 X22:10 DCOM DGND X23:1...8 DO1Ø...17 X23:9 24VIN 5 Setpoint input n2, DC-10 V...0...10 V or DC 0...10 V (Differential input or input with AGND reference potential) Reference potential for analog signals (REF1, REF2, AI.., AO..) 6 Analog voltage output V1, with factory setting to "actual speed" Analog voltage output V2, with factory setting to "output current" Load capacity of the analog voltage outputs: Imax = DC 10 mA Analog current output C1, with factory setting "actual speed" Analog current output C2, with factory setting "output current" P642/645 "Operating mode AO1/2" sets whether the voltage outputs V1/2 (DC-10 V...0...10 V) or the current outputs C1/2 DC(0(4)...20 mA) are in effect. Selection options for the analog outputs → Parameter menu P640/643 Max. permitted cable length: 10 m Reference potential for analog signals (REF1, REF2, AI.., AO..) 7 Binary inputs 1...8, with factory setting "no function" The binary inputs are electrically isolated by optocouplers. Selection options for the binary inputs → Parameter menu P61_ Reference potential for the binary inputs DI1Ø...17 Reference potential for binary signals – Without jumper X22:9-X22:10 (DCOM-DGND) → Isolated binary inputs – With jumper X22:9-X22:10 (DCOM-DGND) → Non-isolated binary inputs Binary outputs 1...8, with factory setting "no function" Load capacity of the binary outputs: Imax = DC 50 mA (short-circuit proof, protected against external voltage) Do not apply external voltage to the binary outputs! Supply voltage DC+24 V for binary outputs D01Ø ... D017, non-isolated (reference potential DGND) X23 1 2 3 4 5 6 X22 AOV 1 AOC1 AGND AOV 2 AOC2 AGND X21 1 2 3 X20 AI21 AI22 AGND Function 8 9 10 11 12 13 14 15 16 17 06193AXX 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 371 Installation Connection and terminal description of the DIO11B option 9 Voltage input 24VIN The 24VIN (X23:9) voltage input serves as DC+24 V supply voltage for the binary outputs DO1Ø ... DO17. Reference potential is DGND (X22:10). The binary outputs do not give a level if the DC+24 V supply voltage is not connected. The supply voltage DC+24 V can also be jumpered from the X10:8 connection of the basic unit if the load does not exceed DC 400 mA (current limitation in X10:8). DIO11B 0V 24V X22 10 DGND 9 24V IN X23 06556AXX Figure 187: Voltage input 24VIN (X23:9) and reference potential DGND (X22:10) Voltage input n2 The analog setpoint input n2 (AI21/22) can be used as a differential input or as an input with AGND reference potential. Differential input Input with AGND reference potential DIO11B DIO11B X20 -10...0...+10 V 1 2 3 AI21 AI22 AGND 0...+10 V X20 + 1 2 3 AI21 AI22 AGND 06668AXX Figure 188: Setpoint input n2 Current input n2 You must use an external load if the analog setpoint input n2 (AI21/22) should be used as a current input. For example RB = 500 Ω → DC 0...20 mA = DC 0...10 V DIO11B X20 0...10 V 0...20 mA 1 2 3 AI21 AI22 AGND 06669AXX Figure 189: Current input with external load 372 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters Installation Connection and terminal description of the DIO11B option Voltage outputs AOV1 and AOV2 9 Analog voltage outputs AOV1 and AOV2 must be assigned as shown in the following diagram: DIO11B X21 V 2 DIO11B 1 2 3 AI21 AI22 AGND 1 2 3 4 5 6 AOV 1 AOC1 AGND AOV 2 AOC2 AGND X20 X21 -10...0...10 V -10...0...10 V X20 1 V 1 2 3 AI21 AI22 AGND 1 2 3 4 5 6 AOV 1 AOC1 AGND AOV 2 AOC2 AGND 3 4 5 6 7 06196AXX Figure 190: Voltage outputs AOV1 and AOV2 8 Current outputs AOC1 and AOC2 9 Analog current outputs AOC1 and AOC2 must be assigned as shown in the following diagram: DIO11B X20 0(4)...20 mA + A - X21 10 DIO11B 1 2 3 AI21 AI22 AGND 1 2 3 4 5 6 AOV 1 AOC1 AGND AOV 2 AOC2 AGND X20 X21 0(4)...20 mA + A 1 2 3 AI21 AI22 AGND 1 2 3 4 5 6 AOV 1 AOC1 AGND AOV 2 AOC2 AGND 11 12 13 14 06197AXX Figure 191: Current outputs AOC1 and AOC2 15 16 17 18 19 20 21 22 System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters 373 Installation Connection OptionDFC11B 9 9.22 Connection OptionDFC11B Part number CAN-Bus interface type DFC11B: 824 317 4 The "CAN-Bus interface type DFC11B" option is only possible in conjunction with MOVIDRIVE® MDX61B, not with MDX60B. The DFC11B option must be plugged into the fieldbus slot. The DFC11B option is powered via MOVIDRIVE® MDX61B. A separate voltage supply is not required. Front view of DFC11B Description DIP switch Terminal Function DIP switch block S1: Sets the terminating resistor R nc Terminating resistor for the CAN-Bus cable Reserved X31: CAN bus connection X31:3 X31:2 X31:1 CAN Low (jumpered with X30:2) CAN High (jumpered with X30:7) DGND X30:1 X30:2 X30:3 X30:4 X30:5 X30:6 X30:7 X30:8 X30:9 Not assigned CAN Low (jumpered with X31:3) DGND Not assigned Not assigned DGND CAN High (jumpered with X31:2) Not assigned Not assigned DFC 11B ON OFF R nc S1 3 2 1 X31 1 6 9 5 X30 X30: CAN bus connection (Sub-D9 to CiA standard) 55405AXX Connection MOVIDRIVE® CAN 374 The DFC11B option is connected to the CAN-Bus at X30 or X31 in the same way as the SBus (→ Sec. "System bus connection (SBus 1)") in the basic unit (X12). In contrast to the SBus1, SBus2 is electrically isolated and made available via option DFC11B. System Manual – MOVIDRIVE® MDX60B/61B Drive Inverters
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project