HP Data Center Environmental Edge and HP Insight
Environmental Observer
QuickSpecs
Overview
The new HP Data Center Environmental Edge technology helps you address one of the most critical issues in today's data centers power and cooling. HP Data Center Environmental Edge is an affordable approach to monitoring your data center environment,
resulting in optimal use of data center capacity and a reduction in energy costs. HP Data Center Environmental Edge measures,
analyzes and visualizes data center environmental parameters, ensuring complete confidence that you're running a much more
efficient data center.
Why HP Data Center Environmental Edge?
Resiliency: Real-time feedback on environmental changes in your data center through data center environmental visualization
and customer defined alarms
Energy savings: Reduces data center cooling energy up to 18% by enabling customers' data center optimization
Provides insight into data center infrastructure over-provisioning
Supports higher rack operating temperature and chilled water temperature through the data center environmental
measurements
Increased Flexibility: Adapt /upgrade the HP Data Center Environmental Edge hardware and HP Insight Environmental
Observer software to meet the changing needs of your data center
HP Data Center Environmental Edge bridges the gap between IT and facilities. HP Data Center Environmental Edge enables both
facilities and IT manager's deeper insight into their current data center environment.
For additional information, please visit: www.hp.com/go/edge
HP Data Center Environmental Edge Base Stations
1. Air Pressure Base Station
2. Environmental Base Station
3. Base Station Gateway
What's New
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 1
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Overview
Data center power visualization, including PUE
Current per phase (Wye only)
Power Factor per phase (Wye only)
Voltage per phase (Wye L-N and Delta L-L)
Total Power
Average Power (period = 5min sampling interval)
THD
Branch circuit monitoring
Current per circuit with breaker capacity and warning status
Power Factor per circuit
Voltage per phase
Chilled water Energy Monitoring
Modbus Gateway
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 2
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Standard Features
Wireless Network and
Network and Network
Security
HP Data Center Environmental Edge sensor and networking devices use 802.15.4 based radios that
operate in the 2.4 GHz industrial and scientific and medical (ISM) unlicensed band. The HP Data Center
Environmental Edge wireless communications low bandwidth will not interfere with other wireless
communications. The HP Data Center Environmental Edge wireless communications uses a mesh
network topology to transfer information.
HP Data Center Environmental Edge wireless systems achieve security at multiple levels: First HP Data
Center Environmental Edge wireless communications are not IP-enabled; they therefore are not
susceptible to external IP-based passive and active attacks. Second, HP Data Center Environmental Edge
network stack uses 128bit-AES cryptograph to provide authentication and data encryption, thereby
providing security against rogue admissions and snooping.
HP Data Center
Environmental Edge
Server
At the centre of the solution is the HP Data Center Environmental Edge Server. This is a HP ProLiant
DL180 G6 running Microsoft Windows Server 2008, HP Insight Environmental Observer software
components.
NOTE: One server can support multiple HP Data Center Environmental Edge data center locations.
HP Insight Environmental HP Insight Environmental Observer S/W key features include: data center environmental visualization;
Observer S/W
metrics tracking, alarming and historical information, including 1 year of 24x7 Technical Support and
Updates.
HP Data Center
Environmental Edge
Environmental Base
Station
HP Data Center Environmental Edge Environmental Base Stations are attached to individual racks or
CRAH units and collect temperature and humidity data. The HP Data Center Environmental Edge
Environmental Base Station is battery powered and reports temperature and humidity information either
once every minute or up to once every 5 minutes based on user desired preferences. Environmental Base
Stations are simple to mount or attach within the data center environment with a couple of different
Mounting Options techniques, and include a one year parts only warranty (excluding batteries).
Server Racks
Environmental Base stations will be combined with the HP Data Center Environmental Edge Rack
Sensor Array
Environmental Base Stations and Rack Sensor Array can be mounted either inside the rack on
outside the rack. The Rack Sensor Array is mounted down the center of both the front and rear of
the rack
The minimum recommended configuration is to install the base stations once every third rack.
Customers can install the base station on every other rack or every rack for increased granularity
of data
CRAH/CRAC (Computer Room Air Handlers / Computer Room Air Conditioning)
One Environmental Base Station and the Plenum Rated Sensor Array will be installed in each
CRAH unit
Environmental Base Stations do not require the customers' CRAH/CRAC units to be modified
Other Locations
Environmental Base Stations can be located anywhere that the customers wants to gain insight into
a specific locations' temperature and humidity
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 3
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Standard Features
HP Data Center
HP Data Center Environmental Edge Rack Sensor Array contains 3 thermistors to measure rack intake
Environmental Edge Rack and 3 thermistors to measure rack exhaust.
Sensor Array
NOTE: One year parts only warranty.
NOTE: Must be combined with AT516A Environmental Base Station
HP Data Center
HP Data Center Environmental Edge Plenum Rated Sensor Array contains 2 plenum rated thermistors
Environmental Edge
and plenum rated wiring.
Plenum Rate Sensor Array
NOTE: One year parts only warranty.
NOTE: Must be combined with AT516A Environmental Base Station
HP Data Center
Environmental Edge Air
Pressure Base Station
HP Data Center Environmental Edge Air Pressure Base Station assesses the air pressure differential in
raised floor environments. HP recommends one Air Pressure Base Station per 50 m2 / 500 ft2 of data
center floor space.
NOTE: One year parts only warranty (excluding batteries).
HP Data Center
HP Data Center Environmental Edge Base Station Gateway provides the wireless communication with the
Environmental Edge Base HP Data Center Environmental Edge Base Stations and transmits the data to the HP Data Center
Station Gateway
Environmental Edge server. HP recommends at least two Base Station Gateways per solution. One Base
Station Gateway pair supports up to 200 base stations. Multiple Base Station Gateway pairs can co-exist
in one data center.
NOTE: One year parts only warranty (excluding batteries).
NOTE: Regional SKU exists
Recommended Base
Configuration
NOTE: The installation of the HP Data Center Environmental Edge recommended base configuration
does not require any data center downtime to implement.
One HP Data Center Environmental Edge Server or server with minimum 4 GB of memory and
250GB of RAID 1 storage
One HP Insight Environmental Observer S/W
One Base Station Gateways per 200 base stations, N+1 configuration
One Environmental Base Station and Plenum Rated Sensor Array per CRAH/CRAC
One Environmental Base Station and Rack Sensor Array per three racks
One Air Pressure Base Station per 500 ft2/50 m2 of data center floor space
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 4
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Standard Features
HP Data Center Environmental Edge Optional Base Stations
HP Data Center
Environmental Edge
Energy Base Station
HP Data Center Environmental Edge Energy Base Station measures kWh (Kilowatt Hours) consumed,
Power, Power Factor, Voltage, Current, THD on each electrical line where installed. Two variants of the
energy meter exist, 208v or 277/480v version with either 200A or 600A split core CTs.
NOTE: One year parts only warranty (excluding batteries).
NOTE: Energy Base Stations must be installed by a local licensed electrician.
HP Data Center
HP Data Center Environmental Edge 200A Current Base Station measures an electrical line true RMS
Environmental Edge 200A current from 0 - 200A.
Current Base Station
NOTE: One year parts only warranty (excluding batteries).
HP Data Center
HP Data Center Environmental Edge Flow Meter Base Station is a non-intrusive ultrasonic flow meter to
Environmental Edge Flow measure chilled water flow.
Meter Base Station
NOTE: One year parts only warranty (excluding batteries).
HP Data Center
Environmental Edge
Water Leak Detection
Base Station
HP Data Center Environmental Edge Water Leak Detection Base Station detects liquid leakage.
NOTE: One year parts only warranty (excluding batteries).
HP Data Center
HP Data Center Environmental Edge Rack Door Position Base Station will alarm the customer when the
Environmental Edge Rack rack door is accessed.
Door Position Base
Station
NOTE: One year parts only warranty (excluding batteries).
HP Data Center
HP Data Center Environmental Edge Rack Sensor Array contains 3 thermistors to be place anywhere the
Environmental Edge Three customer wants detailed thermal information
Point Sensor Array
NOTE: One year parts only warranty (excluding batteries).
NOTE: Must be combined with AT516A Environmental Base Station
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 5
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Standard Features
HP Data Center
Environmental Edge
Universal Base Station
HP Data Center Environmental Edge Universal Base Station can be attached to any monitoring device
which produces a 4-20mA signal / 0-10v signal.
NOTE: One year parts only warranty (excluding batteries).
NOTE: This product can only be procured through the HP specials process, please contact your local HP
Pre-sales or EAM.
HP Data Center
HP Data Center Environmental Edge Branch Circuit Monitoring Base Station comes in up to 208v or
Environmental Edge
240v, and 42 circuit and 84 circuit wall mount, or 42 circuit sub-floor panels
Branch Circuit Monitoring
Base Station
NOTE: One year parts only warranty (excluding batteries).
NOTE: BCM Base Stations must be installed by a local licensed electrician.
HP Data Center
Environmental Edge
Chilled Water Energy
Base Station
HP Data Center Environmental Edge Chilled Water Energy Base Station measures chilled water flow rate
and temperature of both the supply and return lines
NOTE: One year parts only warranty (excluding batteries).
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 6
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Configuration Information
HP Data Center Environmental Edge Configuration
Step 1: Determine base quantity needed for the base recommended configuration:
configuration
One HP Data Center Environmental Edge Server
One HP Insight Environmental Observer S/W
Two HP Base Station Gateways minimum, one per 200 base stations, N+1 configuration
One Environmental Base Station and Plenum Rated Sensor Array per CRAH/CRAC
One Environmental Base Station and Rack Sensor Array per three racks
One Air Pressure Base Station per 500 ft2/50 m2 of data center floor space
One HP Data Center Edge Installer kit per 10,000 ft2/1000 m2
Step 2: Determine extra base stations required for increased granularity
Step 3: Determine optional base stations
HP Data Center Environmental Edge Base SKUs
Models
HP Data Center Environmental Edge Server
NOTE: Includes HP ProLiant DL180 G6, 6 GB Memory, Microsoft Server 2008
standard.
NOTE: HP Data Center Environmental Edge Server can manage several Base Station
gateway networks, deployment license based on installed floor space.
NOTE: For additional information on the HP ProLiant DL180 G6, please see the
following:
http://h18000.www1.hp.com/products/quickspecs/13248_div/13248_div.html
HP Insight Environmental Observer S/W
NOTE: Includes 1 year of 24x7 SW Technical Support and Updates.
HP Data Center Environmental Edge Environmental Base Station
HP Data Center Environmental Edge Rack Sensor Array
HP Data Center Environmental Edge Air Pressure Base Station
HP Data Center Environmental Edge Base Station Gateway
HP Data Center Environmental Edge Installer Kit
DA - 13392
Worldwide — Version 2 — November 16, 2009
AV865A
AT515A
AT516A
AT517A
AT518A
AT519A
AT533A
Page 7
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Configuration Information
HP Data Center
Environmental Edge
Optional SKUs
HP Data Center Environmental Edge 208v/200A Energy Base Station
HP Data Center Environmental Edge 200A Current Base station
HP Data Center Environmental Edge Flow Meter Base Station
HP Data Center Environmental Edge Water Leak Detection Base Station
HP Data Center Environmental Edge 208V/600A Energy Base Station
HP Data Center Environmental Edge Rack Door Position Base Station
HP Data Center Environmental Edge Three Point Sensor Array
HP Data Center Environmental Edge Plenum Rated Sensor Array
HP Data Center Environmental Edge 480v/200A Energy Base Station
HP Data Center Environmental Edge 480v/600A Energy Base Station
HP Data Center Environmental Edge Modbus Base Station
HP Data Center Environmental Edge Chilled Water Energy Base Station
HP Data Center Environmental Edge Dual Chilled Water Energy Base Station
HP Data Center Environmental Edge 208v 42 Circuit Wall Mount BCMS Base Station
HP Data Center Environmental Edge 208v 84 Circuit Wall Mount BCMS Base Station
HP Data Center Environmental Edge 208v 42 Circuit Subfloor BCMS Base Station
HP Data Center Environmental Edge 240v 42 Circuit Wall Mount BCMS Base Station
HP Data Center Environmental Edge 240v 84 Circuit Wall Mount BCMS Base Station
HP Data Center Environmental Edge 240v 42 Circuit Subfloor BCMS Base Station
HP Data Center Environmental Edge Current Sensing Relay Base Station
HP Data Center Environmental Edge Base Station Gateway (EU)
HP Data Center Environmental Edge Base Station Gateway (APJ:UK)
HP Data Center Environmental Edge Base Station Gateway (AUS)
HP Data Center Environmental Edge Base Station Gateway (CN)
HP Data Center Environmental Edge Base Station Gateway (JPN)
HP Data Center Environmental Edge Base Station Gateway (UK)
DA - 13392
Worldwide — Version 2 — November 16, 2009
AT521A
AT520A
AT522A
AT524A
AT527A
AT525A
AT514A
AT526A
AT530A
AT531A
AT532A
AT534A
AT535A
AT536A
AT537A
AT538A
AX723A
AX724A
AX725A
AX726A
AT519A#B19
AT519A#ARS
AT519A#ABG
AT519A#AKM
AT519A#ABJ
AT519A#ACC
Page 8
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Support & Service
Service and Support
Offerings
(HP Care Pack Services)
NOTE: The HP Care Pack service part numbers below for the HP Data Center
Environmental Edge system, cover the server blade and all HP branded hardware
options qualified for the server, purchased at the same time or afterwards, internal to
the server.
Support Plus
Support Plus 24, 1 Year
Support Plus 24, 3 Years
Installation & Startup
HP Installation & Startup Service for HP Data Center Environmental Edge
NOTE: Provides for an integrated hardware and software implementation that
includes remote service planning, onsite deployment of hardware and software,
installation verification testing and customer orientation. Hardware deployment covers
the installation of a single HP Data Center Environmental Edge server, Ethernet
network interconnect, and specified sensor options. Software deployment covers the
installation and configuration of sensors in the HP Data Center Environmental Edge
Software.
DA - 13392
Worldwide — Version 2 — November 16, 2009
HA110A1
HA110A3
HA114A1
Page 9
HP Data Center Environmental Edge and HP Insight
Environmental Observer
QuickSpecs
Technical Specifications
Wireless RF Specifications Band
Data rate maximum
Maximum RF output
power
Base Station Gateway
Antenna
Node to Node Distance
Regulatory Notices
2.4 GHz, ISM unlicensed band
IEEE 802.14.5 MAC
250 Kbps
0dBm
+0 dBi omni-directional antenna
+2.2dBi
Typical 15m/ 50ft
FCC Part 15, Subpart C, 15.247
U62-SRS100 and U62-THERM
Industry Canada
7265A-SRS100 and 7265A-THERM
CE Marking
EN 300 328; V1.7.1 (2006-05) and EN 300 440-2 V1.1.2 (2004-07)
HP Data Center
Environmental Edge
Environmental Base
Station
Housing
Mounting Options
Connectors
Power Requirements
Internal Sensed Data:
Dew Point
Internal Sensed Data:
Temperature Sensor
Environmental
DA - 13392
ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm)
Zip Tie: (4 holes) Accommodates up to 0.18" (4.6mm) width
3M Command Strips
Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - - fits up to #6
Machine Screws
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
4 Approved Batteries (see Approved Batteries Technical Spec)
Typical Life @ 5 min Sample Rate: 5 to 7 years
Typical Life @ 1 min Sample Rate: 4 years
Operating Range: 50ºF-95ºF (10ºC - 35ºC), 20%RH - 80%RH
Accuracy: Nominal +0.86ºF -0.82ºF (+0.48ºC - 0.46ºC)
Accuracy over time: After 1 year +0.92ºF - -0.88ºF (0.51ºC - -0.49ºC)
After 2 years +0.99ºF - -0.94ºF (.0.55ºC - -0.52ºC)
After 3 years +1.06ºF - -0.99ºF (0.59ºC - -0.55ºC)
Accuracy: ±0.5ºF (±0.3ºC)
Stability: Negligible
Operating Range: 32ºF to 122ºF (0ºC to 50ºC)
Time Constant: 231sec moving air (typical)C5
Operating: 32 to 104degF (0 to 40degC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)On-board AC/DC
Operating Temperature: 32ºF to 122ºF (0ºC to 50ºC)
Storage Temperature: 14ºF to 140ºF (-10ºC to 60ºC)
Worldwide — Version 2 — November 16, 2009
Page 10
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Technical Specifications
HP Data Center
Connectors
Environmental Edge Base
Station Gateway
Power requirements
Ethernet
Environmental
HP Data Center
Connectors
Environmental Edge Rack
Sensor Array & Three
Mounting Options
Point Sensor Array
External Temperature
Sensors
HP Data Center
Environmental Edge
Plenum Rated Sensor
Array
Connectors
Mounting Options
External Temperature
Sensors
DA - 13392
RJ45 Ethernet Connection;
2.1x5.5mm 5.0VDC Jack
RPSMA Antenna connector
Gateway node requires 5.0VDC (±5%) via supplied power adapter requiring
110-240VAC (50~60Hz) power source (<2W)
Supplied with 2 approved batteries (See Approved Battery Technical Spec) for
battery backup during 5V power loss.
RJ45 Ethernet 10Base-T or 100Base-TX (auto-sensing)
Ethernet Network Security:SSL v3, SSH2, Rijndael 256-bit encryption,
password protection, IP address filtering, locking features, hardened OS and
stack
Operating: 32 to 104ºF (0 to 40ºC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
Rack Sensor Array: 3M Command strips to front and rear rack doors. If no
doors then side of rack
Three Point Sensor Array: 3M Command strips to attach where the customer
needs temperature and humidity visualization
Rack Sensor Array: 6 external thermistors
Three Point Sensor Array: 3 external thermistors
Temperature Range: 32ºF to 122ºF (0ºC to 50ºC)
Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC)
Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC)
Time Constant: 30sec moving air; 60sec static air (typical)
Resolution:
±0.02ºF at 77ºF (±0.01ºC at 25ºC)
Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years
Thermistors: 10k ohm, Type J Curve
Thermistor Time Constant: 60sec static air; 30sec moving air (typical)
HP 14 position I/O connector for use with HP Data Center Environmental
Edge Rack Sensor Array
3M Command strips to front and rear rack doors. If no doors then side of
rack
2 plenum rated thermistors attached to plenum rated wire
Temperature Range: 32ºF to 122ºF (0ºC to 50ºC)
Temperature Accuracy 10 to 43ºC: ±0.5ºF (±0.3ºC)
Temperature Accuracy 0 to 10 and 43 to 50ºC: ±1.2ºF (±0.7ºC)
Time Constant: 30sec moving air; 60sec static air (typical)
Resolution:
±0.02ºF at 77ºF (±0.01ºC at 25ºC)
Stability: Typically ± 0.0056ºF (0.0031ºC) over 5 years
Thermistors: 10k ohm, Type J Curve
Thermistor Time Constant: 60sec static air; 30sec moving air (typical)
Worldwide — Version 2 — November 16, 2009
Page 11
HP Data Center Environmental Edge and HP Insight
Environmental Observer
QuickSpecs
Technical Specifications
HP Data Center
Environmental Edge Air
Pressure Base Station
Housing
Mounting Options
Connectors
Power Requirements
Sensed Data
Pressure Sensor
Performance
Sensed Data
High and Low Pressure
Ports
Environmental
HP Data Center
Environmental Edge
Universal Base Station
Housing
Mounting Options
Power Requirements
Analog inputs
DA - 13392
ABS plastic L 4.5" x W 2.6" x H 1.4" (L 114.3mm x W 66.1mm x H 35.6mm)
Screw: (4 holes) 1.7" x 1.3" (43.2mm x 33.1mm) - fits up to #6 Machine
Screws
Zip Tie: (4 holes) Accommodates up to 0.18" width
3M Command Strips
1/8" Barbed Hose Fitting for High and Low Pressure Differential connections
4 Approved Batteries (see Approved Batteries Technical Spec)
Typical battery life @ 5 min Sample Rate: 5 to 7 years
Typical battery Life @ 1 min Sample Rate: 4 years
Internal 0 to 0.5 in-H2O Air Pressure Differential (room vs. plenum)
Differential Pressure Range: 0 to 0.5" H2O (0 to 125 Pa)
Zero point accuracy: 0.002" H2O (0.5Pa)
Span Accuracy: ±3.0% of reading
Resolution:
±0.001"H2O (±0.25 Pa)
Offset Stability: <0.1 Pa per year
0.170 inch inner diameter tubing; use with up to
6 feet of tubing, cut to length as required during installation (supplied with
node; plenum rated UL94V2 tubing). Longer tubing length is allowable, but
sensor accuracy and response time may increase; use pressure diffuser tip to
prevent foreign contaminates entering sensor (supplied with node)
Operating: 32 to 104ºF (0 to 40ºC)
Storage: 14ºF to 140ºF (-10ºC to 60ºC)
ABS plastic L 3.6" x W 2.5" x H 1.2" (L 91.5mm x W 63.5mm x H 30.5mm)
Screws: (4 holes) 1.25" x 1.7" (31.75mm x 43.2mm) - fits up to #6 Machine
Screws
Zip Tie: (4 holes) Accommodates up to 0.18" width
3M Command Strips
4 Approved Batteries (see Approved Batteries Technical Spec)
Typical Battery Life @ 5 min Sample Rate: 5 to 7 years
Typical Battery Life @ 1 min Sample Rate: 4 years
4-20mA:
Accuracy: ±1.15% Full Scale
Resolution 0.03%v
0-10V:
Accuracy: ±1.53% Full Scale
Resolution 0.03%
Worldwide — Version 2 — November 16, 2009
Page 12
HP Data Center Environmental Edge and HP Insight
Environmental Observer
QuickSpecs
Technical Specifications
HP Data Center
Accuracy
Environmental Edge 200A Range
Current Base Station
Console Display
Environmental
Installation
±0.5% (from 1 - 100% FSO)
0 - 200A RMS
2 significant digits for volumetric flow
10°C to 40°C / 20% to 95% RH, non-condensing
Licensed electrician, circuit downtime not required
HP Data Center
Flow Range
Environmental Edge Flow
Meter Base Station
Installation
Console Display
0 to 400fps (based on typical industrial pipe applications this equates to no
limitation in terms of volumetric flow)
Non-intrusive ultrasonic flow measurement
Volumetric Flow, range adjusted at installation for min/max
Limits
1/3200th of the installed range
0 significant digits for volumetric flow
Steel, Copper, Plastic (2-16" diameter)
±2.8%
Resolution
Console Display
Pipe materials
Accuracy
HP Data Center
Environmental Edge
Water Leak Detection
Base Station
Leak Detection
Optical sensor detects liquid contacting surface
Adjustable Height
-13ºF to 176ºF (-25ºC to 80ºC)
HP Data Center
Environmental Edge
Installer kit
Kit Contents
Barcode Scanner
Label Maker
Wire Strippers
Plenum Rated Zip Ties
Command Strips
Cable routing clips
Thermistor mounting clips
Return shipping label
Battery Technical
Information
Approved Battery
Battery Life Expectations
ENERGIZER AA LITHIUM, MODEL# L91, 1.5VDC
Typical Battery Life @ 5 min Sample Rate: 5 to 7 years
Typical Battery Life @ 1 min Sample Rate: 4 years
HP BCMS
Components
Sensor Operating
Temperature
Includes 42 or 84 Split Core CT's, 60 amp rated each
Includes 2 or 4 CT to Ribbon Cable Interface Box
Includes 1 data acquisition board
Mounting and Installation Install data acquisition module inside electrical box or in remote electrical
box. Voltage connections are routed to data acquisition module. Split Core
CT's are connected to Ribbon Cable Interface boxes, which then convert to
ribbon cables connected to the data acquisition board. Modbus connection
uses Modbus RTU 4wire multi-drop.
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 13
QuickSpecs
HP Data Center Environmental Edge and HP Insight
Environmental Observer
Technical Specifications
Power Requirements
Sensed Data
110-240VAC, 4 wire
Data acquisition board can be powered in parallel or separately.
HP EIO software will provide the following data points:
Current per circuit with breaker capacity and warning status
Power Factor per circuit
Voltage per phase
HP Energy Meter
Accuracy*
Power per circuit, per phase, and total with warning status
Current (amperage): +/-2%
Voltage (volts): +/-2%
Power (kw): +/-3%
Installation
Local licensed electrician required for installation and *onsite calibration
Components
Includes HP wireless base station, SquareD ION6200 in single HDM
enclosure, and 3 Split Core CT's, both UL and CE rated
Mounting and Installation HDM Dimensions: 11.92"x7.5"x7.88"
Wall mount ION6200 enclosure. Voltage and CT connections are routed
from source to HDM enclosure.
Power Requirements
110-480VAC*, 50/60Hz, up to 2400amps per circuit*, 3 or 4 wire, Wye or
Delta.
* Depending on model ordered
Sensed Data
HP EIO software will provide the following data points:
Accuracy*
Installation
Current per phase (Wye only)
Power Factor per phase (Wye only)
Voltage per phase (Wye L-N and Delta L-L)
Total Power
Average Power (period = 5min sampling interval)
THD
Current (amperage): +/-1%
Voltage (volts): +/-1%
Power (kw): +/-2%
Local licensed electrician required for installation and *onsite calibration
HP Chilled Water Energy Components
Includes HP wireless base station, Ultrasonic Flow Meter with remote
Meter
transducers, and 2 pipe temperature RTD's
Mounting and Installation Ultrasonic transducers are clamped directly to the chilled water pipe surface.
Pipe temperature RTD's are clamped directly to the chilled water pipe
surfaces.
Control box and wireless node mounted remotely.
Power Requirements
110-240VAC, 50/60Hz
Sensed Data
HP EIO software will provide the following data points:
Supply Volumetric Flow Rate
Supply Temperature
Return Temperature
Accumulated Energy
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 14
HP Data Center Environmental Edge and HP Insight
Environmental Observer
QuickSpecs
Technical Specifications
Environment-friendly
Products and Approach
Accuracy
Volumetric Flow: +/-3%
Temperature: +/-0.2degC
Energy: +/-3%
End-of-life Management
and Recycling
Hewlett-Packard offers end-of-life HP product return, trade-in, and recycling
programs in many geographic areas. For trade-in information, please go to:
http://www.hp.com/go/green. To recycle your product, please go to:
http://www.hp.com/go/green or contact your nearest HP sales office.
Products returned to HP will be recycled, recovered or disposed of in a
responsible manner.
The EU WEEE directive (2002/95/EC) requires manufacturers to provide
treatment information for each product type for use by treatment facilities.
This information (product disassembly instructions) is posted on the Hewlett
Packard web site at: http://www.hp.com/go/green. These instructions may
be used by recyclers and other WEEE treatment facilities as well as HP OEM
customers who integrate and re-sell HP equipment.
© Copyright 2009 Hewlett-Packard Development Company, L.P.
The information contained herein is subject to change without notice.
Microsoft and Windows NT are US registered trademarks of Microsoft Corporation. Intel is a US registered trademark of Intel
Corporation.
The only warranties for HP products and services are set forth in the express warranty statements accompanying such products and
services. Nothing herein should be construed as constituting an additional warranty. HP shall not be liable for technical or editorial
errors or omissions contained herein.
DA - 13392
Worldwide — Version 2 — November 16, 2009
Page 15