PACSystems RX3i PROFINET Scanner, IC695PNS001-ABAJ

PACSystems RX3i PROFINET Scanner, IC695PNS001-ABAJ
Important Product Information
PACSystems* RX3i
GFK-2738M
March 2017
IC695PNS001-BABA
RX3i PROFINET Scanner
The PACSystems* RX3i PROFINET Scanner module, IC695PNS001 or PNS001, connects
a remote universal RX3i I/O rack of Series 90-30 or RX3i modules to a PROFINET I/O
Controller. The PROFINET Scanner scans the modules in its rack, retrieving input data
and providing output data, and exchanges that data on the PROFINET I/O LAN at the
configured production rate.
The PNS001 manages PROFINET communication and module configuration between
an I/O Controller and modules in the remote rack. If network communications are lost,
the PNS001 manages I/O states according to the individual module configurations.
The PNS001 supports 10/100/1000 Mbps Copper, 100/1000 Mbps Multi-mode Fiber,
and 100/1000 Mbps Single-mode Fiber. PROFINET communications on the network
require 100 or 1000 Mbps link speed. Although 10 Mbps cannot be used for PROFINET
communications, 10 Mbps can be used for other types of Ethernet traffic such as PING.
Features of the RX3i PNS001 include:
▪
Configuration services for all supported Series 90-30 and RX3i I/O Modules using
Proficy* Machine Edition (PME). For a list of currently supported I/O modules, refer
to Supported Modules, Power Supplies and Backplanes.
▪
Support for daisy-chain/line, star, or ring (PROFINET Media Redundancy Protocol
(MRP)) topologies.
▪
Four switched Ethernet ports - two 8-conductor RJ-45 shielded twisted pair
10/100/1000 Mbps copper interfaces and two Small Form-factor Pluggable (SFP)
cages for user-supplied SFP devices.
▪
▪
The network can include media interfaces of more than one type.
▪
A front panel Ethernet RJ-45 port for field firmware updates.
Support for transfer of I/O Device Name to another PNS001 module using an
SD card. This eliminates the need to connect a configuration tool, such as Proficy
Machine Edition when replacing a module.
Ordering Information
IC695PNS001
PACSystems RX3i PROFINET Scanner Module 10/100/1000 with four Ports (two SFP connections, two
RJ45 connections)
Includes a blank SD card
IC695SPC100
RX3i 10/100/1000Base-T copper SFP
IC695SPF002
RX3i 100Base-FX (fiber 2 km) SFP (Multi-mode fiber - MMF)
IC695SPF550
RX3i 1000Base-SX (fiber 550 m) SFP (MMF)
IC695SPF010
RX3i 1000Base-LX (fiber 10 km) SFP (Single-mode fiber - SMF)
Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their
respective owners.
© 2013-2017 General Electric Company. All Rights Reserved.
*
2
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
Specifications: PNS001
PROFINET Support
PROFINET Version 2.3 Class A I/O Device
Redundantly controlled operation implements PROFINET V2.3 Type S-2 System Redundancy
Proficy Machine Edition
Version Required
Version 8.50 SIM 2 or later
Power Requirements
REV-BXXX or later: 3.3 Vdc
0.6 A with no SFP devices installed
1.3 A maximum (two SFP devices installed,
0.35A per SFP)
REV-BXXX or later: 5Vdc: 0.7 A maximum
Operating Temperature
Range
REV-AXXX:
0°C to 60°C
REV-BXXX or later: -25°C to 60°C
Derated to 57°C:
Derated to 57°C:
• If 100MB Fiber SFPs installed, or
• If 100MB Fiber SFPs installed, or
• If Copper SFPs operating at 1GB
• If Copper SFPs operating at 1GB
Two RJ-45 and Two SFP Cages (SFP devices not included, available separately)
Number of Port Connectors
REV-AXXX: 3.3 Vdc
1.2 A with no SFP devices installed
1.9 A maximum (two SFP devices installed,
0.35A per SFP)
REV-AXXXX: 5Vdc: 1.1 A maximum
FW Upgrade Connector
REV-BXXX: One RJ-45 Ethernet connector on REV-AXXX: One USB connector on front panel
front panel
SD Card
Supports SD and SDHC cards.
PNS001 Status and Control
Bits
32 input status bits and 32 output control bits
PROFINET I/O production
rate (I/O Update Rate)
Configurable selections: 1ms, 2ms, 4ms, 8ms, 16ms, 32ms, 64ms, 128ms, 256ms or 512ms
Number of IP addresses
REV-BXXX: Two
One for PROFINET ports.
One for front panel port. Supports Classless
Inter-Domain Routing (CIDR)
REV-AXXX: One
One for PROFINET ports.
Number of MAC Addresses
REV-BXXXX: Six
One front panel port, one for each of the
four external ports, and one internal port.
REV-AXXXX: Five
One for each of the four external ports, and
one internal port.
I/O Station Maximum Limits Number of I/O Modules per station
I/O data per station
Configuration
Number of backplane slots minus one for
PNS001 and at least one for a power supply
2880 bytes total
1440 bytes of input data
1440 bytes of output data
V2.3 GSDML file is available on the Support website http://support.ge-ip.com for download
and import into Proficy Machine Edition. The GSDML supporting a firmware release is part of
the firmware upgrade kit available on the Support website.
For installation and maintencance requirements, refer to GFK-2975.
RX3i PROFINET Scanner
IC695PNS001-BABA
3
GFK-2738M
PROFINET Scanner Status and Control Data
The RX3i PROFINET Scanner provides 32 bits of input status data and receives 32 bits of output control data. The
application program in the I/O Controller system can monitor the input status bits for the PNS001 module. The
output control bits are reserved for future use and have no function at this time.
Output Control Bits:
Rev -AXXX hardware: The 32 bits of control output assigned to the PNS module are reserved for future use.
Rev -BXXX and later hardware: The 32-bits of control output assigned to the PNS module allow the IO Controller to
dynamically control aspects of the scanner’s operation. All control bits are active high. Bit 1 is the least significant
bit.
Bit #
Name
Description
1
FW Update in A value of 1 allows the webpage firmware update to continue (and restart the PNS
Run
disrupting IO) while the PNS IO is actively controlled.
2–32
Reserved
Set to 0
Input Status Bits:
The PROFINET Scanner’s 32 bits of input status provide information about the scanner. All status bits are active
high. Bit 1 is the least significant bit.
Status
Bits
Name
Description
1
Module OK
Indicates the health of the module. A value of 0 indicates the module is powering
up or has failed. A value of 1 indicates the module is functioning properly.
2
Reserved
Set to 0
3
Port1 Link Up
4
Port2 Link Up
5
Port3 Link Up
1 = port is connected to another device and is communicating.
0 = port is not connected to another device, or the port has some sort of error
preventing communications.
6
Port4 Link Up
7-10
Reserved
Set to 0
11
MRP Enabled
Indicates whether MRP has been enabled or not. A value of 0 indicates that MRP is
not enabled. A value of 1 indicates that MRP is enabled.
12
MRP Role
Indicates the MRP role the PNS001 is operating as when MRP is enabled. A value of
0 indicates that the PNS001 is currently an MRP Client. A value of 1 indicates that
the PNS001 is currently an MRP Manager, however the PNS001 does not currently
support MRP Manager configuration. If MRP is not enabled, then this bit will be set
to zero.
13-32
Reserved
Set to 0
4
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
LEDs on the PROFINET Controller Module
Power-Up LED Patterns
At power-up, the LEDs show the patterns described in the following table. The LEDs also blink diagnostic patterns
for certain operating errors and for module identification.
Step
LED/ Blink pattern
Description
1
All LEDs off
Initial state
2
ACTIVE LED solid green
Normal operation
3
CONNECT LED solid green
Normal operation
4
STATUS LED solidate green
Normal operation
5
LAN LED solid green
Normal operation
OK LED blinks amber with
special blink code
Fatal initialization or diagnostics failure;
H/W Module Identity Information not
available
STATUS LED blinks amber with
special blink code
Fatal initialization failure.
STATUS and LAN LEDs blink
green in unison (0.5 seconds
ON/ 0.5 seconds OFF)
Internal update in process following a
firmware update. Unit should complete
update and restart automatically.
OK LED solid green
Normal operation. Power-up completed.
6
Note: Under certain ambient operating temperatures, the PROFINET Scanner could momentarily display the over
temperature pattern during power up, while it is calibrating its thermal protection functions. This indication can be
ignored. For details, refer to the section entitled Microprocessor Over-Temperature in PACSystems RX3i PROFINET
Scanner Manual, GFK-2737.
RX3i PROFINET Scanner
IC695PNS001-BABA
5
GFK-2738M
Normal Operation of Individual LEDs
The PNS001’s LEDs can operate in tandem to indicate fatal error, module location/identification, microprocessor
over-temperature, and update conditions. For details on these blink patterns, refer to PACSystems RX3i PROFINET
Scanner Manual, GFK-2737.
OK LED
The OK LED indicates whether the module is able to perform normal operation.
Green, on
OK
Off
Not OK
LAN LED
The LAN LED indicates access to and activity on the PROFINET network. The LAN LED indicates network packets are
being processed by the network interface (not just passing through the embedded switch).
Blinking on
The module’s network interface is active
Off
No activity
STATUS LED
The STATUS stays Green during normal operation.
Green, on
Normal Operation
Red, blinking
A MAC address read from nonvolatile memory is invalid. Ports with invalid MAC addresses
remain disconnected from the Ethernet network.
CONNECT LED (CONN on -AXXX versions)
The CONN LED indicates the status of PROFINET connections.
Green, on
At least one PROFINET connection (AR) exists with an I/O Controller.
Amber, blinking
No device name configured.
Off
No PROFINET connection (AR) exists.
Port LEDs
The PROFINET Scanner has four LEDs that indicate link speed, link connection and link activity corresponding to the
four possible external Ethernet ports.
Port Number LED
Red, on
Port 3 and 4 only: Error such as incompatible SFP.
Off
No Port error.
1000 Speed LED
Green on
Link connected, 1000 Mbps
Green blinking
Port active, 1000 Mbps
Off
The associated Ethernet port is not connected to an active link at 1000Mbps
100 Speed LED
Green, on
Link connected, 100 Mbps.
Green, blinking
Port active, 100 Mbps
Off
The associated Ethernet port is not connected to an active link at 100Mbps
Green, on
Link connected, 10 Mbps.
10 Speed LED
Green, blinking
Port active, 10 Mbps
Off
The associated Ethernet port is not connected to an active link at 10Mbps
6
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
ACTIVE LED
The active LED indicates the Scanner is connected to a PROFINET I/O Controller that is controlling the I/O data for
the PNS001’s I/O modules.
Green, on
PNS001 is connected to a PROFINET I/O Controller that is controlling I/O Module IO data.
Off
PNS001 is not connected to a PROFINET I/O Controller.
Front Panel LNK LED
The Front Panel LNK LED indicates link established on the front Ethernet port.
Green, on
Ethernet link established.
Off
No Ethernet link
Front Panel ACT LED
The front panel ACT LED indicates activity on the front Ethernet port when blinking.
Amber, blinking
Activity on front panel Ethernet port.
Amber, On
No activity on front Ethernet port, but link is connected
Off
No link is connected.
RX3i PROFINET Scanner
IC695PNS001-BABA
7
GFK-2738M
Quick Start Guide
Installation and initial startup procedures for the PNS001 include the following steps. Before installing and
operating the PNS001, refer to PACSystems RX3i PROFINET Scanner Manual, GFK-2737, for detailed information.
1. Pre-installation check
Upon receiving your RX3i equipment, carefully inspect all shipping containers for damage. If any part of the system
is damaged, notify the carrier immediately. The damaged shipping container should be saved as evidence for
inspection by the carrier.
As the consignee, it is your responsibility to register a claim with the carrier for damage incurred during shipment.
However, GE Intelligent Platforms will fully cooperate with you, should such action be necessary.
After unpacking the RX3i equipment, record all serial numbers. Serial numbers are required if you should need to
contact Customer Care during the warranty period. All shipping containers and all packing material should be
saved should it be necessary to transport or ship any part of the system.
2. Installing the PNS001 in an RX3i backplane
The Scanner can be installed in slot 1 or 2 of a 7, 12, or 16-slot RX3i Universal Backplane, or in slot 6 of a 7-slot RX3i
Universal Backplane. The installation slot must match the slot that is selected in the module’s hardware
configuration.

RX3i rack power must be turned off. The PNS001 does not
support insertion/removal while power is applied to the
system (hot swap).

Holding the module firmly, align the module with the
correct slot and connector.

Engage the module’s rear pivot hook in the notch on the
top of the backplane (1).

Swing the module down (2) until the module’s connector
engages the backplane’s backplane connector.

Visually inspect the module to be sure it is properly seated.

Secure the bottom of the module to the backplane using
the machine screws provided with the module (3).
1
2
3. Connecting the PNS001 to the PROFINET network and
to a 10BaseT, 100BaseTX or 1000BaseT IEEE 802.3
network for general Ethernet communications
3
Do not connect two or more ports on the PNS001 to the same device, either directly or
indirectly.
Each port on an RX3i PNS001 operates independently, so devices that operate at different speeds and/or duplex
modes may be attached to the ports. By default, all ports, including empty, unconfigured SFP cages, are set for
Automatic, which enables auto-negotiation for the widest range of options supported by the port. For other options,
refer to PACSystems RX3i PROFINET Scanner Manual, GFK-2737.
Bottom of module
Port 1
Port 3
Front
Port 2
Port 4
8
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
4. Installing SFP devices
Optical SFPs use an invisible laser to generate a fiber-optic signal. Always keep the port covered
if a cable is not installed. Do not look into the open port if a cable is not installed.
If the surrounding air operating temperature of the PNS001 is greater than 40 °C, SFP
devices could have operating temperatures over 70°C (158 °F). Under these conditions,
for your safety, do not use bare hands to remove an SFP device from the SFP cage. Use
protective gloves or a tool (needle-nose pliers) to avoid handling the hot SFP device
directly when removing the SFP device.
For a list of SFP module types and network cabling details, refer to the section entitled SFP Modules for Ethernet
Ports in PACSystems RX3i PROFINET Scanner Manual, GFK-2737.
5. Assigning an I/O Device Name to the PNS001
Before attempting to connect to or configure the RX3i PNS001, the I/O Device Name must be set with a Discovery
and Configuration Protocol (DCP) tool, such as the Proficy Machine Edition Discovery Tool.
6.
Configuring the PNS001 and its I/O Modules on a PROFINET network
Proficy Machine Edition is the primary tool used to configure an RX3i PROFINET network. The PNS001 must be
installed in the slot that is selected in the module’s hardware configuration. The GSDML file for the RX3i PNS001 is
included in the firmware upgrade kit. If the version of the GSDML file in the firmware upgrade kit is not already
present in the Proficy Machine Edition tool chest, import the newer GSDML into PME to enable new features.
RX3i PROFINET Scanner
IC695PNS001-BABA
9
GFK-2738M
Supported Modules, Power Supplies and Backplanes
The following modules can be used with this release of the RX3i PROFINET Scanner I/O Device:
Catalog Number
Module Description
Distinguishing Classes 1
Discrete Input Modules
IC693ACC300
Input Simulator Module (8pt & 16pt operation)
8 in, 16 in
IC693MDL230
8 Circuit Input 120 Vac Isolated
8 in
IC693MDL231
8 Circuit Input 240 Vac Isolated
8 in
IC693MDL240
16 Circuit Input 120 Vac
16 in
IC693MDL241
16 Circuit Input 24 Vac / Vdc
16 in
IC693MDL250
16 Circuit Isolated Input 120 Vac, Input Filtering Off
16 in
IC693MDL250
16 Circuit Isolated Input 120 Vac, Input Filtering On
none
IC693MDL260
32 Circuit Input 120 Vac, Input Filtering Off
32 in
IC693MDL260
32 Circuit Input 120 Vac, Input Filtering On
32 in/out
IC693MDL632
8 Circuit Input 125 Vdc Positive / Negative Logic
8 in
IC693MDL634
8 Circuit Input 24 Vdc Positive / Negative Logic
8 in
IC693MDL635
16 Circuit Input 125 Vdc Positive / Negative Logic
16 in
IC693MDL645
16 Circuit Input 24 Vdc Positive / Negative Logic
16 in
IC693MDL646
16 Circuit Input 24 Vdc Positive / Negative Logic Fast
16 in
IC693MDL648
16 Circuit Input 48 Vdc Positive / Negative Logic Fast
16 in
IC693MDL654
32 Circuit Input 5/12 Vdc Positive / Negative Logic
32 in
IC693MDL655
32 Circuit Input 24 Vdc Positive / Negative Logic Fast
32 in
IC693MDL660
32 Circuit Input 24 Vdc Positive / Negative Logic, Input Filtering Off
32 in
IC693MDL660
32 Circuit Input 24 Vdc Positive / Negative Logic, Input Filtering On
32 in/out
IC694ACC300
Input Simulator Module (8pt & 16pt Mode)
8 in, 16 in
IC694MDL230
8 Circuit Input 120 Vac Isolated
8 in
IC694MDL231
8 Circuit Input 240 Vac Isolated
8 in
IC694MDL240
16 Circuit Input 120 Vac
16 in
IC694MDL241
16 Circuit Input 24 Vac / Vdc
16 in
IC694MDL250
16 Circuit Input 120 Vac Isolated
none
IC694MDL260
32 Circuit Input 120 Vac
none
IC694MDL632
8 Circuit Input 125 Vdc Positive / Negative Logic
8 in
IC694MDL634
8 Circuit Input 24 Vdc Positive / Negative Logic
8 in
IC694MDL635
16 Circuit Input 125 Vdc Positive / Negative Logic
16 in
IC694MDL645
16 Circuit Input 24 Vdc Positive / Negative Logic
16 in
IC694MDL646
16 Circuit Input 24 Vdc Positive / Negative Logic Fast
16 in
IC694MDL654
32 Circuit Input 5/12 Vdc Positive / Negative Logic
32 in
IC694MDL655
32 Circuit Input 24 Vdc Positive / Negative Logic Fast
32 in
IC694MDL658
32 Circuit Input 48 Vdc Positive / Negative Logic Fast
32 in
IC694MDL660
32 Circuit Input 24 Vdc Positive / Negative Logic
none
IC695MDL664
16 Circuit Smart Input 24 Vdc Positive Logic 2
none
The PNS001 cannot distinguish between modules within the same Distinguishing Class type. This means that any module
physically present that is within the same class as the one configured will not alert the user with a System Configuration
Mismatch fault on the Controller Fault Table. Refer to the section entitled CPU operation during System Configuration Mismatch
Faults in PACSystems RX7i and RX3i CPU Reference Manual, GFK-2222.
2 The PNS001 currently does not support Fault Reporting from this module.
1
10
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
Catalog Number
Module Description
Distinguishing Classes 1
IC693MDL310
12 Circuit Output 120 Vac 0.5A
16 out
IC693MDL330
8 Circuit Output 120/240 Vac 2A
8 out
IC693MDL340
16 Circuit Output 120 Vac 0.5A
16 out
IC693MDL350
16 Circuit Output 120/240 Vac Isolated
16 out
IC693MDL390
5 Circuit Output 120/240 Vac 2A Isolated
8 out
IC693MDL730
8 Circuit Output 12/24 Vdc 2A Positive
8 out
IC693MDL731
8 Circuit Output 12/24 Vdc 2A Negative
8 out
IC693MDL732
8 Circuit Output 12/24 Vdc 0.5A Positive
8 out
IC693MDL733
8 Circuit Output 12/24 Vdc 0.5A Negative
8 out
IC693MDL734
6 Circuit Output 125 Vdc 1A Positive/Negative
8 out
IC693MDL740
16 Circuit Output 12/24 Vdc 0.5A Positive
16 out
IC693MDL741
16 Circuit Output 12/24 Vdc 0.5A Negative
16 out
IC693MDL742
16 Circuit Output 12/24 Vdc 1A Positive
16 out
IC693MDL748
8 Circuit Output 48 Vdc 0.5A Positive
8 out
IC693MDL752
32 Circuit Output 5/24 Vdc 0.5A Negative
32 out
IC693MDL753
32 Circuit Output 12/24 Vdc 0.5A Positive
32 out
IC693MDL754
32 Circuit Output 24 Vdc 0.75A Positive with ESCP, Diagnostics Off
32 out
IC693MDL754
32 Circuit Output 24 Vdc 0.75A Positive with ESCP, Diagnostics On
32 in/out
IC693MDL758
32 out
IC693MDL760
32 Circuit Output 12/24 Vdc 0.5A Positive with ESCP2
Solenoid Valve Output Module
IC693MDL916
16 Circuit Output 4A Relay
16 out
IC693MDL930
8 Circuit Output 4A Relay Isolated
8 out
IC693MDL931
8 Circuit Output Relay Form BC Isolated
8 out
IC693MDL940
16 Circuit Output 2A Relay
16 out
IC694MDL310
12 Circuit Output 120 Vac 0.5A
16 out
IC694MDL330
8 Circuit Output 120/240 Vac 2A
8 out
IC694MDL340
16 Circuit Output 120 Vac 0.5A
16 out
IC694MDL350
16 Circuit Output 120/240 Vac Isolated
none
IC694MDL390
5 Circuit Output 120/240 Vac 2A Isolated
8 out
IC694MDL732
8 Circuit Output 12/24 Vdc 2A Positive
8 out
IC694MDL734
6 Circuit Output 125 Vdc 1A Positive/Negative
8 out
IC694MDL740
16 Circuit Output 12/24 Vdc 0.5A Positive
16 out
IC694MDL741
16 Circuit Output 12/24 Vdc 1A Negative
16 out
IC694MDL742
16 Circuit Output 12/24 Vdc 1A Positive
16 out
IC694MDL752
32 Circuit Output 5/24 Vdc 0.5A Negative
32 out
IC694MDL753
32 Circuit Output 12/24 Vdc 0.5A Positive
32 out
IC694MDL754
32 Circuit Output with ESCP
Discrete Output Modules
16 out
none
ESCP2
IC694MDL916
32 Circuit Output 12/24 Vdc 0.5A Positive with
16 Circuit Output 4A Relay
IC694MDL930
8 Circuit Output 4A Relay Isolated
8 out
IC694MDL931
8 Circuit Output Relay Form BC Isolated
8 out
IC694MDL940
16 Circuit Output 2A Relay
16 out
IC695MDL765
16 Circuit Smart Output 24/125 Vdc 2A Positive Logic2
None
IC694MDL758
none
none
RX3i PROFINET Scanner
IC695PNS001-BABA
11
GFK-2738M
Catalog Number
Module Description
Distinguishing Classes 1
IC693MAR590
8 Circuit Mixed 120 Vac Input / Relay Output
8 in/out
IC693MDR390
8 Circuit Mixed 24 Vdc Input / Relay Output
8 in/out
Discrete Mixed Modules
Analog Input Modules
IC693ALG220
4 Point Analog Voltage Input
ALG IN 4
IC693ALG221
4 Point Analog Current Input
ALG IN 4
IC693ALG222
16 Point Analog Voltage Input
ALG IN 16
IC693ALG223
16 Point Analog Current Input
ALG IN 16
IC694ALG220
4 Point Analog Voltage Input
ALG IN 4
IC694ALG221
4 Point Analog Current Input
ALG IN 4
IC694ALG222
16 Point Analog Voltage Input
ALG IN 16
IC694ALG223
16 Point Analog Current Input
ALG IN 16
IC695ALG106
6 Point Isolated Analog Input Current/Voltage
none
Input 3
IC695ALG112
12 Point Isolated Analog Current/Voltage
IC695ALG600
8 Point Universal Analog Input Module3
none
IC695ALG608
8 Point Analog Input Current / Voltage Input3
none
Input3
IC695ALG616
16 Point Analog Current / Voltage
IC695ALG626
16 Point Analog Current / Voltage Input3 (HART 4 Support)
Input3
none
none
(HART4
Support)
none
IC695ALG628
8 Point Analog Current / Voltage
none
IC693ALG390
2 Point Analog Voltage Output
ALG OUT 2
IC693ALG391
2 Point Analog Current Output
ALG OUT 2
IC693ALG392
8 Point Analog Current / Voltage Output
ALG OUT 8
IC694ALG390
2 Point Analog Voltage Output
ALG OUT 2
IC694ALG391
2 Point Analog Current Output
ALG OUT 2
IC694ALG392
8 Point Analog Current / Voltage Output
ALG OUT 8
IC695ALG704
4 Point Analog Current / Voltage Output3
none
IC695ALG708
8 Point Analog Current / Voltage Output3
none
IC695ALG728
8 Point Analog Current / Voltage Output3 (HART4 Support)
none
IC695ALG808
8 Point Isolated Analog Current / Voltage Output3
none
Analog Output Modules
Analog Mixed Modules
IC693ALG442
4 Input / 2 Output, Current / Voltage
ALG IN 4, ALG OUT 2
IC694ALG442
4 Input / 2 Output, Current / Voltage
ALG IN 4, ALG OUT 2
RTD Input Modules
IC695ALG508
8 Channel Isolated RTD
Input3
none
Thermocouple Input Modules
IC695ALG312
IC695ALG412
12 Point Isolated Thermocouple Input3
12 Point Isolated High Speed Thermocouple
none
Input3
none
High-speed Counter Modules
3
PNS001 currently does not support Fault Reporting or Interrupts from this module.
4
PNS001 firmware version 2.30 supports the HART Pass Through capabilities of this module. PNS001 firmware version 2.41
supports Remote Get HART Device Information COMMREQ support only (no HART variables in IO Data). HART-compatible CPU
and PNC001 versions are required.
12
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
Catalog Number
Module Description
Distinguishing Classes 1
IC695HSC308
High-speed Counter Module - 8 Counters3
None
Specialty Modules
IC694PSM001
Power Sync and Measurement Module
none
Power Supply Modules
IC695PSA040
Universal 120/240 Vac, 125Vdc 40W Power Supply
none
IC695PSA140
Multifunctional 120/240 Vac, 125Vdc 40W Power Supply
none
IC695PSD040
24Vdc 40W Power Supply
none
IC695PSD140
Multifunctional 24Vdc 40W Power Supply
none
Small Form-factor Pluggable (SFP) Modules
IC695SPC100
10/100/1000Base-T Copper SFP
none
IC695SPF002
100Base-FX (fiber 2km) SFP
none
IC695SPF010
1000Base-LX (fiber 10km) SFP
none
IC695SPF550
1000Base-SX (fiber 550m) SFP
none
The RX3i PROFINET Scanner can be used in the following PACSystems backplanes:
5
Catalog Number
Backplane Type 5
IC695CHS007
7-Slot RX3i Universal Backplane
IC695CHS012
12-Slot RX3i Universal Backplane
IC695CHS016
16-Slot RX3i Universal Backplane
The PNS001 cannot distinguish between the different rack sizes. Choosing the wrong type will not generate a System
Configuration Mismatch fault on the Controller Fault Table.
RX3i PROFINET Scanner
IC695PNS001-BABA
13
GFK-2738M
Release History
®
Version
Firmware
Revision
IC695PNS001-BABA
Date
Comments
3.00
Feb
2017
IC695PNS001-ABAK
2.41
Jun
2016
IC695PNS001-ABAJ
2.40
IC695PNS001-ABAH
2.30
Nov
2015
May
2015
IC695PNS001-ABAG
2.20
IC695PNS001-ABAF
2.10
IC695PNS001-ABAE
2.00
Mar
2014
IC695PNS001-ABAD
1.11
IC695PNS001-ABAC
1.10
IC695PNS001-ABAA
1.00
IC695PNS001-AAAA
1.00
Nov
2013
Jul
2013
Jun
2013
Mar
2013
New hardware platform with new layout of front panel LEDs and Ethernet
connector replaces front panel USB for firmware update. Firmware not
compatible with previous hardware revisions (-AXXX).
IC695PNS001-BABA is Achilles Level 1 Certified.
Added support for the Remote Get HART Device Information COMMREQ.
Information from a HART device connected to an RX3i Analog Module in an
IC695PNS001 RX3i PROFINET Scanner may be read into the user application
using the Remote Get HART Device Information COMMREQ.
Added support for additional RX3i I/O modules (ALG106, ALG312, ALG314,
ALG608, ALG628, ALG704, and MDL758)
Added support for HART ® Pass Through feature set using HART-capable RX3i
Analog modules. Also added support for I/O Module Version information via
Explore PROFINET Networks in PME.
Added support for IC695ALG600 (Universal Analog Input Module) and
IC694PSM001 (Power and Sync Measurement Module).
Added support for IC695HSC308 (High-speed Counter – 8 Counters).
Resolution of ALG508, ALG616, and ALG708 modules larger configuration
causing an IOC Software - Module Firmware Fault when more than three
were placed in a PNS001 rack.
Added PROFINET System Redundancy (S2 NAP – supports Redundant
connections from two IO Controllers).
Resolution of PROFINET connection losses and RX3i PNS001 connection
issues, described below.
Added support for additional RX3i I/O modules (ALG112, ALG626 (No HART),
ALG728 (No HART), and ALG808)
Resolution to Analog Output Anomaly issue, described in PACSystems RX3i
PROFINET Scanner IPI, GFK-2738D.
Support for additional RX3i I/O modules (MDL664, MDL765, ALG508, ALG616,
ALG708).
Hardware update for improved manufacturability. No changes to features,
functions or compatibility
Initial release.
Jun
2014
Apr
2014
HART® is a registered trademark of the HART Communication Foundation of Austin, Texas USA. Any use of the term HART
hereafter in this document, or any document referenced by this document, implies the registered trademark.
14
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
Important Product Information for this Release
Field Upgrade
Upgrade Kit: 41G2416-FW01-000-A0.zip
Only IC695PNS001-BABA or later revisions are field upgradable to this Release using the upgrade kit listed above.
IC695PNS001-ABAn cannot be upgraded with this kit due to HW/FW design changes in this new -BXXX revision.
New Features and Enhancements
Release 3.00 adds support for the new hardware, IC695PNS001-BXXX, which includes a QR code on the front panel
for quick access to web-based product support and a front panel Ethernet port for web-based firmware upgrades.
The IC695PNS001-BABA meets Wurldtech’s Achilles Level 1 Communications Certification security standard.
The first control output bit, previously reserved, is assigned to allow firmware update while in Run Mode. If the bit is
not set and the IC695PNS001-BXXX is being actively controlled by a PROFINET IO Controller, the firmware update is
rejected. If the bit is set, the firmware update is allowed to disrupt IO. If the IC695PNS001-BXXX is not being actively
controlled, the firmware update is allowed.
Problems Resolved by this Revision
Release 3.00 resolves the following issues:
Subject
RX3i PNS Allows Firmware
Update While Connected to
Running PROFINET IO
Controller
Port LED for Ethernet Ports
Configured to 100 Mbps May
Briefly Flash Blue Before
Changing to Green
RX3i PNS power-up time may
vary
Description
The RX3i PNS USB firmware update does not prevent initiation of
firmware update when it is actively connected to an IO-Controller. When
the PNS enters firmware update mode, the PNS and its modules go to their
IO default modes. During the update, the PNS does not drive module
outputs or send inputs to the IO-Controller.
When the firmware update is completed and the PNS is rebooted, its
previous connections are re-established and control resumes.
Web-based firmware updates require one of the following to be true to
update firmware:
- No PROFINET Connection exists,
- Active PROFINET Connection reports that CPU is in STOP
mode, or
- PNS Control bit has been set to allow firmware updates to disrupt
IO while PNS is connected to PROFINET IO Controller.
During power-up of Rev -AXXX hardware, Port LEDs of the RX3i PNS
Ethernet ports configured for 100 Mbps operation may briefly flash blue
before turning green. The port remains configured for 100 Mbps operation
during the power-up process and afterwards.
Rev -BAXX hardware turns on LEDs later in power-up sequence.
Some RX3i PNS units of Rev -AXXX may restart part way through the
power up sequence adding delay to when the RX3i PNS OK LED turns on
and the RX3i PNS is ready to control IO. This is on the order of 10-40
seconds.
This has been fixed in Rev -BAXX hardware.
RX3i PROFINET Scanner
IC695PNS001-BABA
15
GFK-2738M
Functional Compatibility
The following CPU firmware, programming software and backplane hardware versions are required to use the
features introduced in the most recent PNS001 release:
Description
Subject
Feature
Controller CPU
firmware
RX3i PNS001 Release 3.00 or
RX3i PNS001 Release 2.41
Support Remote Get Device
Information COMMREQ
RX3i PNS001 Release 2.40
Minimum Version Required
CPU320/CPU315 Primary Firmware Release 8.95 or later
CPE310/CPE305 Primary Firmware Release 8.95 or later
CRU320 Primary Firmware Release 8.95
CPE330 Primary Firmware Release 8.95 or later
(Other CPU models are not supported)
CPE330 Primary Firmware Release 8.50 or later
CPU315/CPU320 firmware version 8.50 or later
CPE305/CPE310 firmware version 8.50 or later
RXi Controller firmware version 7.80 6 or later
CRU320 Primary Firmware version 8.50
Programmer
software
Proficy Machine Edition version 8.50 SIM 2 or later
GSDML Version
RX3i PNS001 Release 3.00
GSDML-V2.3-GEIP-RX3iPNS-20170109.xml
RX3i PNS001 Release 2.41
Support Remote Get Device
Information COMMREQ
RX3i PNS001 Release 2.40
GSDML-V2.3-GEIP-RX3iPNS-20160602.xml
RX3i PROFINET
Controller
RX3i backplane
hardware
RX3i PNS001 Release 2.41
Support Remote Get Device
Information COMMREQ
RX3i PNS001 Release 2.40
IC695PNC001 with firmware version 2.20 or later
The following minimum backplane hardware revision must be used:
IC695CHS012-BAMP
IC695CHS016-BAMP
IC695CHS012CA-BAMP
IC695CHS016CA-BAMP
or
IC695CHS012-CA (or later)
IC695CHS016-CA (or later)
IC695CHS012CA-CA (or later)
IC695CHS016CA-CA (or later)
or
IC695CHS007-AA (or later)
When installing, operating, or maintaining the IC695PNS001, personnel must ensure any
electrostatic charge is discharged through the use of a grounded ESD strap or other means.
This requirement does not apply if the IC695PNS001 is used with the following backplane
revisions:
or
Rx3i AC Power
Supply
Compatibility
6
GSDML-V2.3-GEIP-RX3iPNS-20151030.xml
IC695PNC001 with firmware version 2.26 or later
IC695CHS012-EA (or later)
IC695CHS012EA-CA (or later)
IC695CHS016-EA (or later)
IC695CHS016EA-CA (or later)
IC695CHS007-BA (or later)
For new installations using AC power supplies, the IC695PNS001 requires an IC695PSA040H
or IC695PSA140D (or higher) revision power supply to ensure compatibility.
For retrofit installations using AC power supplies, the IC695PNS001 may require an
HART Pass Through COMMREQ feature not supported on RXi Controller. Refer to future RXi Controller IPI for updates.
16
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
IC695PSA040H or IC695PSA140D (or higher) revision power supply depending on the total
current load in the backplane. If the total current load exceeds the existing power supply's
minimum current threshold, no power supply change is required.
Small form-factor
pluggable
modules
IC695SPC100A or later
IC695SPF002A or later
IC695SPF550A or later
IC695SPF010A or later
RX3i modules
For a complete list, refer to Supported Modules, Power Supplies and Backplanes.
Restrictions and Open Issues in Release 3.00
Subject
Description
PROFINET
connection losses
with MRP enabled
and I/O update
rates of 1 ms DE638
Applications with MRP Ring network topologies and I/O Devices configured with I/O Update
Rates of 1 ms on either 100 Mbps or 1000 Mbps may encounter PROFINET Connection
Losses of PROFINET I/O Devices during a ring-break event. Use of MRP with 1 ms I/O
Update rates is not recommended with this release. Refer to the section entitled Media
Redundancy Protocol Support in PACSystems RX3i PROFINET Scanner Manual, GFK-2737
for details on recommended MRP configurations.
Operational Notes for Release 3.00
Subject
Invalid Module
Configurations will cause the
respective RX3i I/O module to
fail configuration
Analog Modules do not
configure if Alarms are
outside High and Low Scale
Value Engineering Units.
Description
When the PNS001 rejects the configuration of an individual I/O module, that
configuration is not delivered to the I/O module, leaving the module in an unconfigured state. In many modules, this is indicated by the OK Led on the I/O
Module blinking. In addition, I/O point faults will be asserted for that module’s I/O.
Correct the configuration of the I/O module and store HWC again.
Refer to the section entitled RX3i PROFINET Scanner Configuration Validation in
PACSystems RX3i PROFINET Scanner Manual, GFK-2737.
For analog input and output modules that support alarms, the PNS001 limits
alarm values to the range specified by the High and Low Engineering Unit values.
If the High and Low Scale A/D Unit values are not the full range of the analog
signal, runtime values reported in Engineering Units may exceed the High or Low
Engineering range. Alarms cannot be configured for this range outside of the
Engineering Units range.
For example, consider an input channel with Range Type as Voltage/Current and
Range selection of -10V to +10V, 16-bit Integer format. If High and Low Scale Eng
Units are set to 8500 and -8500 and the High and Low Scale A/D Units are set to 8
and -8, the alarm range will be limited to a range of -8500 to 8500. Analog input
signals of -10V and +10V correspond to Engineering Unit values of -10625 and
10625. To support alarm values at all possible values of the analog signal, scaling
values should be chosen such that the A/D Units are specified as the high and low
limits for the analog signal. In this example, the High and Low Engineering units
would be 10625 and -10625 with High and Low A/D Units of 10 and -10.
IOPS of power supplies do not
update when power supply is
switched off
The IOPS (status) of a power supply is marked good or bad at the start of each
PROFINET I/O connection. The IOPS is not updated when the power supply is
turned on and off.
PROFINET Alarms are not
supported
PROFINET Alarms are not issued from the RX3i PNS001 in this release.
RX3i PROFINET Scanner
IC695PNS001-BABA
17
GFK-2738M
Subject
Description
Some power supplies use two
backplane slots, but this is
not indicated in the change
module list interface of HWC
Note that the IC695PSA040 and IC695PSA140 each utilize two backplane slots, but
are shown using only one slot in the Change Module List interface for the RX3i
PNS001. Configuring a module for the already utilized slot will result in a Loss of
I/O Module fault.
PNS module supported in
certain backplane slots only.
The RX3i PROFINET Scanner module is configurable for use in Slot 1, Slot 2, and
when installed in the IC695CHS007 backplane, also Slot 6.
SFP modules do not support
hot swap
SFP modules do not support hot swap. This means that if an SFP module is hotinserted into the RX3i PNS001, no Fault Table entry will be logged and
configuration parameters will not be applied to the SFP until the RX3i PNS001 is
power cycled. Until the RX3i PNS001 is power cycled, the SFP will remain enabled
and active with auto negotiation turned on.
I/O modules hot inserted
while an invalid configuration
is stored require re-insertion
or power cycle to recover
If an invalid configuration for an I/O module in the PNS001 is stored to the CPU,
such as a default value outside the engineering units range, and the I/O module
using that configuration is hot inserted in the PNS001, the hot insertion process
fails. No Addition of I/O Module fault is generated and the module is left at its
default operation. The configuration of that module will not be retried until the
module is re-inserted or the PNS001 rack is power cycled, even if the
configuration is corrected in the CPU.
Quickly changing data may
not be detected in PLC Logic
solve
Quickly changing I/O or Module Data such as event flags on a High Speed Counter
module may not be detected in the CPU logic scan. Only event data which is
latched and acknowledged or persists for the Update I/O Rate plus the CPU Logic
Scan rate is guaranteed to be detectable from logic.
Connecting Ethernet Ports
Not Configured as Ring Ports
to the MRP Ring May Inhibit
Ring-Break Detection
In order to insure correct MRP ring-break detection, it is important to connect the
correct Ethernet ports of the RX3i PNS to the MRP ring. The ports connected to the
ring must be the same ports configured as MRP Ring Ports. Failure to connect the
configured ports will prevent the PNS from correctly participating in the MRP ring,
may inhibit ring-break detection, and may result in losses of IO Devices upon ringbreak events. It is recommended during system commissioning that the physical
network connections be verified with the system configuration for ring ports in
system’s hardware configuration. Refer to section “Media Redundancy Protocol
Support” of PACSystems RX3i PROFINET Scanner Manual, GFK-2737, for details on
recommended MRP configuration.
Reset Password returns HTTP
ERROR 503, service
unavailable, after restart.
On power-up, the PNS generates a local security certificate to use with HTTPS
communications. Until this process has completed, attempts to enter the secure
webpages used to reset the password will fail with error 503. This can take from
15-120 seconds.
ALG616, ALG626, & ALG628
Terminal Block Present
Status Bit
IC695ALG616-Fx, IC695ALG626-Fx, and IC695ALG628-Fx (and later hardware
revision) analog modules may not set the terminal block present status bit in their
module status after a PNS001 firmware update completes, even if the terminal
block is installed. Normal operation of the terminal block present status bit may be
restored by removing and reinstalling the terminal block or power cycling the
rack.
MDL660 does not show
correct firmware revision
after PNS firmware update
IC694MDL660 may report incorrect primary and boot firmware through the
Explore PROFINET Networks dialogs in Proficy Machine Edition in a PNS001 rack
after firmware update of the PNS001. Correct versions will be reported after the
next power cycle of the MDL660 module either through a power cycle of the entire
rack or removing and reinstalling the MDL660 module.
QR Code may not link
automatically link to product
landing page
Some older mobile QR Code Scanner/Reader applications may not correctly link to
the target site. This behavior has not been identified to exist on some new QR
Scanner apps. An example of one that has been verified to work correctly is the
QR Code Scanner in Google Chrome for Android and iOS.
18
GFK-2738M
RX3i PROFINET Scanner
IC695PNS001-BABA
Additional Information
For additional information, please refer to the manuals listed below. Manuals can be downloaded from the support
website, http://support.ge-ip.com.
PACSystems RX7i & RX3i CPU Reference Manual
GFK-2222
PACSystems RX3i PROFINET I/O Controller Manual
GFK-2571
PACSystems RX3i PROFINET Controller Command Line Interface Manual
GFK-2572
PACSystems RX3i PROFINET Scanner Manual
GFK-2737
PACSystems RX3i CEP PROFINET Scanner User Manual
GFK-2883
PROFINET I/O Devices Secure Deployment Guide
GFK-2904
PACSystems RXi, RX3i, and RX7i Controller Secure Deployment Guide
GFK-2830
PACSystems HART Pass Through User Manual
GFK-2929
PACSystems RX3i System Manual
GFK-2314
1-800-433-2682
1-434-978-5100
http://www.geautomation.com/
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project