INSTALLATION/OPERATING/ MAINTENANCE

INSTRUCTIONS

Air to Water Heat Pump

LSQ03RC,04RC,05RC,06RC, 10RC

1. READ IMMEDIATELY

1.1. Important Information

Prior to opening the unit it must be ensured that all electrical circuits are disconnected from the power supply.

During transport, the heat pump must not be tilted more than 45 (in either direction).

The intake and outlet openings must not be restricted nor obstructed.

Do not use any cleaning agents containing sand, soda, acid or chloride as these may damage the surface.

To prevent consequential damage it is imperative that the water circuit be neutralized after cleaning using appropriate agents.

The unit is not suitable for frequency converter operation.

Work on the refrigeration circuit may be performed by qualified persons only.

1.2. Legal Provisions and Guidelines

This heat pump was designed and built in compliance with all relevant EU directives, DIN and VDE regulations (see EC Declaration of Conformity). The electrical connection of the heat pump must be performed according to and conforming with all relevant VDE,

EN and IEC standards. Beyond that, all technical connection requirements of the local electrical utility company have to be observed. On connecting the heating system, all relevant regulations have to be complied with.

1.3. Energy-Efficient Use of the Heat Pump

By purchasing this heat pump you contribute to the protection of the environment. A prerequisite for energy-efficient operation is the proper design of the heat source system and the heat utilization system.

One of the most important factors of heat pump efficiency is keeping the temperature difference between the heating water and the heat source as small as possible. It is therefore strongly recommended that the design of both the heat source system and the heat distribution system be carried out with great care. A 1 Kelvin (1 C) higher temperature difference corresponds to an increase

in power consumption of approx. 2.5%. When designing the heating system care must be taken that special applications such as domestic water heating are taken into consideration and dimensioned for low temperature operation. Heat pumps are optimally suited for underfloor heating (surface/radiant heating) applications due to the low supply temperatures (30 C to 40 C).

During operation it is essential that the heat exchanger is not contaminated as this would increase the temperature difference resulting in a lower coefficient of performance.

A considerable contribution to the economical operation is made by the heat pump controller provided it is set correctly. For more detailed information refer to the operating manual of the heat pump controller.

2. PURPOSE OF HEAT PUMP

2.1. Application

The air to water heat pump is designed for use in existing or newly built heating systems.

The heat pump is designed exclusively for the heating of water for space heating and of domestic hot water!

The heat pump is suitable for both mono-energetic and bivalent operation at outdoor temperatures down to -20 C.

2.2. Principle of Operation

Ambient air is drawn in by the fan and passed over the evaporator (heat exchanger). The evaporator cools the air, i.e. it extracts the heat it contains. In the evaporator, the heat removed is transferred to the working fluid (refrigerant).

With the aid of an electrically driven compressor, the absorbed heat is "pumped" to a higher temperature level through an increase in pressure and given off to the heating water via the condenser (heat exchanger).

In so doing, the electrical energy is used to raise the heat of the environment to a higher temperature level.

Due to the fact that the heat energy extracted from the air is transferred to the heating water, this type of appliance is referred to as an air to water heat pump.

The air to water heat pump consists of the following main components: Evaporator, fan and expansion valve as well as the low-noise compressor, the condenser and the electric control unit.

In the case of low ambient temperatures, air humidity may accumulate on the evaporator in the form of frost impairing the heat transfer. The evaporator is automatically defrosted by the heat pump, as required, with the possibility of vapor plumes forming at the air outlet, depending on the weather.

3. SCOPE OF DELIVERY

3.1. Baseline Unit

The heat pump is delivered as a compact unit containing the components listed below.

Copeland Scroll Compressor

Condenser ( 316 stainless steel brazed plate heat exchanger)

Evaporator

Alco Expansion Valve

Accumulator

Gas/Liquid Separator

4-way Reversing Valve

Defrost Heating Cable

The refrigerant used is R404A.

3.2. Control Box

The control box is integrated in the heat pump.

The control box houses the mains terminals as well as the power contactors and mainboard of the controller.

3.3. Heat Pump Controller

For the operation of your air to water heat pump, the heat pump controller included in the scope of delivery is to be used.

The heat pump controller is a comfortable electronic regulating and control unit. It controls and monitors the entire heating system as a function of the outdoor air temperature, the hot water preparation and the safety devices.

Method of functioning and operation of the heat pump controller are described in the enclosed operating manual.

4. TRANSPORT

During transport, the heat pump must not be tilted more than 45 (in either direction).

The unit should be transported to the final installation site on a wooden pallet. The baseline unit can be transported either by means of a lift truck, a sack trolley, or the like.

5. INSTALLATION

5.1. Positioning of the Unit

The unit should always be installed on a permanently level, smooth and horizontal surface.

The entire base frame should thereby make close contact with the floor in order to ensure adequate sound insulation and to prevent water-carrying parts from cooling out. Failing this, additional insulation measures may become necessary. It must be possible to carry out servicing work without any problems. This is ensured if a clearance of 1.2 m to solid walls is maintained.

5.2. Condensate Line

Large amounts of condensation water as well as melt water from defrosting can be produced. Provide good drainage at the installation area and make sure water cannot run out onto paths or the like during periods that ice can form. Ideally condensation water is led off to a drain or similar. The condensation water pipe must have a minimum diameter of 50 mm and should be discharged to the sewer drain in a frost-proof location.

6. MOUNTING

6.1. General Information

The following connections need to be made on the heat pump:

- supply/return lines of the heating system

- condensate drain

- control lead to the heat pump controller

- power supply

6.2. Heating-Side Connection

The connections on the heating side of the heat pump are provided with 1"external thread. The hoses to be connected exit the unit through its side plate.

When carrying out the connections, use a wrench to counterhold at the transitions.

Before completing the heat pump connections on the heating water side, the heating installation must be flushed in order to remove any impurities that may be present, residues of sealing agents, or the like. Any accumulation of residues and other deposits in the

condenser may result in reduced efficiency of the unit or a total failure of the heat pump. On systems equipped with heating water flow shut-off devices such as radiator or thermostat valves, an overflow valve to be provided by the customer needs to be installed at the outlet of the heating pump in a heating bypass. This assures a minimum heating water flow through the heat pump and prevents any malfunctions from occurring.

Once the installation on the heating side has been completed, the heating system must be filled, deaerated and pressure-tested.

6.3. Anti-freeze Protection

On heat pumps installed in a location prone to frost, a manual drain valve should be provided.

Provided the controller and heating circulating pumps are ready for operation, the anti-freeze protection function of the controller is active. If the heat pump is taken out of service or in the event of a power failure, the system has to be drained. In heat pump installations where a power failure cannot be readily detected (holiday house), the heating circuit must contain a suitable antifreeze product.

7. COMMISSIONING

7.1. General Information

To ensure proper commissioning it should be carried out by an after-sales service authorized by the manufacturer. Only then can an extended warranty period of 2 years in total be granted.

7.2. Preparatory Steps

Prior to commissioning, the following items need to be checked:

- All connections of the heat pump must have been made.

- In the heating circuit all valves that could impair the proper heating water flow must be open.

- The air intake/discharge path must be unobstructed.

- The sense of rotation of the fan must correspond to the direction of the arrow.

- The settings of the heat pump controller must be adapted to the heating installation in accordance with the instructions contained in its instruction manual.

- Proper condensate drainage must be ensured.

8. CLEANING / CARE

8.1. Care

To protect the paint finish, avoid placing objects against or on the unit. The external parts of the heat pump can be wiped with a damp cloth and commercially available cleaning agents.

Do not use any cleaning agents containing sand, soda, acid or chloride as these may damage the surface.

To prevent malfunctions in the heat exchanger of the heat pump caused by dirt deposits, care must be taken that the heat exchanger in the heating installation cannot become contaminated. In the event that operating malfunctions due to contamination occur nevertheless, the system should be cleaned as described below.

8.2. Cleaning of Heating Side

The ingress of oxygen into the heating water may result in the formation of oxidation products. An additional contamination of the heating water caused by residues of lubricating and sealing agents occurs in many cases.

Both of the above causes may lead to a reduction in the performance of the heat pump condenser. In these cases the installer needs to clean the condenser. Based on information known to date we recommend cleaning with a 5% phosphoric acid solution or, in the case that cleaning needs to be performed more frequently, with a 5% formic acid solution. In either case, the cleaning fluid should be at room temperature. Thorough flushing is necessary to ensure that all cleaning agent residues are removed from the system. It is recommended that the heat exchanger is cleaned in the direction opposite to the normal flow direction. Owing to their acid content flushing agents must be used with caution. To prevent acidic flushing agents from entering the heating installation when cleaning the condenser, we recommend that the flushing device be mounted directly to the supply and return line of the heat pump.

To prevent consequential damage it is imperative that the water circuit be neutralized after cleaning using appropriate agents.

8.3. Cleaning of Air Side

Evaporator, fan and condensate drain should be cleaned of debris (leaves, branches, etc.) from time to time.

When cleaning do not use any sharp or hard objects so as to prevent any damage to the evaporator and the condensate pan.

9. MALFUNCTIONS /TROUBLESHOOTING

This heat pump is a quality product and is designed for troublefree and maintenance-free operation. In the event that a malfunction occurs nevertheless, you will be able to correct the problem easily yourself in the majority of cases. Simply consult the Malfunctions and Troubleshooting table in the operating manual of the controller. Malfunctions can be interrogated at the heat pump controller. If the problem cannot be corrected by the user, please contact the after-sales service in charge. Any work on the heat pump may

only be performed by authorized and qualified after-sales service technicians.

Error

Code

Description Possible Reason Solution

E1

E2

E3

E4

E5

Inlet Water

Temperature

Sensor

Malfunction

Outlet Water

Temperature

Sensor

Malfunction

Ambient Air

Temperature

Sensor

Malfunction

Evaporator Coil

Temperature

Sensor 1

Malfunction

Evaporator Coil

Temperature 2

Sensor

Malfunction

1) The inlet water temperature sensor has a poor contact

2) The inlet water temperature sensor is damaged

1) The outlet water temperature sensor has a poor contact

2) The outlet water temperature sensor is damaged

1) The ambient temperature sensor has a poor contact

2) The ambient temperature sensor is damaged

1) The evaporator coil temperature sensor

1 has a poor contact

2) The evaporator temperature sensor 1 is damaged

1) The evaporator coil temperature sensor

2 has a poor contact

2) The evaporator coil temperature sensor

2 is damaged

1) Loop wire terminals 1 and 2 (no matter whether water flow switch is installed) to see if E6 still shows up. If yes, the mainboard is defected.

1) Improve the contact

2) Replace the sensor

1) Improve the contact

2) Replace the sensor

1) Improve the contact

2) Replace the sensor

1) Improve the contact

2) Replace the sensor

1) Improve the contact

2) Replace the sensor

Replace mainboard

2) The wires of water flow switch have a poor contact to the terminal block

Improve the contact

E6

Insufficient

Water Flow

Protection

E7,E9

High Pressure

Protection

3) The water flow switch circuit is not closed. a) The water piping system has a leakage; b)The water pump is undersized; c) There is no power supply to the water pump or the water pump is defected; d)

The water circuit ( for example the particle filter) is blocked; e) The mainboard is defected. a) find the leakage point and repair it;b) select the correct water pump size; c) make sure that the water pump will work; d) clean the water circuit; e) replace the mainboard

1) The water pump is undersized.

2) The water pump is installed in the wrong direction or the three phase water pump is running in the opposite direction.

1) Size the water pump correctly; 2)

Check and make sure that the water pump is correctly installed; 3) Vent the air in the water circuit; 4) Clean the particle filter; 5) Size the water pipe

3) Air exists in the water circuit.

4) The particle filter on the inlet water pipe is blocked.

5) The pipe diameter is too small or there is a bottleneck restriction. correctly; 6) Replace the high pressure switch; 7) Replace the mainboard ; 8)

Clean the condenser; 9) Use a water tank with bigger copper coil surface.

6) The high pressure switch is damaged

7) The mainboard is damaged.

8) The condenser is dirty, resulting in poor heat transfer

9) The surface area of the copper coil inside the buffer tank/hot water cylinder is too small.

E8,E10

Low Pressure

Protection

1) There is a gas leakage in the refrigeration system

2) The low pressure switch is damaged

1) Find the hole where the leakage occurs and repair it. Fill the gas after the system is vaccumized; 2) Replace the low pressure switch.

Ice builds up on the evaporator but the system cannot defrost it properly.

Water temperature rises too slowly

1) Defrost cut-in temperature is set incorrectly.

2) The evaporator coil temperature sensor is placed in the wrong position.

3) The Ohm value of the evaporator coil temperature sensor changes abnormally; the sensor has a poor contact or is damaged.

Set the defrost cut-in temperature as factory default "-2 "

Place the sensor on the second lowest row of coil on the evaporator

Improve the contact or replace the sensor

4) The unit cycles on and off too often.

Hence the defrost delay time (P1) condition is not satisfied.

Replace with a smaller heat pump;

Install a bigger buffer water tank in the house heating system; increase set water temperature difference (PA) value.

1) The heat pump is undersized.

2) The water tank is poorly insulated.

Size the correct model

Insulate the water tank/pool properly

3) Water pipes are poorly insulated. Insulate the water pipe properly

4) Mains water supply is unreasonable. Redesign the mains water supply

5) The space between inlet water pipe and outlet water pipe is too narrow, resulting in water shortcircuit.

The space between inlet and outlet water pipes should be no less than 1m

6) The heat pump is installed in a place where the ventilation is not good.

7) Insufficient refrigerant inside the system.

Improve the ventilation

Check where the leakage is and fill refrigerant

Water pump and fan motor is running, but the compressor does not start

1) The phase sequence board in the electrical box activates fault-phase or lack-phase protection

2) Phase sequence board is damaged

1) No power input

2) Power voltage is not correct

3) Power voltage drops when the unit is started. The unit draws a huge current.

Check if there is a lack-phase and put the phase wire in the right position

Replace the phase sequence board

Plug in the power cord

Start the heat pump under the right voltage

Low power capacity in the network;

Wires in wrong diameter (too small) are used.

Heat pump does not start properly

4) Fault-phase or lack-phase problem with the mains power supply.

5) Poor contact problem with the wiring in the system.

6) The heat pump is in clock timer shutdown state.

7) The system is in protection.

Put the phase wires in the right position

Improve the contact

Check the clock timer settings. Reset or cancel it.

Check what kind of protection it is and remedy it.

8) Damaged mainboard or damaged temperature sensor.

Replace the mainboard or sensor

10. DIMENSIONED DRAWINGS

10.1.

Dimensioned Drawing .

10.2.

11. EQUIPMENT DATA

Model

Outlet Water Rated Temp(℃)

Outlet Water Max. Temp(℃)

A7/W35 EN14511

Heating Capacity(KW)

COP

A2/W35 EN14511

Heating Capacity(KW)

COP

A-2/W35 EN14511

A-7/W35 EN14511

Power Supply (V/PH/HZ)

Compressor Type

Compressor Qty

Cabinet Material

Heating Capacity(KW)

COP

Heating Capacity(KW)

COP

Gas Flow Restriction

Defrosting Device

Condenser Type

Water Flow Rate (m3/h)

Two Speed Fan Motor

Refrigerant Type

Refrigerant Charge(kg)

Ambient Air Range

Pipe size (inch)

Dimensions(mm)

Air Discharge

Weight

Length

Width

Height

LSQ03RC LSQ04RC LSQ05RC LSQ06RC LSQ10RC

35

58

10.3

11.9

15.9

18.5 31.5

4.2

8.1

3.4

7.1

3

6.2

4.4

10.3

3.9

8.6

3.3

7.5

4

13.2

3.4

11.9

3.1

10

3.9

15.9

3.5

13.6

3

12.2

2.7 2.9

220(380)/1(3)/50

2.7

2.8

380/3/50

2.6

Copeland Scroll

1 2

Powder Coated Galvanized Steel Cabinet/Stainless Steel Cabinet

Alco Thermal Expansion Valve

4-way Reversing Valve

3.9

25.5

3.4

22.6

3

19

1.4

2.5

115

1080

470

760

1.8

Stainless Steel Brazed Plate

2.3 2.7

3

Yes

R404A

3.8 4.4

-25℃~35℃

1"

135

Horizontal

1050

150

1130

500

160

1.25"

4.6

7.6

1430

600

1260

280

12. WIRING DIAGRAMS

13. Schematics of Installation

13.1. Schematics of Space Heating

13.2. Schematics of Space Heating/Hot Water Heating

14. Controller

Controller type: 15

This controller is applicable to both single compressor and dual compressors units.

This controller includes three parts: mainboard, control panel and connecting wires.

14.1. Mainboard Layout

COMP1: Compressor 1

COMP2: Compressor 2

4WV1: 4-way Reversing Valve 1

4WV2: 4-way Reversing Valve 2

FAN1: Fan Motor, Low Speed

FAN2: Fan Motor, High Speed

PUMP: Water Pump

HOT: Backup Electricity Heater

A-HOT: Crankcase Heater

P-W: Solenoid for Hot Water

S-F: Solenoid for Defrost Heating Cable

ERR: Error Light

CN3 : Inlet Water Temperature Sensor

CN4 : Outlet Water Temperature Sensor

CN5 : Ambient Temperature Sensor

CN6 : Evaporator Coil Temperature 1 Sensor

CN7 : Evaporator Coil Temperature 2 Sensor

CN8 : Hot Water Temperature Sensor

CN9 : Gas Discharge Temperature 1 Sensor

CN10: Gas Discharge Temperature 2 Sensor

CN11: Control Panel

CN12: Assist Unit

COM: Common Port

EN: Interlock Signal

HP1: High Pressure Protection 1

LP1: Low Pressure Protection 1

HP2: High Pressure Protection 2

LP2: Low Pressure Protection 2

OV1: Compressor 1 Overload

OV2: Compressor 2 Overload

FLOW: Water Flow Switch

SET: Anti-freeze Protection

BUS: Comprehensive Protection

14.2. Jumper Settings

State

Function

Switch

Disconnected

JP1

JP2

JP3

JP4

Loop Wired

Equipments Self-checkup. User regulation not allowed.

Both Systems Valid System 1 Valid Only

Jumpers 5, 6,7 and 8 are used to set Duty/Assist Unit No.

JP8

0

0

JP7

0

0

JP6

0

0

JP5

0

1

0 0 1 0

Unit

No. 1 ( Duty)

No. 2 (Assist)

No. 3 (Assist)

Remarks

Backup

Backup

0

0

0

0

1

1

1

0

0

1

0

1

No. 4 (Assist)

No. 5 (Assist)

No. 6 (Assist)

0

0

1

1

X

14.3. Control Panel

1

1

0

0

X

1

1

0

0

X

0

1

0

1

X

No. 7 (Assist)

No. 8 (Assist)

No. 9 (Assist)

No. 10 (Assist)

Invalid

ON/OFF

Press ON/OFF to switch on/off the unit.

MODE

Press MODE to select the running mode.

Mode selection is valid only when the compressor is off.

Cooling Mode: the unit will cool the water till the water temperature reaches the set point.

Heating Mode: the unit will heat the water till the water temperature reached the set point.

Auto Mode: the unit will cool the water till the water temperature reaches the set point, and automatically heat the water till the water temperature reaches the set point.

Note: Hot water heating mode can only be activated in parameter setting.

RESET

When an error code is displayed on the screen, press RESET. If the error is rectified, the error code will disappear. If the error is not rectified, the error code will remain on the screen.

Press

to set the parameter value upwards by 1 degree or 1 min.

Press

▼to set the parameter value upwards by 1 degree or 1 min.

When the unit is off, the user can hold

▼ for 5 seconds to enter forced defrost mode even if the defrost cut-in conditions are not satisfied.

Note: to set water temperature for heating/cooling, switch on the control panel (

ON/OFF), and then press

▲or ▼to adjust the set water temperature.

TIMER (24hours/7days)

Press TIMER and then

▼ to set unit automatic on/off time.

First Press: set HOUR digit for unit automatic on;

Second Press: set MINUTE digit for unit automatic on;

Third Press: set HOUR digit for unit automatic off;

Fourth Press: set MINUTE digit for unit automatic off.

Fifth Press: exit Timer state.

Note: when the set times are the same, the timer setting will become invalid.

Hold Timer Button for five seconds to set clock time.

First Press: set HOUR digit of the clock time.

Second Press: set MINUTE digit clock time.

Third Press: exit clock time setting.

Note: if no action is made in five seconds, the controller will exit setting state.

When both unit automatic on and automatic off times are set, every day the unit will run according to this setting

LANG

Press this button to select the Unit Number for running parameters checkup (if multiple units are installed in one project and modular control function is in use).

SET

Press SET button directly to check running parameters. If the unit No. shown on the display is “1”, the displayed parameters are from the duty unit. Otherwise the displayed parameters are from the assist unit (depending on the Unit

Number set on LANG.

14.4. Running Parameter Checkup

Duty Unit

Item Parameter Name

1 Inlet Water Temp

2 Outlet Water Temp

3 Ambient Air Temp

4 Evaporator Coil Temp 1

5 Evaporator Coil Temp 2

6 Hot Water Temp

7 Discharge Gas Temp Compressor 1

8 Discharge Gas Temp Compressor 2

Unit

Assist Unit

Item Parameter Description Unit

1 Evaporator Coil Temp 1

2 Evaporator Coil Temp 2

3 Discharge Gas Temp Compressor 1

4 Discharge Gas Temp Compressor 2

5 Error?

Code

Hold SET for 10 seconds to enter parameter setting.

Press

SET again to select the parameter item in sequence.

The first two digits stand for the parameter item number and the last two digits stand for the parameter value.

14.5. Screen Symbols

HEAT: heating mode

COOL:

HOT WATER: cooling mode. hot water heating mode. Shows up when hot water heating function activated.

DEF:

NET:

Defrost Mode. Shows up in defrosting mode.

Remote Control Function. Shows up when remote control function activated.

14.6. Parameter Settings

Item Parameter Name

1 Hot Water Temp

2 Defrost Cut-in Time

3 Defrost Cut-out Time

4 Defrost Cut-in Temp

5 Defrost Cut-out Temp

6

7

8

9

Defrost Heating Cable Cut-in

Ambient Temp

Backup Electricity Heater Cut-in

Ambient Temp

E20/E21 Cut-in Discharge Gas

Temp

E20/E21 Cut-out Discharge Gas

Temp

10 E16 Cut-in Outlet Water Temp

Max Min

60

Unit

25 ℃

90

25

30 min

3 min

5

25

10

12

120

120

10

70

-9 ℃

5 ℃

-10 ℃

-10 ℃

70 ℃

70 ℃

0 ℃

40 ℃ 11 E15 Cut-in Outlet Water Temp

12

E6 Cut-in Inlet/Outlet Water

Temp Diff

13 E14 Cut-in Inlet Water Temp

14 Water Temperature Diff

15 Up Limit

16 Down Limit

50

5

10

10

10

5 ℃

0 ℃

1 ℃

1 ℃

1 ℃

17 Unit Type Selection

18 Quantity of Heat Pump Units

2

10

0

1

Default Remarks

55 Only valid when P25 value is set as 1.

30

8

-2

15

0

6

Only valid when defrost heating cable

( to help defrost ice) is installed

Only valid when backup electricity heater is installed

95

75

5

65

10

3

5

5

5

Only valid when unit is in Auto Mode

1

2=heating only,1=heating & cooling,

0=cooling only

1

19 Weather Compensation Valid? 1 0

20

Compensation Temperature in

Heating

21

22

23

Compensation Coefficient in

Heating

Ambient Temp to Change Fan

Motor Speed

Automatic On Allowed after

Power is Restored?

24 Interlock Function Valid?

25

Hot Water Heating Mode

Activated

30

30

20

1

1

1

0

1

0 ℃

0

0

0

0 1=yes;0=no

20

10

5

Only valid when P19 value is set as 1.

Automatically set water temperautre

= P20+P21/10*(P20

– ambient temperature).

The display value for P21 will be 10 times set value

Only valid in heating & hot water heating mode

1 1=yes;0=no

1 1=yes;0=no

0 1=yes;0=no

Water Temperature In Cooling

Mode

Water Temperature In Heating

Mode

Water Temperature in Auto

Mode

25

60

50

8 ℃

25 ℃

10 ℃

12

40

30

Switch on the control panel and then press Up or Down button to change the set water temperature in cooling, heating and auto mode. The range of water temperatures is different in different modes.

15. Function Description

15.1. Automatic Mode

The unit will select heating or cooling mode automatically depending on the current inlet water temperature.

When Ti

≥ Ts + P15, the unit enters cooling mode;

When Ti

≤Ts – P16, the unit enters heating mode;

Where Ti is inlet water temperature read by CN3, Ts is the set water temperature, P15 is the parameter value set in P15, and

P16 is the parameter value set in P16.

15.2. Cooling Mode

l Compressor On Conditions:

When Ti

≥ Ts + P14, the compressor(s) is (are) on; l Compressor Off Conditions:

When Ti

≤ Ts, the compressor(s) is (are) off;

Where P14 is the parameter value as set in P14.

15.3. Heating Mode

l Compressor On Conditions:

When Ti

≤Ts – P14, the compressor(s) is (are) on; l Compressor Off Conditions:

When Ti

≥ Ts, the compressor(s) is (are) off;

In units with dual compressors, there is a delay of thirty seconds between the two compressors

’ starts/shutdowns.

15.4. Hot Water Heating Mode

Hot water heating mode is only a submode in Cooling or Heating Mode. When the unit is installed for house heating or house cooling and at the same time domestic hot water heating is needed, this function is needed. When the unit is installed only for domestic hot water heating ( without house heating and house cooling ), do not activate hot water heating mode. Use heating mode to control hot water heating.

Hot Water Heating Function Cut-in Condition

Water temperature ( ready by CN8)

≤ P1- P14

When above condition is satisfied, the three way valve will energize to direct the water from the condenser to the hot water tank. Unit will be switched from cooling or heating mode to hot water heating mode.

Hot water Heating Function Cut-out Condition

Water temperature ( ready by CN8)

≥ P1

When the above condition is satisfied, the three way valve will de-energize to direct the water back to house heating equipments.

15.5. Backup Electricity Heater Control

l Heater On Conditions a. Ti

≤Ts – P14-3℃, and b. Ta

≤P7,and c. The compressor has run for at least 60 seconds in heating mode.

Where Ti is inlet water temperature read by CN3, Ts is set water temperature, Ta is ambient air temperature read by CN5, and P7 is the parameter value set in P7. l Heater Off Conditions a. Ti

≥Ts - 2℃, or b. Ta>P7

15.6. Fan Motor Control

In cooling mode, only high speed fan (FAN2) will be active.

In heating mode,

When the ambient temperature

≥ P22, only FAN1(low speed) will be active.

When the air temperature<P22, only FAN2 (high speed) will be active.

The fan motor has three speeds, with low speed in yellow color, medium speed in blue color and high speed in black color. A factory set unit has blue wire connected to FAN1 and black wire connected to FAN2. It is not recommended to change high speed to low speed manually because insufficient air volume in low air temperatures could damage the unit.

The fan motor will be off when the unit is in defrost mode.

15.7. Defrost Control

Defrost Cut-in Condition

In Heating or Hot Water Heating Mode, when the evaporator coil temperature (read by CN6/CN7) is lower than P4, the unit begins to count the time. If the count time is equivalent to or bigger than P2, the corresponding system enters defrost mode.

When the defrost cut-in conditions of System 1 (2) are satisfied, and the count time of System 2 (1) is bigger than a half of P2, both systems will enter defrost mode. Otherwise only System 1 (2) will enter defrost mode and System 2 (1) will be shutdown.

Note: During time counting period, if the evaporator coil temperature is observed to be higher than P4, the count time will be restored to zero.

In defrost mode, the water pump and the corresponding compressor continue to work, fan motor stops, and 4-way reversing valve energizes.

Defrost Cut-out Conditions (Sufficient) a. The Evaporator Coil Temp

≥P5; b. Defrost time

≥P3;

When any of the above conditions are satisfied, defrost mode will be terminated.

15.8. Crankcase Heater Control

In heating mode, when the ambient air temperature is lower than 10℃, the heater will turn on when compressor is off and turn off when the compressor is on.

When the ambient air temperature is above 15 ℃, the crankcase heater will turn off.

Control of 4-way Reversing Valve

The 4-way reversing valve will be activated when the unit is in cooling or defrost mode. In heating mode the 4-way reversing valve will not be activated.

15.9. Remote Control

Set P24 as “1”to activate Remote Control Function.

If this function is activated, put a signal switch between ports COM and EN. The mainboard will keep checking the state of switch between ports COM and EN. If it is from on to off, the unit will be started. If it is from off to on, the unit will be shut down.

15.10. Power Failure Memory

The parameter settings will not be lost on power failure occasions; If control panel is disconnected by accident, the system will remain working as normal.

No matter the power failure occurs while the unit is on or off, once the power is restored the unit will be restored to the state prior to the occurrence of power failure (if parameter value for P23 is set as 1).

Note: If hot water heating function is activated, after the power is restored, the unit will run in hot water heating mode first before it goes back to the original mode.

Defrost Heating Cable Control

In heating mode, when ambient temp is lower than P6 set value, the defrost heating cable will turn on to help defrost the ice accumulated in the base pan of the heat pump.

15.11. Weather Compensation

Set P19 value as “1” to activate weather compensation function. Once this function is activated, the water temperature will be automatically set according to different ambient temperatures.

For example, if P20 value is set as”20” and P21 value is set as “10”, the automatic set water temperatures in different ambient temperatures will be as below.

15.12. Modular Control Function

Set P18 value according to actual quantity of units.

Set Jumpers No. 5 to No. 8 on the mainboard of each unit accordingly.

Connect the unit one by one through CN12.

Ambient

Temperature (Ta)

Coefficient

(P21)

10

Compensation

Temperature (P20)

Set Water Temperature

20 =P20+P21*0.1*(P20-Ta)

-7

-8

-9

-10

-11

-1

-2

-3

-4

2

1

0

-5

-6

-12

-13

-14

-15

5

4

3

9

8

7

6

15

14

13

12

11

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

10

Auto Set Water Temp Table

60

50

40

30

20

10

0

15 12

9 6 3 0

-3 -6 -9

Ambient Temp ( deg C)

-12 -15

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

20

Coefficient

Compensation Temp (deg C)

Auto Set Water Temp ( deg

C)

47

48

49

50

51

38

39

40

41

42

43

44

45

46

52

53

54

55

31

32

33

34

35

36

37

25

26

27

28

29

30

Weather compensation settings will only be valid in heating mode and will not affect the manually set water temperature in hot water heating mode and cooling mode.

16. Unit Protection

16.1. Winter Anti-freeze Protection

While the unit is off,

When Ta ≤5℃, and Ti≤P13 where Ta is the ambient temperature, Ti is the inlet water temperature and P13 is the parameter value set in P13, in sixty seconds the unit will automatically run in heating mode to protect water from freezing.

Anti-freeze Protection Process

Display Error Code “E14” ——> Pump On ——> Backup Electricity Heater, Fan Motor 1 and 2, Compressor 1 and 2

On——> Inlet Water Temp>15℃——> All outputs closed in sequence——> Unit back to Off State

When Ta ≤5℃, and Ti≤P13 + 3℃

The water pump will run for 5 min every 30 min.

16.2. Compressor Running Protection

Time Delay from Compressor On to Compressor Off: 60 seconds.

Time Delay from Compressor Off to Compressor On: 180 seconds.

16.3. Brazed Plated Heat Exchanger Anti Freeze Protection

In cooling mode,if the outlet temperature remains below P10 for 60 seconds continuously, the protection will be activated. The compressor will be shut down but the water pump will continue to work. After the outlet water temperature is 3℃ higher than

P10, the unit will be restored to the original running mode in 3 minutes.

When the anti freeze port “SET”is disconnected, the compressor will be shut down. When the anti freeze port is connected, the unit will be restored to the original running mode.

16.4. Outlet Water Temperature in Heating Too High

In heating, if the outlet water temperature is higher than P11, the protection will be activated. The compressor and the backup electricity heater (if installed) will be shut down. When the outlet water temperature is 15℃ lower than P11, the unit will be restored to the original running mode.

16.5. Temperature Sensor Malfunction Protection

Malfunction with any of Inlet Water, Outlet Water, Ambient Air, Hot Water or Evaporator Coil Temperature Sensors will close all outputs.

Note: Water Pump control in antifreeze protection will never be blocked.

16.6. Insufficient Water Flow Protection

All outputs will be closed if water flow is insufficient or the water flow switch is malfunctioning.

System uses two approaches to check whether the water flow is insufficient.

Water Flow Switch

System will check the state of Water Flow Switch one minute after the water pump is on. Insufficient water flow protection will be activated if the switch is observed to be disconnected for a continuous 10 seconds.

Water Temp Difference between Inlet and Outlet

When inlet/outlet water temperature difference is bigger than P12, insufficient water flow protection will be activated.

16.7. High/Low Pressure Protection

1) High Pressure Protection:If the High Pressure Switch is observed to be disconnected, High Pressure Protection will be activated and the corresponding compressor will be shut down.

2) Low Pressure Protection: When the Low Pressure Switch is observed to be disconnected for a continuous 10 seconds, the corresponding compressor will be shut down.

(Low Pressure Protection will be blocked in the first three minutes in heating mode, in the first 30 seconds in cooling mode and in defrosting state.)

Error Code Input Port Error Description Code Results

01

Inlet Water Temp Sensor

Malfunction

E1 Close All Outputs

02

03

04

05

06

07

08

09

10

11

12

13

14

15

16

17

18

19

20

HP1

LP1

HP2

LP2

OV1

OV2

SET

FLOW

Outlet Water Temp

Sensor Malfunction

E2

Ambient Air Temp Sensor

Malfunction

E3

Evaporator Coil Temp

Sensor 1 Malfunction

E4

Evaporator Coil Temp

Sensor 1 Malfunction

Insufficient Water Flow

( Water Flow Switch

Malfunction or Water

Temp Diff too Big)

High Pressure Protection

Compressor 1

E5

E6

E7

Low Pressure Protection

Compressor 1

E8

High Pressure Protection

Compressor 2

E9

Low Pressure Protection

Compressor 2

E10

Hot Water Temp Sensor

Malfunction

E11

Compressor 1 Overload E12

Close All Outputs

Close All Outputs

Close All Outputs

Close All Outputs

Close All Outputs

Compressor 2 Overload

Winter

Protection

Anti

Outlet Water Temp Too

High in Heating

Freeze

Outlet Water Temp Too

Low in Cooling

Discharge Gas Temp

Sensor 1 Malfunction

E17

Discharge Gas Temp

Sensor 2 Malfunction

E18

Communication Error

E13

E14

E15

E16

E19

Discharge Gas Temp 1 too High

E20

Shut Down Compressor

1

Shut Down Compressor

1

Shut Down Compressor

2

Shut Down Compressor

2

Close All Outputs

Shutdown Compressor

1

Shutdown Compressor

2

Turn electricity on backup heating element and run in heating mode

Shutdown Compressor and Backup Electricity

Heater

Turn off compressor, turn on pump and backup electricity heater

Close All Outputs

Close All Outputs

Close All Outputs

Shutdown Compressor

1

21

22 BUS

Discharge Gas Temp 2 too High

E21

Comprehensive Error E22

Shutdown Compressor

2

Close All Outputs