new vrf systems range energy saving, easy installation and high

new vrf systems range energy saving, easy installation and high

NEW VRF

SYSTEMS RANGE

ENERGY SAVING,

EASY INSTALLATION

AND HIGH

EFFICIENCY

2013 / 2014

FS MULTI ECOi ECO G VENTILATION

NEW VRF SYSTEMS 2013 / 2014

2

NEW 2013 / 2014

VRF RANGE

Summary

PANASONIC – LEADING THE WAY IN HEATING & COOLING .............................................................................................4

ECO & SMART IDEAS FOR A SUSTAINABLE LIFESTYLE ....................................................................................................6

PANASONIC PROFESSIONAL .........................................................................................................................................8

THE NEW PANASONIC INDUSTRIAL VRF SYSTEMS ........................................................................................................ 10

FS MULTI VRF FROM PANASONIC ................................................................................................................................ 12

OUTDOOR UNITS ........................................................................................................................................................ 14

INTERNET CONTROL. CONTROL YOUR AIR CONDITIONING SYSTEM WITH YOUR SMART

DEVICE -SMARTPHONE & INTERNET FOR PACI ............................................................................................................ 18

INDIVIDUAL CONTROL SYSTEMS .................................................................................................................................. 20

COMBINATION TABLE / BRANCH PIPES ........................................................................................................................ 22

INDOOR / OUTDOOR UNITS RANGE .............................................................................................................................. 24

FEATURE COMPARISON .............................................................................................................................................. 26

5 AND 6 HP, OUTDOOR UNITS ...................................................................................................................................... 28

8 AND 10 HP, OUTDOOR UNITS .................................................................................................................................... 30

WALL-MOUNTED TYPE // SILVER COLOUR .................................................................................................................... 32

WALL-MOUNTED TYPE // WHITE COLOUR // WHITE COLOUR WIDE TYPE ........................................................................ 34

CASSETTE TYPE (60X60) ............................................................................................................................................. 36

CASSETTE TYPE (90X90) ............................................................................................................................................. 38

LOW-SILHOUETTE // DUCT TYPE // LOW STATIC PRESSURE .......................................................................................... 40

LOW-SILHOUETTE // DUCT TYPE // MID STATIC PRESSURE ........................................................................................... 42

ECOi SERIES .............................................................................................................................................................. 44

2-PIPE MINI ECOi LE1 SERIES .................................................................................................................................... 46

MINI ECOi HIGH EFFICIENCY ....................................................................................................................................... 50

2-PIPE ECOi 6N SERIES .............................................................................................................................................. 52

8-12 HP // 2-PIPE ECOi 6N SERIES ............................................................................................................................. 56

14-16 HP // 2-PIPE ECOi 6N SERIES ........................................................................................................................... 58

18-20 HP // 2-PIPE ECOi 6N SERIES ........................................................................................................................... 60

2-PIPE ECOi 6N SERIES // COMBINATION FROM 22 TO 60 HP ....................................................................................... 62

10-12 HP // 2-PIPE ECOi 6N SERIES // HIGH COP SETTING MODEL ............................................................................... 64

14-16 HP // 2-PIPE ECOi 6N SERIES // HIGH COP SETTING MODEL ............................................................................... 66

2-PIPE ECOi 6N SERIES // HIGH COP SETTING MODEL // COMBINATION FROM 18 TO 48 HP ........................................... 68

NEW 3-PIPE ECOi MF2 SERIES ................................................................................................................................... 70

8-16 HP // 3-PIPE ECOi MF2 SERIES ........................................................................................................................... 74

3-PIPE ECOi MF2 SERIES // COMBINATION FROM 18 TO 48 HP ..................................................................................... 76

3-PIPE ECOi MF2 SERIES // HIGH EFFICIENCY COMBINATION 16 TO 32 HP .................................................................... 78

PANASONIC INTRODUCING THE GAS DRIVEN VRF ......................................................................................................... 80

ECO G OUTDOOR UNITS RANGE ................................................................................................................................... 82

ECO G HIGH POWER, ECO G AND ECO G MULTI ............................................................................................................. 84

ECO G WATER HEAT EXCHANGER FOR HYDRONIC APPLICATIONS ................................................................................... 86

NEW ECO G HIGH POWER ........................................................................................................................................... 88

ECO G AND ECO G MULTI ............................................................................................................................................ 90

ECO G 3 WAY MULTI ................................................................................................................................................... 92

THE NEW PANASONIC SOLUTION FOR CHILLED AND HOT WATER PRODUCTION!............................................................. 94

NEW ECOi 2-PIPE WITH WATER HEAT EXCHANGER FOR CHILLED AND HOT WATER PRODUCTION .................................... 96

NEW ECO G WITH WATER HEAT EXCHANGER FOR CHILLED AND HOT WATER PRODUCTION ............................................. 98

NEW AQUAREA AIR RADIATORS ................................................................................................................................. 100

FEATURES / PANASONIC’S DIAGNOSIS SOFTWARE ..................................................................................................... 102

INDOOR UNITS FOR ECOi, MINI ECOi AND ECO G ........................................................................................................ 104

VRF SYSTEMS INDOOR UNITS RANGE ........................................................................................................................ 106

U1 TYPE 4-WAY 90X90 CASSETTE SEMI CONCEALED CASSETTE .................................................................................. 108

Y1 TYPE 4-WAY 60X60 CASSETTE MINI SEMI CONCEALED CASSETTE ........................................................................... 109

L1 TYPE 2-WAY CASSETTE ........................................................................................................................................ 110

D1 TYPE 1-WAY CASSETTE ........................................................................................................................................ 111

F2 TYPE VARIABLE STATIC PRESSURE HIDE AWAY ...................................................................................................... 112

M1 TYPE SLIM VARIABLE STATIC PRESSURE HIDE AWAY CONCEALED DUCT ................................................................. 113

E1 TYPE HIGH STATIC PRESSURE HIDE AWAY ............................................................................................................. 114

T1 TYPE CEILING ...................................................................................................................................................... 115

K2/K1 TYPE WALL MOUNTED .................................................................................................................................... 116

P1 TYPE FLOOR STANDING // R1 TYPE CONCEALED FLOOR STANDING ......................................................................... 117

PANASONIC VENTILATION SOLUTIONS ....................................................................................................................... 118

AIR HANDLING UNIT KIT ........................................................................................................................................... 120

AHU CONNECTION KIT, 28 KW AND 56 KW FOR ECOi AND GHP .................................................................................... 122

AIR CURTAIN ............................................................................................................................................................ 124

ENERGY RECOVERY VENTILATOR ............................................................................................................................... 126

ENERGY RECOVERY VENTILATION SYSTEM ................................................................................................................. 128

CONTROL SYSTEMS FOR VRF .................................................................................................................................... 130

INDIVIDUAL CONTROL SYSTEMS ................................................................................................................................ 132

CENTRALISED CONTROL SYSTEMS ............................................................................................................................ 134

INTERNET CONTROL. CONTROL YOUR AIR CONDITIONING SYSTEM WITH YOUR SMART

DEVICE -SMARTPHONE & INTERNET FOR VRF SYSTEMS ............................................................................................. 140

ECOi CONNECTIVITY INDOOR UNITS .......................................................................................................................... 143

R22 RENEWAL ......................................................................................................................................................... 144

BRANCHES AND HEADERS ........................................................................................................................................ 148

CONTROL EQUIPMENT EXTERNAL DIMENSIONS ......................................................................................................... 153

VRF INDOOR UNITS DIMENSIONS.............................................................................................................................. 154

NEW

3-PIPE ECOi MF2 SERIES SIMULTANEOUS

HEATING AND COOLING VRF SYSTEM

NEW

ECO G HIGH POWER. THE 2-PIPE GAS DRIVEN VRF

WITH AN ELECTRICAL POWER GENERATOR

NEW

K2/TYPE

WALL MOUNTED

NEW

AIR CURTAIN CONNECTED TO VRF

INSTALLATION

NEW

SUPER LOW TEMPERATURE RADIATORS,

FOR HIGH EFFICIENT INSTALLATION

NEW

SOLENOID VALVE KIT. ”NON-STOP” OIL

RECOVERY OPERATION

EDITORIAL

COP

4,77

PG 70

0.10 kW

ELECTRICITY

CONSUMPTION

PG 88

NEW

DESIGN

PG 116

35°C

WATER

TEMPERATURE

HIGH

EFFICIENCY

WITH EC FAN

MOTORS

PG 124

PG 100

PG 72

3

History of Air Conditioning Group

Panasonic starts with a desire to create things of value. As hard work and dedication results in one innovative product after another, the fledgling company takes its first steps towards becoming the electronics giant of today.

Panasonic – leading the way in Heating

& Cooling

With more than 30 years of experience, selling to more than 120 countries around the world, Panasonic is unquestionably one of the leaders in the heating and cooling sector.

With a diverse network of production and R&D facilities, Panasonic delivers innovative products incorporating cutting-edge technologies that set the standard for air conditioners worldwide.

Expanding globally, Panasonic provides superior international products transcending borders.

4

1936

First electric Fan with Automatic

Oscillation (36 cm table top model).

1958

First room air conditioner launched for domestic installation.

Prior to this date, air conditioners were large and only for commercial use.

Panasonic developed the first compact air conditioner for windows; it was lightweight and easy to install, improving the quality of life in

Japanese homes.

1,100 units were sold in Japan in the first year, and just two years later, in 1960, this figure rose to

230,000.

1973

Panasonic launches the first highly efficient air-to-water heat pump in Japan.

1975

Panasonic becomes the first Japanese air conditioner manufacturer in

Europe.

2002

The Ion and Oxygen

Generator — two of the most important contributions to air conditioning systems.

2008

Etherea new concept of air conditioning systems: high efficiency and high performances with a great design. Etherea also includes a very innovative air quality sensor and air purifier in order to enjoy healthy air at home at all times.

2010

New Aquarea.

Panasonic has created

Aquarea, an innovative new, low-energy system, designed to help you enjoy ideal temperatures and hot water in your home, even with extreme outdoor temperatures.

Aquarea cools or heats to ensure maximum comfort.

Aquarea is far cleaner, safer, cheaper and environmentally friendly than alternatives using gas, oil and other electrical systems.

2011

New Eco i VRF solution.

The new Panasonic

VRF solution for big buildings is the most efficient in the industry in more than 74% of combinations. ECO i satisfies the most demanding standards required by design offices, architects, owners and installers.

2012

New GHP units.

Pansonic’s gasdriven VRF systems are ideal for projects where power restrictions apply. In

2012, Panasonic extends the Gas Heat

Pump range with a new GHP line-up, new GHP G Power

(electricity production) and the new Chiller Units.

2013

New ECOi 3-Pipes.

The best efficiency for your building.

Our New 6 Series

3-Pipes is achieving a COP of 4.77 at full load, and even more when recovering heat from the building.

There is no doubt,

Panasonic is reducing environmental impact!

EDITORIAL

Panasonic Europe

Panasonic is committed to offering our customers innovative products in the heating and cooling market across Europe, which not only meet but exceed their requirements. Key to success is Panasonic’s investment in R&D, manufacture and training to ensure innovative, cutting edge products and investment in our distribution channels and partners so that these products are accessible in Europe. Panasonic has developed a comprehensive network across

Europe of training centers and training academies for installers, design offices and service teams in all major countries.

Panasonic Factories and R&D

Department

There is a close relationship between R&D innovation and good manufacturing processes, and so Panasonic has placed its

R&D facilities very close to its manufacturing bases. This ensures good integration between all divisions to deliver high quality and reliable solutions to our markets.

We control the process

The company is also a world leader in innovation as it has filed more than

91,539 patents to improve its customers’ lives. Moreover, Panasonic is determined to remain at the forefront of its market. In all, the company has produced more than 200 million compressors and its products are manufactured in 294 plants which are located all over the world. You can be assured of the extremely high quality of Panasonic’s heat pumps.

This wish to excel has made Panasonic the international leader in heating and turn-key air conditioning solutions for homes, medium-sized buildings such as offices and restaurants, and large-scale buildings. These offer maximum effectiveness, comply with the strictest environmental standards and meet the most avant-garde construction requirements of our time.

At Panasonic we know what a great responsibility it is to install heating and cooling systems. Because offering you the best solutions in heating and cooling matters.

PRODUCTION 100% PANASONIC

SERVICE PROVIDER

100%

RESEARCH & DEVELOPMENT AND DESIGN

TESTING AND QUALITY INSURANCE

5

6

Eco & smart ideas for a sustainable lifestyle

Panasonic aims to be the No. 1 Green Innovation Company in the Electronics Industry by 2018.

We will make the environment central to all our business activities and work to realize our vision with innovations for both every day life and business.

No. 1

Green Innovation

Company in the

Electronics Industry

Innovation focused on environment in all business activities

Green

Life

Innovation

Green

Business

Innovation

EDITORIAL

Exemplary sustainable projects

Blackfriars Bridge

London, UK with Panasonic solar panels.

Skolkovo City

Moscow, Russia with Panasonic energy saving concept.

Photosynthesis

Milano Salone, Milano, Italy with Panasonic LED light bulbs and HIT solar power generators.

Siestorage

Modular energy storage solution with Panasonic lithium ion batteries.

Solar Power Generator

HIT solar cells achieve maximum output even on smaller roofs. These solar modules are 100% emission free, have no moving parts and produce no noise.

We aim to realize a lifestyle with virtually zero

CO

2

emissions throughout the entire home

Home AV

Panasonic offers a wide range of energy saving home equipment to fulfil a sustainable and comfortable lifestyle.

Heat Pump

The Aquarea Heat Pump is part of a new generation of heating systems that use a renewable, free energy source: air, to heat or cool the home and to produce hot water.

Fuel Cell

The Panasonic Fuel Cell is an energy-creating device, which generates electricity and heat at the same time with chemical reaction between hydrogen extracted from natural gas and oxygen.

Solar Power Generator

Our mobility space can be connected to our HIT solar panels – with help of our storage batteries.

LED Lamps

Expertise gathered over years of research and development has enabled

Panasonic to provide a renaissance in energysaving home LED lighting – with our LED Nostalgic Clear lamp.

Home Appliances

Panasonic is globally committed to develop products which are environmentally friendly. Panasonic delivers home appliances such as refrigerators and washing machines that incorporate the latest energy-efficient technology.

Storage Battery

The battery stores the energy generated by a combination of solar power and fuel cells to ensure a constant supply of electricity on demand.

7

Panasonic Professional

Panasonic has an impressive range of support services for designers, specifiers, engineers and distributors working in the heating and cooling markets.

8

Panasonic’s New Advanced VRF Software with AutoCAD

®

compatibility makes design easier than ever

Software

Panasonic provides bespoke software helping system designers, installers and dealers to very quickly design and size systems, create wiring diagrams and issue bills of quantities at the push of a button.

ECOi VRF Designer

Panasonic is pleased to announce the launch of its new

Advanced VRF Designer software. Building on the success of the ECOi VRF Designer software, this package provides air conditioning system designers, installers and dealers with a program to design and size projects for Panasonic’s VRF ranges.

Similar to the standard VRF Designer software, it is possible to create wiring diagrams, electrical power wiring and issue bills of quantities with a simple push of a button. With Panasonic’s Advanced software, designers are now able to work directly from AutoCAD files, making the process extremely easy to manage and time-saving. AutoCAD drawings, print outs and scans from existing designs can be imported and altered with the system therein. Super-efficient and built for the designers’ every need,

Panasonic’s Advanced VRF software can create life-sized piping designs and automatic length calculation based on their imported drawings

The Panasonic VRF Designer system software can be used for all

Panasonic ECOi 6N and FS Multi VRF

Features include

· Easy to use system wizards.

· Auto piping and wiring features.

· Converted duties for conditions and pipework.

· Auto CAD (DXF), Excel and PDF export.

· Detailed wiring and pipework diagram.

EDITORIAL

PRO Club

Panasonic PRO Club

Panasonic announces a new initiative for all professionals involved in the heating and cooling business - the Panasonic PRO Club (www.

panasonicproclub.com). This exciting new portal provides distributors, installers, engineers and specifiers with a direct communication channel with one of the industry’s major manufacturers.

The website contains a wealth of information from the latest versions of

Panasonic’s Aquarea and Etherea Design Software, to Technical

Documentation, Catalogues and Images for the company’s wide range of heating and cooling systems - all in an easy to navigate and use website.

Also, registered users will be able to access news regarding special promotions and take advantage of these offers, as well as access helpful business advice such as ideas and guidelines for showroom decoration or van livery featuring Panasonic logos and display material.

www.panasonicproclub.com

or connect simply with your smartphone to the proclub using this QR:

The Panasonic PRO-Academy opens its doors

Panasonic takes its responsibility to its distributors, specifiers and installers seriously and has developed a comprehensive Training

Programme. The Panasonic Pro-Academy encompasses the traditional hands-on approach, as well as embracing today’s technology to offer an eLearning facility available 24 hours, 7 days a week!

New training courses cover three levels

Design, installation, and commissioning & trouble-shooting

Training courses include:

· VRF ECOi

· Aquarea air source heat pumps (MCS accredited)

· GHP (2012)

The courses are offered on site at Panasonic’s premises across Europe as well as via the Panasonic ProClub eLearning site. The Training Centres display Panasonic’s latest product range and give delegates an opportunity to get hands-on experience with the latest controllers, indoor and outdoor units from the VRF ECOi, Etherea, GHP and Aquarea ranges.

9

10

NEW

THE NEW PANASONIC

INDUSTRIAL VRF SYSTEMS

PROFESSIONAL SOLUTIONS FOR ALL TYPES OF PROJECTS

The new Panasonic VRF system is specifi cally designed for energy saving, easy installation and high effi ciency performance, with a wide choice of outdoor and indoor unit models and unique features which are designed for the most demanding offi ces and big buildings.

A

class

energy saving

Energy

saving

High

savings

Maximum

flexibility

Inverter+ products improve on the characteristics of standard Inverter range by over 20%. A Inverter plus is also A class on cooling and heating mode.

The Inverter range provides greater efficiency, more comfort. Provides more precise temperature control, without highs and lows, and keeps the ambient temperature constant with lower energy consumption and a significant reduction in noise and vibration levels.

GHP technology offer the best preliminary efficiency.

VRF

VRF. The Inverter plus range provides greater efficiency,

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

The ECOi system works in heating mode at outdoor temperatures down to -25 °C (2-Pipe series) or -20 °C (3-Pipe series and Mini ECOi).

Easy

control by BMS

CONNECTIVITY

The communication port is integrated into the indoor unit and provides easy connection to, and control of, your Panasonic heat pump to your home or building management system.

Environmentally

friendly

refrigerant

R410A

R410A. Environmentally friendly refrigerant.

5 year

compressor warranty

5 YEARS WARRANTY.

We guarantee the compressors in the entire range for five years.

NEW

VRF SYSTEMS

FS Multi VRF

The FS Multi VRF lineup is a full Electrical VRF line up specially designed for small to medium installations.

Benefits:

· Easy to install units

· No additional gas needed (for 4, 5 and 6 HP)

· Indoor units match Etherea wall mounted designs

· Self diagnostic function with 7-digit code for easy set up and repair

Example applications:

1. Apartments

2. Bungalows

3. Offices

4. Shops & Boutiques

Mini ECOi

The Mini ECOi VRF lineup is a high efficiency electrical VRF.

Benefits:

· High efficiency outdoor units

· Compatible with all ECOi indoors units

· Compatible with all remote controls/interfaces from the ECOi range

· Flexible connection to ECOi projects

Example of ECOi and MiniECOi applications:

1. Complexes // 2. High Rise Buildings //

3. Commercial Buildings // 4. Hotels

ECOi

ECOi electrical VRF is specifically designed for the most demanding offices and big buildings.

Benefits:

· High efficiency system

· From 8 to 20 HP in only one chassis

· Extended operating range to provide heating at outdoor temperature as low as -25 °C

· Suitable for refurbishment projects

ECO G

ECO G gas VRF is specially designed for buildings where the electricity is restricted or CO

2 must be reduced.

emissions

Benefits:

· Very high preliminary efficiency ratio

· Very low electrical consumption

· Compatible with all ECOi indoor units and remote controls

· Sanitary hot water is produced freely in summer

Example applications:

1. Complexes

2. High Rise Buildings

3. Commercial Buildings

4. Hotels

11

12

FS MULTI VRF

FROM PANASONIC

Easy to install VRF, specially designed for homes and small commercial buildings: large lineup of indoor units, Etherea wall mounted design,

5-6-8-10 HP outdoor units, single phase and three phase.

FS Multi VRF’s cutting edge VRF technology is perfectly suited to medium-sized or small areas, with single-phase power sources, together with advanced Inverter technology, opening up previously unimagined possibilities in the world of air conditioning.

Air conditioning spaces can now take on a new dimension. If you have bought a new property, home, offi ce or commercial place which is still in the construction phase, or if you are refurbishing, Panasonic offers you the chance to enjoy FS Multi VRF air conditioning.

U-5LA1E5 // U-6LA1E5

For homes and multi-storey apartments.

Enabling air conditioning in multiple rooms with a single outdoor unit.

U-8EA1E8 // U-10EA1E8

Offi ces, shops and boutiques.

As well as being ideal for new buildings.

VRF SYSTEMS FS MULTI

13

OUTDOOR UNITS

U-5LA1E5 // U-6LA1E5

ON

25 °C

OFF

ON

26 °C

ON

23 °C

OFF

Pipes of up to 90 m

The total length of the pipe between a system’s indoor and outdoor units can be extended up to 90 metres, with a height difference of up to 30 metres.

These ample limits make it possible to place the outdoor unit on the roof. The maximum height difference between indoor units in the same system may be up to 15 metres, thus covering 4 or 5 floors in the same system.

Maximum height difference between outdoor unit and indoor unit

30 m

Maximum total pipe length

90 m

Maximum height difference between indoor units

15 m

Farthest pipe length (from outdoor unit to farthest indoor unit)

55 m

(equivalent length) a) Maximum length from outdoor unit to farthest indoor unit (equivalent length): 55 m b) Maximum length from first branch pipe to farthest indoor unit (equivalent length): 30 m c) Maximum length of all main pipes: 40 m d) Maximum length of all branch pipes: 50 m

Residences

Since a layout using long piping is possible, a single outdoor unit can be used even for multi-storey residences.

And we offer a wide range of indoor unit designs to choose from to complement different interiors.

Multi-storey Apartments

Enabling air conditioning in multiple rooms with a single outdoor unit, the

FS Multi VRF system offers an effective solution to today’s demand for aesthetically pleasing buildings.

The indoor units are also available in designs providing an ideal match for modern living environments.

Space-Saving Design

Improvements to the design of the outdoor unit’s fan has reduced the size of the unit to enable installation in a smaller space. Without sacrificing quietness, higher efficiency is also attained. Easy piping facilitates freedom in installation, and reduction in installation costs.

Only 30 cm needed

300 mm

900 mm

1340 mm

350 mm

14

SYSTEM / HP 5HP

Connectable Indoor Unit 8

6HP

8

Refrigerant pipe

URBAN net control line

OUTDOOR UNITS

U-8EA1E8 // U-10EA1E8

HIGH STATIC

PRESSURE

60

Pa

VRF SYSTEMS FS MULTI

Long pipe-runs possible

The total length of the pipe between a system’s indoor and outdoor units can be extended up to 300 metres, with a height difference of up to 50 metres.

These ample limits make it possible to place the outdoor unit on the roof. The maximum height difference between indoor units in the same system may be up to 15 metres, thus covering 4 or 5 floors in the same system.

Maximum height difference between outdoor unit and indoor unit

50 m

Maximum height difference between indoor units

15 m

Maximum total pipe length

300 m

Farthest pipe length (from outdoor unit to farthest indoorunit)

190 m

(eguivalent length) a) Maximum length from outdoor unit to farthest indoor unit

(equivalent length): 190 m;

(actual length): 165 m b) Maximum length from first branch pipe to farthest indoor unit

(equivalent length): 40 m c) Maximum length of all main pipes: 135 m

Offi ces, Shops and Boutiques

As well as being ideal for new buildings, the FS Multi VRF system offers space-saving benefits when refurbishing and renovating existing spaces.

What’s more, independent air conditioning reduces energy wasted in unused offices, and much neater pipe layout is possible than with a single split system. Using the Weekly Timer also enables setting for the optimum

Energy saving operation in offices and commercial facilities. And there are options enabling demand control and digital connection compatibility to meet the needs of business applications.

High External Static Pressure Mode

8 and 10 HP outdoor unit features a high external static pressure mode (up to 60 Pa). Select via the outdoor unit’s local setting mode.

SYSTEM / HP 8HP

Connectable Indoor Unit 13

10HP

16

Refrigerant pipe

URBAN net control line

15

Energy saving

1. Hyper Wave Inverter

The series quickly warms the room up to the set temperature and maintains it within the comfort zone while ensuring energy efficiency and savings.

2. DC Inverter Compressor

A powerful neodymium magnet helps make the motor more compact.

3. Large Diagonal Air Flow Fan

1

3

1

2

3

2

DC Inverter Compressor

Energy Saving

High quality features translate into savings thanks to great energy efficiency. This efficiency is due to the fact that each room is individually controlled and only the rooms that require air-conditioning are heated or cooled. Moreover, thanks to

Inverter technology, the level of air conditioning can be adjusted precisely depending on each room’s condition.

5.00

4.50

4.00

3.50

3.00

2.50

3.25

2.00

5 HP

3.01

6 HP

3.70

8 HP

3.37

10 HP

4.03

5 HP

3.84

6 HP

COOLING HEATING

4.10

4.01

8 HP 10 HP

Broad Operating Range

The heating function will remain stable indoors even when the temperature outside drops to -15 °C, thus meeting users different needs. Moreover, the cooling function operates from -5 °C to 43 °C.

-20

- 1 5 - 1 0 - 5 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 (˚C)

11,2 - 15,5 KW

-15 °C (DB) 24 °C (DB)

Hyper Wave Inverter

Panasonic’s expertise from inverter development is realised in the Hyper

Wave Inverter. The control of the inverter demonstrates optimum compressor torque. The FS Multi VRF series quickly heats up the room to the set temperature and maintains a comfortable condition, whilst ensuring energy efficiency and savings.

HYPER WAVE INVERTER INVERTER / HEAT PUMP

Compressor runs unnecessarily

-5 °C (DB) 43 °C (DB)

22,4 - 28 KW

-20 °C (DB) 24 °C (DB)

The current waveform deviates from the motor voltage waveform, so power is wasted.

COMPARE THIS TO A CAR ROUNDING A CORNER

The current waveform closely matches the motor voltage waveform, so power consumption is reduced.

-5 °C (DB) 43 °C (DB)

Quiet Operation

A host of silencing technologies achieve superquiet operation. We’ve also improved operating efficiency and reduced energy consumption.

Noise-Suppressing

Winglet Fan

Power is wasted when the car swings off course.

When the car stays right on course, there’s no power loss.

16

3

3

1

2

1 2

3

VRF SYSTEMS FS MULTI

Frequent Single Split System Problems

1. Requires many outdoor units and large installation space.

Thus, spoiling the building’s appearance, and the building’s strength must be assessed.

2. Requires many pipe shafts.

3. Pipes are short so outdoor units have to be installed on wall surfaces.

Insufficient pipe length makes installation impossible.

FS Multi VRF System Solution

1. Minimized number of outdoor units thanks to multi system. Rooftop space can be used more effectively and the unit load on the roof is considerably reduced.

2. Outdoor units can be installed close to each other, maintaining the building’s appearance and enhancing the installation flexibility.

3. The number of pipings is reduced, thus minimising the space required in pipe shafts.

Easy maintenance

When there is a breakdown in an indoor unit, the system continues to work without this indoor unit. The outdoor unit does not stop, and the rest of the indoor units continue to operate.

When installation space is limited

A single compact FS Multi VRF system outdoor unit enables air conditioning in multiple rooms, solving the problems of narrow or limited installation space.

SINGLE SPLIT FS MULTI VRF

Innovative and perfect control of loading for the 5 and 6 HP

The outdoor unit controls and optimises the loading of refrigerant in the system by asking each indoor unit its requirements. With this very innovative loading control, the system is highly efficient and the indoor unit responds very quickly to demands.

Cooling Only Model Setting

· The unit designed for cooling only can be set by the JP wire on the outdoor unit PC board.

· After setting this mode, the FS Multi VRF system cools only.

Outdoor Unit Silent Operation Mode

The Silent Operation mode of the outdoor unit can be selected by remote control.

There are three mode settings that reduce the noise level by up to 6 dB(A). (When the Silent Operation mode is selected, cooling and heating capacity are reduced.)

LV1

LV2

LV3

EXAMPLE AT 4HP MODEL AT COOLING OPERATION

Reference Capacity index*

Normal mode 100

80

72

62

* The indexes are nominal capacity operation reference values

48

46

Sound pressure dB(A)

52

50

17

INTERNET CONTROL. CONTROL YOUR AIR CONDITIONING SYSTEM WITH YOUR SMART DEVICE

-SMARTPHONE & INTERNET FOR PACi

NEW

Internet

Control

Ready

CONTROL YOUR

AIR CONDITIONING FROM

EVERYWHERE

OPTIONAL

INTERNET CONTROL

Reference PA-AC-WIFI-1 KX-UT670 Smart Desktop Phone from Panasonic.

Control your comfort and effi ciency with the lowest energy consumption

What’s Internet Control?

Internet Control is a next generation system providing a user-friendly remote control of air conditioning or heat pump units from everywhere, using a simple Android or iOS smartphone, tablet or PC via internet.

Simple Installation

Just connect the Internet Control device to the air conditioner or heat pump with the supplied wire and then link it to your WIFI Access point.

Internet Control. Easy to install. Maximum benefit

Internet Control is underlined with the slogan “Your home in the cloud”, meaning a simple and easy to handle solution has been considered for every user to manage the device, not requiring any communication or computer skills.

No servers. No adaptors. No wires. Just a small box to be connected and placed close to the air conditioning indoor unit is needed… and your smartphone, tablet or PC.

Start the App from your smartphone device, your tablet or your computer, and enjoy a new experience in comfort. An intuitive and user-friendly application on the screen of your smartphone or PC let you manage the air conditioning unit in the same way you do with the remote controller.

Internet Control can be downloaded in Apple’s AppStore and Android’s

PlayStore.

Study Case. Alice, Shop Owner

“I want maximum comfort and the best savings for my shop. And I manage to get these in the easiest and most natural way possible. From my smartphone, something I always carry with me, I can control the temperature of my shop and in this way, as well as maintaining an ideal temperature I also save a small fortune in electricity at the end of the year.”

TAKE CONTROL FROM WHEREVER YOU ARE!

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

COMPUTER SMARTPHONE TABLET HOME OFFICE STREET WORK GYM

Home or Office

Control your air conditioning with the smart internet control device via smartphones, tablet, PC and smart desktop phone via internet

Offering the same functions as if you were at home or office: start/stop,

Mode Operation, Set Temperature, Room Temperature etc as well as the new, advanced functionality provided by Internet Control to achieve the best comfort and efficiency with the lowest energy consumption.

18

INTERNET service in the cloud*

INTERFACE

WIFI

AIR

CONDITIONING

ROUTER WIFI

* Functionalities depend on the license. The information indicated above is subject to changes and updates.

VRF SYSTEMS FS MULTI

FS MULTI CONNECTIVITY. NEW INTERFACES FOR FS LINE UP. INCREASED FLEXIBILITY FOR

INTEGRATION INTO YOUR PROJECTS

Easy

control by BMS

CONNECTIVITY

Great flexibility for integration into your KNX /

EnOcean / Modbus / LonWorks / BACnet projects allows fully bi-directional monitoring and control of all the functioning parameters

Panasonic Partners have designed solutions specifically for Panasonic air conditioners, and provide complete monitoring, control and full functionality of the entire Commercial line-up from

KNX / EnOcean / Modbus / LonWorks / BACnet installations.

For more information, contact Panasonic.

AIR CONDITIONING

INTERFACE

FS Multi

PANASONIC MODEL

NAME

PAW-RC-KNX-1i

PAW-RC-MBS-1

PAW-RC-ENO-1i

PA-RC-WIFI-1

INTERFACE

KNX

Modbus RTU

EnOcean

IntesisHome

CONNECTED ON P-LINK OR IN THE

INDOOR UNIT

Indoor unit

Indoor unit

Indoor unit

Indoor unit

MAX NUMBER OF INDOOR UNITS

CONNECTED

1 (1 Group of Indoor units)

1 (1 Group of Indoor units)

1 (1 Group of Indoor units)

1 (1 Group of Indoor units.)

POSSIBLE TO CONNECT MORE THAN 1

INDOOR UNIT (GROUP OF INDOORS)

No

No

No

No

AIRZONE. CONTROL OF THE PACI HIDE AWAYS

Airzone has developed interfaces to easily connect to Panasonic PACi Hide

Away units. Ensuring optimum performance, comfort and energy savings, the new system is efficient and easy to install.

AIRZONE FULL RANGE OF ACCESSORIES FOR ANY DUCT PROJECT

Room control

Air

Outlet

AIRZONE

Interface

I_U

PCB

ON

24 °C

Different type of outlets

Also plenum automatic doors

Full range of RC

(wired/wireless, ...)

Interface dimensions: 120 x 25 x 65 cm (W x H x D). Interfaces must be purchased direct from Airzone.

OFF

ON

22 °C

OFF

19

INDIVIDUAL CONTROL SYSTEMS

Unlike conventional air conditioning systems, the VRF system is applied separately to each room. So, this system is ideal for areas with fl uctuation in traffi c. Moreover, you can have precise control over each of the rooms to achieve exact conditions.

Individual control makes this system more cost-effective and effi cient.

Wired Remote Controller

CZ-RT1

· Remote controller with LCD and selfdiagnosis

· Constant monitoring of the system with fault detection

· Weekly timer function

· Maintenance time and cost reduction

OPERATING BUTTONS

· ON/OFF

· Real time daily timer

· Weekly timer: 6 actions per day

(total 42 actions per week), including temperature setting.

· Temperature adjustment

· Adjusting air direction

· Selection of operating mode

· Fan speed control

· Restart filter

· Ventilation interlink

MONITOR

· Operating mode

· Centralised control indicator

· Demand control indicator

· Operation priority indicator

· Selected temperature

· Air direction

· Clock

· Day of the week indicator

· Inspection/operating test

· Fan speed

· Filter maintenance

· Defrost/hot start indicator

· Error mode display

1. Weekly Timer

Weekly timer setting (each day of the week) is available to control the air conditioner. Max. 6 settings/day and 42 settings/week can be executed. The setting temperature can also be programmed for optimal comfort.

1

2

EXAMPLES OF SETTING WEEKLY TIMER

SHOP WITH REGULAR HOLIDAYS

Example: Closed Saturday afternoon and all day Sunday.

Mon-Fri On 9:00, Off 18:00

Sat On 9:00, Off 12:00

Sun Not set

The timer can have different settings for every day of the week.

THE NUMBER OF PERSONS VARIES DEPENDING ON

TIME ZONES.

Example: Set a lower temperature at lunch time when many people may visit.

Everyday

On 12:00 23 °C

On 14:00 28 °C

In this case, the temperature can be set at the same time.

NOT TO FORGET TO SWITCH OFF

Example: To prevent forgetting to switch OFF weekdays

Mon-Fri

Off 20:00

The timer can be set for simple shut-off operation.

HOW TO SET

1

SELECT

THE DAY

2

ENTER

THE TIME

*Simple Timer Mode

2. Ventilation Interlink

When an external device such as a ventilator is connected to the indoor unit, switch ON/OFF of the ventilator can be controlled by the wired remote control. Either link-ventilation or independent-ventilation is selectable.

Energy recovery ventilators are also offered by Panasonic.

Optional printed circuit board (Interface Adapter for External Signals: CZ-TA31P*) is needed.

(digital connection)

ON

ON

Interface Adapter for External Signals

CZ-TA31P*

· By connecting to the indoor unit, a separately sold ventilator can be controlled.

· Remote control operation of the indoor unit is enabled (ON/OFF control).

· The operating condition of the indoor unit (malfunctions, operating status) can be externally output.

· Control in linkage with a Energy Recovery Ventilators (ERV) or similar is possible.

CONNECTION WITH EXTERNAL CENTRAL SYSTEM

(digital connection)

CZ-TA31P

INTERLINK WITH VENTILATION OR ERV

(digital connection)

ON

20

· Remote ON/OFF

· Remote /Local Selection

· ON/OFF Monitor Signal

· Malfunction Signal

· Fan Operation Signal

Central control system (local supply)

ON

*CZ-TA31P NOT applicable for wall-mounted indoor unit

VRF SYSTEMS FS MULTI

Wireless Remote Controller

CZ-RWS1 . Heat Pump Models

CZ-RWC1. Cooling Only Models

· Remote controller with LCD and self-diagnosis

· Error code recognition

· Maintenance time and cost reduction

· Real time daily timer

OPERATING BUTTONS

· ON/OFF

· Activate/deactivate programmer

· Real time daily timer

· Temperature adjustment

· Air direction

· Operating mode

· Fan speed control

· Restart filter

· Inspection of error code

MONITOR

· Operating mode

· Temperature selected

· Air direction

· Time programming

· Error code display

· Fan speed

· Clock

Wireless Controller Receiver

For Cassette Type

CZ-RWRU1

For Duct Type

CZ-RWRM1

Cooling/Heating Controller for the

Outdoor Unit

CZ-RD1

Enables the cooling, heating and ventilating operating mode for each outdoor unit. Allows the operating mode to be changed for several outdoor units at the same time by means of a single remote control.

Wireless receivers for wall-mounted and 60x60 Cassette types are equipped as standard.

Terminal Module (Equipped as Standard on the Outdoor Unit)

CZ-CAP1

Control terminal to be connected with outside devices or CZ-RD1 controller.

· Used to receive forced stop digital signal from local procured central control system.

· Used to receive demand control signal from local procured central control system. (Demand control for energy saving with 3-level selection)

· Required to connect with CZ-RD1 cooling/heating controller.

· Group control of several FS Multi VRF systems for forced stop and CZ-RD1 cooling/heating controller.

WHEN CONNECTING DEMAND CONTROLLER WHEN CONNECTING FORCED STOP INPUT

Terminal module

Central control system

(local supply) such as

Fire Alarm device

6 5

Terminal block

Outdoor unit

WHEN USING CZ-RD1 (COOLING / HEATING SELECTOR)

Outdoor unit

GROUP CONNECTION

COM LV3 LV2 LV1

Terminal block

Demand controller

4/5/6 HP 8/10 HP

LV1 70% 85%

LV2

LV3

30%

0%

70%

0%

Further Outdoor unit system

4 3 2

Terminal block

1

Outdoor unit

Outdoor unit Outdoor unit

*Not applicable for demand controller

Outdoor unit

21

COMBINATION TABLE

The FS Multi VRF system attains maximum indoor unit connection capacity of up to 130% in the units connection range, depending on the outdoor and indoor models selected.

In the case of a 6 HP outdoor unit (15.5 kW / 53,000 Btu/h), connection is possible with a maximum indoor unit range of 20.15 kW. So for a reasonable investment, the FS Multi

VRF system provides an ideal air conditioning solution for locations where full cooling/heating is not always required.

COMBINATION TABLE

Reference

U-5LA1E5

U-6LA1E5

Outdoor unit System cooling capacity Maximum indoor unit Standard combination capacity* Maximum combination capacity Minimum combination capacity

5.0HP/ 14.0 kW/ 47,800 Btu/h 8 14.0 kW 18.20 kW 7.0 kW

6.0HP/ 15.5 kW/ 52,900 Btu/h 8 15.5 kW 20.15 kW 7.75 kW

100% 130% 50%

*Standard combination capacity is the system’s maximum cooling capacity.

COMBINATION EXAMPLE

Correct

Outdoor

Indoor

Total indoor capacity

Reference

U-6LA1E5

S-22KA1E5

S-36KA1E5

S-22NA1E5

S-28NA1E5

1

3

7

1

2

Quantity

1

Capacity

15.5 kW*

2.2 kW

(3.6x2)7.2 kW

2.2 kW

(2.8x3)8.4 kW

20.0 kW(129%)

22

Incorrect

Outdoor

Indoor

Total indoor capacity

Reference

U-6LA1E5

S-22KA1E5

S-36KA1E5

S-45KA1E5

S-22NA1E5

S-28NA1E5

8

3

1

1

1

2

Quantity

1

*Standard combination capacity is the system’s maximum cooling capacity.

Capacity

15.5 kW*

2.2 kW

(3.6x2)7.2 kW

4.5 kW

2.2 kW

(2.8x3)8.4 kW

24.5 kW(158%)

-

-

-

-

Minimum combination capacity

7.75 kW

-

-

-

-

Maximum combination capacity

20.15 kW

-

-

-

-

Minimum combination capacity

7.75 kW

-

-

-

-

Maximum combination capacity

20.15 kW

VRF SYSTEMS FS MULTI

BRANCH PIPES

CZ-P155BK1 / CZ-P280BK1

R410A Branch pipe kits

The use of branch piping combined with expansion valves mounted in VRF indoor units considerably reduces the imbalance of the refrigerant liquid flow between indoor units despite the smaller piping diameter. The joints for these pipes have been designed to reduce installation time, as they are easy to fit. Finally, the branch pipes optimise refrigerant flow.

Section

ONLY FOR 8-10 HP

CZ-P3HPC2BM: 3-PIPE HEADER

CZ-P4HP4C2BM

Thermal insulation material

Refrigerant

Branch Pipe

BRANCH PIPE KIT CZ-P155BK1 (FOR 4, 5 AND 6 HP SYSTEMS)

1

Liquid side branch pipe (inner diameter)

1/4 3/8 3/8

Header pipe models for 2-Pipe systems:

CZ-P4HP4C2BM

11

10

9

576

1/4 3/8

2

Gas side branch pipe (inner diameter)

1/4 3/8

5/8

1/2

6 7 8 9

5

4

3

569

3 4 5

1/2 5/8

BRANCH PIPE KIT CZ-P280BK1 (FOR 8 AND 10 HP SYSTEMS)

1

Liquid side branch pipe (inner diameter)

1/4 3/8 3/8

2

1

1/4

3/8

2

Gas side branch pipe (inner diameter)

1/2 3/4

3/4

8

9

10

11

6

7

4

5

2

3

DIAMETERS

1 6.35 mm

9.52 mm

12.70 mm

15.88 mm

19.05 mm

22.40 mm

25.40 mm

28.57 mm

31.75 mm

34.92 mm

38.10 mm

1/4’’

3/8’’

1/2’’

5/8’’

3/4’’

7/8’’

1’’

1’’ 1/8

1’’ 1/4

1’’3/8

1’’1/2

1/2

3/4

PIPE ADAPTORS ARE SUPPLIED WITH THE PACKAGE.

Pipe Adaptor

A

019.05

B Quantity

0 15.88

1

0 12.70

0 15.88

2

0 19.05

0 25.40

1

0 19.05

22.2

0 9.52

12.7

3

1

23

INDOOR UNITS RANGE

COOLING CAPACITY

HEATING CAPACITY

WALL-MOUNTED TYPE

0.8 HP

2.2kW / 7,500 Btu/h

2.5kW / 8,500 Btu/h

1.0 HP

2.8kW / 9,600 Btu/h

1.25 HP

3.2kW / 10,900 Btu/h

3.2kW / 10,900 Btu/h 3.6kW / 12,300 Btu/h

1.5 HP

3.6kW / 12,300 Btu/h

4.2kW / 14,300 Btu/h

S-22KA1E5 S-28KA1E5 S-36KA1E5

S-22KA1E5S S-28KA1E5S S-36KA1E5S

CASSETTE TYPE

60x60 CASSETTE TYPE

LOW-SILHOUETTE DUCT TYPE (LOW STATIC PRESSURE

TYPE)

S-22YA1E5

LOW-SILHOUETTE DUCT TYPE (MID STATIC PRESSURE

TYPE)

S-22NA1E5

S-28YA1E5

S-28NA1E5 S-32NA1E5

S-36YA1E5

S-36NA1E5

OUTDOOR UNITS RANGE

COOLING CAPACITY

HEATING CAPACITY

OUTDOOR UNIT

5.0 HP

14.0 kW / 47,800 Btu/h

16.0 kW / 54,600 Btu/h

6.0 HP

15.5 kW / 52,900 Btu/h

18.0 kW / 61,400 Btu/h

24

U-5LA1E5 U-6LA1E5

VRF SYSTEMS FS MULTI

1.75 HP

4.5kW / 15,400 Btu/h

5.1kW / 17,400 Btu/h

2.0 HP

5.6kW / 19,100 Btu/h

6.4kW / 21,800 Btu/h

2.5 HP

6.3kW / 21,500 Btu/h

7.1kW / 24,200 Btu/h

3.0 HP 3.5 HP

7.1kW / 24,200 Btu/h 9.0kW / 30,700 Btu/h

4 HP

10.0kW

8.0kW / 27,300 Btu/h 10.0kW / 34,100 Btu/h 11.2kW

S-45KA1E5 S-56KA1E5 S-63KA1E5 S-71KA1E5

S-45KA1E5S

S-63UA1E5 S-71UA1E5 S-90UA1E5 S-100UA1E5

S-45YA1E5 S-56YA1E5

S-45NA1E5 S-56NA1E5

S-45MA1E5 S-56MA1E5 S-63MA1E5 S-71MA1E5 S-90MA1E5 S-100MA1E5

8.0 HP

22.4 kW / 76,000 Btu/h

25.0kW

10.0 HP

28.0 kW / 95,000 Btu/h

31.5kW

U-8EA1E8 U-10EA1E8

25

FEATURE COMPARISON

INDOOR UNIT WALL MOUNTED 60X60 CASSETTE

FEATURE

CONTROL

FLEXIBILITY

Remote controller Wired remote controller Infrared remote controller Wired remote controller Infrared remote controller

24 h ON/OFF Real setting timer

✘ ✘ ✘ ✘

Weekly timer (6-Pattern/Max.

42-Pattern with temp setting)

Group control by single remote

✘ controller

O_U Silent operation mode (3-Level) ✘

I_U Thermistor switching (I_U or RC) ✘

Ventilation unit control

Digital input / Output contact

COMFORTABILITY Filter sign

Hot start control

Filter

✘ with CZ-TA31P

✘ with CZ-TA31P

FIELD SERVICE

& MAINTENANCE

Anti Bacterial Filter (optional)

Indoor unit address setting

Outdoor unit address setting

Indoor unit test run mode

Emergency operation

Self diagnosis function

Self diagnosis records

CZ-SA16P (10 years)

CZ-SA16P (10 years)

CZ-SA13P (3 years)

CZ-SA13P (3 years)

OUTDOOR UNIT 5-6 HP 8-10 HP

CONTROL

FLEXIBILITY

FIELD SERVICE

& MAINTENANCE

DIGITAL INPUT/

OUTPUT

"Cooling Only" model setting (Locked)

Power save mode

O_U Silent operation Mode (3-Level)

Auto restart

Pump down operation

Cooling operation TESTRUN

Heating operation TESTRUN

Automatic address resetting

Self diagnosis function

Cooling / Heating selector (optional)

Demand control input (3 Levels demand control input)

Forced stop input

26

✘ (LED display)

✘ (LED display)

VRF SYSTEMS FS MULTI

CASSETTE DUCT (LOW STATIC PRESSURE) DUCT (MID STATIC PRESSURE)

Wired remote controller Infrared remote controller Wired remote controller Infrared remote controller Wired remote controller Infrared remote controller

✘ ✘ ✘ ✘ ✘ ✘

✘ ✘ ✘

✘ with CZ-TA31P

✘ with CZ-TA31P

✘ with CZ-TA31P

✘ with CZ-TA31P

✘ with CZ-TA31P

✘ with CZ-TA31P

27

Maximum

flexibility

VRF

VRF

flexibility

Maximum

5 AND 6 HP, OUTDOOR UNITS

THE MONOPHASE 5 AND 6 HP OUTDOOR UNITS ARE IDEAL FOR INSTALLATION IN

RESTAURANTS, OFFICES AND HOMES.

All Panasonic FS Multi VRF series modules are equipped with DC inverter compressor for the higher energy saving operation. The new design attains the quiet and high-efficient operation and reduces the running cost.

A

class

energy saving

Environmentally

friendly

refrigerant

R410A

Down to

-15 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL ZOOM

· REFRIGERANT CHARGE-FREE SYSTEM (NO ADDITIONAL

REFRIGERANT IS REQUIRED)

. VERY QUIET OUTDOOR UNITS

· FLEXIBLE INSTALLATION AND EASY SETUP

. EASY TROUBLE CHECK FUNCTION

· SPACE-SAVING DESIGN

HP

MODEL NUMBER

Power Source

Cooling

Heating

Capacity

Power Input phase

V

Hz kW (Btu/h)

W

5HP

U-5LA1E5

220-230-240

50Hz

14.00 (47,800)

4,310

EER W/W (Btu/h) 3.25 (11.09)

Current¹ A 19.80

Air Volume

Sound Pressure Level Hi/Lo

Sound Power Level Hi/Lo

Operating Range

Capacity

Power Input

COP

Current¹ m³/min (ft³/min) 95.0 (3,353) dB (A) dB

Min. - Max. °C

53/-

71/-

-5 - 43

6HP

U-6LA1E5

220-230-240

50Hz

15.50 (52,900)

5,150

3.01 (10.27)

23.50

98.0 (3,459)

55/-

73/-

-5 - 43 kW (Btu/h)

W

16.00 (54,600)

3,970

18.00 (61,400)

4,690

W/W (Btu/h) 4.03 (13.75)

A

3.84 (13.09)

18.10 21.40

Air Volume

Sound Pressure Level Hi/Lo

Sound Power Level Hi/Lo

Operating Range

Connectable Indoor Unit Total Capacity

Model/Qty

Moisture Removal Volume

Dimensions H x W x D

Net Weight

Piping Connection

Maximum Total Piping Length

Height Difference (Maximum)

Max Charge less Length

Refrigerant

Liquid Side

Gas Side

Min. - Max. °C

Min. - Max. m (ft)

Max

Max m³/min (ft³/min) 95.0 (3,353) dB (A) dB unit

L/h (Pt/h) mm inch kg (lb) mm (inch) mm (inch) m (ft) m (ft)

55/-

72/-

-15 - 24

50~130% of Outdoor Unit Capacity

S-22 ~ S-90 /2 - 8

9.0 (18.9)

1,340 x 900 x 350(+40)²

52-3/4 x 35-7/16 x 13-25/32(+1-9/16)

123 (271)

9.52 (3/8)

15.88 (5/8)

20 - 90 (65.6 - 295.2)

30 (98.4)

90 (295.2)

R410A / 8 kg

98.0 (3,459)

57/-

74/-

-15 - 24

S-22 ~ S-90 /2 - 8

10.3 (21.6)

1,340 x 900 x 350(+40)²

52-3/4 x 35-7/16 x 13-25/32(+1-9/16)

123 (271)

9.52 (3/8)

15.88 (5/8)

20 - 90 (65.6 - 295.2)

30 (98.4)

90 (295.2)

R410A / 8 kg

1 These values are at 230V only. For 220V and 240V specifications, please refer to the technical data book.

2 Add 40mm for discharge grille.

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

POWER

REFERENCE

Maximum combination of indoor unit

Power rates (kW)

Power supply (V/Hz)

5HP

U-5LA1E5

8

7.0 - 14.0 - 18.2

220-240 / 50

6HP

U-6LA1E5

8

7.8 - 15.5 - 20.2

220-240 / 50

28

VRF SYSTEMS FS MULTI

U-5LA1E5 // U-6LA1E5

Control Flexibility

· Cooling Only Model Setting (by jumper line cut)

· Power Save Mode

· Outdoor Unit Silent Operation Mode

· Auto Restart

Field Service & Maintenance

· Pump Down Operation

· Cooling Operation TESTRUN

· Heating Operation TESTRUN

· Automatic Address Resetting

· Self Diagnosis Function (LED display)

Digital Input/Output

· Cooling/Heating Selector

· Demand Control Input (LV1/LV2/LV3)

· Forced STOP Input

140 620 140

900

40

200 or more

100 or more

Air intake side

500 or more

Space for piping, wiring and maintenance

30

Air outlet side

350

29

Maximum

flexibility

VRF

VRF

flexibility

Maximum

8 AND 10 HP, OUTDOOR UNITS

NEW THREE PHASE 8 AND 10 HP OUTDOOR UNITS. EASY TO INSTALL, HIGH PERFORMANCES!

All the models of Panasonic FS Multi VRF series are equipped with DC inverter compressor for the higher energy saving operation. The new design attains the quiet and high-efficient operation and reduces the running cost.

A

class

energy saving

Environmentally

friendly

refrigerant

R410A

Down to

-15 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL ZOOM

. VERY QUIET OUTDOOR UNITS

· FLEXIBLE INSTALLATION AND EASY SETUP

. EASY TROUBLE CHECK FUNCTION

· SPACE-SAVING DESIGN

HP

MODEL NUMBER

Power Source

Cooling

Heating

Capacity

Power Input phase

V

Hz kW (Btu/h)

W

8HP

U-8EA1E8

380-400-415

50Hz

22.40 (76,500)

6,050

EER W/W (Btu/h) 3.70 (12.64)

Current¹ A 9.40

Air Volume

Sound Pressure Level Hi/Lo

Sound Power Level Hi/Lo

Operating Range

Capacity

Power Input

COP

Current¹ m³/min (ft³/min) 150 (5,297) dB (A) dB

Min. - Max. °C

58/-

78/-

-5 - 43

10HP

U-10EA1E8

380-400-415

50Hz

28.00 (95,600)

8,310

3.37

12.80

154 (5,438)

59/-

79/-

-5 - 43 kW (Btu/h)

W

25.00 (85,300)

6,100

31.50 (107,500)

7,860

W/W (Btu/h) 4.10 (13.98)

A

4.01

9.40 12.10

Air Volume

Sound Pressure Level Hi/Lo m³/min (ft³/min) 150 (5,297) dB (A) 59/-

Sound Power Level Hi/Lo

Operating Range dB

Min. - Max. °C

79/-

-20 - 24

Connectable Indoor Unit Total Capacity

Model/Qty

Dimensions H x W x D

Net Weight

Piping Connection

Maximum Total Piping Length

Height Difference (Maximum)

Refrigerant

Liquid Side

Gas Side

Max unit mm inch kg (lb) mm (inch) mm (inch)

Min. - Max. m (ft) m (ft)

50~130% of Outdoor Unit Capacity

S-22 ~ S-125 /2 - 13

1,745 x 920 x 760

68-11/16 x 36-7/32 x 29-29/32

195 (430)

9.52 (3/8)

19.05 (4/3)

15 - 300 (49.2 - 984.2)

50 (164.0)

R410A / 8.5 kg

154 (5,438)

60/-

80/-

-20 - 24

50~130% of Outdoor Unit Capacity

S-22 ~ S-125 /2 - 16

1,745 x 920 x 760

68-11/16 x 36-7/32 x 29-29/32

210 (463)

9.52 (3/8)

22.22 (7/8)

15 - 300 (49.2 - 984.2)

50 (164.0)

R410A / 11.0 kg

1 These values are at 400 V only. For 380 V and 415 V specifications, please refer to the technical data book.

2 Add 40 mm for discharge grille.

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

POWER

REFERENCE

Maximum combination of indoor unit

Power rates (kW)

Power supply (V/Hz)

8HP

U-8EA1E8

13

11.2 - 22.4 - 29.1

380 - 415 / 50

10HP

U-10EA1E8

16

14.0 - 28.0 - 36.4

380 - 415 / 50

30

VRF SYSTEMS FS MULTI

HIGH STATIC

PRESSURE

60

Pa

U-8EA1E8 // U-10EA1E8

Control Flexibility

. Cooling/Heating Selector

. Demand Control Input (LV1/LV2/LV3)

. Forced STOP Input

. Cooling Only Model Setting (by jumper line cut)

. Power Save Mode

. Outdoor Unit Silent Operation Mode

. Auto Restart

Field Service & Maintenance

. Cooling Operation TESTRUN

. Heating Operation TESTRUN

. Automatic Adress Resetting

. Self Diagnosis Function (LED display)

10 H.P.

8 H.P.

Model

326

196*

A

Connecting Pipe

* Dimension when use the accessory pipe

9.52 Flare

Liquid Side

22.22 Brazing

19.05 Brazing

Gas Side

920

1

2

5

6

145

175

105

241 45

168

120

80

140

3

135 126 113

1

4 2

4-15x20 Hole

(Hole of anchor bolt)

100 720

Hole pitch of anchor bolt

100

53

760

53

460

1 3-Way Valve (Liquid Side)

2 3-Way Valve (Gas Side)

3 Pipe Hole (Front)

4 Pipe Hole (Bottom)

5 Conduit Hole (Power Cord)

6 Conduit Hole (Bus Line)

No Application

31

Maximum

flexibility

VRF

VRF

flexibility

Maximum

WALL-MOUNTED TYPE // SILVER COLOUR

FS MULTI VRF WALL-MOUNTED TYPE AIR CONDITIONERS HAVE BEEN DESIGNED IN A BEAUTIFUL AND STYLISH WAY.

The fresh new horizontal curved form characterizes the air conditioner’s new design. The gentle curve at the centre stylishly conceals the complex high-performance mechanisms inside, while thin ends emphasize the air conditioner’s slim style. This allows it to blend into the wall in an attractive manner, and to harmonise with virtually any room interior.

TECHNICAL ZOOM

· FLEXIBLE INSTALLATION

· EFFECTIVE LONG-LIFE FILTER

· SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE DISPLAY

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

INDOOR

Cooling

Heating

Capacity

Power Input phase

V

Hz kW (Btu/h)

W

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level

Capacity

Power Input

Hi/Lo dB kW (Btu/h)

W

Moisture Removal Volume

Dimensions

Net Weight

Piping Connection

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level Hi/Lo dB

H x W x D

Liquid Side

Gas Side

L/h (Pt/h) mm inch kg (lb) mm (inch) mm (inch)

0.8HP

S-22KA1E5S

1.0HP

S-28KA1E5S

1.5HP

S-36KA1E5S

1.75HP

S-45KA1E5S

1Ø 1Ø 1Ø 1Ø

220-230-240 220-230-240 220-230-240 220-230-240

50 Hz

2.20 (7,500)

50 Hz

2.80 (9,600)

50 Hz

3.60 (12,300)

50 Hz

4.50 (15,400)

25 27 30 35

0.25 0.30 0.35 0.40

9.5 (335)

38/33

53/48

2.50 (8,500)

25

9.7 (342)

39/33

54/48

3.20 (10,900)

27

10.9 (385)

42/34

57/49

4.20 (14,300)

30

11.3 (399)

43/35

58/50

5.10 (17,400)

35

0.25 0.30 0.35 0.40

10.3 (364) 10.9 (385) 11.6 (409) 12.1 (427)

38/33

53/48

39/33

54/48

42/34

57/49

43/35

58/50

1.3 (2.7)

290 x 870 x 204

11-7/16 x 34-9/32 x 8-1/16

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

1.6 (3.4)

290 x 870 x 204

11-7/16 x 34-9/32 x 8-1/16

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

2.1 (4.4)

290 x 870 x 204

11-7/16 x 34-9/32 x 8-1/16

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

2.5 (5.3)

290 x 870 x 204

11-7/16 x 34-9/32 x 8-1/16

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

Before installing in quiet room such as a bedroom, please consult with an authorized distributor.

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

FLEXIBLE INSTALLATION

Thanks to its compact and stylish design, Panasonic’s wall mounted air conditioner can be installed in very limited spaces, without detracting from your room’s interior design.

SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE

DISPLAY

When the air conditioner has trouble the indicator and

7-seg code displays on the panel making it easier for service technicians to diagnose problems.

EFFECTIVE LONG-LIFE FILTER

This long-life filter can trap dust mites, tobacco smoke and other common pollutants effectively. When it catches certain airborne particles, the clean-indicator will remind you to clean. You can remove the filter quickly with a simple one step operation, after cleaning, it can be re-fitted.

OPTIONAL ACCESSORIES

Anti Bacterial Filter - 10 - year filter life

CZ-SA16P

Replacement: every 10 years

32

VRF SYSTEMS FS MULTI

S-22KA1E5S // S-28KA1E5S // S-36KA1E5S // S-45KA1E5S

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

Comfortability

· Filter Sign

· Hot Start Control

· Filter

· Anti Bacterial Filter (optional/10-year lifetime)

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

TOP VIEW

SIDE VIEW

Air intake direction

FRONT VIEW

Left piping hole

Air outlet direction

1-2

870

REAR VIEW

Liquid side

Gas side

1-2

410 (41-61)

SIDE VIEW

204

Right piping hole

125

60

BOTTOM VIEW

60

115

33

Maximum

flexibility

VRF

VRF

flexibility

Maximum

WALL-MOUNTED TYPE // WHITE COLOUR // WHITE COLOUR WIDE TYPE

FS MULTI VRF WALL-MOUNTED TYPE AIR CONDITIONERS HAVE BEEN DESIGNED IN A BEAUTIFUL AND STYLISH WAY.

The fresh new horizontal curved form characterizes the air conditioner’s new design. The gentle curve at the centre stylishly conceals the complex high-performance mechanisms inside, while thin ends emphasize the air conditioner’s slim style. This allows it to blend into the wall in an attractive manner, and to harmonise with virtually any room interior.

TECHNICAL ZOOM

· FLEXIBLE INSTALLATION

· EFFECTIVE LONG-LIFE FILTER

· SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE DISPLAY

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

INDOOR

Cooling

Heating

Moisture Removal Volume

Dimensions

Net Weight

Piping Connection

Capacity

Power Input

Current phase

V

Hz kW (Btu/h)

W

A

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level

Capacity

Power Input

Hi/Lo dB kW (Btu/h)

W

Current

Air Volume Hi

A m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level Hi/Lo dB

H x W x D

L/h (Pt/h) mm inch

Liquid Side

Gas Side kg (lb) mm (inch) mm (inch)

0.8HP

S-22KA1E5

1.0HP

S-28KA1E5

1.5HP

S-36KA1E5

1.75HP

S-45KA1E5

2.0HP

S-56KA1E5

2.5HP

S-63KA1E5

3.0HP

S-71KA1E5

1Ø 1Ø 1Ø 1Ø 1Ø 1Ø 1Ø

220-230-240 220-230-240 220-230-240 220-230-240 220-230-240 220-230-240 220-230-240

50 Hz

2.20 (7,500)

50 Hz

2.80 (9,600)

50 Hz

3.60 (12,300)

50 Hz

4.50 (15,400)

50 Hz

5.60 (19,100)

50 Hz

6.30 (21,500)

50 Hz

7.10 (24,200)

25 27 30 35 45 50 55

0.25 0.30 0.35 0.40 0.40 0.45 0.50

9.5 (335)

38/33

53/48

2.50 (8,500)

25

9.7 (342)

39/33

54/48

3.20 (10,900)

27

10.9 (385)

42/34

57/49

4.20 (14,300)

30

11.3 (399)

43/35

58/50

5.10 (17,400)

35

15.3 (540)

44/38

59/53

6.40 (21,800)

45

16.0 (565)

46/39

61/54

7.10 (24,200)

50

17.4 (614)

48/40

63/55

8.00 (27,300)

55

0.25 0.30 0.35 0.40 0.40 0.45 0.50

10.3 (364) 10.9 (385) 11.6 (409) 12.1 (427) 16.7 (590) 17.1 (604) 18.3 (648)

38/33

53/48

39/33

54/48

42/34

57/49

43/35

58/50

44/38

59/53

46/39

61/54

48/40

63/55

1.3 (2.7)

290 x 870 x 204

11-7/16 x 34-9/32

x 8-1/16

1.6 (3.4)

290 x 870 x 204

11-7/16 x 34-9/32

x 8-1/16

2.1 (4.4)

290 x 870 x 204

11-7/16 x 34-9/32

x 8-1/16

2.5 (5.3)

290 x 870 x 204

11-7/16 x 34-9/32

x 8-1/16

3.2 (6.7)

290 x 1,070 x 235

11-7/16 x 42-5/32

x 9-9/32

3.6 (7.6)

290 x 1,070 x 235

11-7/16 x 42-5/32

x 9-9/32

4.2 (8.8)

290 x 1,070 x 235

11-7/16 x 42-5/32

x 9-9/32

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

9 (20)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

11 (24)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

12 (26)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

12 (26)

Ø 9.52 (3/8)

Ø 15.88 (5/8)

Before installing in quiet room such as a bedroom, please consult with an authorized distributor.

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

FLEXIBLE INSTALLATION

Thanks to its compact and stylish design, Panasonic’s wall mounted air conditioner can be installed in very limited spaces, without detracting from your room’s interior design.

SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE

DISPLAY

When the air conditioner has trouble the indicator and

7-seg code displays on the panel making it easier for service technicians to diagnose problems.

EFFECTIVE LONG-LIFE FILTER

This long-life filter can trap dust mites, tobacco smoke and other common pollutants effectively. When it catches certain airborne particles, the clean-indicator will remind you to clean. You can remove the filter quickly with a simple one step operation, after cleaning, it can be re-fitted.

OPTIONAL ACCESSORIES

Anti Bacterial Filter - 10 - year filter life

CZ-SA16P

Replacement: every 10 years

34

VRF SYSTEMS FS MULTI

WHITE COLOUR -WIDE TYPE-

WHITE COLOUR

S-22KA1E5 // S-28KA1E5 // S-36KA1E5 // S-45KA1E5 //

S-56KA1E5 // S-63KA1E5 // S-71KA1E5

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

Comfortability

· Filter Sign

· Hot Start Control

· Filter

· Anti Bacterial Filter (optional/10-year lifetime)

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

Side View

Air intake direction

0.8HP - 1.75HP MODELS

Top View

Front View

Side View

204

Side View

Air intake direction

2HP - 3HP MODELS

Top View

Front View

Side View

235

Left piping hole Air outlet direction

1-2

870

Bottom View

1-2

125

60

Rear View

Liquid side

Gas side

60

115

Right piping hole

Left piping hole Air outlet direction

1~2

1070

Bottom View

1~2

125

61

Rear View

Liquid side

Gas side

410 (41-61)

61

115

410 (41-61)

Right piping hole

35

Maximum

flexibility

VRF

VRF

flexibility

Maximum

CASSETTE TYPE (60x60)

4-WAY AIRFLOW COMFORT WITH ELEGANT, COMPACT PANEL

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

TECHNICAL ZOOM

· COMPACT DESIGN ALLOWS SPACE SAVING!

· SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE DISPLAY

· ONLY 260 mm THIN

· 750 mm DRAIN-UP MECHANISM

· ANTI-MOULD LONG-LIFE AIR FILTER

INDOOR

Panel

Cooling

Heating

Moisture Removal Volume

Dimensions

(H x W x D) phase

V

Capacity

Power Input

Hz kW (Btu/h)

W

Current A

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level

Capacity

Hi/Lo dB kW (Btu/h)

Power Input W

Current A

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level Hi/Lo dB (A)

Sound Power Level Hi/Lo dB

L/h (Pt/h)

Indoor unit mm inch

Panel

Net Weight

Piping Connection Liquid Side

Gas Side

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb mm kg (lb) mm (inch) mm (inch)

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

0.8HP

S-22YA1E5

1.0HP

S-28YA1E5

1.5HP

S-36YA1E5

1.75HP

S-45YA1E5

2.0HP

S-56YA1E5

CZ-KPY1 CZ-KPY1 CZ-KPY1 CZ-KPY1 CZ-KPY1

1Ø 1Ø 1Ø 1Ø 1Ø

220-230-240

50Hz

2.20 (7,500)

35

220-230-240

50Hz

2.80 (9,600)

35

220-230-240

50Hz

3.60 (12,300)

40

220-230-240

50Hz

4.50 (15,400)

40

220-230-240

50Hz

5.60 (19,100)

45

0.30 0.30 0.35 0.35 0.35

8.3 (293) 8.6 (304) 9.0 (318) 9.3 (328) 9.9 (349)

36/33

51/48

2.50 (8,500)

37/33

52/48

3.20 (10,900)

38/34

53/49

4.20 (14,300)

39/35

54/50

5.10 (17,400)

40/36

55/51

6.40 (21,800)

35 35 40 40 45

0.30 0.30 0.35 0.35 0.35

9.3 (328)

36/33

9.6 (339)

37/33

9.9 (349)

38/34

10.3 (364)

39/35

10.6 (374)

40/36

51/48

1.3 (2.7)

260 x 575 x 575

10-1/4 x 22-21/32

x 22-21/32

52/48

1.6 (3.4)

260 x 575 x 575

10-1/4 x 22-21/32

x 22-21/32

53/49

2.1 (4.4)

260 x 575 x 575

10-1/4 x 22-21/32

x 22-21/32

54/50

2.5 (5.3)

260 x 575 x 575

10-1/4 x 22-21/32

x 22-21/32

55/51

3.2 (6.7)

260 x 575 x 575

101/4 x 22-21/32

x 22-21/32

51 x 700 x 700

18 (40)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

51 x 700 x 700

18 (40)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

51 x 700 x 700

18 (40)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

51 x 700 x 700

18 (40)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

51 x 700 x 700

18 (40)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

ANTI-MOULD LONG-LIFE AIR FILTER COMPACT DESIGN ALLOWS SPACE

SAVING!

The panel is a compact 70x70 cm so it can be installed even in a small room where space is limited. The ceiling space required is 65x65 cm.

SELF DIAGNOSIS FUNCTION WITH

7-SEG CODE DISPLAY

When the air conditioner has trouble the indicator and 7-seg code displays on the panel making it easier for service technicians to diagnose problems.

ONLY 260 mm THIN AND 750 mm

DRAIN-UP MECHANISM

260 mm

With only 260mm high body, fitting easily in ceiling spaces and tight spots.

* For optimum comfort, we recommend cleaning the air filter every 1.5 months.

OPTIONAL ACCESSORIES

750 mm

700 mm

700 mm

The internal pump allows the drain line to be elevated up to 750 mm above the base of the unit.

Anti Bacterial Filter

CZ-SA13P

Replacement: every 3 years

36

VRF SYSTEMS FS MULTI

S-22YA1E5 // S-28YA1E5 // S-36YA1E5 // S-45YA1E5 // S-56YA1E5

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

· Digital Input/Output Contact - with CZ-TA31P (Optional)

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

Comfortability

· Filter Sign

· Mildew-Proofing Drain pan

· Hot Start Control

· Filter

· Anti Bacterial Filter (optional/3-year lifetime)

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

(Handing bolt)

(Ceiling opening)

Air Intel

Gas piping Liquid piping Drain pipe

37

Maximum

flexibility

CASSETTE TYPE (90x90)

4-WAY AIRFLOW, POWERFUL, AND COMPACT (ONLY 246 cm HIGH)

VRF

VRF

flexibility

Maximum

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

TECHNICAL ZOOM

· SELF DIAGNOSIS FUNCTION WITH 7-SEG CODE DISPLAY

· ONLY 246 mm THIN

· 750 mm DRAIN-UP MECHANISM

· ELEGANT PANEL, 4-DIRECTION BLOW

· THREE AIRFLOW PATTERNS FOR EXTRA COMFORT

· FLEXIBLE PIPING LAYOUT

· INNOVATIVE DESIGN CREATES EXTRA QUIET OPERATION

INDOOR

Panel

Cooling

Heating

Capacity

Power Input ¹ phase

V

Hz kW (Btu/h)

W

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level ¹ Hi/Lo dB (A)

Sound Power Level ¹ Hi/Lo dB

Capacity kW (Btu/h)

Power Input ¹ W

Moisture Removal Volume

Dimensions

(H x W x D)

Net Weight

Piping Connection

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level ¹ Hi/Lo dB (A)

Sound Power Level ¹ Hi/Lo dB

L/h (Pt/h)

Indoor unit mm inch

Panel

Liquid Side

Gas Side mm kg (lb) mm (inch) mm (inch)

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

2.5HP

S-63UA1E5

3.0HP

S-71UA1E5

3.5HP

S-90UA1E5

4.0HP

S-100UA1E5

CZ-BT03P CZ-BT03P CZ-BT03P CZ-BT03P

1Ø 1Ø 1Ø 1Ø

220-230-240

50Hz

6.30 (21,500)

110

220-230-240

50Hz

7.10 (24,200)

115

220-230-240

50Hz

9.00 (30,700)

115

220-230-240

50Hz

10.00 (34,100)

205

0.50 0.55 0.55 1.05

21 (741) 22 (777) 22 (777) 30 (1,059)

41/35

56/50

7.10 (24,200)

42/36

57/51

8.00 (27,300)

42/36

57/51

10.00 (34,100)

48/43

63/58

11.20 (38,200)

110 115 115 205

0.50 0.55 0.55 1.05

21 (741)

41/35

22 (777)

42/36

22 (777)

42/36

30 (1,059)

48/43

56/50

3.6 (7.6)

246 x 840 x 840

9-11/16 x 33-1/16 x 33/1/16

57/51

4.2 (8.8)

246 x 840 x 840

9-11/16 x 33-1/16 x 33/1/16

57/51

5.4 (11.3)

246 x 840 x 840

9-11/16 x 33-1/16 x 33/1/16

63/58

6.0 (12.6)

288 x 840 x 840

11-11/32x33-1/16x33-1/16

45 x 950 x 950

26 (57)

Ø 6.35 (1/4)

Ø 12.7 (1/2)

45 x 950 x 950

26 (57)

Ø 9.52 (3/8)

Ø 15.88 (5/8)

45 x 950 x 950

26 (57)

Ø 9.52 (3/8)

Ø 15.88 (5/8)

45 x 950 x 950

30 (66)

Ø 9.52 (3/8)

Ø 15.88 (5/8)

1 These values are at 230V only. For 220V and 240V specifications, please refer to the technical data book.

ONLY 246 MM THIN AND 750 MM DRAIN-UP MECHANISM

246 mm

With only 246 mm high body, fitting easily in ceiling spaces and tight spots.

ELEGANT PANEL, 4-DIRECTION BLOW

The slim body can be totally hidden in the ceiling, only leaving its elegant panel outside to decorate your room. The 4-direction blow can deliver airflows evenly throughout the room, eliminating the temperature difference.

FLEXIBLE PIPING LAYOUT

Drainpipe and refrigerant pipe distributed on the different sides of the unit, giving more flexibility of piping layout. Its excellent inside heat-protection material effectively avoids frost and water-leakage, and reduces the damage possibility in the transportation.

Refrigerant

Pipe

Drainpipe

750 mm

The internal pump allows the drain line to be elevated up to 750 mm above the base of the unit.

THREE AIRFLOW PATTERNS FOR EXTRA COMFORT

· Multi-Comfort Air Control

SELF DIAGNOSIS FUNCTION WITH

7-SEG CODE DISPLAY

When the air conditioner has trouble the indicator and 7-seg code displays on the panel making it easier for service technicians to diagnose problems.

38

INNOVATIVE DESIGN CREATES EXTRA QUIET OPERATION

More de-noising Material

Adopting de-noising material inside, improving the seal quality to isolate and reduce the operation noises.

VRF SYSTEMS FS MULTI

S-63UA1E5 // S-71UA1E5 // S-90UA1E5 // S-100UA1E5

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

· Digital Input/Output Contact - with CZ-TA31P (Optional)

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

Comfortability

· Filter Sign

· Mildew-Proofing Drain pan

· Hot Start Control

· Filter

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

Fresh air inlet position

SPACE NEEDED FOR INSTALLATION more

Obstacles

DRAINAGE

Drainage opening Downward slope more

Beam

Indoor unit

Gas pipe

Liquid pipe Drainage opening

Remote control photoreceiver position

39

Maximum

flexibility

VRF

VRF

flexibility

Maximum

LOW-SILHOUETTE // DUCT TYPE // LOW STATIC PRESSURE

OFFERS MAXIMUM INSTALLATION FLEXIBILITY WITH SLIM, LIGHTWEIGHT DESIGN

Only 200 mm tall! Ideal for hotels and offices.

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

TECHNICAL ZOOM

· ULTRA-THIN, DUCT-TYPE INDOOR UNIT

· ULTRA-THIN 200 mm DESIGN: FITS IN EVEN WHERE CEILING

HEIGHT IS LIMITED

· BUILT-IN SELECTABLE STATIC PRESSURE SETTINGS

· THOROUGHLY CONSIDERED CONNECTING FLANGE DESIGN

INDOOR

Cooling

Heating

Moisture Removal Volume

External Static Pressure ²

Dimensions phase

V

Capacity

Hz kW (Btu/h)

Power Input ¹ W

Current A

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level ¹ Hi/Lo dB (A)

Sound Power Level ¹ Hi/Lo dB

Capacity

Power Input ¹ kW(Btu/h)

W

Current A

Air Volume Hi m³/min (ft³/min)

Sound Pressure Level ¹ Hi/Lo dB (A)

Sound Power Level ¹ Hi/Lo dB

H x W x D

L/h (Pt/h)

Pa (mmAq) mm inch

Net Weight

Piping Connection Liquid Side

Gas Side

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb kg(lb) mm (inch) mm (inch)

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

0.8HP

S-22NA1E5

1.0HP

S-28NA1E5

1.25HP

S-32NA1E5

1.5HP

S-36NA1E5

1.75HP

S-45NA1E5

2.0HP

S-56NA1E5

1Ø 1Ø 1Ø 1Ø 1Ø 1Ø

220-230-240 220-230-240 220-230-240 220-230-240 220-230-240 220-230-240

50Hz

2.20 (7,500)

50Hz

2.80 (9,600)

50Hz

3.20 (10,900)

50Hz

3.60 (12,300)

50Hz

4.50 (15,400)

50Hz

5.60 (19,100)

75 80 85 85 95 105

0.40 0.45 0.45 0.45 0.50 0.50

10 (353)

36/30

51/45

2.50 (8,500)

75

11 (388)

37/30

52/45

3.20 (10,900)

80

11 (388)

38/31

53/46

3.60 (12,300)

85

11 (388)

38/31

53/46

4.20 (14,300)

85

12 (424)

39/32

54/47

5.10 (17,400)

95

12.5 (441)

39/32

54/47

6.40 (21,800)

105

0.40 0.45 0.45 0.45 0.50 0.50

10 (353) 11 (388) 11 (388) 11 (388) 12 (424) 12.5 (441)

36/30

51/45

37/30

52/45

38/31

53/46

38/31

53/46

39/32

54/47

39/32

54/47

1.3 (2.7)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

1.6 (3.4)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

1.8 (3.8)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

2.1 (4.4)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

2.5 (5.3)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

3.2 (6.7)

0/29 (0/3)

200 x 900 x 550

7-7/8 x 35-7/16

x 21-21/32

21 (46)

Ø 6.35 (1/4)

12.7 (1/2)

21 (46)

Ø 6.35 (1/4)

12.7 (1/2)

22 (48)

Ø 6.35 (1/4)

12.7 (1/2)

22 (48)

Ø 6.35 (1/4)

12.7 (1/2)

22 (48)

Ø 6.35 (1/4)

12.7 (1/2)

22 (48)

Ø 6.35 (1/4)

12.7 (1/2)

1 These values are at 230 V only. For 220 V and 240 V specifications, please refer to the technical data book.

2 The external static pressure is set to 0pa at factory default setting.

ULTRA-THIN, DUCT-TYPE INDOOR UNIT

The slim design of this ultra-thin, duct-type indoor unit is especially suited for rooms with partially or minimally dropped ceilings. Its space-saving design contributes to a brighter and more spacious living environment.

BUILT-IN SELECTABLE STATIC PRESSURE SETTINGS

Our ultra thin duct-type indoor units have two static pressure settings: 0 Pa and 29

Pa. In situations without ducting, the 0 Pa* static pressure setting is applicable.

Where ducting is present, set the unit to 29 Pa* static pressure.

*0 Pa is the default setting: 29 Pa must be selected if required.

ULTRA-THIN 20 CM DESIGN: FITS IN EVEN WHERE CEILING HEIGHT IS LIMITED

Even where ceiling height is limited, the indoor units effectively fit in and provide a more spacious feel in most suspended ceiling situations. Occupying only 20 cm of vertical space and projecting only 55 cm, the unit can be installed in semi-dropped ceiling situations, thus helping to create spacious and comfortable surroundings.

Air outlet

Air duct

Installation Diagram for

19 Pa Setting

Air in let

Indoor unit

Suspended ceiling

Ceiling Ceiling

Indoor unit

Air outlet

Installation Diagram for

0 Pa Setting

Air in let

Suspended ceiling

THOROUGHLY CONSIDERED CONNECTING FLANGE DESIGN

The addition of air duct connecting flanges on the indoor unit enables easy connection to short air ducts. Thus flange design both greatly simplifies installation and makes it easy to effectively seal the air duct.

DROPPED CEILING EFFECT

40

VRF SYSTEMS FS MULTI

53

34

133

65

22

124

154

80

65

940

900

868

780(12×P65)

S-22NA1E5 // S-28NA1E5 // S-32NA1E5 // S-36NA1E5 // S-45NA1E5 // S-56NA1E5

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

· Digital Input/Output Contact - with CZ-TA31P (Optional)

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

Comfortability

· Filter Sign

· Hot Start Control

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

SCALE 1:10

(UNIT:mm

REQUIRED SPACE FOR INSTALLATION

<Top View>

Inspection hole

Control box

600

Air conditioner

Front

600

<Front view>

Above 250cm

41

Maximum

flexibility

VRF

VRF

flexibility

Maximum

LOW-SILHOUETTE // DUCT TYPE // MID STATIC PRESSURE

DUCT TYPE WITH A MAXIMUM OF 7 mmAq OF STATIC PRESSURE WITH SLIM PROFILE OF ONLY 250 mm.

COMPACT AND POWERFUL!

A

class

energy saving

Easy

control by BMS

CONNECTIVITY

Environmentally

friendly

refrigerant

R410A

5 year

compressor warranty

TECHNICAL ZOOM

· COMPACT, LIGHTWEIGHT DESIGN FOR EASY INSTALLATION

· 3-WAY REMOVABLE AIR FILTER

· VERSATILE AIR INLET AND DRAIN INSTALLATION

· STATIC PRESSURE SELECTION

INDOOR

Cooling

Heating

Capacity

Power Input ¹ phase

V

Hz kW (Btu/h)

W

1.75 HP

S-45MA1E5

2.0 HP

S-56MA1E5

2.5 HP

S-63MA1E5

3.0 HP

S-71MA1E5

3.5 HP

S-90MA1E5

4.0HP

S-100MA1E5

1Ø 1Ø 1Ø 1Ø 1Ø 1Ø

220-230-240 220-230-240 220-230-240 220-230-240 220-230-240 220-230-240

50Hz

4.50 (15,400)

50Hz

5.60 (19,100)

50Hz

6.30 (21,500)

50Hz

7.10 (24,200)

50Hz

9.00 (30,700)

50Hz

10.00 (34,100)

135 135 135 135 175 300

0.60 0.60 0.60 0.60 0.80 1.35

Air Volume Hi m³/min (ft³/min) 15 (530)

Sound Pressure Level ¹ Hi/Lo dB (A) 42/35

Sound Power Level ¹ Hi/Lo dB

Capacity

Power Input ¹ kW(Btu/h)

W

57/50

5.10 (17,400)

135

15 (530)

42/35

57/50

6.40 (21,800)

135

17 (600)

43/36

58/51

7.10 (24,200)

135

17 (600)

43/36

58/51

8.00 (27,300)

135

19 (671)

44/37

59/52

10.00 (34,100)

175

34 (1,201)

47/43

62/58

11.20 (38,200)

300

Air Volume Hi

0.60 0.60 0.60 0.60 0.80 1.35 m³/min (ft³/min) 15 (530)

Sound Pressure Level ¹ Hi/Lo dB (A)

Sound Power Level ¹ Hi/Lo dB

42/35

57/50

15 (530)

42/35

57/50

17 (600)

43/36

58/51

17 (600)

43/36

58/51

19 (671)

44/37

59/52

34 (1,201)

47/43

62/58

Moisture Removal Volume

External Static Pressure ²

Dimensions H x W x D

L/h (Pt/h)

Pa (mmAq) mm inch

2.5 (5.3)

49/69 (5/7)

250x780(+100)³x650

9-27/32x30-23/32(+3-

15/16) x25-19/32

3.2 (6.7)

49/69 (5/7)

250x780(+100)³x650

9-27/32x30-23/32(+3-

15/16) x25-19/32

3.6 (7.6)

49/69 (5/7)

4.2 (8.8)

49/69 (5/7)

5.4 (11.3)

49/69 (5/7)

6.0 (12.6)

49/69 (5/7)

250x1,000(+100)³x650 250x1,000(+100)³x650 250x1,000(+100)³x650 250x1,200(+100)³x650

9-27/32x39-3/8(+3-15/16) x25-19/32

9-27/32x39-3/8(+3-15/16) x25-19/32

9-27/32x39-3/8(+3-15/16) x25-19/32

9-27/32 x47-1/4(+3-15/16) x25-19/32

Net Weight

Piping Connection Liquid Side

Gas Side kg(lb) mm (inch) mm (inch)

28 (62)

Ø 6.35 (1/4)

12.7 (1/2)

28 (62)

Ø 6.35 (1/4)

12.7 (1/2)

32 (71)

Ø 6.35 (1/4)

12.7 (1/2)

32 (71)

Ø 9.52 (3/8)

15.88 (5/8)

32 (71)

Ø 9.52 (3/8)

15.88 (5/8)

41 (90)

Ø 9.52 (3/8)

15.88 (5/8)

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

DB: Dry Bulb; WB: Wet Bulb

Cooling Heating

27 °C DB / 19 °C WB 20 °C DB

35 °C DB / 24 °C WB 7 °C DB / 6 °C WB

1 These values are at 230 V only. For 220 V and 240 V specifications, please refer to the technical data book.

2 The external static pressure is set to 49 Pa at factory default setting.

3 Add 100 mm for piping port.

COMPACT, LIGHTWEIGHT DESIGN FOR EASY INSTALLATION

Thin and only 250 mm high, with a slim width. This compact unit fits easily in limited spaces. The lightweight and small size also make it easier to transport and install.

Width*: 780 mm (45/56MA1E5) / 1,000 mm (63/71/90MA1E5)

3-WAY REMOVABLE AIR FILTER

Height:

250 mm (H)

* Add 100 mm for power supply equipment.

The air filter can be slide in-out in three directions even after duct installation for easier maintenance.

VERSATILE AIR INLET AND DRAIN INSTALLATION

The mounting locations for the air inlet and drain outlet can be changed as desired for easy, flexible system layout and installation.

STATIC PRESSURE SELECTION

The static pressure is selectable from 5 or 7 mmAq according to the condition of the duct. For short ducts, the lower pressure of

5 mmAq provides efficient operation.

Standard Air Inlet Air Inlet from below

Provided locally

PLENUMS

MA1 E5 MEDIUM PRESSURE DUCTED

Air Outlet Plenum (without regulation adaptor)

S-_MA1E5 N. of exits with diameters Model

45 & 56 3 x Ø 160 CZ-DUMPA45MAS3

63 , 71 & 90 4 x Ø 160

100 & 125 5 x Ø 200

CZ-DUMPA63MAS4

CZ-DUMPA100MAS5

MA1 E5 MEDIUM PRESSURE DUCTED

Air Inlet Plenum

S-_MA1E5

N.of exits with diameters Model

45 & 56

2 x Ø 200

CZ-DUMPA45MAR2

63 , 71 & 90 2 x Ø 250

100 & 125 4 x Ø 200

CZ-DUMPA63MAR2

CZ-DUMPA100MAR4

Left-side Drain Piping Right-side Drain Piping

Front

Side

Air Outlet Plenum Air Intlet Plenum

Bottom

42

VRF SYSTEMS FS MULTI

S-45MA1E5 // S-56MA1E5 // S-63MA1E5 // S-71MA1E5 // S-90MA1E5

S-100MA1E5

Control Flexibility

· 24-Hours ON/OFF Real Setting Timer

· Weekly Timer (Wired Only)

· Group Control by Single Remote Controller

· Outdoor Unit Silent Operation Mode

· Indoor Unit Thermistor Switching (Wired Only)

· Ventilation Unit Control (Wired Only)

· Digital Input/Output Contact - with CZ-TA31P (Optional)

Comfortability

· Filter Sign

· Hot Start Control

· Filter

Field Service & Maintenance

· Indoor Unit Address Setting

· Outdoor Unit Address Setting

· Automatic Address Resetting for Group Control

(Wired Only)

· Indoor Unit Test Run Mode

· Emergency Operation (Infrared Only)

· Self Diagnosis Function

· Self Diagnosis Records (Wired Only)

* Wired: Wired Remote Controller / Infrared: Infrared Remote Controller.

SPACE NEEDED FOR INSTALLATION

INDOOR UNIT DIMENSIONS

20

45

740

650 (P65 x 10)

65

Wall

TOP VIEW Inspection zone

(600 x 600)

Control box

600

Front

600

Wall

20

57.5

65

960

845 (P65 x 13)

Wall

FRONT VIEW Ceiling

False ceiling

Floor

20

60

65

1260

1160

1040(P65 x 16)

31 187 32

1.75 - 2.0 HP

54

100 56

65

585 (P65 x 9)

668

840

900

780

2.5 - 3.0 - 3.5 HP

54

100 56

65

780 (P65 x 12)

888

1060

1120

1000

4.0 HP

100

56.5

65

975 (P65 x 15)

1088

1320

1200

23

32

47 65 47

159 59

Drainage pipe connection Drainage pipe connection Drainage pipe connection

43

44

PANASONIC

INTRODUCING

THE NEW 3 WAY

BEST EFFICIENCY ECOi

ECOi SERIES

DC-inverter control technology for rapid and powerful cooling & heating.

The ever-evolving Panasonic ECOi 6N series

The ECOi 6N series is designed for energy savings, easy installation, and high efficiency.

Always continuing to evolve, Panasonic uses advanced technologies to meet the requirements of diverse situations and contribute to the creation of comfortable living spaces.

Lower running and life cycle costs

Panasonic ECOi 6N systems are amongst the most efficient VRF systems on the market, offering COPs in excess of 4.0 at full load conditions. The system is also designed to make sure that we reduce the running cost of each system by using our unique road map control routine to ensure that the most efficient combination of compressors are running at any one time. Improved defrost sequencing also reduces running costs by defrosting each outdoor coil in turn when conditions allow.

The range of outdoor unit modules consists of 7 models from 8 HP to 20 HP. The module sizes from

10 HP to 20 HP can be configured for HI-COP.

Standard mode offers the highest capacity while still delivering excellent efficiency, while HI-COP mode delivers exceptional efficiency and low running costs with a slight reduction in capacity.

Up to 64 indoor units can be connected up to a capacity of 200% indexed indoor unit loads, enabling the system to be used effectively on highly diversified building loads: this large connectability feature makes it an easy-to-design solution for schools, hotels, hospitals and other large buildings.

Up to 1,000 m in pipe length enables the New VRF

ECOi 6N series to be used in very large buildings, with maximum design flexibility.

The ECOi 6N system is also easy to control. It has more than 8 types of control from standard wired remote controls to touch screen panels or web access interfaces.

NEW

VRF SYSTEMS ECOi

MINI ECOi

Panasonic’s policy of product development continues with the expansion of the Mini

ECOi 6N, the 2-Pipe heat pump small

VRF system specifi cally designed for the

European market.

2-PIPE ECOi 6N SERIES

The 2-Pipe ECOi 6N series is specifi cally designed for energy saving, easy installation and high effi ciency performance as its main focus.

3-PIPE ECOi MF2 SERIES

ECOi 3-Pipe is one of the most advanced

VRF systems available. Not only offering high-effi ciency and performance for simultaneous heating and cooling, its sophisticated design makes installation

45

2-PIPE MINI ECOi LE1 SERIES

COOLING AND HEATING TYPE 1-PHASE

COOLING AND HEATING TYPE 3-PHASE

FOR SMALL-SCALE COMMERCIAL AND RESIDENTIAL USE

46

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

Energy

saving

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

Panasonic 2-Pipe Mini ECOi, the 2-pipe heat pump is specifi cally designed for the most demanding applications.

Mini ECOi is available in 3 sizes with cooling capacities ranging from 12.1 kW to 15.5 kW and connectable up to 9 indoor units

(applicable for 15.5 kW).

An expansion from the Panasonic VRF line up, the Mini ECOi is compatible with the same indoor units and controls as the rest of the ECOi range.

VRF SYSTEMS ECOi

Energy saving concept

The energy saving designs for the structure of fans, fan motors, compressors and heat exchangers has resulted in high COP values, which rank as one of the top classed in the industry. In addition, use of highly efficient R410A refrigerant reduces CO

2

emission and lowers operating costs.

Improved energy saving

The operation efficiency has been improved using highly efficient R410A refrigerant, new DC inverter compressor, new DC motor and new design of heat exchanger.

FS MULTI VRF COOLING

Mini ECOi COOLING

FS MULTI VRF HEATING

Mini ECOi HEATING

All Mini ECOi VRF systems are rated as EEL

Category A, which confirms that they are amongst the most energy efficient systems available. Power consumption during operation is substantially less than that of lower rated units and consequently both the day to day running costs and full life cycle costs are significantly reduced.

5.00

4.00

3.00

2.00

3.61

4.30

4 HP

3.25

4.20

5 HP

3.01

6 HP

3.45

4.11

4 HP

4.62

4.03

4.30

5 HP

3.84

3.95

6 HP

47

48

Drastically reduced sound level

The pressure sound level has been reduced drastically thanks to the new DC

Inverter compressor, newly designed heat exchanger and Fan.

Increased piping length for Greater design fl exibility

Adaptable to various building types and sizes.

Actual piping length: 120 m (equivalent piping length 140 m).

Max. piping length: 150 m.

FS MULTI VRF COOLING

ECOi COOLING

54.0

53.0

52.0

51.0

58.0

57.0

56.0

55.0

50.0

49.0

52

4 HP

50

53

5 HP

51

55

6 HP

52

54

FS MULTI VRF HEATING

ECOi HEATING

57

55

53

52

55

4 HP 5 HP 6 HP

MAX. TOTAL LENGTH: 150 m

System difference of elevation:

50 m *

Actual length:

120 m

Wide operating range

The operating range for heating operation is to -20 °C, the cooling range is to -10 °C. The remote controller temperature setting offers a range from 16 °C to 30 °C.

4 HP ~ 6 HP

Difference in elevation between indoor units:

15 m

* 40 m if the outdoor unit is below the indoor unit.

Silent mode

3 dB can be reduced by setting. External input signal is also available.

-20

-15 -10 -5 0 5 10 15 20 25 30 35 40 46

Cooling: -10 °C DB ~ 46 °C DB // Heating: -20~18 (WB)

Up to 9 indoor units per system

SYSTEM /HP

Connectable Indoor Unit

4 HP

6

Lightweight

In case of 5/6 HP, the weight has been reduced from 123 kg into 104 kg.

5 HP

8

6 HP

9

DOWN TO

19

kg

FS Multi VRF

LA 1 Series

ECOi

LE 1 Series

Compact & Flexibility-design

The slim and lightweight design can be installed on various places.

FOR BALCONIES FOR NARROW SPACES

Power suppression control for energy saving (Demand control)*

ECOi systems have a demand control utilising inverter technology. With this control, power consumption can be set in three steps to deliver optimum performance. This helps to reduce annual power consumption and electricity costs while maintaining comfort.

* Demand control kit outdoor unit (CZ-CAPDC3) is required to input the signal. Setting is possible as 0% or in the range from 40 to

100% (in steps of 5%). At the time of shipping, setting has been done to the three steps of 0%, 70% and 100%.

Power input

Set point Normal operation

Level 1

Level 2

Level 3

Time

100% (Preset)

70% (Preset)

0% (Always in stop condition)

Power input

Possible to change 40-100%

6

4

5

5

VRF SYSTEMS ECOi

7

2

3

Mini ECOi

1 Inverter compressor. Large-capacity inverter compressor has been adopted. The inverter compressor is superior in performance with improved partial-load capacity.

2 Printed Circuit Board. PCBs have been reduced to two, to improve maintenance.

3 Accumulator. Larger accumulator has been adopted to maintain compressor reliability and because of the increased refrigerant quantity, extended max piping length can be achieved. Furthermore, the refrigerant pressure loss was reduced, which contributes to an improved operating efficiency.

4 DC Fan motor. Checking load and outside temperature, the DC motor is controlled for optimum air volume.

5 Newly designed Big Edgy Fan. The newly designed Fan edge has been realized to inhibit air turbulent and to increase efficiency. As Fan diameter has been sized up to 490 mm, the air volume has been increased by 12% keeping low sound level.

6 Heat exchanger & copper tubes. The heat exchanger size and the copper tube sizes in the heat exchanger has been redesigned to increase efficiency.

7 Oil separator. New centrifugal separator has been adopted to improve oil separation efficiency and reduce refrigerant pressure loss.

1

Demand control Kit information

CZ-CAPDC2 Seri-Para I/O unit for outdoor unit

CZ-CAPDC3 Demand Control Kit

CZ-CAPDC4 Demand Control Kit

PACi

Yes

Yes

-

MINI ECOi ECOi 6N

Yes Yes

Yes

-

-

Yes

Function of Demand control

This function limits the maximum operating input at peak time.

3 levels as 100%/70%/0% is set at the factory¹.

The limit value setting for level 1 & 2 can be changed from 40% ~ 100% by

5% at the system commitioning.

1. The 3rd level is available only for CZ-CAPDC3 & CZ-CAPDC4.)

Level 1

Level 2

Level 3

POWER INPUT LEVEL (VS. RATED CONDITION

100% (at ship)

70% (at ship)

From 40%-100% setting can be changed (by 5% step)

0% (Forcible thermo-OFF)

CZ-CAPDC2

Demand control input signals sent to this outdoor interface will be transferred to the system via inter-unit control wiring. Other controls (ex.

Operation ON/OFF, Mode switch Cool/Heat) are also available. Demand level

1 & 2 are available.

Outdoor unit

1 2

Inter-unit wiring terminal

Input terminal

CZ-CAPDC2

COM

Demand 1

Demand 2

Demand controller

OPERATING IMAGE

POWER

INPUT

Demand level

A%

B%

Level 1

Level 2

Limit Max level

CZ-CAPDC3 for PACi and Mini ECOi // CZ-CAPDC4 for ECOi 6N 2way

Optional terminal block kit for demand control to be mounted in the outdoor unit. Via this interface, the demand control signals go directly to the outdoor unit control PCB. 3 control levels are available.

8 12 16 20

TIME

Outdoor unit

DRM1 DRM2 DRM3 C

Terminal block

CZ-CAPDC3/4

* Only for 6N series ECO-i outdoor unit, “Regular Demand control” setting is available.

(The system will be limited the maximum input level for all the time without any signal input.)

(The setting to be done at the time of system start-up or service by maintenance remote controller.)

Demand controller

49

Energy

saving saving

Energy

MINI ECOi HIGH EFFICIENCY

FOR LIGHT COMMERCIAL USE

Panasonic’s Mini ECOi, the 2-Pipe heat pump small VRF system, is specifically designed for the most demanding applications. Offering between 11 kW and 16 kW cooling capacity in 3 sizes and up to 9 indoor units connected, the Mini ECOi sets standards of performance and flexibility.

Utilising R410A and DC inverter technology, Panasonic offers VRF to a new and growing market.

Forming a new key part of the Panasonic VRF line up, the Mini ECOi is compatible with the same indoor units and controls as the rest of the ECOi range.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· SINGLE PHASE OR THREE PHASE POWER SUPPLY

· ONE AMP START CURRENT

· DC INVERTER TECHNOLOGY COMBINED WITH R410A

· DIVERSITY RATIO 50-130%

· COOLING OPERATION TO -10 °C

· COMPACT OUTDOOR UNIT 1,330 x 940 x 410 mm

HP

Model name

Power supply

Cooling capacity

EER

Heating capacity

COP

Dimensions

Piping connection

H x W x D

Gas

Liquid

Cooling Sound pressure level

Heating

Maximum number of indoor units

Preliminary specifiactions, subject to change without notice.

4.0 HP

U-4LE1E5 U-4LE1E8

5.0 HP

U-5LE1E5 U-5LE1E8

6.0 HP

U-6LE1E5 U-6LE1E8

220/230/240 V, 50 Hz 380/400/415 V, 50 Hz 220/230/240 V, 50 Hz 380/400/415 V, 50 Hz 220/230/240 V, 50 Hz 380/400/415 V, 50 Hz kW 12.1

BTU/h 41,300

12.1

41,300

14.0

47,800

14.0

47,800

15.5

52,900

15.5

52,900

W/W 4.30

kW 12.5

BTU/h 42,700

W/W 4.62

4.30

12.5

42,700

4.62

4.20

16.0

54,600

4.30

4.20

16.0

54,600

4.30

3.45

18.0

61,400

3.95

3.45

18.0

61,400

3.95

mm 1,330 x 940 x 340 (410) 1,330 x 940 x 340 (410) 1,330 x 940 x 340 (410) 1,330 x 940 x 340 (410) 1,330 x 940 x 340 (410) 1,330 x 940 x 340 (410) mm 15.88

15.88

15.88

15.88

19.05

19.05

mm 9.52

dB(A) 50

9.52

50

9.52

51

9.52

51

9.52

52

9.52

52 dB(A) 52

6

52

6

53

8

53

8

55

9

55

9

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

50

VRF SYSTEMS ECOi

Flexible pipework

CATEGORY ITEM

Allowable pipework length

L1

L2-L3

DESCRIPTION

Maximum pipe run

MAX LENGTH (m)

Actual length 120

Equivalent length 140

Difference between maximum length and minimum length from the first distribution joint

40

Allowable height difference

L3 L4 Ln Maximum length of each distribution joint

L1+L3+L4 Maximum total pipe run length

H1 When outdoor unit installed higher

When outdoor unit installer lower

H2 Maximum difference between indoor units

30

150

50

40

15

L3

L1

L2

L4

Ln

H2

H1

TOP VIEW

105

170 660

219 75 75

110

50

13

4

4 x Ø 32 holes (holes for drain)

Of the 4 Ø 32 holes, use 1 of the 2 holes specified for drain use to install the port.

Use rubber plugs to seal the remaining 3 holes.

FRONT VIEW

Air discharge

940

13

1

2

3

20

5 6 7 8 4

9

60

55

Air discharge

5

4

60

87

20

64

Air intake

6

7

8

1 Mounting hole (4-R6.5), anchor bolt:

Size (mm)

M10

2 Refrigerant tubing (liquid tube), flared connection Ø 9.52

3 Refrigerant tubing (gas tube), flared connection 15.88 or 19.05

4 Refrigerant tubing port.

5 Electrical wirang port

6 Electrical wiring port

7 Electrical wiring port

8 Electrical wiring port

Ø 16

Ø 19

Ø 29

Ø 38

51

52

2-PIPE ECOi 6N SERIES

HIGH-EFFICIENCY AND LARGE-

CAPACITY VRF SYSTEM

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

Energy

saving

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

Large-capacity VRF systems using R410A with advanced technology.

Newly designed next generation VRF!

VRF SYSTEMS ECOi

Energy savings

The operation efficiency has been improved using highly efficient R410A refrigerant, new DC inverter compressor, new DC motor and new design of heat exchanger.

5.00

5.00

4.50

4.56

COOLING HEATING

4.50

HIGH COP SETTING MODEL

4.45

4.45

COOLING HEATING

4.52

4.41

4.39

4.50

4.10

4.10

4.21

4.06

4.07

4.04

4.01

4.07

4.06

4.00

4.00

3.88

3.85

3.86

3.82

3.50

3.60

3.61

3.60

3.36

3.50

3.33

3.50

3.00

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 8 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP

3.00

10 HP 12 HP 14 HP 16 HP 18 HP 20 HP 10 HP 12 HP 14 HP 16 HP 18 HP 20 HP

Extended operating range

Heating operation range: Extended heating operation range enables heating even when outdoor temperature as low as -25 °C. Using a wired remote control, indoor heating temperature range can be set from 16 °C to 30 °C.

-25

-20 -15 -10 -5 0 5 10 15 20

Outside air temperature (Upto 15 (°C WB))

Wide temperature setting range.

Cooling operation range: -10 °C DB to +43 °C DB.

43

45

Outside air temperature (°C DB)

E F F I

H I

C

I G

I E

H

N C Y

53

Connectable indoor/outdoor unit capacity ratio up to 200%

VRF systems attain maximum indoor unit connection capacity of up to 200 % of the unit’s connection range, depending on the outdoor and indoor models selected. So for a reasonable investment, VRF systems provide an ideal air conditioning solution for locations where full cooling/heating are not always required.

SYSTEM (HP)

CONNECTABLE INDOOR UNITS: 130%

CONNECTABLE INDOOR UNITS: 200%

8

13 16 19 23 26 29 33 36

20

10

25

12

30

14

35

16

40

18

45

20

50

22

55

24

40

60

26

43

28

47

30

50

32

53

34

56

36

59

If more than 100% indoor units are operated with a high load, the units may not perform at the rated capacity. For the details, please consult with an authorized Panasonic dealer.

38 40 42

64

44 46 48

64

50 52 54 56 58 60

Increased piping lengths and design fl exibility

Adaptable to various building types and sizes. Actual piping length: 180 m.

Maximum piping length: 1000 m.

Non-stop operation during maintenance

In the event of an indoor unit malfunctioning, other indoor units can be set to continue operation even during maintenance.

MAX. TOTAL LENGTH: 1000 m

1ø, 220-240 V

Lights,etc.

Breaker

System difference of elevation:

50 m

*

Actual length:

180 m

POWER CUT OFF

(Under renovation)

Difference in elevation between indoor units:

15 m

* 40 m if the outdoor unit is below the indoor unit.

IN OPERATION

Extended compressor life by uniform compressor operation times

Total compressors run-time is monitored by a built-in microcomputer, which ensures that operation times of all compressors within the same refrigerant circuit are balanced. Compressors with histories showing shorter run times are selected first, ensuring equal wear and tear across all units and extended working life for the system.

A, C: DC inverter compressor

Load increase

A B C D A B

50 h 30 h 60 h 10 h

1

A

C

C D

Load increase

B, D: Constant speed compressor

Load increase

A B C D A B C D

2

D

C

10

Example: Time leveling of compressor operating hours

A

C

3 4

D

C

A

C

5

5

0

DC

2

AC

1

In case of the above graph, compressor drives from

DC

4

Compressor

4 2

AC

3

3

AC

5

1 5

Newly designed fan

Optimized air flow and noise reduction

Newly designed fan and bell-mouth reduces stress to fan by dispersing fast wind speed. Thus, lower air resistance results in lower energy consumption.

The turbulent flow (blue part) can be suppressed and the noise can be reduced. Even though the high speed circulation is utilized, the noise level is held at the same level as normal.

Automatic backup operation in the case of compressor and outdoor units malfunction

Backup operation is applied during in the case of emergencies. If error message is displayed, please contact your local service office. (Except for 8

HP single unit installation).

Even if either Fan motor or

Sensors are failed

Even if a compressor is failed

Even if a compressor at single system is failed

NEW FUNCTION

BACKUP OPERATION CAN BE DONE

Easy to design solutions for schools, hotels, hospitals and other large buildings

Difference between Max. and Min. pipe runs after first branch can be a maximum of 50 m; larger pipe runs can be up to 180 m.

MAX. 50 m

The other outdoor unit can keep running

The other compressor can keep running

MAX. 180 m

L1

Conventional model

ME1

L2

L1 = Longest pipe run

L2 = Shortest pipe run

L1 - L2 = max. 50 m

Optimized air flow

54

Noise reduction Smaller hub diameter

VRF SYSTEMS ECOi

Anti-corrosion model available

For bespoke projects: for use in coastal areas and other locations where sea air can easily cause salt damage to units. As well as the heat exchanger, various other parts are specially treated to provide exceptional durability.

Note: Using this unit does not completely eliminate the possibility of rust developing.

For details concerning unit installation and maintenance, please consult with an authorized dealer.

Fan Fan motor

PC board

Outer body

Electric box

Heat exchanger

(fins, tube, tube panel)

Screws

Accumulator

Refrigerant pipe port

Demand control Kit information

CZ-CAPDC2 Seri-Para I/O unit for outdoor unit

CZ-CAPDC3 Demand Control Kit

CZ-CAPDC4 Demand Control Kit

PACi

Yes

Yes

-

MINI ECOi ECOi 6N

Yes Yes

Yes

-

-

Yes

Demand Control Functions

This function limits the maximum operating input at peak time.

3 levels as 100%/70%/0% is set at the factory¹.

The limit value setting for level 1 & 2 can be changed from 40% ~ 100% by

5% when the system is commissioned.

1. The 3rd level is available only for CZ-CAPDC3 & CZ-CAPDC4.)

Level 1

Level 2

Level 3

OPERATING IMAGE

POWER

INPUT

Demand level

A%

B%

Level 1

Level 2

Limit Max level

CZ-CAPDC2

Demand control input signals sent to this outdoor interface will be transferred to the system via inter-unit control wiring. Other controls (ex.

Operation ON/OFF, Mode switch Cool/Heat) are also available. Demand level

1 & 2 are available.

POWER INPUT LEVEL (VS. RATED CONDITION

100% (at ship)

70% (at ship)

From 40%-100% setting can be changed (by 5% step)

0% (Forcible thermo-OFF)

1 2

Inter-unit wiring terminal

Input terminal

CZ-CAPDC2

COM

Demand 1

Demand 2

Demand controller

Outdoor unit

CZ-CAPDC3 for PACi and Mini ECOi // CZ-CAPDC4 for ECOi 6N 2way

Optional terminal block kit for demand control to be mounted in the outdoor unit. Via this interface, the demand control signals go directly to the outdoor unit control PCB. Three control levels are available.

8 12 16 20

TIME

Outdoor unit

DRM1 DRM2 DRM3 C

Terminal block

CZ-CAPDC3/4

* Only for 6N series ECO-i outdoor unit, “Regular Demand control” setting is available.

(The system will be limited the maximum input level for all the time without any signal input.)

(The setting to be done at the time of system start-up or service by maintenance remote controller.)

Demand controller

55

Energy

saving saving

Energy

8-12 HP // 2-PIPE ECOi 6N SERIES

NEXT GENERATION VRF NEWLY-REDESIGNED!

At start up stage a unit can have Hi COP function selected - this lowers the capacity and increases the COP. It’s your choice.

· Top class COP= 4.56 (In case of 8 HP heating).

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· COMPACT CASING

· LONGER MAX PIPING LENGTH UP TO 1,000 m

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

· SUITABLE FOR REFURBISHMENT PROJECTS (REFER TO

TECHNICAL DATA BOOK)

HP

STANDARD MODEL

Power supply

Cooling capacity

EER

Electrical ratings kW

W/W

Operating current A

Power input kW

Heating capacity

COP

Electrical ratings kW

W/W

Operating current A

Power input kW

H x W x D mm kg

Dimensions

Net weight

Starting current

Air flow rate

A m³/h kg Refrigerant amount at shipment

Demand control

External static pressure

Piping connections

Sound pressure level

Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Normal mode

Silent mode

Pa mm mm mm dB(A) dB(A)

Sound power level Normal mode dB

8.0 HP

U-8ME1E81

25.0

4.56

8.4

5.48

22.4

4.04

8.5

5.54

1,758 x 770 x 930

234

1

8,820

6.5

13 steps (0 – 100 %)

80

19.05

9.52

6.35

56.5

53.5

71.0

10.0 HP

U-10ME1E81

400 V / 3 phase / 50 Hz

28.0

3.60

12.2

7.78

31.5

4.10

12.1

7.68

1,758 x 770 x 930

234

1

9,180

6.8

13 steps (0 – 100 %)

80

22.22

9.52

6.35

12.0 HP

U-12ME1E81

33.5

3.61

14.6

9.29

37.5

4.10

14.4

9.15

1,758 x 770 x 930

281

81

11,400

6.8

13 steps (0 – 100 %)

80

25.4

12.7

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

59.0

61.0

56.0

73.5

58.0

75.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

56

VRF SYSTEMS ECOi

Compact design

8-12 HP fit inside a lift for easy handling at site.

FRONT VIEW

Air discharge

Electrical component box

4

3

2

H 1758

D 930

W 770

TOP VIEW

Air intake

363

601

628 71*

* Installation fixing bracket, installation side.

71*

740 (installation hole pitch)

770

1

A 894 (installation hole pitch). The tubing is routed out frpm the front

B 730 (installation hole pitch). The tubing is routed out frpm the front

C 730 (installation hole pitch).

1 Installation holes (8-15x21 elongated holes) anchor bolts M12 or larger.

2 Pressure outlet port (for high pressure: Ø 7.94 Scrader-type connection).

3 Pressure outlet port (for low pressure: Ø 7.94 Scrader-type connection).

4 Knock-out hole for connecting pressure gauge (optional).

5 Terminal board.

6 Terminal board (for inter-outdoor-unit control wiring).

57

Energy

saving saving

Energy

14-16 HP // 2-PIPE ECOi 6N SERIES

NEXT GENERATION VRF NEWLY-REDESIGNED!

At start up stage a unit can have Hi COP function selected - this lowers the capacity and increases the COP. It’s your choice.

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· LONGER MAX PIPING LENGTH UP TO 1,000 m

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

· SUITABLE FOR REFURBISHMENT PROJECTS (REFER TO

TECHNICAL DATA BOOK)

HP

STANDARD MODEL

Power supply

Cooling capacity

EER

Electrical ratings kW

W/W

Operating current A

Power input kW

Heating capacity

COP

Electrical ratings kW

W/W

Operating current A

Power input kW

H x W x D mm kg

Dimensions

Net weight

Starting current

Air flow rate

A m³/h kg Refrigerant amount at shipment

Demand control

External static pressure

Piping connections

Sound pressure level

Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Normal mode

Silent mode

Pa mm mm mm dB(A) dB(A)

Sound power level Normal mode dB

14.0 HP

U-14ME1E81

45.0

4.21

16.5

10.7

40.0

3.60

17.1

11.1

1,758 x 1,000 x 930

309

77

12,720

8.5

13 steps (0 – 100 %)

80

25.4

12.7

6.35

62.0

59.0

76.5

16.0 HP

U-16ME1E81

400 V / 3 phase / 50 Hz

45.0

3.36

20.7

13.4

50.0

3.85

20.1

13.0

1,758 x 1,000 x 930

309

81

12,720

8.5

13 steps (0 – 100 %)

80

28.58

12.7

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

62.0

59.0

76.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

58

VRF SYSTEMS ECOi

High external static pressure

Special setting at site allows all models to provide up to 80 Pa due to newly designed fan, fan motor and casing.

The flexible design requires an air discharge duct to avoid a reduction in performance due to shortcut of air circulation.

The new feature allows the outdoor unit to be installed inside plant rooms on any floor of the building.

HIGH STATIC

PRESSURE

80

Pa

FRONT VIEW

Air discharge

Electrical component box

4

3

2

TOP VIEW

Air intake

71*

363

601

858

* Installation fixing bracket, installation side.

71*

970

(installation hole pitch)

1000

1

A 894 (installation hole pitch). The tubing is routed out frpm the front

B 730 (installation hole pitch). The tubing is routed out frpm the front

C 730 (installation hole pitch).

1 Installation holes (8-15x21 elongated holes) anchor bolts M12 or larger.

2 Pressure outlet port (for high pressure: Ø 7.94 Scrader-type connection).

3 Pressure outlet port (for low pressure: Ø 7.94 Scrader-type connection).

4 Knock-out hole for connecting pressure gauge (optional).

5 Terminal board.

6 Terminal board (for inter-outdoor-unit control wiring).

59

Energy

saving saving

Energy

18-20 HP // 2-PIPE ECOi 6N SERIES

NEXT GENERATION VRF NEWLY-REDESIGNED!

At start up stage a unit can have Hi COP function selected - this lowers the capacity and increases the COP. It’s your choice.

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· BIGGER CAPACITY IN ONE CASING

· LONGER MAX PIPING LENGTH UP TO 1,000 m

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

· SUITABLE FOR REFURBISHMENT PROJECTS (REFER TO

TECHNICAL DATA BOOK)

HP

STANDARD MODEL

Power supply

Cooling capacity

EER

Electrical ratings kW

W/W

Operating current A

Power input kW

Heating capacity

COP

Electrical ratings kW

W/W

Operating current A

Power input kW

H x W x D mm kg

Dimensions

Net weight

Starting current

Air flow rate

A m³/h kg Refrigerant amount at shipment

Demand control

External static pressure

Piping connections

Sound pressure level

Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Normal mode

Silent mode

Pa mm mm mm dB(A) dB(A)

Sound power level Normal mode dB

18.0 HP

U-18ME1E81

56.0

3.86

23.1

14.5

50.0

3.50

22.8

14.3

1,758 x 1,540 x 930

421

93

14,640

9.0

13 steps (0 – 100 %)

80

28.58

15.88

6.35

60.0

57.0

74.5

20.0 HP

U-20ME1E81

400 V / 3 phase / 50 Hz

56.0

3.33

26.8

16.8

63.0

3.82

26.3

16.5

1,758 x 1,540 x 930

421

101

16,980

9.0

13 steps (0 – 100 %)

80

28.58

15.88

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

63.0

60.0

77.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

60

VRF SYSTEMS ECOi

Compact design

2-Pipe ECOi 6N series has reduced the installation space required by 1 chassis for sizes up to 20 HP.

WEIGHT: 423 Kg

Required installation space. Unit: mm

FRONT VIEW

Air discharge

Electrical component box

TOP VIEW

Air intake

4

3

2

71*

487

601

641

116*

* Installation fixing bracket, installation side.

641 71*

1510 (installation hole pitch)

1540

A 894 (installation hole pitch). The tubing is routed out frpm the front

B 730 (installation hole pitch). The tubing is routed out frpm the front

C 730 (installation hole pitch).

1 Installation holes (8-15x21 elongated holes) anchor bolts M12 or larger.

2 Pressure outlet port (for high pressure: Ø 7.94 Scrader-type connection).

3 Pressure outlet port (for low pressure: Ø 7.94 Scrader-type connection).

4 Knock-out hole for connecting pressure gauge (optional).

5 Terminal board.

6 Terminal board (for inter-outdoor-unit control wiring).

1

61

Energy

saving saving

Energy

2-PIPE ECOi 6N SERIES // COMBINATION FROM

22 TO 60 HP

NEXT GENERATION VRF NEWLY-REDESIGNED!

At start up stage a unit can have Hi COP function selected - this lowers the capacity and increases the COP. It’s your choice.

· Wide range of system up to 60 HP.

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· INCREASED CONNECTABLE I_U/O_U CAP. RATIO UP TO 200%

· INCREASED MAX NO. OF CONNECTABLE I_U UP TO 64 UNITS

· INCREASED HIGH EXTERNAL STATIC PRESSURE UP TO 80 Pa

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

HP

STANDARD MODEL

22

U-14ME1E81

U-8ME1E81

24

U-14ME1E81

U-10ME1E81

26

U-14ME1E81

U-12ME1E81

28

U-16ME1E81

U-12ME1E81

30

U-16ME1E81

U-14ME1E81

32

U-16ME1E81

U-16ME1E81

34

U-18ME1E81

U-16ME1E81

36

U-20ME1E81

U-16ME1E81

Power supply

Cooling capacity

EER

Electrical ratings

Heating capacity

COP

Electrical ratings

Dimensions

Operating current A

Power input

H x W x D kW

W/W kW kW

W/W

Operating current A

Power input kW mm

Net weight

Starting current

Air flow rate

Refrigerant amount at shipment

Demand control kg

A m³/h kg

External static pressure

Piping connections

Sound pressure level

Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Normal mode

Silent mode

Pa mm mm mm dB(A) dB(A)

63.0

60.0

80

28.58

15.88

6.35

Sound power level Normal mode dB

543

86

21,540

15.0

13 steps

(0 – 100 %)

77.5

61.5

3.75

25.2

16.4

69.0

4.34

24.5

15.9

1,758 x 1,830 x

930

543

94

21,900

15.3

13 steps

(0 – 100 %)

80

28.58

15.88

6.35

68.0

3.60

29.4

18.9

76.5

4.09

29.1

18.7

1,758 x 1,830 x

930

63.5

60.5

78.0

73.0

3.60

31.6

20.3

81.5

4.12

30.8

19.8

1,758 x 1,830 x

930

590

98

24,120

15.3

13 steps

(0 – 100 %)

80

31.75

19.05

6.35

64.5

61.5

79.0

78.5

3.47

35.2

22.6

87.5

3.96

34.4

22.1

1,758 x 1,830 x

930

590

102

24,120

15.3

13 steps

(0 – 100 %)

400 V / 3 phase / 50 Hz

85.0

90.0

3.47

37.8

3.35

41.5

24.5

95.0

4.03

36.4

23.6

1,758 x 2,060 x

930

618

98

25,440

17.0

13 steps

(0 – 100 %)

26.9

100.0

3.86

40.0

25.9

1,758 x 2,060 x

930

618

102

25,440

17.0

13 steps

(0 – 100 %)

80

31.75

19.05

6.35

80

31.75

19.05

6.35

80

31.75

19.05

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

64.5

65.0

65.0

64.0

61.5

79.0

62.0

79.5

62.0

79.5

61.0

78.5

730

114

27,360

17.5

13 steps

(0 – 100 %)

80

31.75

19.05

6.35

96.0

3.43

44.0

28.0

108.0

3.86

44.0

28.0

1,758 x 2,600 x

930

65.5

62.5

80.0

730

122

29,700

17.5

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

101.0

3.34

47.5

30.2

113.0

3.83

46.4

29.5

1,758 x 2,600 x

930

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

62

VRF SYSTEMS ECOi

38

U-20ME1E81

U-18ME1E81

842

123

31,620

18.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

107.0

3.44

49.6

31.1

119.0

3.84

49.4

31.0

1,758 x 3,140 x

930

65.0

62.0

79.5

40

U-20ME1E81

U-20ME1E81

42

U-16ME1E81

U-14ME1E81

U-12ME1E81

842

127

33,960

18.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

113.0

3.36

53.6

33.6

127.0

3.85

52.6

33.0

1,758 x 3,140 x

930

899

119

36,840

23.8

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

118.0

3.51

52.1

33.6

132.0

4.04

50.8

32.7

1,758 x 2,890 x

930

66.0

63.0

80.5

66.5

63.5

81.0

44

U-16ME1E81

U-16ME1E81

U-12ME1E81

899

122

36,840

23.8

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

124.0

3.43

56.2

36.2

138.0

3.92

54.6

35.2

1,758 x 2,890 x

930

66.5

63.5

81.0

46

U-16ME1E81

U-16ME1E81

U-14ME1E81

130.0

3.43

58.5

37.9

145.0

3.96

56.5

36.6

1,758 x 3,120 x

930

48

U-16ME1E81

U-16ME1E81

U-16ME1E81

50

U-18ME1E81

U-16ME1E81

U-16ME1E81

135.0

400 V / 3 phase / 50 Hz

140.0

3.35

62.2

40.3

150.0

3.86

60.1

38.9

1,758 x 3,120 x

930

3.41

64.2

41.1

155.0

3.86

62.8

40.2

1,758 x 3,660 x

930

52

U-20ME1E81

U-16ME1E81

U-16ME1E81

145.0

3.35

67.7

43.3

160.0

3.84

65.2

41.7

1,758 x 3,660 x

930

927

119

38,160

25.5

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

927

122

38,160

25.5

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

1,039

134

40,080

26.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

1,039

142

42,420

26.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

67.0

67.0

66.0

67.0

64.0

81.5

64.0

81.5

63.0

80.5

64.0

81.5

54

U-20ME1E81

U-18ME1E81

U-16ME1E81

66.5

63.5

81.0

56

U-20ME1E81

U-18ME1E81

U-18ME1E81

1,151

144

44,340

26.5

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

151.0

3.39

70.3

44.5

169.0

3.85

69.3

43.9

1,758 x 4,200 x

930

1,263

146

46,260

27.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

156.0

3.44

72.4

45.4

175.0

3.85

72.4

45.4

1,758 x 4,740 x

930

66.0

63.0

80.5

58

U-20ME1E81

U-20ME1E81

U-18ME1E81

67.0

64.0

81.5

60

U-20ME1E81

U-20ME1E81

U-20ME1E81

1,263

149

48,600

27.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

162.0

3.38

76.4

47.9

182.0

3.83

75.8

47.5

1,758 x 4,740 x

930

1,263

153

50,940

27.0

13 steps

(0 – 100 %)

80

38.10

19.05

6.35

168.0

3.33

80.4

50.4

189.0

3.81

79.1

49.6

1,758 x 4,740 x

930

68.0

65.0

82.5

63

Energy

saving saving

Energy

10-12 HP // 2-PIPE ECOi 6N SERIES //

HIGH COP SETTING MODEL

NEXT GENERATION VRF NEWLY-REDESIGNED!

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· LONGER MAX PIPING LENGTH UP TO 1,000 m

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

· SUITABLE FOR REFURBISHMENT PROJECTS (REFER TO

TECHNICAL DATA BOOK)

HP

HIGH COP SETTING MODEL

Power supply

Cooling capacity

EER

Electrical ratings Operating current

Power input

Heating capacity

COP

Electrical ratings Operating current

Power input

H x W x D Dimensions

Net weight

Starting current

Air flow rate

Demand control

External static pressure

Refrigerant amount at shipment

Piping connections Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Sound pressure level Normal mode

Silent mode

Sound power level Normal mode

Pa kg mm mm mm dB(A) dB(A) dB kW

W/W

A kW kW

W/W

A kW mm kg

A m³/h

10.0 HP

U-14ME1E81

31.5

4.45

10.9

7.08

28.0

4.06

10.7

6.90

1,758 x 1,000 x 930

307

77

12,720

13 steps (0 – 100 %)

80

8.5

22.22

9.52

6.35

62.0

59.0

76.5

12.0 HP

U-16ME1E81

400 V / 3 phase / 50 Hz

33.5

4.07

12.7

8.23

37.5

4.45

13.0

8.43

1,758 x 1,000 x 930

307

81

12,720

13 steps (0 – 100 %)

80

8.5

25.40

12.70

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

62.0

59.0

76.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

64

VRF SYSTEMS ECOi

High external static pressure

Special setting at site allows all models to provide up to 80 Pa due to newly designed fan, fan motor and casing.

The flexible design requires an air discharge duct to avoid a reduction in performance due to shortcut of air circulation.

The new feature allows the outdoor unit to be installed inside plant rooms on any floor of the building.

HIGH STATIC

PRESSURE

80

Pa

FRONT VIEW

Air discharge

Electrical component box

4

3

2

TOP VIEW

Air intake

71*

363

601

858

* Installation fixing bracket, installation side.

71*

970

(installation hole pitch)

1000

1

A 894 (installation hole pitch). The tubing is routed out frpm the front

B 730 (installation hole pitch). The tubing is routed out frpm the front

C 730 (installation hole pitch).

1 Installation holes (8-15x21 elongated holes) anchor bolts M12 or larger.

2 Pressure outlet port (for high pressure: Ø 7.94 Scrader-type connection).

3 Pressure outlet port (for low pressure: Ø 7.94 Scrader-type connection).

4 Knock-out hole for connecting pressure gauge (optional).

5 Terminal board.

6 Terminal board (for inter-outdoor-unit control wiring).

65

Energy

saving saving

Energy

14-16 HP // 2-PIPE ECOi 6N SERIES //

HIGH COP SETTING MODEL

NEXT GENERATION VRF NEWLY-REDESIGNED!

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· BIGGER CAPACITY IN ONE CASING

· LONGER MAX PIPING LENGTH UP TO 1,000 m

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

· SUITABLE FOR REFURBISHMENT PROJECTS (REFER TO

TECHNICAL DATA BOOK)

HP

HIGH COP SETTING MODEL

Power supply

Cooling capacity

EER

Electrical ratings Operating current

Power input

Heating capacity

COP

Electrical ratings Operating current

Power input

H x W x D Dimensions

Net weight

Starting current

Air flow rate

Demand control

External static pressure

Refrigerant amount at shipment

Piping connections Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Sound pressure level Normal mode

Silent mode

Sound power level Normal mode

Pa kg mm mm mm dB(A) dB(A) dB kW

W/W

A kW kW

W/W

A kW mm kg

A m³/h

14.0 HP

U-18ME1E81

45.0

4.41

15.8

10.2

40.0

4.01

15.4

9.98

1,758 x 1,540 x 930

423

92

14,640

13 steps (0 – 100 %)

80

9.0

25.40

12.70

6.35

60.0

57.0

74.5

16.0 HP

U-20ME1E81

400 V / 3 phase / 50 Hz

45.0

3.88

17.9

11.6

50.0

4.39

17.6

11.4

1,758 x 1,540 x 930

423

98

16,980

13 steps (0 – 100 %)

80

9.0

28.58

12.70

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

63.0

60.0

77.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

66

VRF SYSTEMS ECOi

Compact design

2-Pipe ECOi 6N series has reduced the installation space required by one chassis for sizes up to 20 HP.

WEIGHT: 423 Kg

Required installation space. Unit: mm

FRONT VIEW

Air discharge

Electrical component box

TOP VIEW

Air intake

4

3

2

71*

487

601

641

116*

* Installation fixing bracket, installation side.

641

71*

1510 (installation hole pitch)

1540

A 894 (installation hole pitch). The tubing is routed out from the front

B 730 (installation hole pitch). The tubing is routed out from the front

C 730 (installation hole pitch).

1 Installation holes (8-15x21 elongated holes) anchor bolts M12 or larger.

2 Pressure outlet port (for high pressure: Ø 7.94 Scrader-type connection).

3 Pressure outlet port (for low pressure: Ø 7.94 Scrader-type connection).

4 Knock-out hole for connecting pressure gauge (optional).

5 Terminal board.

6 Terminal board (for inter-outdoor-unit control wiring).

1

67

Energy

saving saving

Energy

2-PIPE ECOi 6N SERIES // HIGH COP SETTING MODEL //

COMBINATION FROM 18 TO 48 HP

NEXT GENERATION VRF NEWLY-REDESIGNED!

· Wide range of system up to 48 HP.

· Heating operation at outdoor temperatures down to –25 °C.

· Extended pipe runs of up to 180 m.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· INCREASED CONNECTABLE I_U/O_U CAP. RATIO UP TO 200%

· INCREASED MAX NO. OF CONNECTABLE I_U UP TO 64 UNITS

· INCREASED HIGH EXTERNAL STATIC PRESSURE UP TO 80 Pa

· EXTENDED OPERATING RANGE TO PROVIDE HEATING AT

OUTDOOR TEMPERATURE AS LOW AS -25 °C

HP

HIGH COP SETTING MODEL

Power supply

Cooling capacity

EER

Electrical ratings

Heating capacity

COP

Electrical ratings

Dimensions

Net weight

Starting current

Air flow rate kW

W/W

Operating current A

Power input kW kW

W/W

Operating current A

Power input kW

H x W x D mm kg

A m³/h

Demand control

External static pressure

Refrigerant amount at shipment

Piping connections Gas pipe

Liquid pipe

Balance pipe

Ambient temperature operating range

Sound pressure level Normal mode

Silent mode dB(A) dB(A)

Pa kg mm mm mm

Sound power level Normal mode dB

18

U-14ME1E81

U-8ME1E81

20

U-16ME1E81

U-8ME1E81

22

U-18ME1E81

U-8ME1E81

24

U-16ME1E81

U-16ME1E81

26

U-18ME1E81

U-16ME1E81

28

U-20ME1E81

U-16ME1E81

30

U-20ME1E81

U-18ME1E81

50.0

4.07

18.9

12.3

56.0

4.52

19.1

12.4

56.0

4.06

21.2

13.8

63.0

4.50

21.5

14.0

61.5

3.97

23.9

15.5

69.0

4.39

24.2

15.7

68.0

4.07

25.8

16.7

76.5

4.45

26.6

17.2

400 V / 3 phase / 50 Hz

73.0

4.01

28.1

18.2

81.5

4.38

28.7

18.6

78.5

3.96

30.6

19.8

87.5

4.42

30.6

19.8

85.0

3.94

33.4

21.6

95.0

4.40

33.4

21.6

1,758 x 1,830 x 930 1,758 x 1,830 x 930 1,758 x 2,370 x 930 1,758 x 2,060 x 930 1,780 x 2,600 x 930 1,780 x 2,600 x 930 1,758 x 3,140 x 930

537

86

537

90

653

101

614

94

730

105

730

111

846

114

21,540 21,540 23,460 25,440 27,360 29,700 31,620

13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %)

80

15.0

80

15.0

80

15,5

80

17.0

80

17.5

80

17.5

80

18.0

28.58

15.88

6.35

63.0

60.0

77.5

28.58

15.88

6.35

63.0

60.0

77.5

28.58

15.88

6.35

61.5

58.5

76.0

28.58

15.88

6.35

65.0

62.0

79.5

31.75

19.05

6.35

64.0

61.0

78.5

31.75

19.05

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

65.5

62.5

80.0

31.75

19.05

6.35

65.0

62.0

79.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

68

COP

4.52

VRF SYSTEMS ECOi

32

U-20ME1E81

U-20ME1E81

34

U-18ME1E81

U-16ME1E81

U-8ME1E81

36

U-16ME1E81

U-16ME1E81

U-16ME1E81

38

U-18ME1E81

U-16ME1E81

U-16ME1E81

40

U-20ME1E81

U-16ME1E81

U-16ME1E81

42

U-20ME1E81

U-18ME1E81

U-16ME1E81

44

U-20ME1E81

U-18ME1E81

U-18ME1E81

46

U-20ME1E81

U-20ME1E81

U-18ME1E81

48

U-20ME1E81

U-20ME1E81

U-20ME1E81

90.0

3.88

35.9

23.2

100.0

4.41

35.1

22.7

96.0

4.09

36.2

23.5

108.0

4.54

36.7

23.8

101.0

4.07

38.3

24.8

113.0

4.45

39.2

25.4

107.0

4.08

40.5

26.2

119.0

4.44

41.4

26.8

4.04

43.3

28.0

4.47

43.9

28.4

400 V / 3 phase / 50 Hz

113.0

127.0

118.0

3.96

46.1

29.8

132.0

4.40

46.4

30.0

124.0

3.97

48.3

31.2

138.0

4.42

48.3

31.2

130.0

3.92

51.4

33.2

145.0

4.41

50.9

32.9

135.0

3.88

53.8

34.8

150.0

4.40

52.8

34.1

1,758 x 3,140 x 930 1,758 x 3,430 x 930 1,758 x 3,120 x 930 1,758 x 3,660 x 930 1,758 x 3,660 x 930 1,758 x 4,200 x 930 1,758 x 4,740 x 930 1,758 x 4,740 x 930 1,758 x 4,740 x 930

846

116

960

113

921

107

1,037

118

1,037

124

1,153

127

1,269

130

1,269

131

1,269

134

33,960 36,180 38,160 40,080 42,420 44,340 46,260 48,600 50,940

13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %) 13 steps (0 – 100 %)

80

18.0

80

24.0

80

25.5

80

26.0

80

26.0

80

26.5

80

27.0

80

27.0

80

27.0

31.75

19.05

6.35

66.0

63.0

80.5

31.75

19.05

6.35

64.5

61.5

79.0

38.10

19.05

6.35

66.5

63.5

81.0

38.10

19.05

6.35

66.0

63.0

80.5

38.10

19.05

67.0

64.0

81.5

38.10

19.05

66.5

63.5

81.0

38.10

19.05

6.35

6.35

Cooling: -10 °C DB ~ +43 °C DB, Heating: -25 °C WB ~ +15 °C WB

6.35

66.0

63.0

80.5

38.10

19.05

6.35

67.0

64.0

81.5

38.10

19.05

6.35

67.5

64.5

82.0

69

NEW 3-PIPE ECOi MF2 SERIES

SIMULTANEOUS HEATING AND COOLING VRF

SYSTEM

70

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

Energy

saving

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

NEW

The New Panasonic 3-Pipe MF2 series offers the best to the most demanding customers.

· The new 3-Pipe units have only one chassis size, with a very small footprint (only 0.93 m²)

· 1 body for all sizes: H1.758 x W1.000 x D930 mm, for 8, 10, 12,

14 and 16 HP

· Maximum capacity size as 48 HP by 3 unit combinations (16 HP x 3 = 48 HP)

· Up to 52 indoor units connectable

· Maximun capacity ratio of 150%

VRF SYSTEMS ECOi

NEW

COP

4,77

Large combination of outdoor units, up to 48 HP

Inverter unit

8

10

12

14

16

System (HP)

8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48

1

1

1 1

1 1

1 1 1 1 1 1

1

1

1

1

1

1

1 2 1

1 2

1

1 2 1

1 2

3 2

1

1

2 3

High effi ciency combination

Inverter unit

8

10

12

14

16

System (HP)

16 24 26 28 30 32

2 3 2 2 2 1

1

1 2

1

Top of de market COP (at full load), standard effi ciency

COP

5.00

4.77

4.55

4.41

4.50

4.30

4.09

3.95

4.00

3.91

3.81

4.03

3.79

3.50

3.00

8 HP 10 HP 12 HP 14 HP 16 HP

NEW 3-PIPE 6 SERIES OLD SERIES

EER

5.00

4.50

4.50

4.00

3.50

3.78

3.00

8 HP

4.10

3.45

10 HP

3.70

3.41

3.45

3.45

3.38

3.38

12 HP 14 HP 16 HP

NEW 3-PIPE 6 SERIES OLD SERIES

Heating

Cooling

71

Connectable indoor/outdoor unit capacity ratio up to 150%

Extended operating range

Cooling operation range: The cooling operation range has been extended to

-10 °C by changing the outdoor fan to an inverter type.

New Solenoid valve kit

Oil-recovery operation to gives more stable comfort air-conditioning control.

3-PIPE CONTROL SOLENOID VALVE KIT 3-PIPE CONTROL PCB

-20

46

50

Outside air temperature (°C DB)

Heating operation range: Stable heating operation even with an outside air temperature of -20 °C. The heating operation range has been extended to

-20 °C by use of a compressor with a high-pressure vessel.

CZ-P56HR3

Up to 5.6 kW

CZ-P160HR3

From 5.7 to 16 kW

KIT-P56HR3

(CZ-P56HR3+CZ-CAPE2)

KIT-P160HR3

(CZ-P160HR3+CZ-CAPE2)

3-Pipe control PCB

CZ-CAPE2*.

Must be added to the CZ-P56HR3 OR CZ-P160HR3.

* For wall mounted S-22MK2E5/S-28MK2E5/S-36MK2E5.

For S-45MK1E5/S-56MK1E5/S-73MK1E5/S-106MK1E5: CZ-CAPE2.

-20

-10 0 10 20 30 40

Outside air temperature (°C WB)

50

Wide temperature setting range

Wired remote control heating temperature setting range is 16 to 30 °C.

Individual control of multiple indoor units with solenoid valve kits

· Any design and layout can be used in a single system.

· Cooling operation is possible up to an outdoor temperature of -10 °C.

Up to max. 40 indoor units

Increased piping lengths and design fl exibility

Adaptable to various building types and sizes. Actual piping length: 180 m.

Maximum piping length: 500 m.

MAX. TOTAL LENGTH: 500 M

System difference of elevation:

50 m *

Difference between the Max - Min tubing lenght after the first branch

40 m

Maximum Length

(indoor/Outdoor)

180 m

Difference in elevation between indoor units:

15 m

* 40 m if the outdoor unit is below the indoor unit.

COOLING HEATING HEATING STOP

Liquid pipe

(medium-temperature, medium-pressure liquid pipe)

Discharge pipe

(high-temperature, high-pressure gas pipe)

Suction pipe

(low-temperature, low-pressure gas pipe)

COOLING STOP

Individual control

Compact design for superb space saving and low noise level

5 types of outdoor units with different capacities have been standardized to one compact casing.

Uniquely constructed with two compartments, the upper chamber contains the heat exchange, with the lower chamber stores the compressors. The benefits are two-fold - superb space saving and low noise level.

INSTALLATION SPACE: 0.93 m²

(In case of 16 HP)

Non-stop operation during maintenance

Even when an indoor unit needs maintenance, the other indoor units can be kept operating by setting. (Not applicable for all situations)

Power suppression control for energy saving (Demand control)¹

The 3-Pipe ECOi MF2 series has a built-in demand function which uses the inverter characteristics. With this demand function, the power consumption can be set in three steps, and operation² at optimum performance is performed according to the setting and the power consumption. This function is useful to reduce the annual power consumption and to save electricity costs while maintaining comfort.

1 An outdoor Seri-Para I/O unit is required for demand input.

2 Setting is possible as 0% or in the range from 40 to 100% (in steps of 5%). At the time of shipping, setting has been done to the three steps of 0%, 70%, and 100%.

56.0

54.0

60.0

58.0

52.0

50.0

57.0

8 HP

54.0

72

59.0

10 HP

56.0

1000

OPERATING SOUND dB(A)

Standard

Silent mode

NEW

VRF SYSTEMS ECOi

Excellent cost saving and smaller piping size

By using R410a with low pressure loss, pipe sizes for discharge, suction and liquid are all reduced.

This makes it possible to aim for reduced piping space, improved workability at the site, and reduction of the piping material costs.

Extended compressor life

The total operation time of the compressors is monitored by a microcomputer, so that there is no imbalance for the operation times of all compressors in the same refrigerant system, and compressors with a shorter operation time are operated with preference.

8 HP

ø15.88

Piping Insulation

ø19.05

ø9.52

10 HP

ø19.05

ø22.22

ø9.52

(mm)

A, C: DC inverter compressor

B, D: Constant speed compressor

A B C D

Load increase

A B C D

Load increase

A B C D

Load increase

A B C D

50 h 30 h 60 h 10 h

3-PIPE ECOi MF2

HP SUCTION PIPE

8 Ø 19.05

10 Ø 22.22

DISCHARGE PIPE

Ø 15.88

Ø 19.05

LIQUID PIPE

Ø 9.52

Ø 9.52

Piping design

Balance tubing

Main piping length LM = LA + LB···

Main distribution pipes LC-LH are selected according to the capacity after the distribution joint.

Size of indoor unit connection piping 1-40 is determined by the connection piping size on the indoor units.

The outdoor connection main tubing (LO portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.

EXPLANATION OF SYMBOLS

Distribution joint (CZ, option)

Ball valve (BV, option)

T-joint (field supply)

Solidly welded shut (pinch weld)

Note: Do not use commercial T-pieces for the liquid pipes of and.

* Be sure to use R410A distribution joints for outdoor unit connections and piping branches.

1. The connection between the indoor unit(s) and the solenoid valve kit(s) has three (3) types of methods. For further details, refer to the Section 2. 3-4. “Connecting Multiple Indoor Units to a Single Solenoid Valve Kit”.

Max. 400 mm

For extension

For extension

Max. 400 mm

T-joint tubing

(header joint system)

L3

7

Solenoid Valve Kit 1

R410A distribution joint

RANGES THAT APPLY TO REFRIGERANT PIPING LENGTHS AND TO DIFFERENCES IN INSTALLATION HEIGHTS

Items

Allowable piping length

Allowable elevation difference

Allowable length of joint tubing

Marks

L1

Δ L (L2–L4)

LM

Contents

Max. piping length Actual piping length

Equivalent piping length

Difference between the max. length and the min. length from the No. 1 distribution

Max. length of main piping (at max. diameter)

Length (m)

≤180¹

≤200

≤40

—²

1, 2~ 40

L1+ 1+ 2... 39+ A+ B+LF+LG+LH

L5

H1

H2

H3

L3

Max. length of each distribution

Total max. piping length including length of each distribution (only liquid tubing)

Distance between outdoor units

When outdoor unit is installed higher than indoor unit

When outdoor unit is installed lower than indoor unit

Max. difference between indoor units

≤40

≤15

Max. difference between outdoor units ≤4

T-joint tubing (field-supply); Max. tubing length between the first T-joint and solidly welded-shut end point ≤2

≤30

≤500³

≤10

≤50

L = Length, H = Height

1. If the longest tubing length (L1) exceeds 90 m (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for the discharge tubes, suction tubes, and narrow tubes. (field supplied).

2. If the longest main tube length (LM) exceeds 50 m, increase the main tube size at the portion before 50 m by 1 rank for the suction tubes and discharge tubes. (field supplied). (For the portion that exceeds 50 m, set based on the main tube sizes (LA) listed in the table on the following page).

3. 24 HP - 30HP of high efficiency combination is 300 m.

73

Energy

saving saving

Energy

8-16 HP // 3-PIPE ECOi MF2 SERIES

WITH SIMULTANEOUS HEATING AND COOLING OPERATION HEAT RECOVERY TYPE

ECOi 3-Pipe is one of the most advanced VRF systems available. Not only offering high-efficiency and performance for simultaneous heating and cooling, its sophisticated design makes installation and maintenance much easier.

· Achieves COP 4.77 as the top class in the industry (Average cooling and heating value for 8 HP outdoor unit).

· Simultaneous cooling or heating operation for up to 26 indoor units.

· Small installation space, top class in the industry.

· Rotation operation function and back-up operation function provided.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

TECHNICAL FOCUS

· STANDARDIZATION OF O_U TO ONE COMPACT CASING SIZE

· IMPROVED OPERATION EFFICIENCY

· THE CONSTANT-SPEED COMPRESSOR ADOPTS A HIGH-

PERFORMANCE INTERNAL HIGH-PRESSURE SCROLL

· IMPROVEMENT OF THE HEAT EXCHANGER

· REDESIGN OF STRUCTURAL PARTS

· CLOSE SIDE-BY-SIDE INSTALLATION IS POSSIBLE

HP

MODEL NAME

Power supply

Cooling capacity

EER

Running current

Power input

Heating capacity kW

BTU/h

W/W

380 / 400 / 415 V A kW kW

8

U-8MF2E8

22.4

76,500

4.50

8.60 / 8.20/ 8.00

4.98

25.0

COP

Running current

Power input

Dimensions

Net weight

Air circulation

Piping connections

BTU/h

W/W

380 / 400 / 415 V A

H x W x D

Refrigerant amount at shipment

Suction pipe kW mm kg

85,300

4.77

8.95 / 8.50 / 8.30

5.24

1758 x 1000 x 930

269 m³/min 158 kg 8.3

mm (Inch) Ø 19.05 (3/4)

Discharge pipe mm (Inch) Ø 15.88 (5/8)

Sound pressure level

Sound power level

Liquid pipe

Balance pipe

Ambient temperature operating range

High / Low mm (Inch) Ø 9.52 (3/8) mm (Inch) Ø 6.35 (1/4) dBA

Normal mode dB

57.0 / 54.0

71.5 / 68.5

10

U-10MF2E8

28.0

95,600

4.10

11.3 / 10.8 / 10.6

6.83

31.5

107,500

4.55

11.6 / 11.0 / 10.7

6.92

1758 x 1000 x 930

269

178

8.5

Ø 22.22 (7/8)

Ø 19.05 (3/4)

Ø 9.52 (3/8)

Ø 6.35 (1/4)

12

U-12MF2E8

14

U-14MF2E8

380 / 400 / 415 V - Three Phase / 50 Hz

33.5

114,300

3.70

15.1 / 14.5 / 14.1

9.05

37.5

128,000

4.30

14.7 / 14.1 / 13.8

8.72

1758 x 1000 x 930

314

212

8.8

Ø 25.40 (1)

Ø 19.05 (3/4)

Ø 12.70 (1/2)

Ø 6.35 (1/4)

40.0

136,500

3.45

19.2 / 18.4 / 17.9

11.00

45.0

153,600

4.41

17.0 / 16.4 / 15.9

10.2

1758 x 1000 x 930

322

212

9.3

Ø 25.40 (1)

Ø 22.22 (7/8)

Ø 12.70 (1/2)

Ø 6.35 (1/4)

16

U-16MF2E8

45.0

153,600

3.38

22.0/ 21.1 / 20.6

13.00

50.0

170,600

4.03

20.7 / 19.9 / 19.4

12.4

1758 x 1000 x 930

322

212

9.3

Ø 28.58 (1-1/8)

Ø 22.22 (7/8)

Ø 12.70 (1/2)

Ø 6.35 (1/4)

Cooling/Dry: -10 °C~+46 °C (DB). Heating: -20 °C~+18 °C (WB) Simultaneous operation: -10 °C~+24 °C (DB)

59.0 / 56.0

61.0 / 58.0

62.0 / 59.0

62.0 / 59.0

73.5 / 70.5

75.5 / 72.5

76.5 / 73.5

76.5 / 73.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

74

NEW

NEW

COP

4,77

VRF SYSTEMS ECOi

System limitations

Max. number of combined outdoor units

Max. HP of combined outdoor units

Max. number of connectable indoor units

Indoor/outdoor unit capacity ratio

3

135 kW (48 HP)

52

50 -150%

Additional refrigerant charge

LIQUID PIPING

SIZE

AMOUNT OF REFRIGERANT

CHARGE/m (g/m)

Ø 6.35

Ø 9.52

Ø 12.7

Ø 15.88

26

56

128

185

LIQUID PIPING

SIZE

AMOUNT OF REFRIGERANT

CHARGE/m (g/m)

Ø 19.05

Ø 22.22

Ø 25.40

259

366

490

Refrigerant piping

PIPING SIZE (mm)

O MATERIAL

Outer diameter

Ø 6.35

Ø 9.52

Wall thickness

0.8

0.8

Ø 12.7

Ø 15.88

Ø 19.05

Ø 22.22

0.8

1.0

1.0

1.15

1/2 H, H MATERIAL

Outer diameter

Ø 25.4

Ø 28.58

Ø 31.75

Ø 38.1

Ø 41.28

Wall thickness

1.0

1.0

1.1

over 1.35

over 1.45

Note: When pipe bending is to be performed, the bending radius shall be at least 4 times the outer diameter. Also, take sufficient care to prevent pipe collapse and damage at the time of bending.

TOP VIEW

Air intake

FRONT VIEW

Air discharge

Electrical component box

SIDE VIEW

970 (Installation hole pitch)

1000

According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

A: 894 (Installation hole pitch) * The tubing is routed out from the front.

B: 730 (Installation hole pitch) * The tubing is routed out from the bottom.

C: 730 (Installation hole pitch)

* Installation fixing bracket, installation side.

71*

363

601

858

71*

930

75

Energy

saving saving

Energy

3-PIPE ECOi MF2 SERIES // COMBINATION FROM 18 TO 48 HP

WITH SIMULTANEOUS HEATING AND COOLING OPERATION HEAT RECOVERY TYPE

ECOi 3-Pipe is one of the most advanced VRF systems available. Not only offering high-efficiency and performance for simultaneous heating and cooling, its sophisticated design makes installation and maintenance much easier.

· Achieves COP 4,63 as the top class in the industry (Average cooling and heating value for 8 HP outdoor unit).

· Simultaneous cooling or heating operation for up to 52 indoor units.

· Small installation space, top class in the industry.

· Rotation operation function and back-up operation function provided.

TECHNICAL FOCUS

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

· STANDARDIZATION OF O_U TO ONE COMPACT CASING SIZE

· IMPROVED OPERATION EFFICIENCY

· THE CONSTANT-SPEED COMPRESSOR ADOPTS A HIGH-

PERFORMANCE INTERNAL HIGH-PRESSURE SCROLL

· IMPROVEMENT OF THE HEAT EXCHANGER

· REDESIGN OF STRUCTURAL PARTS

· CLOSE SIDE-BY-SIDE INSTALLATION IS POSSIBLE

HP

MODEL NAME

18

U-8MF2E8

U-10MF2E8

20

U-8MF2E8

U-12MF2E8

22

U-8MF2E8

U-14MF2E8

24

U-8MF2E8

U-16MF2E8

26

U-12MF2E8

U-14MF2E8

28

U-14MF2E8

U-14MF2E8

30

U-14MF2E8

U-16MF2E8

Power supply

Cooling capacity

EER

Running current kW

BTU/h

W/W

380 / 400 / 415 V A

50.4

172,000

4.27

56.0

191,100

3.97

61.5

209,900

3.80

380 / 400 / 415 V - Three Phase / 50 Hz

68.0

232,100

3.68

73.0

249,100

3.58

78.5

267,900

3.49

85.0

290,100

3,41

19.7 / 18.9 / 18.4

23.8 / 22.9 / 22.3

27.0 / 26.0 / 25.3

30.9 / 29.7 / 28.9

33.7 / 32.4 / 31.5

37.2 / 35.7 / 34.8

41.1 / 39.5 / 38.5

Power input

Heating capacity kW kW

11.8

56.5

14.1

63.0

16.2

69.0

18.5

76.5

20.4

81.5

22.5

87.5

24,90

95.0

COP

Running current

Power input

Dimensions

Net weight

Air circulation

Piping connections

BTU/h

W/W

380 / 400 / 415 V A

H x W x D

Refrigerant amount at shipment

Suction pipe kW mm kg m³/min 336 kg

192,800

4.63

20.4 / 19.6 / 19.1

12.2

1758 x 2060 x 930

538

16.8

mm (Inch) Ø 28.58 (1-1/8)

Discharge pipe mm (Inch) Ø 22.22 (7/8)

215,000

4.47

23.8 / 22.9 / 22.3

14.1

1758 x 2060 x 930

538

370

17.1

Ø 28.58

Ø 22.22

235,500

4.57

25.2 / 24.2 / 23.6

15.1

1758 x 2060 x 930

591

370

17.6

Ø 28.58

Ø 25.40 (1)

261,100

4.20

30.4 / 29.2 / 28.5

18.2

1758 x 2060 x 930

591

370

17.6

Ø 28.58

Ø 25.40

278,200

4.38

31.1 / 29.8 / 29.1

18.6

1758 x 2060 x 930

636

424

18.1

Ø 31.75 (1-1/4)

Ø 25.40

298,600

4.49

32.6 / 31.3 / 30.5

19.5

1758 x 2060 x 930

644

424

18.6

Ø 31.75

Ø 28.58

324,200

4.20

37.7 / 36.2 / 35.3

22.6

1758 x 2060 x 930

644

424

18.6

Ø 31.75

Ø 28.58

Sound pressure level

Sound power level

Liquid pipe

Ambient temperature operating range

High / Low mm (Inch) Ø 15.88 (5/8)

Balance pipe mm (Inch) Ø 6.35 (1/4) dBA

Normal mode dB

61.0 / 58.0

75.5 / 72.5

Ø 15.88

Ø 6.35 (1/4)

Ø 15.88

Ø 6.35 (1/4)

Ø 15.88

Ø 6.35 (1/4)

Ø 19.05 (3/4)

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Cooling/Dry: -10 °C~+46 °C (DB). Heating: -20 °C~+18 °C (WB) Simultaneous operation: -10 °C~+24 °C (DB)

62.5 / 59.5

63.0 / 60.0

63.0 / 60.0

64.5 / 61.5

65.0 / 62.0

65.0 / 62.0

77.0 / 74.0

77.5 / 74.5

77.5 / 74.5

79.0 / 76.0

79.5 / 76.5

79.5 / 76.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

76

NEW

NEW

150%

CAPACITY

RATIO

VRF SYSTEMS ECOi

32

U-16MF2E8

U-16MF2E8

34

U-8MF2E8

U-12MF2E8

U-14MF2E8

90.0

307,200

96.0

327,600

3,38 3.74

43.9 / 42.2 / 41.1 42.9 / 41.2 / 39.7

26.6

100.0

341,300

4.03

25.7

108.0

368,600

4.44

41.7 / 40.1 / 39.1 41.0 / 39.4 / 38.4

24.8

24.3

1758 x 2060 x 930 1758 x 3120 x 930

644 905

424

18.6

Ø 31.75

Ø 28.58

Ø 19.05

Ø 6.35 (1/4)

582

26.4

Ø 31.75

Ø 28.58

Ø 19.05

Ø 6.35 (1/4)

65.0 / 62.0

79.5 / 76.5

65.0 / 62.0

79.5 / 76.5

36

U-8MF2E8

U-14MF2E8

U-14MF2E8

101.0

344,700

3.66

46.1 / 44.3 / 43.1

38

U-8MF2E8

U-14MF2E8

U-16MF2E8

107.0

365,200

3.60

49.6 / 47.6 / 46.4

40

U-8MF2E8

U-16MF2E8

U-16MF2E8

42

U-14MF2E8

U-14MF2E8

U-14MF2E8

380 / 400 / 415 V - Three Phase / 50 Hz

113.0

118.0

385,700

3.55

53.1 / 51.0 / 49.7

402,700

3.48

56.0 / 53.8 / 52.4

44

U-14MF2E8

U-14MF2E8

U-16MF2E8

124.0

423,200

3.43

59.6 / 57.3 / 55.8

27.6

113.0

385,700

4.52

41.6 / 39.9 / 38.9

25.0

1758 x 3120 x 930

913

29.7

119.0

406,100

4.33

46.1 / 44.3 / 43.1

27.5

1758 x 3120 x 930

913

31.8

127.0

433,400

4.12

52.2 / 49.6 / 47.8

30.8

1758 x 3120 x 930

913

33.9

132.0

450,500

4.46

49.3 / 47.3 / 46.1

29.6

1758 x 3120 x 930

966

36.1

138.0

471,000

4.30

53.8 / 51.6 / 50.3

32.1

1758 x 3120 x 930

966

582

26.9

Ø 38.10 (1-1/2)

Ø 28.58

582

26.9

Ø 38.10

Ø 31.75

582

26.9

Ø 38.10

Ø 31.75

636

27.9

Ø 38.10

Ø 31.75

636

27.9

Ø 38.10

Ø 31.75

Ø 19.05

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Ø 19.05

Ø 6.35 (1/4)

Cooling/Dry: -10 °C~+46 °C (DB). Heating: -20 °C~+18 °C (WB) Simultaneous operation: -10 °C~+24 °C (DB)

65.5 / 62.5

65.5 / 62.5

65.5 / 62.5

67.0 / 64.0

67.0 / 64.0

80.0 / 77.0

80.0 / 77.0

80.0 / 77.0

81.5 / 78.5

81.5 / 78.5

46

U-14MF2E8

U-16MF2E8

U-16MF2E8

130.0

443,700

3.40

63.8 / 61.3 / 59.7

38.2

145.0

494,900

4.14

58.8 / 56.5 / 55.0

35.0

1758 x 3120 x 930

966

636

27.9

Ø 38.10

Ø 31.75

Ø 19.05

Ø 6.35 (1/4)

67.0 / 64.0

81.5 / 78.5

48

U-16MF2E8

U-16MF2E8

U-16MF2E8

135.0

460,800

3.38

65.9 / 63.3 / 61.7

39.9

150.0

511,900

4.03

62.6 / 60.1 / 58.6

37.2

1758 x 3120 x 930

966

636

27.9

Ø 38.10

Ø 31.75

Ø 19.05

Ø 6.35 (1/4)

67.0 / 64.0

81.5 / 78.5

SYSTEM EXAMPLE

CONNECTION

Panasonic make it possible to link outdoor units together for a large capacity (48 HP)

If indoor/outdoor units need servicing, a ball valve (optional) cuts off non-operational units to let other units stay running.

ADDITION

Outdoor unit

If your indoor capacity load changes in the future, it’s easy to add on both indoor and outdoor units using the same pipings.

If the additional instalment of outdoor and indoor units is expected, the size of refrigerant piping should be decided according to the total capacity after the addition.

CONCENTRATION

Since all pipes are concentrated into one pipe shaft, you can minimise pipe space and construction labour.

Solenoid valve kit

Indoor unit

77

Energy

saving saving

Energy

3-PIPE ECOi MF2 SERIES // HIGH EFFICIENCY COMBINATION 16 TO 32 HP

WITH SIMULTANEOUS HEATING AND COOLING OPERATION HEAT RECOVERY TYPE

ECOi 3-Pipe is one of the most advanced VRF systems available. Not only offering high-efficiency and performance for simultaneous heating and cooling, its sophisticated design makes installation and maintenance much easier.

· Achieves COP 4.76 as the top class in the industry (Average cooling and heating value for 8 HP outdoor unit).

· Simultaneous cooling or heating operation for up to 52 indoor units.

· Small installation space, top class in the industry.

· Rotation operation function and back-up operation function provided.

TECHNICAL FOCUS

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

Down to

-20 ºC

in heating mode

OUTDOOR

TEMPERATURE

5 year

compressor warranty

· STANDARDIZATION OF O_U TO ONE COMPACT CASING SIZE

· IMPROVED OPERATION EFFICIENCY

· THE CONSTANT-SPEED COMPRESSOR ADOPTS A HIGH-

PERFORMANCE INTERNAL HIGH-PRESSURE SCROLL

· IMPROVEMENT OF THE HEAT EXCHANGER

· REDESIGN OF STRUCTURAL PARTS

· CLOSE SIDE-BY-SIDE INSTALLATION IS POSSIBLE

HP

MODEL NAME

Power supply

Cooling capacity

EER

Running current

16

U-8MF2E8

U-8MF2E8

kW 45.0

BTU/h 153,600

W/W 4.50

380 / 400 / 415 V A 17.3 / 16.4 / 16.0

24

U-8MF2E8

U-8MF2E8

U-8MF2E8

68.0

232,100

4.47

26.2 / 24.9 / 24.3

26

U-8MF2E8

U-8MF2E8

U-10MF2E8

28

U-8MF2E8

U-8MF2E8

U-12MF2E8

73.0

380 / 400 / 415 V - Three Phase / 50 Hz

78.5

249,100

4.32

28.5 / 27.4 / 26.7

267,900

4.11

32.2 / 31.0 / 30.2

30

U-8MF2E8

U-8MF2E8

U-14MF2E8

85.0

290,100

3.94

36.5 / 35.0 / 34.1

32

U-8MF2E8

U-12MF2E8

U-12MF2E8

90.0

307,200

3.86

38.9 / 37.4 / 36.4

Power input

Heating capacity kW 10.0

kW 50.0

COP

Running current

Power input

Dimensions (Combination) H x W x D

BTU/h 170,600

W/W

380 / 400 / 415 V A

4.76

kW 10.5

mm

17.9 / 17.0 / 16.6

1758 x 2060 x 930

Net weight

Air circulation

Refrigerant amount at shipment

Piping connections Suction pipe kg mm

538 m³/min 316 kg 16.6

Ø 28.58

Discharge pipe mm Ø 22.22

Liquid pipe

Normal mode mm dB

Ø 12.70

Balance pipe mm Ø 6.35

Ambient temperature operating range

Sound pressure level

Sound power level

High / Low dB(A) 60.0 / 57.0

74.5 / 71.5

15.2

76.5

261,100

4.72

27.7 / 26.3 / 25.6

16.2

1758 x 3120 x 930

807

16.9

81.5

278,200

4.68

29.4 / 27.9 / 27.5

17.4

1758 x 3120 x 930

807

19.1

87.5

298,600

4.56

32.4 / 31.1 / 30.4

19.2

1758 x 3120 x 930

852

21.6

95.0

324,200

4.59

35.0 / 33.6 / 32.7

20.7

1758 x 3120 x 930

860

23.3

100.0

341,300

4.41

38.3 / 36.8 / 35.9

22.7

1758 x 3120 x 930

897

474

24.9

Ø 28.58

Ø 25.40

494

25.1

Ø 31.75

Ø 25.40

528

25.4

Ø 31.75

Ø 28.58

528

25.9

Ø 31.75

Ø 28.58

582

25.9

Ø 31.75

Ø 28.58

Ø 15.88

Ø 6.35

Ø 19.05

Ø 6.35

Ø 19.05

Ø 6.35

Ø 19.05

Ø 6.35

Ø 19.05

Ø 6.35

Cooling/Dry: -10 °C~+46 °C (DBT). Heating: -20 °C~+18 °C (WBT) Simultaneous operation: -10 °C~+24 °C (DBT)

62.0 / 59.0

62.5 / 59.5

63.5 / 60.5

64.0 / 61.0

65.0 / 62.0

76.5 / 73.5

77.0 / 74.0

78.0 / 75.0

78.5 / 75.5

79.5 / 76.5

GLOBAL REMARKS Rated conditions:

Indoor air temperature

Outdoor air temperature

Specifications subject to change without notice.

Cooling Heating

27 ºC DB / 19 ºC WB 20 ºC DB

35 ºC DB / 24 ºC WB 7 ºC DB / 6 ºC WB

78

NEW

NEW

COP

4.76

VRF SYSTEMS ECOi

Market-leading COP (at full load), standard efficiency

5.00

4.50

4.76

4.03

4.72

4.20

4.68

4.38

4.56

4.49

NEW 3-PIPE MF2 SERIES COP

4.59

4.41

4.20

4.03

4.00

4.00

5.00

4.50

4.50

3.50

3.50

3.38

4.47

3.68

4.32

3.58

4.11

3.49

NEW 3-PIPE MF2 SERIES EER

3.94

3.41

3.86

3.38

3.00

16 HP 24HP 26HP 28 HP 30 HP 32 HP

HIGH COP COMBINATION STANDARD COMBINATION

3.00

16 HP

TOP VIEW

Air intake

FRONT VIEW

Air discharge

24HP 26HP 28 HP 30 HP 32 HP

HIGH COP COMBINATION STANDARD COMBINATION

SIDE VIEW

Electrical component box

970 (Installation hole pitch)

1000

According to the installation site, you may choose the setting position in the depth direction of the anchor bolt from “A”, “B” or “C”.

A: 894 (Installation hole pitch) * The tubing is routed out from the front.

B: 730 (Installation hole pitch) * The tubing is routed out from the bottom.

C: 730 (Installation hole pitch)

* Installation fixing bracket, installation side.

71*

363

601

858

71*

930

79

PANASONIC INTRODUCING

THE GAS DRIVEN VRF

80

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

High

savings

Environmentally

friendly

refrigerant

R410A

ECO G AND ECO G MULTI, S SERIES

Panasonic’s GHP range is extensive and covers the ECO G and ECO G Multi Series, and the S Series. Our

GHP VRF range of commercial systems is leading the industry in the development of efficient and flexible systems, and is the natural choice for commercial projects, especially those where power restrictions apply. As you would expect, all our gas-driven VRF systems have the highest reliability rates in the industry and a leading customer service programme. The torque and rpm control functions of the

GHP’s motor are comparable with an inverter-type electric air conditioner. Thus, the GHP ensures individual, and efficient control and performance - just as you expect from an electric inverter controlled air conditioner.

Easy to position

The advanced Gas Driven VRF systems offers increased efficiency and performance across the range.

Now more powerful than ever before, it can connect up to 48 indoor units.

Improvements include increased part load performance, reduced gas consumption with a Miller-cycle engine and reduced electrical consumption by using DC fan motors.

· Up to 71 kW of cooling from a current consumption of 11.0 AMPs

· Single phase power supply across the range

· The option of natural gas or LPG as its main power source

· A Water Heat Exchanger to connect to domestic hot water systems

16–25 HP (2-Pipe units only)

· Option of DX or chilled water for indoor heat exchange

· Reduced CO

2

emissions

NEW

VRF SYSTEMS ECO G

NEW ECO G HIGH POWER

1% this is what the new ECO G High Power is consuming versus your Electrical VRF.

Your savings start now!

Ideal for locations with low electricity grid, for Chiller, Ventilation and Air conditioning

ECO G AND ECO G MULTI

The S Series 2-Pipe not only offers improved performance but also increased fl exibility.

ECO G 3 WAY MULTI

3 Way heat recovery system with simultaneous heating & cooling.

81

ECO G OUTDOOR UNITS RANGE

HP 16 20 25 30 32 36 40 45 50

CAPACITY

(Cooling /

Heating) kW

45.00 / 50.00

56.00 / 63.00

71.00 / 80.00

85.00 / 95.00

90.00 / 100.00 101.00 / 113.00 112.00 / 126.00 127.00 / 143.00 142.00 / 160.00

NEW

ECO G HIGH

POWER

U-16GEP2E5

ECO G AND

ECO G MULTI

U-16GE2E5

ECO G 3 WAY U-16GF2E5

MULTI

U-20GEP2E5

U-20GE2E5

U-20GF2E5

U-25GEP2E5

U-25GE2E5

U-25GF2E5

U-30GE2E5 U-16GE2E5

U-16GE2E5

U-16GE2E5

U-20GE2E5

U-20GE2E5

U-20GE2E5

U-20GE2E5

U-25GE2E5

U-25GE2E5

U-25GE2E5

Comparison of heating capacity

Heating capacity (%)

Gas heat pump*

Electric heat pump

-20 -15 -10 -5 0 5 10

* regarding models 16 and 20 HP.

Outside air temperature (°C)

Comparison of the start times for heating operation

10

5

20

15

0

Room temperature (°C)

25

Gas heat pump

Electric heat pump

Time axis (in case of the same load)

The Gas Heat Pump (GHP)

Panasonic Gas Heat Pump is the natural choice for commercial projects, especially for those projects where power restrictions apply. As you would expect, all of our Gas Driven VRF systems are designed to give the highest reliability rates. The GHP engine or (internal combustion engine) varies the engine speed to match the building load functions that are comparable with an inverter type electric air conditioner.

Exhaust Fan

Power supply problems?

If you are short of electrical power, our gas heat pump could be the perfect solution:

· Runs on natural gas or LPG and just needs single phase supply

· Enables the building’s electrical power supply to be used for other critical electrical demands

· Reduces capital cost to upgrade power substations to run heating and cooling systems

· Reduces power loadings within a building especially during peak periods

· Electricity supply freed up for other uses such as IT servers, commercial refrigeration, manufacturing, lighting etc.

Water coil

Accumulator

GHP Outdoor Heat Exchanger

· Integrated DX and hot water coil

· No defrost required

· Faster reaction to demand for heating

DX coil

82

VRF SYSTEMS ECO G

ECO G 3 Way Multi

SYSTEM EXAMPLE

EXCELLENT PERFORMANCE

Panasonic 3 WAY Multi system is capable of simultaneous heating/cooling and individual operation of each indoor unit by only one outdoor unit. As a result, efficient individual air conditioning is possible in buildings having diverse room temperatures.

IMPROVED MAINTENANCE INTERVALS

The unit only needs to be serviced every 10,000 hours. This is the best in the industry.

UP TO 35% ENERGY SAVING

Effective heat recovery system enables up to 35% energy saving

The waste heat removed from the cooled room is effectively used as a heat source for the room to be heated. As a result, the load on the compressor and heat exchanger on the outdoor unit can be reduced, enabling excellent heat recovery.

ECO G Water Heat Exchanger

Mixed System Application

· Combined with a Water Heat Exchanger unit, the Panasonic GHP can create a flexible system--the ideal replacement for existing chiller and boiler systems.

· The GHP Multi System can have an indoor unit plus a GHP chiller. When the two systems are operated independently, an outdoor unit with 130% capacity can be connected.

SYSTEM EXAMPLE

Fan Coil Unit

GHP Chiller

Water Heat Exchanger

Buffer Tank

Water Piping

Refrigerant piping

Duct*

Outdoor unit Air Handling Unit

* Standard DX type indoor unit system

Liquid pipe

Medium-temperature, mediumpressure liquid pipe

STOP Heating Cooling

Suction pipe

Low-temperature, low-pressure gas pipe

Heating Cooling

Discharge pipe high-temperature, high-pressure gas pipe

Heating

SOLENOID VALVE KIT CZ-P56HR3, CZ-P160HR3

KIT-P56HR3 (CZ-P56HR3+CZ-CAPE2), KIT-P160HR3 (CZ-P160HR3+CZ-CAPE2)

To be fitted on all ‘zones’ to allow simultaneous heating and cooling.

Up to 36 indoor units are capable of simultaneous heating/cooling operation.

SOLENOIDE VALVE CONTROLLER

CZ-CAPE2*.

Must be added to the CZ-P56HR3 OR CZ-P160HR3.

* For wall mounted S-22MK2E5/S-28MK2E5/S-36MK2E5.

For S-45MK1E5/S-56MK1E5/S-73MK1E5/S-106MK1E5: CZ-CAPE2.

control wiring

Note: The mode of running of outdoor unit depends on the Water Heat Exchanger’s mode. The water pump is not included in the Water Heat Exchanger unit. For simultaneous operation, however, the maximum capacity is 130%. Please contact

Panasonic for details of this system design.

83

84

ECO G HIGH POWER ECO G HIGH POWER, ECO G AND

ECO G MULTI

2-Pipe Heat Pump System with Electrical Power Generator

Production of electricity

Generates up to 2 kW depending on air conditioning load.

Panasonic innovates again introducing a new GHP producing his own electricity.

Equipped with a small generator of high-performance.

Compressor and generator are driven by gas engine. The generated electricity is used for the fan motor and cooling water pump of its own unit.

The generating efficiency is more than 40%.

2-Pipe Heat Pump System

Easy to add additional units in the future

Load can easily be increased in the future by the addition of indoor and outdoor units without having to plumb pipe shafts.

* When specifying refrigerant pipe work, please choose the size according to the horsepower after the increase of units.

EXAMPLE OF A SYSTEM

ADDED OUTDOOR UNITS.

(Only for models with the same refrigerant.)

If there is a possibility for addition after setting up, please plan it so that the placement of a ball valve (sold separately) on a branch pipe on indoor/outdoor units is possible.

ADDED INDOOR UNITS.

(Only for models with the same refrigerant.)

Main pipe: Maximum gas pipe diameter 38.1 (1 1/2)

Maximum fluid pipe diameter 19.05 (3/4)

Fan motor

Cooling water pump

Engine

Compressor

Electricity flow

Electric control BOX

(Inverter/

Comverter)

Maximum possible number of outdoor units to be combined: 2 units.

Maximum horsepower of combined outdoor units: 50 HP.

Maximum possible number of indoor units to be connected: 48 units¹.

Indoor/outdoor units capacity ratio: 50%~130%².

1 When 2 outdoor units are connected.

2 Capacity of indoor units connection is: Minimum) 50% of the capacity of the smallest outdoor unit within the system.

Maximum) 130%: total capacity of the system outdoor units.

Indoor units are same as multi series for buildings.

SYSTEM DIAGRAM

gas pipe fluid pipe

Generator

Electric supply

4 direction valve oil separator oil-surface sensor compresor electronic control valve

Ev

Outdoor units

4 direction valve oil separator oil-surface sensor compresor electronic control valve

Ev

Outdoor units electronic control valve

Indoor units electronic control valve

Indoor units

Saving Energy

· Energy savings achieved by the Appropriate Capacity.

· Equational Program Function.

Energy savings are achieved by the Appropriate Load Divider Function, which enables efficient operation by concentrating the cooling/heating capacity to one outdoor unit and stopping the other. Compared to conventional machines with a similar COP, this function allows energy savings and thus reduces the running costs, especially in part-load seasons like spring and autumn.

Load of around 10 HP

(8 h operating)

UP TO THIS TIME

Load of around 10 HP

(8 h operating)

STOP

W-MULTI

Load of around 10hp

(8 h operating)

TOTAL OPERATING HOURS: 16 HOURS TOTAL OPERATING HOURS: 8 HOURS

VRF SYSTEMS ECO G

Non-stop operation, even during maintenance

· System will not stop even during maintenance, due to Manual

Backup Operating Function.

· Maintenance is possible during weekdays because it can continue operating during maintenance.

· Automatic Backup Operating Function enables continuous operation.

If one outdoor unit stops the backup function will automatically start on the remaining unit and continue operating. During service intervals, the system being serviced can be isolated by a closing valve in the outdoor unit, enabling continuous operation with the still operative outdoor unit.

Combining all pipes, which were needed for each outdoor unit, into a pipe in each system. (Number of pipes is reduced by half).

EXAMPLE OF A SYSTEM WITH APPROXIMATELY 40 HP

UP TO THIS TIME W-MULTI

20 HP

+

20 HP 20 HP

+

20 HP

UP TO THIS TIME W-MULTI

System stops during maintenance

Machine in need of maintenance

Maintenance during holidays

STOP

OPEN OPEN OPERATING

Machine in need of maintenance

Continuous operation under the maintenance

OPERATING

CLOSE CLOSE OPERATING

BACKUP

Maintenance during weekdays

OPERATING

Hot Water Supply Function

· System Advantage.

The engine waste heat, which is normally exhausted into the atmosphere, is recovered via the heat exchanger and effectively used as hot water, so the

GHP Chiller acts as a sub system that alleviates the load on the client’s main hot water system, and therefore offers ‘free’ hot water.

Long lifetime

· Renewal period prolonged due to rotation function.

Rotation function, which is run from outdoor units with low operating time, will average the operating hours of each outdoor unit. TThis extends the periods between maintenance or replacement.

CAPACITY AT COOLING STANDARD POINT

Outdoor unit U-16GE2E5

U-20GE2E5

U-25GE2E5

U-30GE2E5

Hot water piping allowable pressure

Hot water circulation rate

Hot water tube size

OUTLET TEMP 75 °C

kW 15.00

20.00

30.00

MPa m³/h

30.00

0.7

3.9

Rp 3/4

Electric connection: 240 Vac, 3 A

EXAMPLE OF

THE ROTATION

FUNCTION

STOP

A

STOP

B

STOP

A B

ELECTRIC DESIGN

Operating hours

A

2,100 h

B

2,050 h

SYSTEM STARTUP

Only unit is operating

B

Magnetic Relay Pump

REALIZATION OF

AVERAGING

OPERATING HOURS

STOP

A B

A B

GHP Panasonic

Hot water

Operating hours

A

2,105 h

B

2,058 h

Load reduced

Only machine is operating

B

Operating hours

A

2,100 h

B

2,053 h

Load increased

Machine and are operating

A

B

Ease of construction

· By using common header pipe work the installation cost and time is significantly reduced.

By combining all pipes, which were needed for each indoor unit, into a common pipe in each system, the number of pipes are reduced by half* which leads to ease of construction. Furthermore, space of pipes within pipe shafts can be reduced by 2/3.*

*System with approximately 40hp (20hp x 2 units)

Water tank

Manometer

Boiler

Pump

Cold water

· All the items illustrated in this drawing (except the outdoor unit) are not supplied by Panasonic.

· During start up, set temperature value of the water in the outdoor unit’s parameter.

Expansion tank

Valve

85

86

ECO G WATER HEAT EXCHANGER FOR HYDRONIC APPLICATIONS

Application Examples

Application Examples

CONNECTION TO ‘CLOSE CONTROL’ COMPUTER EQUIPMENT.

COMPUTER ROOM APPLICATIONS

When all available electrical power needed to be utilised for the IT equipment for a leading international bank, the cooling load of over 450 kW had to be powered by gas. The outdoor units were connected via Water Heat

Exchangers to cooling coils inside the ‘close control’ units thereby maintaining a conditioned environment for temperature and humidity. By utilising the hot water function over 100 kW of hot water are supplied to the building and therefore the additional benefit of considerable CO

2 ensured.

savings is

This drawing is copyright. // 1. Do not scale this drawing // 2. Errors / omissions to be immediately notified to the Engineer. // 3. All dimensions to be checked on site.

Low Pressure Hot Water Supply

Feed

Return

Input Electricity

Nat. Gas

Cooling Load

Room A

Cooling Load

Room B

100 mm CHW F&R

Air Cooled

Chiller

This Part L design has reduced C0

2

Emissions by 26% or 166 tonnes per annum compared to electric chillers.

Specifications subject to change without notice.

Rating Conditions: Cooling Indoor 27 °C DB 19 °C WB Outdoor 35 °C DB 24 °C WB Heating Indoor 20 °C DB Outdoor 7 °C DB 6 °C WB.

Package

Auto Fill

Unit

100 Litre pressure vessel

65 mm CHW F&R

150 mm Header

VRF SYSTEMS ECO G

CONNECTION TO CHILLED WATER COILS IN AIR HANDLING EQUIPMENT.

AIR HANDLING APPLICATION

When a top London restaurant opened, it needed large volumes of fresh air to ensure the optimum dining environment. GHP units connected to the cooling coils within the air handling equipment ensured the air was introduced in the right condition in both summer and winter.

CHILLER REPLACEMENT. CHILLED WATER SUPPLY TO FAN COILS.

CHILLER REPLACEMENT

When some old chillers needed replacing at the end of their operational lifetime, GHPs with Water Heat Exchangers enabled the project to be carried out in stages whilst still utilising the existing water pipe work and fan coils. This enabled the project to be delivered on time, to a restricted budget and avoided all issues regarding refrigerant in confined spaces.

87

High

savings savings

High

NEW ECO G HIGH POWER

THE 2-PIPE GAS DRIVEN VRF WITH AN ELECTRICAL POWER GENERATOR

ECO G High Power is a revolution in air conditioning design. Fitted with a permanent magnet, non-bearing type generator, it is the first VRF system that can supply heating, cooling, hot water and now also supply electrical power. Each ECO G High Power unit has a 2.0 kW generator, drastically reducing the outdoor unit’s electricity consumption.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

TECHNICAL ZOOM

· 2-PIPE AIR CONDITIONING SYSTEM PROVIDING COOLING OR HEATING

· UP TO 2 kW ELECTRICITY GENERATED (USED ON THE OUTDOOR UNIT)

· VERY EFFICIENT GENERATOR

· CAN CONNECT TO UP TO 24 INDOOR UNITS

· IU/OU CAPACITY RATIO 50–200%

· 15 TO 30 kW HOT WATER GENERATION CAPACITY

HP

MODEL NAME

Cooling capacity

Hot water (cooling mode)

Power Input

EER

Max COP (inc hot water)

Gas consumption kW

Heating capacity STD / Low temp¹ kW

Power Input

COP kW kW kW kW

16 HP

U-16GEP2E5

45.00

15.0

0.1 (220~230) 0.36 (240)

31.3

50.0 / 53.0

0.1 (220~230) 0.36 (240)

Gas consumption STD / Low temp¹ kW

COP Average

Size Height

Width mm mm

33.8

2,273

1,650

Weight

Starter amperes

Depth

Pipe Connections Gas

Liquid mm kg

A

1,000 (+80)

770

30

Inches (mm) 1 1/8 (Ø 28.58)

Inches (mm) 1/2 (Ø 12.70)

Fuel gas

Exhaust drain port mm

R3/4 (bolt thread)

Ø 25

Operation sound

Indoor/outdoor capacity ratio dB(A) 57

50-200%¹

Number of connections indoor² 24

1) Low temp condition: outdoor temperture 2 °C.

2) Indoor unit can be connected to up to 16 kW model (model size 60)

20 HP

U-20GEP2E5

56.00

20.0

0.1 (220~230) 0.36 (240)

41.4

63.0 / 67.0

0.1 (220~230) 0.36 (240)

43.9

2,273

1,650

1,000 (+80)

795

30

1 1/8 (Ø 28.58)

5/8 (Ø 15.88)

R3/4 (bolt thread)

Ø 25

58

50-200%¹

24

GLOBAL

REMARKS

Rated conditions: Cooling

Indoor air temperature 27 °C DB / 19°C WB

Outdoor air temperature 35 °C DB

Heating (standard)

20 °C DB

7 °C DB / 6 °C WB

Heating (low temp.)

20 °C DB / 15 °C WB or less

2 °C DB / 1 °C WB

Cooling and heating capacities in the tables are determined under the test conditions of JIS B 8627.

Effective heating requires that the outdoor air intake temperature be at least –20 °C DB or –21 °C WB.

DB: Dry Bulb; WB: Wet Bulb

· Gas consumption is the total (high) calorific value standard.

· Outdoor unit operating sound is measured 1 meter from the front and 1.5 meters above the floor (in an anechoic environment).

Actual installations may have larger values due to ambient noise and reflections.

· Values in parentheses () for refrigerant gas and liquid types are those when the maximum piping length exceeds 90 meters

(equivalent length). (Reducers are available locally.)

· Specifications are subject to change without notice.

· Hot water heating capacity is applicable during cooling operation as in Note 1.

· The maximum water temperature that can be obtained is 75 °C. Water heating performance and temperature vary with the air conditioning load. Because the hot water heating system uses waste heat from the engine, which runs the air conditioning, its ability to heat water is not guaranteed.

88

SERVICE KITS MODEL

Outdoor unit reference

MATERIAL INCLUDED

Oil Filter

Air Cleaner Element

Plug

V BELT (for compressor)

V Belt (for generator)

Oil Strainer

Drain Filter Packing

25 HP

U-25GEP2E5

71.00

30.0

0.1 (220~230) 0.36 (240)

63.5

80.0 / 78.0

0.1 (220~230) 0.36 (240)

55.1

2,273

1,650

1,000 (+80)

825

30

1 1/8 (Ø 28.58)

5/8 (Ø 15.88)

R3/4 (bolt thread)

Ø 25

62

50-200%¹

24

Specifications subject to change without notice.

1

1

1

4

1

1

1

KIT CZ-PSK560SP

U-16GEP2E5 / U-20GEP2E5 / U-25GEP2E5

NEW

NEW

130 W

ELECTRICITY

CONSUMPTION

VRF SYSTEMS ECO G

More Technical Zoom

· Free Hot water provided when in cooling throughout temperature range and in heating when the ambient is above 7 °C

· 200 m maximum allowable piping length (L1)

* Referring to outside temperature.

New ECO G High Power

GHP with electrical generator. Only consumes 1% of the electricity required by Standard VRF systems!

COMPARISON OF ELECTRICAL

CONSUMPTION ON A 71 kW

OUTDOOR UNIT

Less than

1% of electrical consumption

Generates electricity during heating or cooling operation

Generates electricity and air conditioning (heating or cooling) at the same time by using remaining engine power. ECO G High Power can generate

2.0 kW electricity at a generation efficiency of more than 40%.

18.2 KW

Standard VRF for 73 kW

1.33 KW 0.10 KW

ECO G for 71 kW

ECO G High Power for 71 kW at least 2000

SERVICE CLEARANCES FOR INSTALLATION

Rear (refrigerant tubing) Rear (refrigerant tubing)

9

TOP VIEW

1 Suction refrigerant pipe

2 Liquid refrigerant pipe

3 Exhaust gas drain port

4 Electrical power supply port

5 Inter-unit cable port

6 Fuel gas port

7 Condensation drain opening

8 Rain and condensation outlet

9 Engine exhaust outlet

10 Suspension holes 4-Ø 20x30

11 Anchor holes 4-Ø 22x30

12 Segmented display

13 Coolant intake (top)

14 Vent

15 Hot water inlet

16 Hot water outlet

45.0 kW 56.0-71.0 kW

Ø 28.58

Ø 12.7

Ø 15.88

HOSE OD Ø 25 (accessory)

Ø 28

Ø 28

R3/4

Ø 20

Rp 3/4

Rp 3/4

12

4

5

1

2

Front View Front View at least

100 at least

350

Single-unit installation at least

100 at least

100 at least

350

Multi-unit series Installation

1000

(external)

Ø726

6

14

8

10

8

10

325

1000

(anchor pitch)

11 13

7

153

213

243

329

353

15 16 3

60

422

51

REAR VIEW

1050

(suspension holes)

1080

(frame width)

LEFT SIDE VIEW

1650

(external)

FRONT VIEW

89

High

savings savings

High

ECO G AND ECO G MULTI

2-PIPE HEAT PUMP SYSTEM

ECO G and ECO G Multi 2-Pipe for Heat Pump Applications.

The S Series 2-Pipe not only offers improved performance but also increased flexibility. Now available as multi-systems, many combinations are possible, from 16 HP to 50 HP, allowing for more power and enabling accurate matching of a system building load. Additional new features include part load engine management and compressor run hour equalisation.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

TECHNICAL ZOOM

· REDUCED GAS CONSUMPTION BY MILLER-CYCLE ENGINE

· REDUCED ELECTRICAL POWER CONSUMPTION BY USING DC MOTORS

· NEW LIGHTWEIGHT DESIGN BY USE OF REDUCES WEIGHT

· DIVERSITY RATIO 50-200% (SINGLE MODELS ONLY)

· QUIET MODE OFFERS A FURTHER 2 dB(A) REDUCTION

· PART LOAD EFFICIENCIES INCREASED

HP

MODEL NAME

16 HP 20 HP 25 HP 30 HP 32 HP

U-16GE2E5 U-20GE2E5 U-25GE2E5 U-30GE2E5 U-16GE2E5

U-16GE2E5

36 HP*

U-16GE2E5

U-20GE2E5

40 HP*

U-20GE2E5

U-20GE2E5

45 HP*

U-20GE2E5

U-25GE2E5

50 HP

U-25GE2E5

U-25GE2E5

Cooling capacity

Hot water (cooling mode) kW kW kW

45.00

15.00

56.00

20.00

71.00

30.00

85.00

30.00

90.00

30.00

101.00

35.00

112.00

40.00

127.00

50.00

142.00

60.00

0.71

1.02

1.33

1.70

1.42 1.73 2.04 2.35 2.66

1.48 1.40 1.15 1.22 1.48 1.43 1.40 1.25 1.15 EER

Heating capacity STD Low temp¹

Power Input

COP kW kW kW

Gas consumption STD Low temp¹ kW

COP

Size

Weight

Starter amperes

Average

Height

Width

Depth

Pipe Connections Gas mm mm mm kg

A

1.97 1.89 1.64 1.65 1.97 1.93 1.89 1.74 1.64

29.70

0.60

1.51

32.50 / 41.50

1000 (+80) 1000 (+80) 1000 (+80) 1000 (+80)

1.66

1.48

106.40 / 124.60

1.50 1.43 1.32 1.29 1.50 1.46 1.43 1.36 1.32

2273

1650

1000 (+80)

755

30

39.10

0.64

1.46

42.50 / 56.40

2273

1650

1000 (+80)

780

30

60.40

0.83

1.48

53.20 / 62.30

2273

1650

1000 (+80)

810

30

67.9

1.45

1.37

68.10 / 78.00

2273

2026

1000 (+80)

840

30

59.40 68.80 78.20 99.50 120.80

50.00 / 53.00

63.00 / 67.00

80.00 / 78.00

95.00 / 90.00

100.00 / 106.00 113.00 / 120.00 126.00 / 134.00 143.00 / 145.00 160.00 / 156.00

1.20

1.51

65.00 / 83.00

2273

1650+100+1650 1650+100+1650 1650+100+1650 1650+100+1650 1650+100+1650

755.775

30

1.24

1.48

75.00 / 97.90

2273

755.780

30

1.28

1.46

85.00 / 112.80

2273

780.780

30

1.47

1.47

95.70 / 118.70

2273

780.810

30

2273

1000 (+80)

810

30

Inches (mm) 1 1/8 (Ø 28.58) 1 1/8 (Ø 28.58) 1 1/8 (28.58) 1 1/4 (Ø 31.75) 1 1/4 (Ø 31.75) 1 1/4 (Ø 31.75) 1 1/2 (Ø 38.10) 1 1/2 (Ø 38.10) 1 1/2 (Ø 38.10)

Liquid

Fuel gas

Inches (mm) 1/2 (Ø 12.70) 5/8 (Ø 15.88) 5/8 (Ø 15.88) 3/4 (Ø 19.05) 3/4 (Ø 19.05) 3/4 (Ø 19.05) 3/4 (Ø 19.05) 3/4 (Ø 19.05) 3/4 (Ø 19.05)

R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread) R3/4 (bolt thread)

Exhaust drain port mm

Operation sound

Indoor/outdoor capacity ratio

Number of connections indoor* dB(A)

Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose Ø 25 rubber hose

57 58 62 63 60 61 61 63 65

50-200 %

24

50-200 %

24

50-200 %

24

50-170 %

32

50-130 %

48

50-130 %

48

50-130 %

48

50-130 %

48

50-130 %

48

* In these combinations, GEP2E5 is able to connect to a W-multi system Specifications subject to change without notice instead of a GE2E5.

1 Low temp condition: outdoor temperature 2 °C.

Specifications subject to change without notice.

GLOBAL

REMARKS

Rated conditions: Cooling

Indoor air temperature 27 °C DB / 19°C WB

Outdoor air temperature 35 °C DB

Heating (standard)

20 °C DB

7 °C DB / 6 °C WB

Heating (low temp.)

20 °C DB / 15 °C WB or less

2 °C DB / 1 °C WB

Cooling and heating capacities in the tables are determined under the test conditions of JIS B 8627.

Effective heating requires that the outdoor air intake temperature be at least –20 °C DB or –21 °C WB.

DB: Dry Bulb; WB: Wet Bulb

· Gas consumption is the total (high) calorific value standard.

· Outdoor unit operating sound is measured 1 meter from the front and 1.5 meters above the floor (in an anechoic environment).

Actual installations may have larger values due to ambient noise and reflections.

· Values in parentheses () for refrigerant gas and liquid types are those when the maximum piping length exceeds 90 meters

(equivalent length). (Reducers are available locally.)

· Specifications are subject to change without notice.

· Hot water heating capacity is applicable during cooling operation as in Note 1.

· The maximum water temperature that can be obtained is 75 °C. Water heating performance and temperature vary with the air conditioning load. Because the hot water heating system uses waste heat from the engine, which runs the air conditioning, its ability to heat water is not guaranteed.

90

GHP SERVICE KITS MODEL NAMES KIT CZ-PSK560S

Outdoor unit reference

MATERIAL INCLUDED ON THE KIT

Oil Filter

Air Cleaner Element (Air Filter)

Plug

V BELT (for compressor)

V Belt (for generator)

Oil Strainer

Drain Filter Packing

-

U-16GE2E5 / U-20GE2E5 /

U-25GE2E5

1

1

4

1

1

1

-

KIT CZ-PSK850S

U-30GE2E5

1

1

4

1

1

1

VRF SYSTEMS ECO G

More Technical Zoom

· Connectivity increased - now up to 48 indoor units

· Multi-systems with combinations from 13 HP up to 50 HP

· 200 m maximum allowable piping length (L1)

· Extended pipe runs (total 780 m)

· 10,000 run hours between engine service intervals (equivalent to one maintenance every 3.2 years*)

· Full heating capacity down to -20 °C

· No defrost cycle

· Assuming 3,120 running hours per year - 12 h x 5 days x 52 weeks

* Referring to outside temperature

Sample installation

1 Gas refrigerant pipe

2 Liquid refrigerant pipe

3 Exhaust gas drain port

4 Electrical power supply port

5 Inter-unit cable port

6 Fuel gas port

7 Condensation drain opening

8 Rain and condensation outlet

9 Engine exhaust outlet

10 Suspension holes 4-Ø 20x30

11 Anchor holes 4-Ø 22x30

12 Segmented display

13 Coolant intake (top)

14 Vent

15 Hot water intake

16 Hot water outlet

45 kW 56 - 71 kW 85 kW

Ø 28.58

Ø 31.75

Ø 12.7

Ø 15.88

Ø 19.05

HOSE OD Ø 25 (accessory)

Ø 28

Ø 28

R3/4

Ø 20

Rp3/4

Rp3/4

SERVICE CLEARANCES FOR INSTALLATION

Single-unit installation at least

2000

Rear (refrigerant tubing)

FRONT VIEW

at least

100 at least

350

Multi-unit series Installation

Rear (refrigerant tubing)

12

4

5

1

2

9

U-16GE2E5 // U-20GE2E5 // U-25GE2E5

TOP VIEW

325

1000

(anchor pitch)

1650

11 13

6

FRONT VIEW

at least

100 at least

350

7

153

213

243

329

353

15 16 3

51

REAR VIEW

60

422

14

8

10

1000

(external)

726

1050

(suspension holes)

1080

(frame width)

LEFT SIDE VIEW

8

10

9

U-30GE2E5

TOP VIEW

513 1000

(anchor pitch)

11

2026

13

12

4

5

1

2

6

7

153

213

243

329

353

15 16

51

3

REAR VIEW

60

422

80 150

91

High

savings savings

High

ECO G 3 WAY MULTI

3 WAY HEAT RECOVERY SYSTEM WITH SIMULTANEOUS HEATING & COOLING

The only 3 Way GHP system in Europe, the S Series ECO G 3 Way offers even more performance and outstanding features when you need simultaneous heating and cooling. Now with capacities available from 16 HP to 25 HP, Panasonic offers the greatest choice and flexibility to solve any power problem or site requirement.

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

OPTIONAL

Environmentally

friendly

refrigerant

R410A

TECHNICAL ZOOM

· SIMULTANEOUS HEATING AND COOLING FOR TOTAL CONTROL

· REDUCED GAS CONSUMPTION BY MILLER-CYCLE ENGINE

· REDUCED ELECTRICAL POWER CONSUMPTION BY USING DC MOTORS

· NEW LIGHTWEIGHT DESIGN

· PART LOAD EFFICIENCIES INCREASED

· CONNECTABILITY INCREASED TO UP TO 24 INDOOR UNITS

· 145 m MAXIMUM ALLOWABLE PIPING LENGTH, L1

HP

MODEL NAME

Cooling capacity

Cooling power input

EER

Cooling gas consumption

Heating capacity STD

Low temp*

Heating power input kW kW kW kW kW kW

16 HP

U-16GF2E5

45.00

29.7

50.00

53.00

0.60

20 HP

U-20GF2E5

56.00

0.71

1.02

1.33

1.48 1.40 1.15

39.1

63.00

67.00

0.64

25 HP

U-25GF2E5

71.00

60.4

80.00

78.00

0.83

COP

Heating gas consumption

COP

Size

Weight

Starter amperes

Pipe

STD

Low

Average

H x W x D kW kW

1.51 1.46 1.48

32.5

42.5

53.2

41.5

56.4

62.3

1.50 1.43 1.32 mm kg

2273 x 1650 x 1000 (+80)

775

A 30

Inches (mm) 1 1/8 (Ø 28.58) Gas

Liquid

Discharge

Fuel gas

Inches (mm) 3/4 (Ø 19.05)

Inches (mm) 7/8 (Ø 22.22)

R3/4

Ø 25 Exhaust drain port mm

Operation sound

Indoor/outdoor capacity ratio dB(A) 57

50-200%¹

2273 x 1650 x 1000 (+80)

775

30

1 1/8 (Ø 28.58)

3/4 (Ø 19.05)

1 (Ø 25.40)

R3/4

Ø 25

58

50-200%¹

2273 x 1650 x 1000 (+80)

805

30

1 1/8 (Ø 28.58)

3/4 (Ø 19.05)

1 (Ø 25.40)

R3/4

Ø 25

62

50-200%¹

Number of connected indoor units* 24 24 24

*Low temp condition: outdoor temperture 2 °C.

1 Indoor unit can be connected to up to 16 kW model (model size 60)

Specifications subject to change without notice.

GLOBAL

REMARKS

Rated conditions: Cooling

Indoor air temperature 27 °C DB / 19°C WB

Outdoor air temperature 35 °C DB

Heating (standard)

20 °C DB

7 °C DB / 6 °C WB

Heating (low temp.)

20 °C DB / 15 °C WB or less

2 °C DB / 1 °C WB

Cooling and heating capacities in the tables are determined under the test conditions of JIS B 8627.

Effective heating requires that the outdoor air intake temperature be at least –20 °C DB or –21 °C WB.

DB: Dry Bulb; WB: Wet Bulb

· Gas consumption is the total (high) calorific value standard.

· Outdoor unit operating sound is measured 1 meter from the front and 1.5 meters above the floor (in an anechoic environment).

Actual installations may have larger values due to ambient noise and reflections.

· Values in parentheses () for refrigerant gas and liquid types are those when the maximum piping length exceeds 90 meters

(equivalent length). (Reducers are available locally.)

· Specifications are subject to change without notice.

· Hot water heating capacity is applicable during cooling operation as in Note 1.

· The maximum water temperature that can be obtained is 75 °C. Water heating performance and temperature vary with the air conditioning load. Because the hot water heating system uses waste heat from the engine, which runs the air conditioning, its ability to heat water is not guaranteed.

92

GHP SERVICE KITS MODEL NAME

Outdoor unit reference

MATERIAL INCLUDED ON THE KIT

Oil Filter

Air Cleaner Element (Air Filter)

Plug

V BELT (for compressor)

V Belt (for generator)

Oil Strainer

Drain Filter Packing

-

1

1

4

1

1

1

KIT CZ-PSK560S

U-16GF2E5 / U-20GF2E5 / U-25GF2E5

VRF SYSTEMS ECO G

More Technical Zoom

· Diversity ratio 50–200%

· Extended pipe runs (total 780 m)

· Quiet mode offers a further 2 dB(A) reduction

· Full heating capacity down to -21 °C

· No defrost cycle

· Option of using LPG as a power supply (increases flexibility and avoids problems of potential site restrictions in the future. The purer fuel is also excellent for further reductions in CO

2

emissions)

· 10,000 run hours between engine service intervals (equivalent to one maintenance every 3.2 years*)

· Assuming 3,120 running hours per year - 12 h x 5 days x 52 weeks

Additional parts

SERVICE CLEARANCES FOR INSTALLATION

Rear (refrigerant tubing) Rear (refrigerant tubing)

Solenoid valve controller

3-Pipe control PCB CZ-CAPE2*.

Must be added to the CZ-P56HR3 OR CZ-P160HR3.

KIT-P56HR3 (CZ-P56HR3+CZ-CAPE2), KIT-P160HR3 (CZ-P160HR3+CZ-CAPE2)

* For wall mounted S-22MK2E5/S-28MK2E5/S-36MK2E5.

For S-45MK1E5/S-56MK1E5/S-73MK1E5/S-106MK1E5: CZ-CAPE2.

Solenoid valve kit

CZ-P56HR3 (up to 5.6 kW) CZ-P160HR3 (from 5.7 to 16 kW)

KIT-P56HR3 (CZ-P56HR3+CZ-CAPE2), KIT-P160HR3 (CZ-P160HR3+CZ-CAPE2)

* For conference rooms and other locations where low noise is required, pay attention to the installation location and install in a corridor etc.

10

TOP VIEW

1 Suction refrigerant pipe

2 Discharge refrigerant pipe

3 Liquid refrigerant pipe

4 Exhaust gas drain port

5 Electrical power supply port

6 Inter-unit cable port

7 Fuel gas port

8 Condensation drain opening

9 Rain and condensation outlet

10 Engine exhaust outlet

11 Suspension holes 4-Ø 20x30

12 Anchor holes 4-Ø 22x30

13 Segmented display

14 Coolant intake (top)

15 Vent

45.0 kW 56.0-71.0 kW

Ø 28.58

Ø 22.22

Ø 25.4

19.05

HOSE OD Ø 25 (accessory)

Ø 28

Ø 28

R3/4

Ø 20

Front View Front View at least

100 at least

350

Single-unit installation at least

100 at least

100 at least

350

Multi-unit series Installation

1000 (external)

726

15

325

1000

(anchor pitch)

12 14

13

2

3

5

6

7

9

11

9

11

8

153

183

213

243

353

1 4

51

REAR VIEW

60

422

1050

(suspension holes)

1080

(frame width)

LEFT SIDE VIEW

1650

(external)

FRONT VIEW

93

94

Energy

saving

Environmentally

friendly

refrigerant

R410A

THE NEW PANASONIC SOLUTION FOR

CHILLED AND HOT WATER PRODUCTION!

FROM 28 kW TO 80 kW

Key benefi ts:

· No cascade installation up to 80 kW with GHP outdoor unit and 51.3 kW with ECOi

· No Glycol needed when WHE is located on the heated part of the building

· Full line-up of outdoor units which can cover up to 80 kW heat demand

· Large choice of remote controls and interfaces

· 3.25 COP with water at 45 °C and outdoor temperature of +7 °C

High

savings

Environmentally

friendly

refrigerant

R410A

VRF SYSTEMS

With ECOi outdoor units

· Maximum hot water outlet temperature: 45 °C

· Minimum chilled water outlet temperature: 7 °C

· Outdoor temperature range in cooling mode: +5 °C to +43 °C

· Outdoor temperature range in heating mode: -20 °C to +15 °C

With GHP outdoor units:

· Hot water outlet temperatures from 35 °C to 55 °C

· Chilled water outlet temperatures from 5 °C to 15 °C

· Outdoor temperature range in cooling mode: -10 °C to +43 °C

· Minimum outdoor temperature in heating mode: -21 °C

ECOi Water Heat Exchanger

Electrical VRF with Water Heat Exchanger

· With this easy to install Water Heat Exchanger unit, you can now cover projects up to 51 kW hot water demand or 44 kW on chilled application on a efficient way and cost effective.

ECO G Water Heat Exchanger. Mixed System Application

· Combined with a Water Heat Exchanger unit, the Panasonic GHP can create a flexible system, the ideal replacement for existing chiller and boiler systems.

· The GHP Multi System can have an indoor unit plus a GHP chiller. When the two systems are operated independently, an outdoor unit with 130% capacity can be connected.

SYSTEM EXAMPLE SYSTEM EXAMPLE

Floor Heating

Floor Heating

Fan Coil Unit

ECO G Chiller

Water Heat Exchanger

Buffer Tank

Fan Coil Unit

ECOi Chiller

Water Heat Exchanger

Buffer Tank

Duct*

Refrigerant piping

Water Piping

Outdoor unit

Air Handling Unit

Note: The mode of running of outdoor unit depends on the Water Heat Exchanger’s mode. The water pump is not included in the Water Heat Exchanger unit. For simultaneous operation, however, the maximum capacity is 130%.

Please inquire details of this system design of Panasonic. * Standard DX type indoor unit system.

Outdoor unit

Refrigerant piping

Water Piping

Air Handling Unit

Duct*

Control wiring

Note: The mode of running of outdoor unit depends on the Water Heat Exchanger’s mode. The water pump is not included in the Water Heat Exchanger unit. For simultaneous operation, however, the maximum capacity is 130%.

Please inquire details of this system design of Panasonic. * Standard DX type indoor unit system.

MODEL

Rated capacity

Rated power input

Rated current

Cooling/Heating

Cooling/Heating kW kW

A

S-250WX2E5¹

25 / 30

0.01

0.07

V / Ph / Hz 220-240 / 1 / 50 Power supply

Water volume flow

Pressure loss m³/h kPa

Water volume in heat exchanger / in primary circuit (min) m³

4.3

6.6

0.008 / 0.28

Max. water pressure

Type of anti-freeze protection

MPa 0.686

Flow switch

Dimensions / Weight

Pipe connections

Power supply wire diameter

Communication wire (LIYCY)

Fuse size (slow-blow)

H x W x D mm / kg 1,000 x 395 x 965 / 110

Gas pipe / Liquid pipe mm

Max. piping length

Max. height difference IU above OU / OU above IU m m mm² mm²

A

22.22 / 9.52

170³

35³ 5 / 50³

S-500WX2E5

50 / 60

0.01

0.07

220-240 / 1 / 50

8.6

9.6

0.012 / 0.5

0.686

1,000 x 395 x 965 / 130

28.58 / 15.88

170³

35³ 5 / 50³

S-710WX2E5²

71 / 80

0.01

0.07

220-240 / 1 / 50

12.2

11.7

4

0.017 / 0.73

0.686

1,000 x 395 x 965 / 150

31.75 / 19.05

170³

35³ 5 / 50³

2 x 2.0

2 x 2.0

2 x 2.0

2 x 0.5~2.0 (total length up to 1,000 m) 2 x 0.5~2.0 (total length up to 1,000 m) 2 x 0.5~2.0 (total length up to 1,000 m)

15 15 15

1. Only with indoors combination. Can not be used as 1 to 1.

2. Only connectable with GHP.

3. Not valid in case of mixed systems, combination ratio in case of mixed systems: 50 to 130 %, combination ratio in case of one-to-one-systems: 100 %.

4. Water circulating pump. Power supply: 230 V / 1 Ph / 50 Hz; power input: 0.75 kW; external pressure head: 6 m.

5. For cooling operation where the outdoor air temperature is 10 °C or less, this value should be 30 m.

95

Energy

saving saving

Energy

NEW ECOi 2-PIPE WITH WATER HEAT EXCHANGER FOR

CHILLED AND HOT WATER PRODUCTION

FOR HYDRONIC APPLICATIONS

New Water Heat Exchanger for GHP and ECOi, dimensions reduced by 45 %. Operation and control by wired remote control CZ-RTC2. Energy-efficient capacity control.

Stainless steel plate heat exchanger with anti-freeze protection control. Change-over between heating and cooling operation

Environmentally

friendly

refrigerant

R410A

TECHNICAL ZOOM

· MAXIMUM DISTANCE BETWEEN OUTDOOR UNIT AND WATER

HEAT EXCHANGER: 170 m

· MAXIMUM HOT WATER OUTLET TEMPERATURE: 45 °C

· MINIMUM CHILLED WATER OUTLET TEMPERATURE: 7 °C

· OUTDOOR TEMP. RANGE IN COOLING MODE: +5 °C TO +43 °C

· OUTDOOR TEMP. RANGE IN HEATING MODE: -20 °C TO +15 °C

WATER HEAT EXCHANGER

Nominal Cooling Capacity

Nominal Heating Capacity

Heating Capacity at +7°C, heating water temperature at 45 °C

COP at +7°C with heating water temperature at 45 °C

Dimensions / Weight H x W x D

Water pipe connector

Pump

Heating water flow (ΔT=5 K. 35 °C)

Capacity of integrated electric heater

Input Power

Maximum Current

OUTDOOR UNIT

Sound pressure / Sound power level

Dimensions Weight

Pipe Diameter

Refrigerant (R410A)

Pipe Length Range

Pipe Length for nominal capacity

Pipe Length for additional gas

Additional Gas Amount (R410A)

I/D&O/D Hight Difference

Operation Range

H x W x D

Liquid / Gas kW l/min kW kW

A

S-250WX2E5*

25.0

28.0

28.0

3.25 mm / kg 1,000 x 395 x 965 / 165

Rp2 Nut thread (50A)

(Field supply)

4.3

(Not equipped)

0.01

0.07

U-10ME1E81

dB(A) / dB 59 / 73.5

m m g/m m mm / kg 1,758 x 770 x 930 / 283 mm (Inch) 22.22 / 9.52

kg m

6.3 *Need Additional charge at site max. 170

Outdoor Ambient °C

Water Outlet (at-2/-7/-15) 2) °C

7.5

0 <

Reffer to Manual

50 (OD above) 35 (OD below)

-20 — 15

35 — 45

S-500WX2E5

50.0

51.3

51.3

3.10

1,000 x 395 x 965 / 190

Rp2 Nut thread (50A)

(Field supply)

8.6

(Not equipped)

0.01

0.07

U-20ME1E81

63 / 77.5

1,758 x 1,540 x 930 / 423

28.58 / 15.88

9.0 *Need Additional charge at site max. 170

7.5

0 <

Reffer to Manual

50 (OD above) 35 (OD below)

-20 — 15

35 — 45

All values shown as tentative data.

Performance calculation in agreement with Eurovent.

Sound pressure measured at 1 m from the outdoor unit and at 1.5-m height.

* Only with indoors combination. Can not be used as 1 to 1.

Rating Conditions: Cooling Indoor 27 ºC DB / 19 ºC WB. Cooling Outdoor 35 ºC DB / 24 ºC WB. Heating Indoor 20 ºC DB. Cooling Outdoor 7 ºC DB / 6 ºC WB.

DB: Dry Bulb; WB: Wet Bulb

96

Newly Slim & Light design

Due to the unit’s internal redesign, the width and weight are drastically reduced.

50 mm or over

50 mm or over

50 mm or over

300 mm or over

INSTALLATION

SPACE

45

%

REDUCTION

Standard system example

Water Heat Exchanger

Refrigerant Piping

Water Piping

Outdoor unit

900 mm 495 mm

TOP VIEW

Connecting cable openings

Liquid pipe (brazed)

Ø19.05 (710WX2E5)

Ø15.88 (500WX2E5)

Ø 9.52 (250WX2E5)

REAR VIEW

4-Ø24

(for anchor holes)

Hot/cold water inlet

(Rp2 female thread) (50 A)

1014

(anchor hole pitch)

LEFT SIDE VIEW

965

(external cladding)

Gas pipe (brazed)

Ø31.75 (710WX2E5)

Ø28.58 (500WX2E5)

Ø22.22 (250WX2E5)

Drain opening

(R1 male thread) (25 A)

140

208.5

272

Hot/cold water inlet

(Rp2 female thread) (50 A)

1006

(suspension holes pitch)

1060

(frame width)

Transmitter box

FRONT VIEW

395

(external cladding) at least

50

4-Ø30 suspension holes

417

(frame width) at least

50

97

High

savings savings

High

NEW ECO G WITH WATER HEAT EXCHANGER FOR CHILLED

AND HOT WATER PRODUCTION

FOR HYDRONIC APPLICATIONS

New Water Heat Exchanger, dimensions reduced by 45 % (250 W x 2 and 500 W x 2).

Operation and control by wired remote control CZ-RTC2. Energy-efficient capacity control. Stainless steel plate heat exchanger with anti-freeze protection control.

Change-over between heating and cooling operation.

Environmentally

friendly

refrigerant

R410A

TECHNICAL ZOOM

· MAXIMUM DISTANCE BETWEEN O_U AND WHE: 170 m

· POSSIBILITY TO MIX DX AND WATER HEAT EXCHANGER SYSTEMS

· NO COOLING TOWER NECESSARY

· HOT WATER OUTLET TEMPERATURES FROM 35 °C TO 55 °C

· CHILLED WATER OUTLET TEMPERATURES FROM 5 °C TO 15 °C

· OUTDOOR TEMP. RANGE IN COOLING MODE: -10 °C TO +43 °C

· MINIMUM OUTDOOR TEMPERATURE IN HEATING MODE: -21 °C

WATER HEAT EXCHANGER

Nominal Heating Capacity

Heating Capacity at +7 °C, heating water temperature at 35 °C

COP at +7 °C with heating water temperature at 35 °C

Heating Capacity at +7 °C, heating water temperature at 45 °C

COP at +7 °C with heating water temperature at 45 °C

Heating Capacity at -7 °C, heating water temperature at 35 °C

COP at -7 °C, heating water temperature at 35 °C

Heating Capacity at -15 °C, heating water temperature at 35 °C

COP at -15 °C with heating water temperature at 35 °C

Nominal Cooling Capacity

Cooling capacity at +35 °C, outlet tp 7 °C, inlet tp 12 °C

EER at +35 °C, outlet tp 7 °C, inlet tp 12 °C

Dimensions / Weight H x W x D

Water pipe connector

Pump

Heating water flow (ΔT=5 K. 35 °C)

Capacity of integrated electric heater

Input Power

Maximum Current

OUTDOOR UNIT

Sound pressure / Sound power level

Dimensions / Weight

Pipe Diameter

Refrigerant (R410A)

Pipe Length Range

Pipe Length for nominal capacity

Pipe Length for additional gas

Additional Gas Amount (R410A)

I/D&O/D High Difference

Operation Range kW kW kW kW kW

S-250WX2E5*

30

30

25

H x W x D

Liquid / Gas m g/m

Outdoor Ambient m

°C

Water Outlet (at-2/-7/-15) 2) °C mm / kg 1,000 x 395 x 965 / 110

Rp2 Nut thread (50A) l/min kW kW

A

(Field supply)

4.3

(Not equipped)

0.01

-

0.07

dB(A) / dB mm / kg m m mm (Inch) kg

50 (OD above) 35 (OD below)

S-500WX2E5

60

62

1.49

60

1.30

57.2

0.76

59.2

0.75

50

50

1.15

1,000 x 395 x 965 / 130

Rp2 Nut thread (50A)

(Field supply)

80

1.17

74.6

0.77

S-710WX2E5

80

82,8

1.34

77.4

0.76

71

71

1.05

1,000 x 395 x 965 / 150

Rp2 Nut thread (50A)

(Field supply)

8.6

(Not equipped)

0.01

0.07

U-20GE2E5

58 / 83

12.2

(Not equipped)

0.01

0.07

U-30GE2E5

63 / 86

2,273 x 1,650 x 1,000 / 780

28.58 / 15.88

2,273 x 2,026 x 1,000 / 840

31.75 / 19.05

11.5 *Need additional chatge at site 11.5 *Need additional chatge at site max. 170 max. 170

7

0<

Refer to Manual

50 (OD above) 35 (OD below)

-21 — 15.5

35 — 55

7

0<

Refer to Manual

50 (OD above) 35 (OD below)

-21 — 15.5

35 — 55

All values shown as tentative data.

Performance calculation in agreement with Eurovent.

Sound pressure measured at 1 m from the outdoor unit and at 1.5 m height.

* Only with indoors combination. Can not be used as 1 to 1.

Rating Conditions: Cooling Indoor 27 ºC DB / 19 ºC WB. Cooling Outdoor 35 ºC DB / 24 ºC WB. Heating Indoor 20 ºC DB. Cooling Outdoor 7 ºC DB / 6 ºC WB.

DB: Dry Bulb; WB: Wet Bulb

98

VRF SYSTEMS

Combination system example

The GHP multi system can have indoor units with a GHP chiller. When the two systems are operated independently, an outdoor unit with 130% capacity can be connected.

Standard system example

Water Heat Exchanger

Water Piping

Outdoor unit

Connecting cable openings

Liquid pipe (brazed)

Ø19.05 (710)

Ø15.88 (500)

Ø9.52 (250)

TOP VIEW

4-Ø24

(for anchor holes)

REAR VIEW

Hot/cold water intlet

(Rp2 female thread) (50A)

1014

(anchor hole pitch)

LEFT SIDE VIEW

965

(external cladding)

Transmitter box

FRONT VIEW

395

(external cladding) at least

50

Refrigerant piping side at least

50

Gas pipe (brazed)

Ø31.75 (710)

Ø28.58 (500)

Ø22.22 (250)

Drain opening

(R1 male thread) (25A)

140

208.5

272

Hot/cold water outlet

(Rp2 female thread) (50A)

1006

(suspension holes pitch)

1060

(frame width)

417

(frame width)

4-Ø30

(suspension holes)

99

NEW AQUAREA AIR

RADIATORS

High efficiency climate control High Efficiency Radiators

Aquarea Air radiators are extremely slim. With a depth of just under 13 cm they are at the cutting edge of the market. Blending easily into the home, Aquarea Air’s elegant design, and product refinements are clear to see in every detail.

Its particular slimness has been obtained thanks to the innovative layout of the ventilation unit and the heat exchanger. The fan is tangential with asymmetric blades and the heat exchanger has large surface, enabling high airflows to be achieved with low pressure loss and and low noise levels. Exceptional ventilation efficiency means the motor uses considerably less energy (low wattage). The fan speed is continuously modulated by the temperature controller with proportional integral logic, with undoubted advantages for regulating the temperature and humidity in summer mode.

WATER AT

35°C

NEEDED

2.0

kW

WITH AQUAREA AIR

WITH STANDARD CAST

RADIATORS

2.0

kW

WATER AT

65°C

NEEDED

Fan Coils for Heat Pump application PAW-AAIR-200

Total heating capacity

Water flow

W kg/h

138

23.7

160

27.5

Water pressure drop

Air flow

Maximum input power

Sound pressure level

Inlet water temperature

Outlet water temperature °C

Inlet air temperature °C

Outlet air temperature

Dimentions (H x W x D) kPa m³/h

Speed

W dB(A)

°C

°C mm kg

0.1

28

17.6

35

30

19

34.5

0.2

37

18.8

35

30

19

32.6

735 x 576 x 129

217

37.3

0.4

55

Main Fan Off Super Min Min

2 5 7

24.7

35

30

19

38.9

Weight

3 ways valve included

Touch schreen thermostat

17

Yes

Yes

33.2

35

30

19

32.0

470

80.8

2.0

113

Med

9

39.4

35

30

19

30.0

570

98.0

2.9

162

Max

13

18.4

35

30

19

PAW-AAIR-700

223

38.4

360

61.9

708

121.8

0.1

44

0.1

84

0.3

155

Main Fan Off Super Min Min

3 9 14

25.8

35

30

19

33.3

34.9

32.4

935 x 579 x 129

20

Yes

Yes

19.6

35

30

19

34.1

35

30

19

31.8

1032

177.5

0.8

252

Med

18

40.2

35

30

19

30.6

1188

204.3

1.0

320

Max

22

18.4

35

30

19

PAW-AAIR-900

273

47.0

475

81.7

886

152.4

0.1

54

0.2

110

0.5

248

Main Fan Off Super Min Min

3 11 16

26.2

35

30

19

30.2

34.8

32.5

1135 x 579 x 129

23

Yes

Yes

22.3

35

30

19

34.4

35

30

19

31.1

1420

244.2

1.6

367

Med

20

42.2

35

30

19

30.6

1703

292.9

2.2

461

Max

24

Front panel with a radiant effect

Dc fan motor for high efficiency

During winter, the operating principle is based on micro fans of very low power consumption and minimum noise that send hot air, coming from the heat exchanger, to the inside of the front panel of the device and therefore heat it effectively. With this principle, the terminal also provides significant power while heating, without running the main fan. Comfort temperatures therefore maintained, without air movements and in silence. In summer mode, the airflow generated by the micro fans is stopped to avoid any dew formation on the terminal’s front surface.

100

Very silent and efficient

DC fan motor

Filter Drain for cooling mode operation

VRF SYSTEMS

NEW

NEW

PAW-AAIR-900 PAW-AAIR-700 PAW-AAIR-200

New line up of Super low temperature radiators for Heat Pump application:

Aquarea Air 200/700/900 with radiating effect

Main features

· Front panel heating with radiant effect

· High heating capacity (without main fan running)

· 4 fan speeds and capacities

· Exclusive design

· Extremely compact (only 12.9 cm deep)

· Cooling and dehumidification functions possible (drain is needed)

· 3-way valve included (no overflow valve needed on the installation if more than 3 radiators installed)

· Touch screen thermostat

Operating on heating mode with radiator using only radiant effect

Operating on heating mode with radiant effect and fan mode

A

129

Operating on cooling mode with fan

A

200R 700R 900R

735 935 1135

101

FEATURES

High technology features

Down to

-25 ºC

in heating mode

OUTDOOR

TEMPERATURE

Wider operation

Cooling can be performed throughout the year for computer rooms, banquet halls, etc. Wider operation range covers outdoor temperatures of as low as -10 °C DB for cooling and

-21 °C WB for heating.

45

40

43

Cooling

RATED CONDITION

Heating

35

25

30

20

10

15.5

25

20

5

10

0

5

-5

0

-10

-5

-15

-10

14

10 15 20 25 30

-20

-21

27

10 15 20 25 30

Indoor air intake temp. °C (WB)

Practical

operation

AUTOMATIC RESTART

Automatic restart function for power failure

Even when power failure occurs, preset programmed operation can be reactivated once power is resumed.

Easy

maintenance

SELF-DIAGNOSING

Self-diagnosing function

By using electronic control valves past warnings are stored and can be verified on the liquid crystal display. This makes it easier to diagnose malfunctions, greatly reducing service labour and therefore costs.

Simple, convenient features (Indoor Units)

For more

comfort

AUTOMATIC FAN

Automatic fan operation

Convenient microprocessor control automatically adjusts fan speed to High, Medium or Low, corresponding to room sensor and maintains comfortable airflow throughout the room.

Comfort

everywhere

AIR SWEEP

Air Sweep

The air sweep function moves the flap up and down in the air outlet, directing air in a “sweeping” motion around the room and providing comfort in every corner.

Perfect

humidity control

MILD DRY

Mild dry

By intermittent control of compressor and indoor unit’s fan,

“New Mild Dry” gives you comfort. It realizes efficient dehumidification according to room temperature.

Easy

to install

BUILT-IN

DRAIN PUMP

Further

comfort

AUTO-FLAP

CONTROL

Built-in drain pump

Maximum head 50 cm (or 75 cm for U type) from the bottom of the unit.

Comfortable auto-flap control

When the unit is first

Auto flap section turned on, flap position is automatically adjusted inn accordance with the cooling or heating operation. This initial flap position can be preset within a certain range, for both cooling and heating. Auto button is included for continuous movement of flap to vary airflow direction.

Maintenance and inspection is a must for gas heat pump airconditioning systems.

Just like an automobile, a heat pump air-conditioning system requires periodic servicing so that it can perform efficiently.

Maintenance and inspection

Fixing problems

Preserving durability

Energy saving

Efficient operation

Safe and reliable operation

Main maintenance and inspection items

1. Changing the engine oil

2. Checking the coolant level

3. Inspecting the engine system

4. Checking the safety protection system

5. Checking and adjusting the running conditions, collecting operating data, etc.

Since a heat pump air-conditioning system uses a gas engine as its power source, it should be periodically inspected to avoid trouble and keep it running efficiently. We recommend a maintenance contract for your

Panasonic Gas Heat Pump, a great value because it not only ensures that problems will be fixed, but it helps reduce running costs and improve comfort and economical efficiency as well.

102

VRF SYSTEMS

PANASONIC’S DIAGNOSIS SOFTWARE

GHP Checker Software

The handy tool for optimising the running of your system:

Diagnosis for start ups, maintenance and system supervising.

Features:

· Diagnosis with a PC

· Endless recording function allows analysis diagnosis even for long term running

· The GHP checker software needs no additional communication adaptor

· The communication between the PC and GHP is done by RS232

Panasonic VRF Service Checker

Panasonic will make available to installers and commissioning companies the VRF Service Checker as a communication interface to Panasonic VRF systems. This easy to manage tool checks all parameters of the system.

The VRF Service Checker allows:

· On ECOi and Mini ECOi connect anywhere on the P-Link.

· Search the P-Link to validate systems that are connected.

· Monitor of all indoor and outdoor units simultaneously on 1 screen.

· Monitor all Temperature data, Pressure data , Valve position, and alarm status on 1 screen

· Data can be viewed in Graph or number format.

· Controlling the indoor unit ON/OFF, MODE, SET POINT, FAN, and TEST mode.

· Switching between various systems on same communication P-Link (ECOi only).

· Monitor and record at a set interval time.

· Record and review the data at a later date.

· Update software as ROM flash writer.

This Panasonic VRF Service Checker is available on your service partner.

INTERFACE BOX:

103

104

INDOOR UNITS FOR ECOi,

MINI ECOi AND ECO G

WIDE CHOICE OF MODELS DEPENDING

ON THE INDOOR REQUIREMENTS

VRF SYSTEMS

4 Way 90x90 Cassette

Wide & Comfortable Airflow

This proprietary design has wide-angle discharge outlets and flaps are larger in the middle, featuring a shape based on a combination of geometrics and the testing of prototype units. Air coming out of the center of the discharge outlets travels farther. From the sides of each outlet, where the openings are larger, airflow spreads out to reach the corners of the room. Air is discharged across a wide area from the four sides of the unit.

The curves on the room temperature distribution graph expand gently out through 360° in a circle centered on the indoor unit.

HIGH-EFFICIENT & SILENT TURBO FAN.

It is realized more air volume and more silent due to new development of a bigger fan chassis than previous one and optimization design of airflow path.

HIGHER EFFICIENCY SPLIT FIN.

Improved heat-transfer coefficient due to adoption of high efficiently grooved heat exchanger tube.

NEW DC-FAN MOTOR.

It is realized more optimum air-flow by a new DC-fan motor with independent control.

INDIVIDUAL FLAP CONTROL.

Flexible Air flow direction control by individual flap control is possible. 4 Flaps can be controlled individually by setting on wired timer remote controller.

Several demands can be accommodated in one space.

360º

air flow

Flexible 3D air-flow control

Comfort air flow control & proper energy use. Flexible Air flow direction control by individual flap control:

· 4 Flaps can be controlled individually (by standard wired remote controller*).

· It can make more flexible Air-flow control to be matched to several demands can be accommodated in one space.

New 360º Air Flow for better comfort

By the new Design for the air-outlet and flap, Soft & 3D air flow circulates whole space and it keeps flat temperature distribution in the room.

CURRENT MODEL 360º AIR FLOW

IT’S COLD IT’S HOT

1 m above the floor

25.0

Temp.

Simulated condition: Floor area: 225 m². Ceiling height: 3 m, Unit 5 HP type.

CURRENT MODEL

OUTLET C:

SWING OUTLET D:

FIXED TO LOWER

OUTLET B:

FIX TO UPPER

OUTLET A:

SWING (ONLY

UPPER)

* It needs pre-setting for this function at

System Test-run procedure.

More even temperature in the room.

New design

Wide direction air discharge by outlet design.

The Circle Flow Flap and redesigned air outlet eliminate airflow along recessed parts on the ceiling to reduce contamination. If air flows only along these recessed parts, they will quickly become dirty. These new features greatly reduce accumulations of dirt.

Dirt collects on the ceiling

Airflow of conventional models

Airflow image from the new model

360º AIR FLOW

105

VRF SYSTEMS INDOOR UNITS RANGE

2.2 kW

U1 TYPE // 4-WAY 90x90

CASSETTE

S-22MU1E51

Y1 TYPE // 4-WAY 60x60

CASSETTE

L1 TYPE // 2-WAY CASSETTE

S-22MY1E51

2.8 kW

S-28MY1E51

3.6 kW

S-28MU1E51 S-36MU1E51 S-45MU1E51

S-36MY1E51

4.5 kW

S-45MY1E51

5.6 kW 6.0 kW 7.3 kW

S-56MU1E51 S-60MU1E51 S-73MU1E51

S-56MY1E51

8.4 kW 9.0 kW

S-90MU1E51

D1 TYPE // 1-WAY CASSETTE

S-22ML1E5 S-28ML1E5 S-36ML1E5 S-45ML1E5 S- 56ML1E5 S-73ML1E5

S-28MD1E5 S-36MD1E5 S-45MD1E5

F2 TYPE // VARIABLE STATIC

PRESSURE HIDE AWAY

S-22MF2E5 S-28MF2E5 S-36MF2E5 S-45MF2E5

M1 TYPE // SLIM VARIABLE

STATIC PRESSURE HIDE

AWAY

S-22MM1E51 S-28MM1E51 S-36MM1E51 S-45MM1E51

E1 TYPE // HIGH STATIC

PRESSURE HIDE AWAY

S-56MD1E5

S-56MF2E5

S-56MM1E51

S-60MF2E5

S-73MD1E5

S-73MF2E5 S-90MF2E5

T1 TYPE // CEILING

S-36MT1E5 S-45MT1E5

K2/K1 TYPE // WALL

MOUNTED

P1 TYPE // FLOOR STANDING

S-22MK2E5¹

S-22MK1E5²

S-28MK2E5¹

S-28MK1E5²

S-36MK2E5¹

S-36MK1E5² S-45MK1E5

S-56MT1E5

S-56MK1E5

R1 TYPE // CONCEALED

FLOOR STANDING

S-22MP1E5 S-28MP1E5 S-36MP1E5 S-45MP1E5 S-56MP1E5

S-22MR1E5 S-28MR1E5 S-36MR1E5 S-45MR1E5 S-56MR1E5

AHU CONNECTION KIT,

28 kW AND 56 kW FOR

ECOi AND GHP

AIR CURTAIN JET-FLOW

CZ-280MAH1 CZ-560MAH1

S-73MT1E5

S-73MK1E5

S-71MP1E5

S-71MR1E5

CZ-280MAH1 +

CZ-560MAH1

AIR CURTAIN STANDARD

Wide choice of models depending on the indoor requirements. 1 Available from June 2013. 2 Available until current stock ends.

106

VRF SYSTEMS

10.6 kW 11.2 kW 12.5 kW 14.0 kW 16.0 kW 16.8 kW 20.0 kW 22.4 kW 25.0 kW 28.0 kW 30.0 kW

S-106MU1E51 S-140MU1E51 S-160MU1E51

S-106MF2E5 S-140MF2E5 S-160MF2E5

S-224ME1E5A S-280ME1E5

S-106MT1E5

S-106MK1E5

S-140MT1E5

CZ-560MAH1 x 2

PAW-10EAIRC-MJ

PAW-10EAIRC-MS

CZ-280MAH1 +

CZ-560MAH1 x 2 CZ-560MAH1 x 3

PAW-15EAIRC-MJ

PAW-20EAIRC-MS

PAW-20EAIRC-MJ PAW-25EAIRC-MJ

107

U1 TYPE

4-WAY 90X90 CASSETTE

SEMI CONCEALED CASSETTE

360º

air flow

The award winning range of U1 type cassettes are smaller, shallower and lighter than previous models and feature a 950 x 950 mm panel throughout. The DC fan motor and air discharge louvre ensure quiet, optimum air distribution.

Technical focus

· Compact design

· Reduced sound levels (from previous models)

· DC fan motor for increased efficiency

· Powerful drain pump gives 850 mm lift

· Lightweight design

· Fresh air knockout

· Branch duct connection

· Optional air-intake plenum CZ-FDU2

1

2

Air intake chamber

1. Air intake box CZ-BCU2 for main unit.

2. Air intake box CZ-ATU2* for Air intake plenum.

* When using Air intake box (CZ-ATU2), Air intake plenum (CZ-FDU2) is required.

A drain height of approx. 850 mm from the ceiling surface

The drain height can be increased by approximately 350 mm over the conventional value by using a high-lift drain pump, and long horizontal piping is possible.

Up to 350 mm

Up to 850 mm

Drain Pump of about

850 mm from the ceiling surface

PANEL

CZ-KPU2

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSU2

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current kW

W

A kW

W

A

Fan Type

Air flow rate (Hi) m³/h

Sound pressure level (L/M/H) dB(A)

Dimensions

Net weight

H x W x D

Pipe connections Liquid

Gas

Drain piping

S-22MU1E51 S-28MU1E51 S-36MU1E51 S-45MU1E51 S-56MU1E51 S-60MU1E51 S-73MU1E51 S-90MU1E51 S-106MU1E51 S-140MU1E51 S-160MU1E51

230 V / 1 phase / 50 Hz

2.2

20

0.19

2.5

20

0.17

2.8

20

0.19

3.2

20

0.17

3.6

20

0.19

4.2

20

0.17

4.5

20

0.19

5.0

20

0.17

5.6

25

0.22

6.3

25

0.20

6.0

35

0.31

7.1

35

0.30

7.3

40

0.33

8.0

40

0.32

9.0

40

0.36

10.0

40

0.34

10.6

95

0.71

11.4

85

0.65

14.0

100

0.76

16.0

100

0.73

16.0

115

0.89

18.0

105

0.80

Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan Turbo fan

840 840 840 900 960 1,260 1,320 1,380 1,980 2,100 2,160

28/29/30 28/29/30 28/29/30 28/29/31 28/30/33 29/32/36 29/32/37 32/35/38 34/38/44 35/39/45 38/40/46 mm 256 (+33.5) x 840 (950) x 840 (950) 319 (+33.5) x 840 (950) x 840 (950) inches (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) inches (mm) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 1/2 (12.7) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 VP-25 kg 23 23 23 23 23 24 24 24 27 27 27

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

108

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

VRF SYSTEMS

Y1 TYPE

4-WAY 60X60 CASSETTE

MINI SEMI CONCEALED

CASSETTE

Designed to fit exactly into a 600 x 600 mm ceiling grid without the need to alter the bar configuration, the Y1 is ideal for small commercial and retrofit applications. In addition, the improvements to efficiency make this one of the most advanced units in the industry.

Technical focus

· Mini cassette fits into a 600x600 mm ceiling grid

· Fresh air knock out

· Multidirectional air flow

· Anti-mould and anti-bacteria washable filters

· Powerful drain pump gives 850 mm lift

· Turbo fans and heat exchanger fins with improved design

· DC fan motors with variable speed, new heat exchangers, etc. ensure an efficient power consumption

Special designed flap

The flap can be removed easily for washing with water.

A drain height of approx. 850 mm from the ceiling surface

The drain height can be increased by approximately 350 mm over the conventional value by using a high-lift drain pump, and long horizontal piping is possible.

Up to 350 mm

A lightweight unit at 18.4 kg the unit is also very slim with a height of only 283 mm, making installation possible even in narrow ceilings.

Up to 283 mm

Up to 850 mm

Drain Pump of about

850 mm from the ceiling surface

PANEL

CZ-KPY21

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSU2

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Sound pressure level (L/M/H)

Dimensions H x W x D

Pipe connections Liquid

Net weight

Gas

Drain piping dB(A) mm

S-22MY1E51

2.2

25

0.16

2.5

15

0.13

Centrifugal fan

480 / 420 / 360

25 / 27 / 30 inches (mm) 1/4 (6.35) inches (mm) 1/2 (12.7)

S-28MY1E51

2.8

25

0.16

3.2

15

0.13

Centrifugal fan

480 / 420 / 360

25 / 27 / 30

283+(30) x 575 (625) x 575 (625) 283+(30) x 575 (625) x 575 (625) 283+(30) x 575 (625) x 575 (625) 283+(30) x 575 (625) x 575 (625) 283+(30) x 575 (625) x 575 (625)

1/4 (6.35)

1/2 (12.7)

S-36MY1E51

230 V / 1 phase / 50 Hz

3.6

27

0.18

4.2

17

0.15

Centrifugal fan

540 / 480 / 420

26 / 29 / 32

1/4 (6.35)

1/2 (12.7)

S-45MY1E51

4.7

31

0.21

5.0

21

0.18

Centrifugal fan

640 / 510 / 450

28 / 32 / 36

1/4 (6.35)

1/2 (12.7)

S-56MY1E51

5.6

38

0.29

6.3

29

0.26

Centrifugal fan

750 / 630 / 540

33 / 37 / 41

1/4 (6.35)

1/2 (12.7) kg

VP-20

18.4

VP-20

18.4

VP-20

18.4

VP-20

18.4

VP-20

18.4

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

109

L1 TYPE

2-WAY CASSETTE

Slim, compact and lightweight units. Remarkable size and weight reductions have been achieved by improvement of the design around the fan, the weight of all models now being 30 kg.

Technical focus

· Airflow and distribution is automatically altered depending on the operational mode of the unit

· Drain up is possible up to 500 mm from the drain port

· Simple maintenance

Simple maintenance

The drain pan is equipped with site wiring and can be removed. The fan case has a split construction, and the fan motor can be removed easily when the lower case is removed.

Airflow and distribution is automatically altered depending on the operational mode of the unit.

auto flap section

20¡

40¡

Cooling/(Fan)

500 mm or less

310 mm

Heating/(Hi,M)

Drain up is possible up to 500 mm from the drain port.

300 mm or less

Maintenance of the drain pump is possible from two sides, from the left side (piping side) and from the inside of the unit.

PANEL

CZ-02KPL2

Big size panel (for S-73ML1E5)

CZ-03KPL2

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSL2

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Sound pressure level (L/M/H)

Dimensions H x W x D dB(A) mm

Pipe connections Liquid

Net weight

Gas

Drain piping

S-22ML1E5

2.2

90

0.45

2.5

58

0.29

Sirocco fan

480 / 420 / 360

S-28ML1E5

2.8

92

0.45

3.2

60

0.29

Sirocco fan

540 / 480 / 420

S-36ML1E5 S-45ML1E5

230 V / 1 phase / 50 Hz

3.6

93

0.45

4.2

61

0.29

Sirocco fan

580 / 520 / 460

4.5

97

0.45

5.0

65

0.29

Sirocco fan

660 / 540 / 480

S-56ML1E5

5.6

97

0.45

6.3

65

0.29

Sirocco fan

660 / 540 / 480

S-73ML1E5

7.3

145

0.65

8.0

109

0.48

Sirocco fan

1,140 / 960 / 840

24 / 27 / 30 26 / 29 / 33 28 / 31 / 34 29 / 33 / 35 29 / 33 / 35 33 / 35 / 38

350+(8) x 840 (1,060) x

600 (680)

350+(8) x 840 (1,060) x

600 (680)

350+(8) x 840 (1,060) x

600 (680)

350+(8) x 840 (1,060) x

600 (680)

350+(8) x 840 (1,060) x

600 (680)

350+(8) x 1,140 (1,360) x 600 (680) inches (mm) 1/4 (6.35) inches (mm) 1/2 (12.7) kg

VP-25

28.5

1/4 (6.35)

1/2 (12.7)

VP-25

28.5

1/4 (6.35)

1/2 (12.7)

VP-25

28.5

1/4 (6.35)

1/2 (12.7)

VP-25

28.5

1/4 (6.35)

1/2 (12.7)

VP-25

28.5

3/8 (9.52)

5/8 (15.88)

VP-25

39

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

110

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

D1 TYPE

1-WAY CASSETTE

Designed for installation within the ceiling void, the D1 range of slimline

1 way blow cassettes feature powerful yet quiet fans for up to 4.2 m.

Technical focus

· Ultra-Slim

· Suitable for standard and high ceilings

· Built-in drain pump provides 590 mm lift

· Easy to install and maintain

· Hanging height can be easily adjusted

· Uses a DC fan motor to improve energy-efficiency

Drain height

300 mm or less

590 mm

VRF SYSTEMS

PANEL

CZ-KPD2

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWST2

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Sound pressure level (L/M/H)

Dimensions H x W x D dB(A) mm

Pipe connections Liquid

Net weight

Gas

Drain piping

0.39

3.2

40

0.35

S-28MD1E5

230 V / 1 phase / 50 Hz

2.8

51

Sirocco fan

720 / 600 / 540

33 / 34 / 36

200+(20) x 1,000 (1,230) x

710 (800) inches (mm) 1/4 (6.35) inches (mm) 1/2 (12.7) kg

VP-25

26.5

S-36MD1E5

3.6

51

0.39

4.2

40

0.35

Sirocco fan

720 / 600 / 540

33 / 34 / 36

200+(20) x 1,000 (1,230) x

710 (800)

1/4 (6.35)

1/2 (12.7)

VP-25

26.5

S-45MD1E5 S-56MD1E5 S-73MD1E5

4.5

51

0.39

5.0

40

0.35

Sirocco fan

720 / 660 / 600

34 / 35 / 36

200+(20) x 1,000 (1,230) x

710 (800)

1/4 (6.35)

1/2 (12.7)

VP-25

26.5

5.6

58

0.46

6.3

48

0.41

Sirocco fan

780 / 690 / 600

34 / 36 / 38

200+(20) x 1,000 (1,230) x

710 (800)

1/4 (6.35)

1/2 (12.7)

VP-25

26.5

7.3

87

0.7

8.0

76

0.65

Sirocco fan

1,080 / 900 / 780

36 / 40 / 45

200+(20) x 1,000 (1,230) x

710 (800)

3/8 (9.52)

5/8 (15.88)

VP-25

27.5

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

111

F2 TYPE

VARIABLE

STATIC

PRESSURE

HIDE AWAY

S-22MF2E5 // S-28MF2E5 // S-36MF2E5 //

S-45MF2E5 // S-56MF2E5

S-60MF2E5 // S-73MF2E5 // S-90MF2E5 S-106MF2E5 // S-140MF2E5 // S-160MF2E5

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSC2

The new F2 type is designed specifically for applications requiring fixed square ducting. The internal filter is equipped as standard.

Technical focus

· Industry-leading low sound levels from 25 dB(A)

· Built-in drain pump provides 785 mm lift

· Easy to install and maintain

· Air off sensor avoids cold air dumping

· Configurable air temperature control

· Anti-mould washable filters included

System example

An inspection port (450 x 450 mm or more) is required at the lower side of the indoor unit body.

Rectangle duct

Inspection port

(450 x 450 mm or more)

Canvas duct

Intake grille

New Variable Static Pressure Hide Away MF2 series

STANDARDIZED

HEIGHT OF 290 mm

FOR ALL MODELS

Height standardization enables easy and uniform installation for models with different capacities.

Built-in Drain pump (DC motor pump)

- Built-in filter

- Side removable filter

EXTERNAL ELECTRICAL

EQUIPMENT BOX MAKES

MAINTENANCE EASY

P-link PCB

Lowest noise levels in the industry.

The static pressure outside the unit can be increased. New DC fan motor is adopted to new unit. External static pressure is available up to 150 Pa.

*No booster cable is needed.

TYPE

Standard

Range

22-90

70 Pa

10-150 Pa

106-160

100 Pa

10-150 Pa

Air Outlet & Inlet Plenum

S-...MF2E5

Diameters Air Outlet Plenum Diameters Air Inlet Plenum

22, 28, 36, 45 & 56 2 x ø 200 CZ-56DAF2 2 x ø 200 CZ-DUMPA56MF2

60, 73 & 90

106, 140 & 160

3 x ø 200

4 x ø 200

CZ-90DAF2

CZ-160DAF2

2 x ø 250

4 x ø 200

CZ-DUMPA90MF2

CZ-DUMPA160MF2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RELC2

More powerful drain pump

Using a high-lift drain pump, drain piping can be elevated up to 785 mm from the base of the unit.

Up to 300 mm

Up to 500 mm

285 mm

Air Outlet Plenum Air Inlet Plenum

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan kW

W

A kW

W

A

Type

Air flow rate (Hi) m³/h

External static pressure Pa

S-22MF2E5 S-28MF2E5 S-36MF2E5 S-45MF2E5 S-56MF2E5 S-60MF2E5 S-73MF2E5 S-90MF2E5 S-106MF2E5 S-140MF2E5 S-160MF2E5

230 V / 1 phase / 50 Hz

2.2

70

0.57

2.5

70

0.57

2.8

70

0.57

3.2

70

0.57

3.6

70

0.57

4.2

70

0.57

4.5

70

0.57

5.0

100

0.57

5.6

100

0.74

6.3

100

0.74

6.0

120

0.89

7.1

120

0.89

7.3

120

0.89

8.0

120

0.89

9.0

135

0.97

10.0

135

0.97

10.6

195

1.30

11.4

200

1.30

14.0

215

1.44

16.0

210

1.44

16.0

225

1.50

18.0

225

1.50

Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan Sirocco fan

840 840 840 840 960 1,260 1,260 1,500 1,920 2,040 2,160

70 (10-150) 70 (10-150) 70 (10-150) 70 (10-150) 70 (10-150) 70 (10-150) 70 (10-150) 70 (10-150) 100 (10-150) 100 (10-150) 100 (10-150)

Sound power level (L/M/H) dB

Sound pressure level (L/M/H/(H-booster)) dB(A)

Dimensions H x W x D

Pipe connections Liquid mm

47/51/55

25/29/33

47/51/55

25/29/33

47/51/55

25/29/33

50/54/56

28/32/34

50/54/56

28/32/34

48/54/57

26/32/35

48/54/57

26/32/35

50/56/59

28/34/37

53/56/60

31/34/38

54/57/61

32/35/39

55/58/62

33/36/40

290x800x700 290x800x700 290x800x700 290x800x700 290x800x700 290x1,000x700 290x1,000x700 290x1,000x700 290x1,400x700 290x1,400x700 290x1,400x700 inches (mm) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 1/4 (6.35) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)

Net weight

Gas

Drain piping inches (mm) 1/2 (12.7) kg

VP-25

29

1/2 (12.7)

VP-25

29

1/2 (12.7)

VP-25

29

1/2 (12.7)

VP-25

29

1/2 (12.7)

VP-25

29

5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88) 5/8 (15.88)

VP-25

34

VP-25

34

VP-25

34

VP-25

46

VP-25

46

VP-25

46

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Practical

operation

AUTOMATIC RESTART

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

112

VRF SYSTEMS

M1 TYPE

SLIM VARIABLE STATIC

PRESSURE HIDE AWAY

CONCEALED DUCT

The ultra slim M1 type is one of the leading products of its type in the industry. With a depth of only 200 mm it provides greater flexibility and can be used in far more applications. In addition, its high-efficiency and extremely quiet sound levels make it very popular with many users, including hotels and small offices.

Technical focus

· Ultra-slim profile: 200 mm for all models

· DC fan motor greatly reduces power consumption

· Ideal for hotel application with very narrow false ceilings

· Anti-mould washable filters included

· Easy maintenance and service by external electrical box

· 40 Pa static pressure enables ductwork to be fitted.

· Includes drain pump

Ultra-slim profile for all models

200 mm

Drain pump with increased power!

By adoption of a high-lift drain pump, the drain piping rise height can be increased to 785 mm from the lower surface of the body.

Up to 300 mm

Up to 500 mm

Air Outlet & Inlet Plenum

S-...MM1E51

22 , 28 & 36

45 & 56

Diameters Air Outlet Plenum Diameters Air Inlet Plenum

2 x ø 200 CZ-DUMPA22MMS2 2 x ø 200 CZ-DUMPA22MMR2

3 x ø 160 CZ-DUMPA45MMS3 2 x ø 200 CZ-DUMPA22MMR3

PANEL

CZ-KPU2

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

External static pressure Pa

Sound pressure level (L/M/H) dB(A)

Dimensions H x W x D

Pipe connections Liquid mm

S-22MM1E51

2.2

36

0.26

2.5

26

0.23

Sirocco fan

480 / 420 / 360

10 (30)

25 / 27 / 28 (27 / 29 / 30)¹

200 x 750 x 640 inches (mm) 1/4 (6.35)

S-28MM1E51

2.8

40

0.30

3.2

30

0.27

Sirocco fan

510 / 450 / 390

15 (30)

27 / 29 / 30 (29 / 31 / 32)¹

200 x 750 x 640

1/4 (6.35)

S-36MM1E51

230 V / 1 phase / 50 Hz

3.6

42

0.31

4.2

32

0.28

Sirocco fan

540 / 480 / 420

15 (40)

28 / 30 / 32 (30 / 32 / 34)¹

200 x 750 x 640

1/4 (6.35)

S-45MM1E51

4.5

49

0.37

5.0

39

0.34

Sirocco fan

630 / 570 / 480

15 (40)

30 / 32 / 34 (32 / 34 / 36)¹

200 x 750 x 640

1/4 (6.35)

S-56MM1E51

5.6

64

0.48

6.3

54

0.45

Sirocco fan

750 / 690 / 600

15 (40)

31 / 33 / 35 (32 / 35 / 37)¹

200 x 750 x 640

1/4 (6.35)

Net weight

Gas

Drain piping inches (mm) 1/2 (12.7) kg

VP-20

19

1/2 (12.7)

VP-20

19

1/2 (12.7)

VP-20

19

1/2 (12.7)

VP-20

19

1/2 (12.7)

VP-20

19

1. With booster cable using short circuit connection.

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

to install

BUILT-IN

DRAIN PUMP

Easy

control by BMS

CONNECTIVITY

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24

°C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

113

E1 TYPE

HIGH STATIC PRESSURE

HIDE AWAY

The E1 range of ducted units offers improved design flexibility for extended duct layouts as a result of their increased external static pressures.

Technical focus

· Complete flexibility for ductwork design

· Can be located into a weatherproof housing for external siting

· Air off sensor avoids cold air dumping

· Configurable air temperature control

System example

An inspection port (450 x 450 mm or more) is required at the lower side of the indoor unit body (field supply).

Rap valve kit CZ-P160RVK2

The types 224 and 280 require two rap valve kits for each unit.

(not required on a 1:1 installation)

Plenums

AIR OUTLET PLENUM (SUITABLE FOR RIGID + FLEXIBLE DUCT)

N. of exits with diameters Model

S-224ME1E5A / S-280ME1E5 1 x 500 mm CZ-TREMIESPW706

Inspection port (450 x 450 mm or more)

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Net weight

Gas

Drain piping

S-224ME1E5A

22.4

1310

5.98

25.0

1310

5.98

Sirocco fan

4,320 / 4,200 / 3,960

External static pressure Pa

Sound pressure level (L/M/H) dB(A)

Dimensions H x W x D

Pipe connections Liquid mm

216 (235)¹

49 / 50 / 51 (50 / 51 / 52)¹

479 x 1,428 x 1,230 inches (mm) 3/8 (9.52) inches (mm) 7/8 (22.22) kg

VP-25

120

1 With booster cable.

114

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Practical

operation

AUTOMATIC RESTART

Easy

control by BMS

CONNECTIVITY

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

S-280ME1E5

230 V / 1 phase / 50 Hz

28.0

1330

6.06

31.5

1330

6.06

Sirocco fan

4,320 / 4,200 / 3,960

216 (235)¹

49 / 50 / 51 (50 / 51 / 52)¹

479 x 1,428 x 1,230

3/8 (9.52)

7/8 (22.22)

VP-25

120

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating

Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

VRF SYSTEMS

T1 TYPE

CEILING

The T1 type ceiling mounted unit feature a DC fan motor for increased efficiency and reduced operating sound levels. All the units are the same height and depth for a uniform appearance in mixed installations and feature a fresh air knockout for improved air quality.

Further comfort improvement with airflow distribution

Technical focus

· Low sound levels

· New design, all units just 210 mm high

· Large and wide air distribution

· Easy to install and maintain

· Fresh air knockout

Further comfort improvement

The wide air discharge opening widens the air flow to the left and the right, so that a comfortable temperature is obtained in the entire room.

The unpleasant feeling caused when the air flow directly hits the human body is prevented by the

“Draft prevention position”, which changes the swing width, so that the degree of comfort is increased.

Air distribution is automatically altered depending on the operational mode of the unit

F1

F2

F3

F4

60¡

F5

Heating: F1 to F5

Cooling: F1 to F3

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Sound pressure level (L/M/H)

Dimensions H x W x D

Pipe connections Liquid

Gas

Drain piping

Net weight dB(A) mm kg

S-36MT1E5

3.6

29

0.24

4.2

28

0.24

Sirocco fan

720 / 600 / 540

30 / 32 / 35

210 x 910 x 680 inches (mm) 1/4 (6.35) inches (mm) 1/2 (12.7)

VP-20

21

S-45MT1E5

4.5

29

0.24

5.0

28

0.24

Sirocco fan

780 / 660 / 540

30 / 33 / 36

210 x 910 x 680

1/4 (6.35)

1/2 (12.7)

VP-20

21

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

0.26

6.3

31

0.26

S-56MT1E5 S-73MT1E5

230 V / 1 phase / 50 Hz

5.6

32

7.3

43

0.35

8.0

42

0.35

Sirocco fan

780 / 660 / 540

30 / 33 / 36

210 x 910 x 680

1/4 (6.35)

1/2 (12.7)

VP-20

21

Sirocco fan

1,110 / 900 / 840

33 / 36 / 38

210 x 1,180 x 680

3/8 (9.52)

5/8 (15.88)

VP-20

25

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWST2

CZ-RWSC2

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

S-106MT1E5 S-140MT1E5

10.6

74

0.57

11.4

14.0

86

0.63

16.0

73

0.57

85

0.63

Sirocco fan Sirocco fan

1,650 / 1,380 / 1,200 1,800 / 1,560 / 1,320

35 / 38 / 41

210 x 1,595 x 680

3/8 (9.52)

5/8 (15.88)

VP-20

33

37 / 40 / 43

210 x 1,595 x 680

3/8 (9.52)

5/8 (15.88)

VP-20

33

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

control by BMS

CONNECTIVITY

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24

°C WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

115

K2/K1 TYPE

WALL MOUNTED

S-22MK1E5 / S-28MK1E5 / S-36MK1E5

S-22MK2E5 / S-28MK2E5 / S-36MK2E5

S-45MK1E5 / S-56MK1E5 / S-73MK1E5 / S-106MK1E5

EXTERNAL VALVE (OPTIONAL)

CZ-P56SVK2 (model sizes 22 to 56)

CZ-P160SVK2 (model sizes 73 to 106)

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSK2

The K2/K1 Type wall mounted unit has a stylish smooth panel which not only looks good but is also easy to clean.

The unit is also smaller, lighter and substantially quieter than previous models making it ideal for small offices and other commercial applications.

Technical focus

· Closed discharge port

· Lighter and smaller units make the installation easy

· Quiet operation

· Smooth and durable design

· Piping outlet in three directions

· Washable front panel

· Air distribution is automatically altered depending on the operational mode of the unit

· Anti-mould filters are standard

Closed discharge port

When the unit is turned off, the flap closes completely to prevent entry of dust into the unit and to keep the equipment clean.

Lighter and smaller units make the installation easy

The width has been decreased by 17% and the units are lighter.

Quiet operation

These units are among the quietest in the industry, making them ideal for hotels and hospitals.

Smooth and durable design

The smooth cover means these units match most modern interiors. Their compact size enables them to blend in, even in small spaces.

Piping outlet in three directions

Piping outlet is possible in the three directions of rear, right, and left, making the installation work easier.

Washable front panel

The indoor unit’s front panel can be easily removed and washed for trouble-free cleaning.

Air distribution is automatically altered depending on the operational mode of the unit

NEW

290 mm

F1

F2

F3

90º

F4

F5

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

NEW 870 mm (Current 995 mm)

Heating

Cooling

MODEL NAME

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

S-22MK2E5¹ S-28MK2E5¹ S-36MK2E5¹ S-22MK1E5² S-28MK1E5² S-36MK1E5² S-45MK1E5 S-56MK1E5 S-73MK1E5 S-106MK1E5

2.2

25

0.21

2.5

25

0.21

2.8

25

0.23

3.2

25

0.23

3.6

30

0.25

4.2

30

0.25

2.20

19

0.16

2.50

19

0.17

2.80

19

0.16

3.20

19

0.17

230 V / 1 phase / 50 Hz

3.60

22

0.19

4.20

23

0.20

4.5

20

0.26

5.0

20

0.26

5.6

30

0.35

6.3

30

0.35

7.3

57

0.58

8.0

57

0.58

10.6

60

0.62

11.4

68

0.70

Sound pressure level (L/M/H) dB(A)

Dimensions H x W x D mm

Pipe connections

Net weight

Liquid

Gas

Drain piping (O.D.) kg

Cross flow Cross flow Cross flow Sirocco fan Sirocco fan Sirocco fan Cross flow Cross flow Cross flow Cross flow

540/450/390 570/500/390 655/540/390 540/450/360 540/450/360 600/510/390 720/630/510 840/720/630 1,080/870/690 1,140/990/780

29/33/36

VP-13

10

VP-13

10

VP-13

10

40/44/47 42/45/49

290x870x214 290x870x214 290x870x214 285x825x217 285x825x217 285x825x217 300x1,065x230 300x1,065x230 300x1,065x230 300x1,065x230 inches (mm) 1/4 (6.35) inches (mm) 1/2 (12.7) ϕ 16

9

29/34/37

1/4 (6.35)

1/2 (12.7) ϕ 16

9

29/36/40

1/4 (6.35)

1/2 (12.7) ϕ 16

9

28/32/35

1/4 (6.35)

1/2 (12.7)

28/32/35

1/4 (6.35)

1/2 (12.7)

29/33/37

1/4 (6.35)

1/2 (12.7)

30/34/38

1/4 (6.35)

1/2 (12.7) ϕ 18

13

32/36/40

1/4 (6.35)

1/2 (12.7) ϕ 18

13

3/8 (9.52)

5/8 (15.88) ϕ 18

14.5

3/8 (9.52)

5/8 (15.88) ϕ 18

14.5

1. Available from June 2013.

2. Available until current stock ends.

116

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

Perfect

humidity control

MILD DRY

Further

comfort

AUTO-FLAP

CONTROL

Practical

operation

AUTOMATIC RESTART

Comfort

everywhere

AIR SWEEP

Easy

control by BMS

CONNECTIVITY

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C

WB. Heating Indoor 20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

VRF SYSTEMS

P1 TYPE

FLOOR STANDING

R1 TYPE

CONCEALED FLOOR

STANDING

OPTIONAL CONTROLLER

Timer remote controller

CZ-RTC2

P1 Type

The compact floor standing P1 units are the ideal solution for providing perimeter air conditioning. The standard wired controller can be incorporated into the body of the unit.

Technical focus

· Pipes can be connected to either side of the unit from the bottom or rear

· Easy to install

· Front panel opens fully for easy maintenance

· Removable air discharge grille gives flexible air flow

· Room for condensate pump

Effective perimeter handling

R1 Type

At just 229 mm deep, the R1 unit can be easily concealed in perimeter areas to provide powerful and effective air conditioning.

Technical focus

· Chassis unit for discreet installation

· Complete with removable filters

· Pipes can be connected to either side of the unit from the bottom or rear

· Easy to install

Perimeter air conditioning with high interior quality

OPTIONAL CONTROLLER

Wireless remote controller

CZ-RWSC2

A standard wired remote control can be installed in the body

OPTIONAL CONTROLLER

Simplified remote controller

CZ-RE2C2

MODEL NAME P1 TYPE S-22MP1E5

R1 TYPE S-22MR1E5

Power source

Cooling capacity

Cooling power input

Cooling operating current

Heating capacity

Heating power input

Heating operating current

Fan

Dimensions P1 Type H x W x D

Dimensions R1 Type H x W x D

Pipe connections

Type kW

W

A kW

W

A

Air flow rate (H/M/L) m³/h

Sound pressure level (L/M/H)

Liquid dB(A) mm mm

2.2

56

0.25

2.5

40

0.18

Sirocco fan

420 / 360 / 300

28 / 30 / 33

615 x 1,065 x 230

616 x 904 x 229 inches (mm) 1/4 (6.35)

Gas

Drain piping inches (mm) 1/2 (12.7)

VP-20

Net weight P1 Type

Net weight R1 Type kg kg

29

21

Energy

saving

Environmentally

friendly

refrigerant

R410A

Easy

maintenance

SELF-DIAGNOSING

For more

comfort

AUTOMATIC FAN

S-28MP1E5

S-28MR1E5

2.8

56

0.25

3.2

40

0.18

Sirocco fan

420 / 360 / 300

28 / 30 / 33

615 x 1,065 x 230

616 x 904 x 229

1/4 (6.35)

1/2 (12.7)

VP-20

29

21

Perfect

humidity control

MILD DRY

Practical

operation

AUTOMATIC RESTART

Easy

control by BMS

CONNECTIVITY

0.38

4.2

70

0.31

S-36MP1E5

S-36MR1E5

S-45MP1E5

S-45MR1E5

230 V / 1 phase / 50 Hz

3.6

85

4.5

126

0.56

5.0

91

0.41

Sirocco fan

540 / 420 / 360

29 / 35 / 39

615 x 1,065 x 230

616 x 904 x 229

1/4 (6.35)

1/2 (12.7)

VP-20

29

21

Sirocco fan

720 / 540 / 480

31 / 35 / 38

615 x 1,380 x 230

616 x 1,219 x 229

1/4 (6.35)

1/2 (12.7)

VP-20

39

28

S-56MP1E5

S-56MR1E5

5.6

126

0.56

6.3

91

0.41

Sirocco fan

900 / 780 / 660

31 / 36 / 39

615 x 1,380 x 230

616 x 1,219 x 229

1/4 (6.35)

1/2 (12.7)

VP-20

39

28

S-71MP1E5

S-71MR1E5

7.1

160

0.72

8.0

120

0.54

Sirocco fan

1,020 / 840 / 720

35 / 38 / 41

615 x 1,380 x 230

616 x 1,219 x 229

3/8 (9.52)

5/8 (15.88)

VP-20

39

28

Rating Conditions: Cooling Indoor 27 °C DB / 19 °C WB. Cooling Outdoor 35 °C DB / 24 °C WB. Heating Indoor

20 °C DB. Cooling Outdoor 7 °C DB / 6 °C WB.

DB: Dry Bulb; WB: Wet Bulb

117

118

PANASONIC VENTILATION

SOLUTIONS. FOR MAXIMUM

SAVINGS AND EASY INTEGRATION

VRF SYSTEMS VENTILATION

AIR HANDLING UNIT KIT

Connects easily to your ECOi and GHP systems.

ENERGY RECOVERY VENTILATOR

Energy recovery ventilators offer ventilation which increases comfort and saves energy. They effi ciently recover the heat lost in ventilation during the heat recovery process.

119

AIR HANDLING UNIT KIT

NEW AHU KITS CONNECT VRF SYSTEMS TO AIR

HANDLING UNIT SYSTEMS, USING THE SAME

REFRIGERANT CIRCUIT AS THE VRF SYSTEM.

120

Large connectivity possibilities mean the Panasonic AHU Kit can be easily integrated.

Application: Hotels, offi ces, server rooms or all large buildings where air quality control such as humidity control and fresh air and is needed.

AHU CONNECTION KIT

PCB, Power trans,

Terminal block

Remote control can be easily installed on the AHU Kit box.

Remote control must be purchase separately.

Expansion valve

Thermistor x2

(Refrigerant: E1, E3)

REMOTE CONTROLLER

Standard wired remote controller. Optional

Thermistor x2

(Air: Tf, Tb)

VRF SYSTEMS VENTILATION

Possible Solution 1 by 1

Panasonic AHU Kit, 28 / 56 kW

PCB, Transformer, Solenoid Control Valve, Thermistor x 4 pcs, Terminal Base and Electrical Component Box.

CZ-280MAH1

Controller wiring

CZ-RTC2 (Optional)

ECOi OR GHP

I/D-O/D wiring

Wiring for

Thermostat &

Solenoid Valve

Piping

AIR HANDLING UNIT

System example for large capacity (more than 56 kW)

3 x [PCB, Transformer, Solenoid Control Valve, Thermistor x 4 pcs, Terminal

Base and Electrical Component Box].

EXAMPLE 140 kW SYSTEM

CZ-280MAH1

CZ-560MAH1

MOV

Gas temperature

Liquid temperature

Fan operation signal

28 kW

H/E

56 kW

H/E

16 HP 16 HP

Gas tube

Liquid tube

18 HP

CZ-560MAH1

O_U / I_U communication

Inlet temperature

56 kW

H/E

Outlet temperature

Fan motor control PCB

Optional parts: Following functions are available by using different control accessories:

CZ-RTC2 Wired remote controller

· Operation-ON/OFF

· Mode select

· Temperature setting

* Fan operation signal can be taken from the PCB.

CZ-T10 terminal

· Input signal= Operation ON/OFF

· Remote controller prohibition

· Output signal= Operating-ON status

· Alarm output (by DC12V)

PAW-OCT, DC12 V outlet. OPTION terminal

· Output signal= Cooling/Heating/Fan status

· Defrost

· Thermostat-ON

CZ-CAPBC2 Mini seri-para I/O unit

· Temperature setting by 0-10 V or 0-140 Ω input signal

· Room (inlet air) temp outlet by 4-20 mA

· Mode select or/and ON/OFF control

· Fan operation control

· Operation status output/ Alarm output

121

AHU CONNECTION KIT, 28 kW AND 56 kW FOR ECOi AND GHP

Heat exchanger, Fan & Fan motor to be mounted in AHU Kit shall be provided in the field.

AHU connection Kit can be connected this (field supplied) AHU Kit system. (Contents of kit:

Control PCB, expansion valve, sensors)

Application: Hotels, offices, server rooms or all large buildings where air quality control such as humidity control and fresh air and is needed.

AHU Kit combine air conditioning and fresh air in only one solution.

6N SERIES 2-PIPE ECOi OUTDOOR UNIT SHALL BE USED FOR AHU CONNECTION KIT.

2 models for VRF system: 10 HP (CZ-280MAH1) and 20 HP (CZ-560MAH1)

WITH GHP OUTDOOR UNITS:

· One AHU kit may be used for one GHP unit (2 way, 56 kW). Multiple AHU kits cannot be used.

· Mix connection with standard indoor units is not allowed.

· Power specifications are single-phase 220 V to 240 V.

MODEL CZ-280MAH1

Nominal Cooling capacity @ 50hz

Nominal Heating @ 50hz

Horsepower

Cooling Airflow High

Cooling Airflow Low

Heating Airflow High kW kW

HP m³/min m³/min m³/min

28.0

31.5

CZ-560MAH1

56.0

63.0

CZ-560MAH1

CZ-560MAH1 +

CZ-560MAH1

CZ-560MAH1 +

CZ-560MAH1 +

CZ-280MAH1

CZ-560MAH1 +

CZ-560MAH1+

CZ-560MAH1

84.0

95.0

112.0

127.0

140.0

155.0

168.0

189.0

10 20 30 40 50 60

5,000 10,000 15,000 20,000 25,000 30,000

3,500 7,000 10,500 14,000 17,500 21,000 m³/min Heating Airflow Low

Bypass Factor

Fan Input Power

Total Cooling (incl. T-Heat exch.) Nom (Min - Max)

0.9 (recommended)

Total Heating (incl. T-Heat exch.)

Fuse Size

Running Current @ 230v

Input Power @ 230v

Nom (Min - Max)

A

Dimensions of the box (H x W x D)

Weight mm kg

Sound pressure level on cooling mode (nominal) dB(A)

Sound power level on cooling mode (nominal)

Piping length (min/max)

Installation height difference (max)

Pipe Diameters m m

Inch (mm)

Inch (mm)

10/100

10

3/8 (9.52)

7/8 (22.22)

Intake temperature of AHU Kit (Min / Max) °C

Ambient temperature of outdoor unit (min / Max) °C

10/100

10

5/8 (15.88)

1 1/8 (28.58)

10/100

10

3/4 (19.05)

1 1/4 (31.75)

420 x 280 x 160

10/100

10

3/4 (19.05)

1 1/2 (38.15)

10/100

10

3/4 (19.05)

1 1/2 (38.15)

Cooling:18 - 32DB (13 - 23 WB) / Heating:16 - 30 DB

Cooling: -5 - 43 DB / Heating: -15 - 15.5 WB

10/100

10

3/4 (19.05)

1 1/2 (38.15)

AHU CONNECTION KIT / SYSTEM COMBINATION

CAPACITY (HP) OUTDOOR UNIT COMBINATION

28 kW (10 HP) U-10ME1E81

56 kW (20 HP)

84 kW (30 HP)

112 kW (40 HP)

140 kW (50 HP)

168 kW (60 HP)

U-20ME1E81

U-16ME1E81

U-20ME1E81

U-18ME1E81

U-20ME1E81

U-14ME1E81

U-20ME1E81

U-16ME1E81

U-20ME1E81

56 kW (20 HP) U-20GE2E5

122

U-16ME1E81

U-20ME1E81

AHU KIT COMBINATION

CZ-280MAH1

CZ-560MAH1

CZ-560MAH1

CZ-560MAH1

CZ-560MAH1

CZ-560MAH1

CZ-560MAH1

CZ-280MAH1

CZ-560MAH1

CZ-560MAH1

CZ-560MAH1

CZ-280MAH1

CZ-560MAH1

VRF SYSTEMS VENTILATION

OPTIONAL

Standard wired remote controller

CZ-RTC2

TECHNICAL ZOOM

· MAX. CAPACITY: 60HP (168 kW)

· MAX. PIPING LENGTH: 180 m

· MAX. TOTAL PIPING: 210 m

· ELEV. DIFF. (O_U~I_U): 50 m (O_U ABOVE)

· ELEV. DIFF. (I_U~I_U): 4 m

· IN/OUT CAPACITY RATIO: 50~100%

MAX. I_U NUMBER: 2 UNITS*

· AVAILABLE TEMPERATURE RANGE IN HEATING: -15~15.5 °C

· AVAILABLE TEMPERATURE RANGE FOR THE SUCTION AIR AT AHU

KIT: COOL: 15~24 °C / HEAT: 10~30 °C

* To be simultaneous operation controlled by one remote controller sensor.

B

E

L

H

J

I

K

C

A

F

G

D

CZ-280MAH1 // CZ-560MAH1

· The system controlled by the suction air (or return air from room) temperature as same as standard indoor unit. (Selectable mode: Automatic / Cooling / Heating / Fan / Dry (but same as

Cool)

· The discharge air temperature is also controlled to prevent too-low air discharge in Cooling or too-high air discharge in Heating. (in case of VRF system)

· Demand control (Forcible thermostat-OFF control by operating current)

· Defrost operation signal, Thermo-ON/OFF states output

· Drain pump control (Drain-pump and the float switch to be supplied in local)

· External target temperature setting via Indoor/Outdoor signal interface is available with

CZ-CAPBC2. (Ex. 0 – 10 V)

· Connectable with P-LINK system

Special care for the electrical noise may necessary depending on the system at site.)

· Fan control signal from the PCB can be used for control the air volume (High/Mid/Low and LL for Th-off)

Need to change the fan control circuit wiring at field.

B

E

L

H

J

I

K

C

A

F

G

D

SYSTEM & REGULATIONS. SYSTEM OVERVIEW

A: AHU Kit controller box (with control PCB)

B: AHU Kit equipment (Field supplied)

C: AHU Kit system controller (Field supplied)

D: Outdoor unit

F: Gas piping (Field supplied)

G: Liquid piping (Field supplied)

H: Electronic expansion valve

I: Thermistor for Gas pipe

J: Thermistor for Liquid pipe

K: Thermister for Suction air

L: Thermistor for Discharge air

123

AIR CURTAIN

High efficiency Air curtain connected to your VRF installation. EC Fan motor for a smooth operation and efficient performance.

Plug & Play Installation

2 types of Air flow available: Jet-Flow and Standard.

2015 Fan Standard available today.

Easy Cleaning and Servicing.

INTERNET CONTROL

An intuitive and user-friendly application on your PC or smartphone screen lets you manage the air conditioning system in the same way you do with the remote controller.

HP

AIR CURTAIN*

Air flow type

Air Volume

Air Flow Length (A)

Max Installation high

Refrigerant

High / Med / Low

Heating capacity nominal

Heating capacity max (at air in 20 °C) m²/h m kW kW m

Pressure

Tubing Gas

Tubing Liquid

Fan bar mm mm

4 8 10 14 4 10

PAW-10EAIRC-MJ PAW-15EAIRC-MJ¹ PAW-20EAIRC-MJ² PAW-25EAIRC-MJ² PAW-10EAIRC-MS PAW-20EAIRC-MS¹

Jetflow

2700 / 1900 / 1200 3600 / 2500 / 1600

1.0

11.4

12.47

2.7

R410A

45

16

1.5

25.0

19.55

2.7

R410A

45

18

5400 / 3800 / 2400

2.0

31.5

29.99

2.7

R410A

45

22

6300 / 4400 / 2800

2.5

37.5

37.53

2.7

R410A

45

22

Standard

2700 / 1900 / 1200

1.0

11.4

12.47

2.4

R410A

45

16

5400 / 3800 / 2400

2.0

31.5

29.99

2.4

R410A

45

22

10 10 10 10 10 10

230 V / 50 Hz / 1 / N / PE 230 V / 50 Hz / 1 / N / PE 230 V / 50 Hz / 1 / N / PE 230 V / 50 Hz / 1 / N / PE 230 V / 50 Hz / 1 / N / PE 230 V / 50 Hz / 1 / N / PE

Fan type

Currency High / Med / Low A

Electrical Consumption High / Med / Low kW

Protecting Fuse

Noise

Dimensions / Weight L x H x D

A dB(A)

EC

2.1 / 0.8 / 0.3

0.44 / 0.17 / 0.06

M16A

40-55

EC

2.8 / 1.1 / 0.4

0.59 / 0.23 / 0.08

M16A

40-56

EC

4.2 / 1.6 / 0.6

0.89 / 0.34 / 0.12

M16A

40-57

EC

4.9 / 1.9 / 0.7

1.03 / 0.4 / 0.14

M16A

40-58

EC

2.1 / 0.8 / 0.3

0.44 / 0.17 / 0.06

M16A

40-55

EC

4.2 / 1.6 / 0.6

0.89 / 0.34 / 0.12

M16A

40-57 mm / kg 1210 x 260 x 590 / 70 1710 x 260 x 590 / 100 2210 x 260 x 590 / 138 2710 x 260 x 590 / 160 1210 x 260 x 490 / 60 2210 x 260 x 490 / 128

Outdoor combination with Mini ECOi

Outdoor combination with ECOi

Outdoor combination with GHP

U-4LE1E5/8

All models

All models

* Available from April 2013. 1) Needs 2 RAP Valve CZ-160RVK2. 2) Needs 3 RAP Valve CZ-160RVK2.

All models

All models

U-4LE1E5/8

All model without 8HP All model without 8/10HP All models

All models All models All models

All model without 8HP

All models

JETFLOW DIMENSIONS

TOP VIEW

A

75

45

60

100

Rivetting nut M8

Pressure line

Intake line

FRONT VIEW

105

A+210

45

85

295 560

SIDE VIEW

105

SECTION

260

100

30

STANDARD DIMENSIONS

TOP VIEW

A

75

45

Rivetting nut M8

Pressure line

Intake line

60

100

FRONT VIEW

105

A+210

45

35 295

460

SIDE VIEW

105

260

SECTION

100

30

30

BOTTOM VIEW

120

30

BOTTOM VIEW

70

25

A

PAW-10PAIRC-MJ PAW-15PAIRC-MJ PAW-20PAIRC-MJ

1000 1500 2000 A

PAW-10PAIRC-MS PAW-20PAIRC-MS

1000 2000

124

NEW

JET-FLOW: PAW-10PAIRC-MJ // PAW-15PAIRC-MJ

// PAW-20PAIRC-MJ

Technical Focus

· PLUG & PLAY INSTALLATION

· SAVE UP TO 40% ENERGY COSTS BY USE OF THE INTEGRATED EC

FAN TECHNOLOGY

- HIGHER EFFICIENCY CONVENTIONAL AC FAN

- SOFTSTART

- LONGER MOTOR DURATION

· 3 LENGTHS OF AIR CURTAINS, FROM 1.0 TO 2.0 m

· INSTALLATION HEIGHT UP TO 2.7 m

· OUTLET GRILLES CAN BE ADJUSTED IN FIVE POSITIONS, TO SUITE

DIFFERENT INDOOR AND INSTALLATION REQUIREMENTS

· CONTROL WITH PANASONIC REMOTE CONTROL SYSTEMS (OPTIONAL)

· DIRECT INTEGRATION TO BMS BY OPTIONAL PANASONIC

INTERFACES

· DRAIN INCLUDED FOR COOLING OPERATION

STANDARD: PAW-10PAIRC-MS // PAW-20PAIRC-MS

Technical Focus

· PLUG & PLAY INSTALLATION

· SAVE UP TO 40% ENERGY COSTS BY USE OF THE INTEGRATED EC

FAN TECHNOLOGY

- HIGHER EFFICIENCY CONVENTIONAL AC FAN

- SOFTSTART

- LONGER MOTOR DURATION

· 2 LENGTHS OF AIR CURTAINS, 1.0 AND 2.0 m

· INSTALLATION HEIGHT UP TO 2.4 m

· CONTROL WITH PANASONIC REMOTE CONTROL SYSTEMS (OPTIONAL)

· DIRECT INTEGRATION TO BMS BY OPTIONAL PANASONIC

INTERFACES

· DRAIN INCLUDED FOR COOLING OPERATION

Features

COMFORT

· Easy redirection of Air-Flow by means of manual deflector (Jet-Flow)

EASE OF USE

· Speed selector (high and low) on the unit itself

EASY INSTALLATION AND MAINTENANCE

· Easy installation

· Compact dimensions improve installation and positinioning (Jet-Flow)

· Easy cleaning of grid without opening of the unit

MAX INSTALLATION HIGH

Jet-Flow: 2.7 m

Standard flow: 2.4 m

125

ENERGY RECOVERY VENTILATOR

SUPPRESSES INDOOR TEMPERATURE

CHANGES WHILE PROVIDING FRESH AIR

126

Heat exchange ventilation and normal ventilation

Heat exchange ventilation

When a room is cooled or heated, the exhausted cooling / heating energy is recovered by heat-exchange ventilation.

Normal ventilation

This is used in the spring and autumn, when rooms are not cooled or heated, that is, when there is little difference between the indoor and outdoor air conditions. In addition, at night during the hot season, when the outside air temperature drops the outside air is drawn inside without heat exchange, alleviating the load on the air conditioning equipment.

ADOPTS A HIGHLY EFFICIENT COUNTER-FLOW HEAT EXCHANGE ELEMENT

Outside air

Exhaust air

The heat exchanger is made up of a membrane manufactured from a special material covered in resin for optimal heat transmission. The nylon/polyester fibre filter offers high dust retention capacity. We have also redesigned the air ducts to obtain a long-lasting heat exchange system which does not need periodic cleaning.

Energy effi ciency and ecology

20

%

energy savings

Energy consumption is dramatically reduced by using a counter-flow heat-exchange element. Air conditioning load is reduced by approximately 20%, resulting in significant energy savings.

HEAT EXCHANGER CHARACTERISTICS

Former

(cross-flow element)

New

(counter-flow element)

Room air Supply air

VRF SYSTEMS VENTILATION

Heat exchanger

With the cross-flow element, air moves in a straight line across the element. With the counter-flow element, air flows through the element for a longer time (longer distance), so the heat-exchange effect remains unchanged even if the element is made thinner.

Easy Installation and Maintenance

Slim shape and easier installation

Counter-flow heat exchange element used for reduced noise and slimmer, more compact body shape.

Characteristics common to all models

· Counter-flow heat exchange element used for reduced noise and slimmer, more compact body shape.

· All maintenance can be performed through a single inspection hole.

· Straight air supply / exhaust system used for easier installation.

· Each unit can be mounted in reverse position.

· Equipped with an Extra-High setting.

· Can incorporate a medium performance filter (optional, installed on site).

More Comfort

Quiet operation

Low noise operation results in noticeably quieter units. All models with capacities below 500 m³/h run at noise levels below 32 dB (High setting) and even our largest 1,000 m³/h-capacity model runs at only 37.5 dB (High setting).

Height

270

FY-250ZDY8 // FY-350ZDY8 // FY-500ZDY8

Room air Supply air

mm

FY-800ZDY8 // FY-01KZDY8A

Height

388

mm

Reverse mountable direct air supply / exhaust system

Adoption of straight air supply / exhaust system: Duct design is simplified because the air supply / exhaust ducts are straight.

Since each unit can be mounted in reverse position, only one inspection hole is needed for two units: Two units can share one inspection hole so duct work is easier and more flexible.

Inspection cover

Supply air Room air

Straight unit Reverse mounted unit

Long heat-exchange element service life

Cleaning reduced due to the special material heat exchanger.

The nylon/polyester fibre filter offers high dust retention capacity.

Inspection hatch

CHANGES IN AIRFLOW RESISTANCE BASED ON NUMBER OF YEARS IN SERVICE

20

Exhaust air Outside air Outside air Exhaust air

15

Service Cleaning

5

10

Balanced Ventilation

WINTER

Cool

SUMMER

Warm

Warm Cool

0

0 1 2 3 4 5 6 7 8 9 10

Number of years in service

Cool Warm

Warm Cool

Former element before cleaning

Former element after cleaning

New element

Former element requires periodic cleaning.

The counter-flow type element requires no periodic cleaning because it produces practically no increase in resistance.

Outside Inside Outside Inside

127

ENERGY RECOVERY VENTILATION SYSTEM

Recovers up to 77% of the heat in the outgoing air, for an ecological and energy efficient building.

FY-250ZDY8 FY-350ZDY8 FY-500ZDY8 FY-800ZDY8 FY-01KZDY8A

RATED FLOW RATE

MODELS

Power Source

150 m³/h

FY-150ZDY8

220-240 V - 50 Hz

250 m³/h

FY-250ZDY8

220-240 V - 50 Hz

350 m³/h

FY-350ZDY8

220-240 V - 50 Hz

500 m³/h

FY-500ZDY8

220-240 V - 50 Hz

650 m³/h

FY-650ZDY8

220-240 V - 50 Hz

800 m³/h

FY-800ZDY8

220-240 V - 50 Hz

1000 m³/h

FY-01KZDY8A

220-240 V - 50 Hz

Input W 97-114 92-107 69-77 112-

128

108-

123

87-96 182-

190

178-

185

175-

168

263-

289

204-

225

165-

185

326-

347

269-

295

200-

210

387-

418

360-

378

293-

295

437-

464

416-

432

301-

311

Air Volume m³/h 150 150 120 250 250 190 350 350 240 500 500 440 650 650 460 800 800 630 1000 1000 700

External Static Pressure Pa 80 70 25 105 95 45 140 60 45 120 60 35 65 40 40 140 110 55 105 80 75

Noise dB 28.5-

29.0

28.0-

29.0

19.5-

21.5

30.0-

31.5

29.5-

30.5

23.5-

26.5

32.5-

33.0

30.5-

31.0

22.5-

25.5

36.5-

37.5

34.5-

35.5

31.0-

32.5

36.5-

37.5

34.5-

35.5

30.0-

32.0

37.0-

37.5

36.5-

37.0

33.5-

34.5

37.5-

38.5

37.0-

37.5

33.5-

34.5

Temp. Exchange Effiency % 75 75

Input

77 75 75 77 75 75 78 75 75 76 75 75 79 75 75 76 75 75 79

E-High High Low E-High High Low E-High High Low E-High High Low E-High High Low E-High High Low E-High High Low

W 97-114 92-107 69-77 112-

128

108-

123

87-96 182-

190

178-

185

175-

168

263-

289

204-

225

165-

185

326-

347

269-

295

200-

210

387-

418

360-

378

293-

295

437-

464

416-

432

301-

311

Air Volume m³/h 150 150 120 250 250 190 350 350 240 500 500 440 650 650 460 800 800 630 1000 1000 700

External Static Pressure Pa 80 70 25 105 95 45 140 60 45 120 60 35 65 40 40 140 110 55 105 80 75

Noise dB 28.5-

29.0

28.0-

29.0

19.5-

21.5

30.0-

31.5

29.5-

30.5

23.5-

26.5

32.5-

33.0

30.5-

31.0

22.5-

25.5

37.5-

38.5

37.0-

38.0

31.0-

32.5

36.5-

37.5

35.0-

35.5

30.0-

32.0

37.0-

37.5

36.5-

37.0

33.5-

34.5

39.5-

40.5

39.0-

39.5

35.5-

36.5

Temp. Exchange Effiency % -

Dimensions (W x D x H) mm 970 x 467 x 270

-

Weight kg 25

-

882 x 599 x 270

-

29

-

1050 x 804 x 317

-

49

-

1090 x 904 x 317

-

57

-

1204 x 884 x 388

-

68

-

1322 x 884 x 388

-

71

-

1322 x 1134 x 388

83

This noise of the product is the value which was measured at the acoustic room. Actually, in the established condition, that undergo influence by the echoing of the room and so that become bigger than the display numerical value. The input, the current and the exchange efficiency are values at the time of the mentioned air volume. The noise level shall be measured 1.5m below the centre of the unit. The temperature exchange efficiency averages that of when cooling and when heating.

TYPICAL SYSTEM LINKED TO A CASSETTE TYPE AIR CONDITIONER

POWER SOURCE

AIR CONDITIONER OUTLET;

NO-VOLT CONTACT

CONNECTING LINE

COMPACT AIR CONDITIONER

REMOTE CONTROL ON

AIR CONDITIONER SIDE

POWER SOURCE

ENERGY RECOVERY VENTILATOR

SWITCH (NOT INCLUDED)

USE CONDITIONS

OUTDOOR AIR CONDITIONS

TEMPERATURE RANGE: -10 °C – 40 °C

RELATIVE HUMIDITY: 85% OR LESS

INDOOR AIR CONDITIONS

TEMPERATURE RANGE: -10 °C – 40 °C

RELATIVE HUMIDITY: 85% OR LESS

REQUIREMENTS FOR INSTALLATION

USE IS TO BE AVOIDED IN REFRIGERATED CHAMBERS OR OTHER

PLACES WHERE THE TEMPERATURE MAY UNDERGO SIGNIFICANT

FLUCTUATIONS, EVEN WHEN THE TEMPERATURE RANGE IS

ACCEPTABLE.

128

VRF SYSTEMS VENTILATION

TECHNICAL ZOOM

· HIGH ENERGY SAVING, UP TO 20%

· COUNTER CROSS FLOW TECHNOLOGY FOR BETTER EFFICIENCY

· LONG LIFE ELEMENT CORE

· EASY INSTALLATION AND 20% LESS THICKNESS

· EASY CONNECTION TO AIR CONDITIONING UNITS

· SUPER QUIET UNITS

Maintenance space

Maintenance opening

N

O

L

M

J

K

I

H

C

D

A

B

E

F

G

FY-250ZDY8 // FY-350ZDY8 // FY-500ZDY8 //

FY-800ZDY8 // FY-01KZDY8A

HEALTHY AIR

· The filter guarantees healthier air

ENERGY EFFICIENCY AND ECOLOGY

· Up to 20% energy saving in the installation

· Recovers up to 77% of the heat in the outgoing air

COMFORT

· Quiet units (21,5 dB for the FY-250ZDY8)

· Cleaning reduced due to the revolutionary structure of the exchanger

(recommended every 6 months)

· Ideal for indoor spaces without windows

EASY INSTALLATION AND MAINTENANCE

· Five models for easier selection

· Reduced system height (270 mm and 388 mm)

· Side opening for cleaning (inspection of filter, motor and other parts)

· Installation can be reversed to share an inspection opening between 2 machines

· Easy connection to the air conditioning unit (without additional elements)

· Installation in false ceilings

· Units operate at 220 - 240 V

· High static pressure for easier installation

414

95

219

144

270

135

159

882

142

600

655

19

FY-250ZDY8

810

599

315

414

95

219

144

270

145

159

882

162

600

860

19

FY-350ZDY8

810

804

480

414

107

246

194

270

145

159

962

202

600

960

19

FY-500ZDY8

890

904

500

612

85

258

242

288

194

218

1,322

228

600

940

19

FY-800ZDY8

1,250

884

428

612

85

258

242

388

194

218

1,322

FY-01KZDY8A

1,250

1,134

678

228

600

1,190

19

129

OPERATION SYSTEM

Requirements

External appearance

INDIVIDUAL CONTROL SYSTEMS

Normal operation Operation from each seat Quick and easy operation

TIMER OPERATION

Daily and weekly program

130

Type, model name

Built-in Thermostat

Use limitations

Timer Remote Controller (Wired)

CZ-RTC2

N. of I_O which can be controlled 1 group, 8 units

· Up to 2 controllers can be connected per group.

Wireless Remote Controller

CZ-RWSU2

CZ-RWSY2

CZ-RWSL2

1 group, 8 units

CZ-RWSC2

CZ-RWST2

CZ-RWSK2

· Up to 2 controllers can be connected per group.

Function ON/OFF

Mode setting

Fan speed setting

Temperature setting

Air flow direction

Permit/Prohibit switching

Weekly program

✘¹

✘¹

Simplified Remote

Controller

Backlight remote controller

CZ-RE2C2 CZ-RELC2

Schedule Timer

CZ-ESWC2

1 group, 8 units

· Up to 2 controllers can be connected per group.

64 groups, max. 64 units

· Required power supply from the system controller

· When there is no system controller, connection is possible to the T10 terminal of an indoor unit.

VRF SYSTEMS

CONTROL SYSTEMS FOR VRF

A WIDE VARIETY OF CONTROL OPTIONS TO

MEET THE REQUIREMENTS OF DIFFERENT

APPLICATIONS.

CENTRALIZED CONTROL SYSTEMS

Operation with various function from center station

Only ON/OFF operation from center station

Simplified load distribution ratio (LDR) for each tenant

BMS System. PC Base

P-AIMS. Basic Software

Connection with 3rd Party

Controller

Seri-Para I/O unit for outdoor unit

CZ-CSWKC2

System Controller

CZ-64ESMC2

ON/OFF Controller

CZ-ANC2

Intelligent Controller

(Touch screen panel)

CZ-256ESMC2

(CZ-CFUNC2)

CZ-CSWKC2

Optional software

Local adaptor for ON/OFF control

CZ-CAPC2

✘¹

64 groups, max. 64 units

· Up to 10 controllers, can be connected to one system.

· Main unit/sub unit (1 main unit + 1 sub unit) connection is possible.

· Use without remote controller is possible.

16 groups, max. 64 units

· Up to 8 controllers (4 main units +

4 sub units) can be connected to one system.

· Use without remote controller is impossible.

64 units x 4 systems, max. 256 units

· A communication adaptor

(CZ-CFUNC2) must be installed for three or more systems.

CZ-CSWAC2 for Load distribution.

CZ-CSWWC2 for Web application.

CZ-CSWGC2 for Object layout display.

CZ-CSWBC2 for BAC net software interface.

*PC required (field supply)

✘¹

Web Interface Systems

CZ-CWEBC2

*PC required (field supply)

MINI Seri-Para I/O Unit

CZ-CAPBC2

Communication Adaptor

CZ-CFUNC2

131

INDIVIDUAL CONTROL SYSTEMS

Timer remote controller (CZ-RTC2)

Dimensions

H 120 x W 120 x D 16 mm

Basic remote controller ON/OFF

· Operation mode changeover (Cooling, Heating, Dry, Auto, Fan).

· Temperature setting (Cooling/Dry: 18-30 deg Heating: 16-30 deg).

· Fan speed setting H/ M/ L and Auto.

· Air flow direction adjustment.

Time Function 24 hours real time clock

· Week day indicator.

Weekly Programme Function

· A maximum of 6 actions can be programmed for each day.

Outing Function

· This function can prevent the room temperature from dropping or rising when the occupants are out for a long time.

Sleeping Function

· This function controls the room temperature for comfortable sleeping.

Max. 8 indoor units can be controlled from one remote controller

Remote control by main remote controller and sub controller is possible

Max. 2 remote controllers (main remote controller and sub controller) can be installed for one indoor unit.

Possible to connect to the outdoor unit using PAW-MRC cable for servicing purposes

Wireless remote controller

Y1 TYPE

CZ-RWSY2

K1 TYPE

CZ-RWSK2

U1 TYPE

CZ-RWSU2

D1 AND T1 TYPE

CZ-RWST2

L1 TYPE

CZ-RWSL2

WIRELESS REMOTE CONTROL

FOR ALL INDOOR UNITS

CZ-RWSC2

Easy installation for the 4-way cassette type simply by replacing the corner part

24 hour timer function

Remote control by main remote controller and sub controller is possible

· Max. 2 remote controllers (main remote controller and sub controller) can be installed for one indoor unit.

When CZ-RWSC2 is used, wireless control becomes possible for all indoor units

· When a separate receiver is set up in a different room, control from that room also becomes possible.

· Automatic operation by means of the emergency operation button is possible even when the remote controller has been lost or the batteries have been exhausted.

Operation of separate energy recovery ventilators

When commercial ventilation fans or heat-exchange ventilation fans have been installed, they can be operated with this remote control (interlocked operation with the indoor unit or independent ventilation ON/OFF).

132

VRF SYSTEMS

Simplifi ed remote controller (CZ-RE2C2)

Dimensions

H 120 x W 70 x D 16 mm

Backlight remote controller (CZ-RELC2)

A remote controller with simple functions and basic operation

· Suitable for open rooms or hotels where detailed functions are not required.

· ON/OFF, operation mode switching, temperature setting, air speed switching, air flow direction setting, alarm display, and remote controller self-diagnosis can be performed.

· Batch group control for up to 8 indoor units.

· Remote control by main remote controller and sub controller is possible with a simplified remote controller or a wired remote controller (up to two units).

Backlight remote controller with simple and friendly operation

· ON/OFF, operation mode switching, temperature setting, air speed switching, air flow direction setting, alarm display can be performed. LCD backlight display.

· Built-in temperature sensor and batch group control for up to 8 indoor units.

Dimensions

H 120 x W 70 x D 16 mm

Remote sensor (CZ-CSRC2)

· This remote sensor can be connected to any indoor unit. Please use it to detect the room temperature when no remote controller sensor or body sensor is used. (connection to a system without a remote controller is possible).

· For joint use with a remote control switch, use the remote control switch as main remote controller.

· Batch group control for up to 8 indoor units.

CONTROL CONTENTS

Standard Control

· Control of the various operations of the indoor unit by wired or wireless remote controller.

· Cooling or heating mode of the outdoor unit is decided by the first priority of the remote controller.

· Switching between remote controller sensor and body sensor is possible.

(1) Group control

· Batch remote control on all indoor units.

· Operation of all indoor cells in the same mode.

· Up to 8 units can be connected.

(2) Main/sub remote control

· Max 2 remote controllers per indoor unit.

· The button pressed last has priority.

· Timer setting is possible even with the sub remote controller.

PART NAME, MODEL NO.

Timer remote controller

CZ-RTC2 // CZ-RE2C2 // CZ-RELC2

Wireless remote controller

CZ-RWSY2 // CZ-RWSU2 // CZ-RWSL2 // CZ-RWSG2

CZ-RWSK2 // CZ-RE2C2

Timer remote controller

CZ-RTC2 // CZ-RE2C2

Wireless remote controller

CZ-RWSY2 // CZ-RWSU2 // CZ-RWSL2 // CZ-RWSG2

CZ-RWSK2 // CZ-RE2C2

Main or sub. Timer remote controller

CZ-RTC2

Wireless remote controller

CZ-RWSY2 // CZ-RWSU2 // CZ-RWSL2 // CZ-RWSG2

CZ-RWSK2 // CZ-RE2C2

QUANTITY

1 unit each

1 unit

As required

133

CENTRALISED CONTROL SYSTEMS

Schedule timer (CZ-ESWC2)

controller, etc. Also, as it does not have an address setting function, the control function of a system controller etc. must be used for address setting.

Up to 64 groups (max. 64 indoor units) can be controlled divided into

8 timer groups

Dimensions

H 120 x W 120 x D 16 mm

The power supply for the schedule timer is taken from one of the following.

1. Control circuit board (T10) of a nearby indoor unit (power supply wiring length: within 200 m from the indoor unit).

2. System controller (power supply wiring length: within 100 m from the indoor unit).

When the power supply for the schedule timer is taken from the control circuit board of the indoor unit, that indoor unit cannot be used with other control devices using the CZ-T10 terminal. As operation mode and temperature settings are not possible with the schedule timer, it must be used together with a remote controller, a system controller, an intelligent

CONNECTION EXAMPLE 1. (POWER SUPPLY FROM THE INDOOR UNIT)

Six program operations (Operation/Stop/Local permission/ Local prohibition) per day can be set in a program for one week

· Only operation or stop, remote controller local permission or remote controller local prohibition, and their respective combinations are possible. (Operation + local permission, stop + local prohibition, only local permission, etc.)

· Local prohibition and the combination of the three items of temperature setting, mode change, and operation/stop can be set at the time of installation.

A function for pausing the timer in case of national holidays has been added, and timer operation also can be stopped for a long time

· By setting holidays or operation stop within one week, the timer can be paused just for that week.

· All timer settings can be stopped with the timer “ON/OFF effective” button. (Return to timer operation is made by pressing the button again.)

CONNECTION EXAMPLE 2. (POWER SUPPLY FROM THE CENTRAL CONTROLLER)

Remote controller

Schedule timer

Indoor/outdoor operation wire

Zone 1

Centralised addresses

1 to 16

Zone 2

Centralised addresses

17 to 32

Zone 3

Centralised addresses

33 to 48

Zone 4

Centralised addresses

49 to 64

System controller

Schedule timer

Timer group 1: Centralised addresses 1 to 8

Timer group 3: Centralised addresses 17 to 24

Timer group 5: Centralised addresses 33 to 40

Timer group 7: Centralised addresses 49 to 56

Timer group 2: Centralised addresses 9 to 16

Timer group 4: Centralised addresses 25 to 32

Timer group 6: Centralised addresses 41 to 48

Timer group 8: Centralised addresses 57 to 64

ON/OFF controller (CZ-ANC2)

Dimensions

H 121 x W 122 x D 14 + 52

(embedding dimension mm)

Power supply: AC 220 to 240 V

I/O part: Remote input (effective voltage: within DC 24 V): All

ON/OFF

Remote output (allowable voltage: within DC 30 V):

All ON, All alarm

· 16 groups of indoor units can be controlled.

· Collective control and individual group (unit) control can also be performed.

· Up to 8 ON/OFF controller (4 main, 4 sub) can be installed in one link system.

· The operation status can be determined immediately.

Note: As operation mode and temperature settings are not possible with the ON/OFF controller, it must be used together with a remote controller, a system controller etc.

134

VRF SYSTEMS

System controller (CZ-64ESMC2)

Dimensions

H 120 x W 120 x D 21 + 69

(embedding dimension mm)

Power supply:

I/O part:

AC 220 to 240 V

Remote input (effective voltage: DC 24 V): All ON/All OFF

Remote output (voltage-free contact): All ON/All OFF (external Power supply within DC 30 V, max 1 A)

Total wiring length 1 km

Individual control is possible for max. 64 groups, 64 indoor units.

Control of 64 indoor units divided into 4 zones. (One zone can have up to 16 groups, and one group can have up to 8 units.)

Control is possible for ON/OFF, operation mode, fan speed, air flow direction

(only when used without a remote controller), operation monitoring, alarm monitoring, ventilation, remote controller local operation prohibition, etc.

Individual All operations are possible from the remote controller. However, the contents will be changed to the last settings used on the controller.

Central 1 The remote controller cannot be used for ON/OFF. (All other operations are possible from the remote controller.)

Central 3 The remote controller cannot be used for mode change or temperature setting change. (All other operations are possible from the remote controller.)

Central 4 The remote controller cannot be used for operation mode change.

(All other operations are possible from the remote controller.)

A control mode corresponding to the use condition can be selected from 10 patterns

A. Operation mode: Central control mode or remote control mode can be selected

Central control mode: The system controller is used as centralised control device. (Setting from a remote controller can be prohibited by prohibiting local operation from the system controller.)

Remote control mode: The system controller is used as a remote controller. (Setting from the system controller can be prohibited by prohibiting local operation from another central control unit.)

B. Controlled unit number mode: All mode or zone 1, 2, 3, 4 mode can be selected

All mode: All, zone, or group unit can be selected.

Zone 1, 2, 3, 4 mode: Setting is possible only for the indoor units of zone

1, 2, 3, or 4.

CONNECTION EXAMPLE

All mode

Central control mode

All central control

Example 1

B

Controlled unit number mode

Zone 1 mode

Zone 1 central control

Zone 2 mode

Example 2

Zone 2 central control

Zone 3 mode

Zone 3 central control

Example 4

Zone 4 mode

Zone 4 central control

A Operation mode

Remote control mode

All remote control

Zone 1 remote control

Zone 2 remote control

Example 3

Zone 3 remote control

Zone 4 remote control

Example 5

System controller

Control mode example 2: Central control for zone 1

Individual remote controller

Joint use with a remote controller, an intelligent controller, a schedule timer, etc. is possible

(The maximum number of connectable system controllers is 10, including other central controllers on the same circuit.)

(In case of joint use with a wireless remote controller, there are limitations for the control mode. Please use only with “Individual” and “Central 1”.)

System controller

Control mode example 3: Remote control for zone 2

Group control

Control of systems without a remote controller and of main/sub systems (a total of up to 2 units) is possible

External Contacts On Central Controllers

Terminals for remote monitoring:

A1) Input for turning ON air conditioners concurrently

A2) Input for turning OFF air conditioners concurrently

A3) Common input for turning air conditioners ON or OFF

B1) On operation state indicator output

B2) Alarm indicator output

B3) Common indicator output

L1

L2

B3 B2 B1 A3 A2 A1

CND2

C1

C2

C3

C4

System controller

Control mode example 4: Central control for zone 3 Individual remote controller

System controller

System without a remote controller

Control mode example 5: Remote control for zone 4

Control of a group without remote controller

System controller

Control mode example 1: All central control

135

Intelligent controller (CZ-256ESMC2)

Touch panel

H 240 x W 280 x D 138 mm

Power supply AC 100 to 240 V (50 Hz), 30 W

I/O part

(separate power supply)

Remote in put (voltage-free contact): All ON/OFF

Remote output (voltage-free contact): All ON, All alarm (external power supply within DC 30 V, 0.5 A)

Total wiring length: 1 km for each system

Only for embedding in the panel

Limitation contents for prohibited operation

Prohibition means limiting the operations possible from the remote controller. It is also possible to change the prohibition items.

Limitation contents (Limitations can be user defined)

Individual No limits are set for the remote controller operation. However, the contents will be changed to the controller’s last settings.

(Last-pressed priority.)

Prohibition 1 The remote controller cannot be used for ON/OFF. (All other operations are possible from the remote controller.)

Prohibition 2 The remote controller cannot be used for ON/OFF, operation mode change and temperature setting. (All other operations are possible from the remote controller.)

Prohibition 3 The remote controller cannot be used for operation mode change and temperature setting. (All other operations are possible from the remote controller.)

Prohibition 4 The remote controller cannot be used for operation mode change.

(All other operations are possible from the remote controller.)

Note: Avoid joint use of the AMY system and the intelligent controller on the same indoor/ outdoor operation line.

Max. 256 indoor units (4 systems x 64 units) can be controlled. In case of three or more systems, a communication adaptor CZ-CFUNC2 must be installed on the outside

Operation is possible as batch, in zone units, in tenant and in group units

ON/OFF, operation mode setting, temperature setting, fan speed setting, air flow direction setting (when used without a remote controller), and remote controller local operation prohibition

(prohibition 1, 2, 3, 4)

A system without a remote controller is possible. Joint use with a remote controller or a system controller is also possible

Use of a schedule timer and holiday setting also can be done

Proportional distribution of the air conditioning energy is possible.

Including csv-file export via CF-card (supplementary accessory)

NEW function: Pulse signal input from electric/gas consumption meter

In case of joint use with a wireless remote control system, there are limitations for the control mode. Please use only with

“Permission” and “Prohibition 1”.

Web application

INTELLIGENT

CONTROLLER

CZ-256ESMC2

System signal x 4

RS 485

(Polarity shield wire)

Linked system No. 1

Linked system No. 2

Linked system No. 3

Communication adaptor

CZ-CFUNC2

Linked system No. 4

System signal x 4

DISPLAY SAMPLE

Max. 4 links can be connected for the indoor/outdoor operation line = Max. 64 indoor units x 4 (256 units) Max. 30 outdoor units x 4 (120 units)

136

VRF SYSTEMS

Web Interface / CZ-CWEBC2

Functions

· Access and operation by Web browser.

· Icon display.

· Language codes available in English, French,

German, Italian, Portguese, Spanish.

· Individual control possible (max. 64 indoor units)

ON/OFF operation mode, set temperature, fan speed, Flap set, timer on/off alarm code monitoring, prohibit Remote Control.

· Zone control*.

· All Units control.

· Alarm Log.

(HxWxD): 248x185x80 mm

AC 100 to 240 V (50/60Hz), 17 W

(separate power supply)

· Mail Sent Log.

· Program Timer set 50 daily timers with 50 actions each day, 50 weekly timers 50 weekly timers, 1 holiday timer, 5 special day timers, for each tenant

· Prohibit Remote Control settings.

· IP ADDRESS could be changed via Internet.

Note: It is recommended to install a remote controller or a system controller on site to enable local control if it network experience a problem.

Easy to set to every room by recognizable icon and user-friendly remote control window

· If any of the indoor units is selected, the remote control window shown will be displayed for detailed setting modifications.

Easy to manage and monitor each tenant use*

· Each floor or tenant, otherwise each zone can be displayed and controlled.

· All unit statuses can also be displayed on one screen.

Program Timer set

· 50 daily timers with 50 actions each day, 50 weekly timers, holiday timer,

5 special day timers, for each tenant.

* Web interface system not applicable for load distribution.

WEB INTERFACE

(CZ-CWEBC2)

LAN (10/100BASE-T)

Link system

Maximum number of connections:

Indoor units: 64

Outdoor units: 30

Link system

(Indoor/outdoor control wire): 1

Web Interface Device (CZ-CWEBC2)

E mail Send

(alarm data)

LAN

Web Interface Device

Functions

· Access and operation by Web browser.

· Icon display.

· Language codes available in English, French, German, Italian, Portuguese,

Spanish.

· Individual control possible (max. 64 indoor units) ON/OFF operation mode, set temperature, fan speed, Flap set, timer on/off alarm code monitoring, prohibit Remote Control.

· Each Tenant (Zone) control.

· All Units control.

· Alarm Log.

· Mail Sent Log.

· Program Timer set 50 daily timers with 50 actions each day, 50 weekly timers 50 weekly timers, 1 holiday timer, 5 special day timers, for each tenant.

· Prohibit Remote Control settings.

· IP ADDRESS could be changed via Internet.

Note: it is recommended to install a remote controller or a system controller on site to enable local control if IT network experiance a problem.

PC (field supply)

137

Seri-Para I /O unit for outdoor unit (CZ-CAPDC2)

· This unit can control up to 4 outdoor units.

· From the central control device, mode changing and batch operation/batch stop are possible.

· Required for demand control.

SYSTEM EXAMPLE

Seri-para I/O

Dimensions H 80 x W 290 x D 260 mm

Power supply Single phase 100/200 V (50/60 Hz), 18 W

Input Batch operation/Batch stop (non-voltage contact/DC 24 V, pulse signal). Cooling/Heating (non-voltage contact/static signal). Demand 1/2 (non-voltage contact/static signal) (Local stop by switching)

Output Operation output (non-voltage contact). Alarm output (non-voltage contact)

Wiring length Indoor/Outdoor operation lines: Total length 1 km. Digital signal: 100 m or shorter

Local adaptor for ON/OFF control (CZ-CAPC2)

· Control and status monitoring is possible for individual indoor unit (or any external electrical device up to 250 V AC, 10 A) by contact signal.

SYSTEM EXAMPLE

CZ-CAPC2

ON/OFF controller For example: fan coil unit etc.

Total heat exchanger unit.

CZ-CAPBC2 Parallel interface 0 -10 V

· Control and status monitoring is possible for individual indoor unit (1 group).

· In addition to operation and stop, there is a digital input function for air speed and operation mode.

· Temperature setting and measuring of the indoor suction temperature can be performed from central monitoring.

· The analog input for temperature setting is 0 to 10 V, or 0 to 140 Ohm.

· Power is supplied from the CZ-T10 terminal of the indoor units.

· Separate power supply also is possible (in case of suction temperature measuring).

SYSTEM EXAMPLE

Remote station

CZ-CAPBC2

Central control panel

138

VRF SYSTEMS

P-AIMS. Panasonic Total Air Conditioning Management System

P-AIMS Basic software / CZ-CSWKC2

~ Up to 1024 indoor units can be controlled by one PC ~

Functions of basic software

· Standard remote control for all indoor units.

· Many timer schedule programs can be set on the calender.

· Detailed information display for alarms.

· CSV file output with alarm history, operating status.

· Automatic data backup to HDD.

With 4 upgrade packages the basic software can be upgraded to suit individual requirements

P-AIMS is suitable for large shopping centers and universities with many areas/ buildings. 1 “P-AIMS” PC can have 4 independent systems at once.

Each system can have max. 8 C/A units, and control max. 512 units. In total, 1024 indoor units can be controlled by 1 “P-AIMS” PC.

USER PC

USB LINE

CONVERTER

(FIELD SUPPLY)

RS485 (POLARIZED)

BUILDING A

CZ-CFUNC2

PC Environment:

XP Professional

CPU: Pentium 2.8 GHz or over

Memory: 2 GB or over

HDD: 100 GB or over

· Wiring length (PC~C/A) Max. 1 km

· Max. 8 C/A for 1 system

· Wiring length for each link from C/A Max. 1 km

CZ-CFUNC2

CZ-CFUNC2

BUILDING D

CZ-CFUNC2

P-AIMS optional software CZ-CSWAC2 for Load distribution

Load distribution calculation for each tenant

· Air-conditioner load distribution ratio is calculated for each unit (tenant) with used energy consumption data (m³, kWh).

· Calculated data is stored as a CSV type file.

· Data from the last 365 days is stored.

P-AIMS optional software CZ-CSWWC2 for Web application

Web access & control from remote station

· Accessing P-AIMS software from remote PC.

· You can monitor/operate ECOi 6N system by using Web browser (Internet

Explorer).

P-AIMS optional software CZ-CSWGC2 for Object layout display

Whole system can be controlled visually

· Operating status monitor is available on the layout display.

· Object’s layout and indoor unit’s location can be checked at once.

· Each unit can be controlled by virtual remote controller on the display.

· Max. 4 layout screens are shown at once.

P-AIMS optional software CZ-CSWBC2 for BACnet software interface

Connectable to BMS system

· Can communicate with other equipment by BACnet protocol.

· ECOi 6N system can be controlled by both BMS and P-AIMS.

· Max. 255 indoor units can be connected to 1 PC (that has P-AIMS basic

& BACnet software).

139

INTERNET CONTROL. CONTROL YOUR AIR CONDITIONING SYSTEM WITH YOUR SMART DEVICE

-SMARTPHONE & INTERNET FOR VRF SYSTEMS

NEW

Internet

Control

Ready

CONTROL YOUR

AIR CONDITIONING FROM

EVERYWHERE

OPTIONAL

INTERNET CONTROL

Reference PA-RC2-WIFI-1 KX-UT670 Smart Desktop Phone from Panasonic.

Control your comfort and effi ciency with the lowest energy consumption

What’s Internet Control?

Internet Control is a next generation system providing a user-friendly remote control of air conditioning or heat pump units from everywhere, using a simple Android or iOS smartphone, tablet or PC via internet.

Simple Installation

Just connect the Internet Control device to the air conditioner or heat pump with the supplied wire and then link it to your WIFI Access point.

Internet Control. Easy to install. Maximum benefit

Internet Control is underlined with the slogan “Your home in the cloud”, meaning a simple and easy to handle solution has been considered for every user to manage the device, not requiring any communication or computer skills.

No servers. No adaptors. No wires. Just a small box is needed to be connected and placed close to the air conditioning indoor unit… and your smartphone, tablet or PC.

Start the App from your smartphone device, your tablet or your computer, and enjoy a new experience in comfort. An intuitive and user-friendly application on the screen of your smartphone or PC that lets you manage the air conditioning unit in the same way you do with the remote controller.

Internet Control can be downloaded in Apple’s AppStore and Android’s

PlayStore.

Study Case. Paul, Business Man

“My business is growing but I still want to feel like I’m in control. So I carry out all the arrangements, transactions and operations I can from my mobile. From bank transactions, processing orders, to controlling the temperature at the company’s different plants; I do everything from my smartphone thanks to

IntesisHome and Panasonic.”

TAKE CONTROL FROM WHEREVER YOU ARE!

Internet

Control

Ready

OPTIONAL

INTERNET CONTROL

COMPUTER SMARTPHONE TABLET HOME OFFICE STREET WORK GYM

Home or Office

Control your air conditioning with the smart internet control device via smartphones, tablet, PC and smart desktop phone via internet

Offering the same functions as if you were at home or office: start/stop,

Mode Operation, Set Temperature, Room Temperature etc as well as the new, advanced functionality provided by Internet Control to achieve the best comfort and efficiency with the lowest energy consumption.

140

INTERNET service in the cloud*

INTERFACE

WIFI

AIR

CONDITIONING

ROUTER WIFI

* Functionalities depend on the license. The information indicated above is subject to changes and updates.

VRF SYSTEMS

ECOi ANG GHP CONNECTIVITY. NEW PLUG AND PLAY INTERFACE CONNECTED DIRECTLY TO

THE P-LINK

Easy

control by BMS

CONNECTIVITY

Great flexibility for integration into your KNX /

EnOcean / Modbus / LonWorks / BACnet projects allows fully bi-directional monitoring and control of all the functioning parameters

Panasonic Partners have designed solutions specifically for Panasonic air conditioners, and provide complete monitoring, control and full functionality of the entire Commercial line-up from

KNX / EnOcean / Modbus / LonWorks / BACnet installations.

For more information, contact Panasonic.

INTERFACE

CZ-CFUNC2

Communication adaptor (CZ-CFUNC2)

This communication interface is required to connect a ECOi and GHP systems to a BMS. An additional interface is needed to convert the information into KNX/

Modbus/Bacnet language. CZ-CFUNC2 is very easy to operate and to connect to the Panasonic P-link, which is the ECOi bus. From the CZ-CFUNC2, all the indoor and outdoor units of the installation can be easily control. Two linked wiring systems can be connected to one CZ-CFUNC2.

Dimensions: H 260 x W 200 x D 68 mm

* As this is not a splash-proof design, it must be installed indoors or in the control panel, etc.

ECOi / PACi

Indoor Units

ECOi P-Link

PANASONIC MODEL NAME INTERFACE

PAW-RC2-KNX-1i KNX

PAW-RC2-MBS-1

PAW-RC2-ENO-1i

Modbus RTU*

EnOcean

PA-RC2-WIFI-1

PAW-AC-KNX-64

PAW-AC-KNX-128

PAW-TM-MBS-RTU-64

IntesisHome

KNX**

KNX**

Modbus RTU**

PAW-TM-MBS-TCP-128

PAW-AC-BAC-64

PAW-AC-BAC-128

CZ-CLNC2

PAW-AC-FIDELIO

Modbus TCP**

Bacnet**

Bacnet**

Lonworks

Fidelio**

* Interface Modbus RTU/TCP is needed in case if Modbus TCP connection.

** Interface CZ-CFUNC2 needed.

CONNECTED ON P-LINK OR IN THE INDOOR UNIT MAX NUMBER OF INDOOR UNITS CONNECTED

Indoor unit 1 (1 Group of Indoor units)

Indoor unit

Indoor unit

1 (1 Group of Indoor units)

1 (1 Group of Indoor units)

Indoor unit

P-link

P-link

P-link

1 (1 Group of Indoor units)

64

128

64

P-link

P-link

P-link

P-link

P-link

128

64

128

16 groupes of max. 8 indoor units, in total max. 64 indoor units

128

141

EXAMPLE OF BMS CONNECTION FOR AIR CONDITIONER CENTRAL CONTROL SYSTEM

RS485/RS232C

Adaptor

(Field supply)

BMS interface

(see interfaces available on P149) Communication adaptor

(RS-485)

(RS-232C)

CZ-FUNC2

Outdoor unit

Group control

Max. 64 I/D

Remote controller

CZ-FUNC2

Outdoor unit

Remote controller

CZ-FUNC2

Outdoor unit

Remote controller

Group control

Group control

Max. 64 I/D

A/C unit settings

A/C unit status

Max. 16 system

Connectable I/D units: Max. 512

Outdoor unit

Unit ON/OFF

Mode-change

Room temperature setting

Fan speed setting

Flap setting

Central control setting

Filter-sign clear

Alarm reset

Unit ON/OFF status

Operation mode

Setting temperature

Fan speed status

Flap status

Central control setting

Filter-sign situation

Correct/incorrect status

Alarm code

Remote controller

142

VRF SYSTEMS

ECOi CONNECTIVITY INDOOR UNITS

PCB’S AND CABLES FOR PACi/VRF INDOOR UNITS

NAME OF THE CABLES

CZ-T10

FUNCTION

All T10 functions

PAW-FDC

PAW-OCT

Operate external fan

All option monitoring signals

CZ-CAPE2

PAW-EXCT

NAME OF THE PBC

PAW-T10

PAW-T10V

Option monitoring signals wo. fan

Forced Thermo OFF/Leakage D.

FUNCTION

All T10 functions

All T10 functions + powermonitoring

PAW-T10H

PAW-T10HW

PAW-PACR2

PAW-PACR3

PAW-ECF

ON/OFF; Prohibit 5VDC & 230VAC

ON/OFF; Prohibit 5VDC

Redundancy of 2 systems; T monitor

Redundancy of 3 systems; T monitor

Fan speed control external EC fan

COMMENT

Requires field supplied accessory

Requires field supplied accessory

Requires field supplied accessory

Requires aditional wires from spare part supply

Requires field supplied accessory

COMMENT

Allows easy connection “Plug & Play”

Same like PAW-T10 + monitoring the power supply of indoor unit

Specials for single hotel card or window contact

For hotel card + window contact at same time

Redundancy of 2 PACi systems including temperature monitoring an equal operating time

Redundancy of 3 PACi systems including temperature monitoring an equal operating time

For external production Air Curtain units allow the EC fan control by standard VRF IU PCB

T10 connector (CN015)

CZ-T10: Panasonic has developed an optional accessory (consisting of plug + wires) called CZ-T10 to enable an easy connection to this T10 connector.

Connecting an ECOi indoor unit to an external device is easy. The T10 terminal featured in the electronic circuit board of all indoor units enables digital connection to external devices.

EXAMPLE OF APPLICATIONS

T10 terminal Specification (T10: CN015 at indoor unit PCB)

· Control items: 1. Start/stop input

2. Remote controller prohibit input

3. Start signal output

4. Alarm signal output

1-2 (pulse input)

300 ms or more

+12

4-5 (output)

Unit condition

ON OFF ON

NOTE: The wire length from indoor unit to the Relay must be within 2.0 m. Pulse signal changeable to static with JP cutting. (Refer to JP001)

Usage Example

Forced OFF control

Term 1 & 2: Free contact for ON/OFF signal (cut *JP1* for static signal) when the hotel card is it connected the contact must be close (the unit can be used).

Term 2 & 3: Free contact to prohibit all function in the remote controller install in the room when the hotel card is it removed the contact must be closed (the unit can not work).

Terminal = T10

ON / OFF

COMMON

PROIBIT

OPERATION OUTPUT +12 V DC

COMMON

OUTPUT ALARM +12 V DC

4

5

6

1

2

3

RELAY 12 V DC

· Condition

1. 1-2 (Pulse input): Unit ON/OFF condition switching with a pulse signal.

(1 pulse signal: shortage status more than 300 msec. or more)

2. 2-3 (Static input): Open / Operation with Remote is permitted.(Normal condition) Close / Remote controller is prohibited.

3. 4-5 (Static output): 12 V output during the unit ON. / No output at OFF.

4. 5-6 (Static output): 12 V output when some errors occur / No output at normal.

· Example of wiring

1

COM 2

COM

3

4

5

6

+12 V

T10 (yellow)

Operation ON/OFF signal output

· Condition:

4-5 (Static output): 12 V output during the unit ON / No output at OFF

· Example of wiring

T10 (yellow)

Relay (Field supply)

3

4

1

2

5

6

3

4

1

2

5

6

Central control

Indoor unit control PCB

2 m

NOTE: The wire length from indoor unit to the Relay must be within 2.0 m. Pulse signal changeable to static with JP cutting. (Refer to JP001)

143

Fan Drive Connector (CN017)

PAW-FDC: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-FDC to enable an easy connection to this Fan

Drive Connector (CN017).

Operating the ventilation fan from the remote controller

· Start / stop of external ventilation and total heat exchanger fans

· Works even if indoor unit is stopped

· In case of group control ➔ all fans will operate; no individual control

EXTERNAL FAN ON / OFF

Option Connector (CN060) Output external signals

PAW-OCT: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-OCT to enable an easy connection to this Option Connector (CN060).

With the combination of the T10 and the option CN060 an external control of the I_U is possible!

6P (WHITE): OUTPUTS EXTERNAL SIGNALS AS SHOWN IN THE FIGURE BELOW.

Relay (DC 12V, field supply) (Note)

Fan signal

OPTION

(white)

6

5

4

3

2

1

6

5

4

3

2

1

Heat start signal

DC 12V

Ventilation button

Cool start signal

Indoor unit control PCB (CR1)

Thermostat signal

FAN DRIVE

(2 plug (white))

1

2

1

2

DC 12V

Indoor unit control PCB

Relay (field supply)

To external-control input terminal on ventilation fan

Defrost signal

Note: The relay must be installed at a distance of 2 m or less from the PCB.

EXCT Connector (CN009)

PAW-EXCT: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-EXCT to enable an easy connection to this EXCT Connector (CN009).

A) With static input

STATIC INPUT THERMO OFF ENERGY SAVING

2P plug (red): Can be used for demand control. When input is present, forces the unit to operate with the thermostat OFF.

· Examples of wiring:

EXCT

(2P plug (red))

2

1

2

1

Relay (field supply)

Relay coil signal

Note: The length of the wiring from the indoor unit control PCB to the relay must be 2m or less.

* Lead wire with 2P plug (special—order part: WIRE K/854 05280 75300)

Indoor unit control PCB

B) Example: In connection with a refrigerant sensor

· Signal from leakage detector: non voltage, static.

· Indoor unit setting: Code 0b

1

· Connector for leak detector: EXCT

· Outdoor unit setting:

Signal

Valves close!

Signal

CN009

Leakage!

Signal

· Displayed alarm message P14

Room 1 Room 2

Ref. detector

S

144

VRF SYSTEMS

R22 RENEWAL

AN IMPORTANT DRIVE TO FURTHER REDUCE

THE POTENTIAL DAMAGE TO OUR OZONE

Possible to use on

R22 pipings

R22 RENEWAL

WHY RENEWAL?

It is often said that legislation is ruling our lives but sometimes it is there to help save lives. R22 phase out can be described as one of these and from Jan 1st 2010 the use of Virgin (new) R22 refrigerant was banned within the

European Community.

Panasonic are doing our part

We at Panasonic are also doing our part – recognising that all finances are under pressure at the moment. Panasonic have developed a clean and cost effective solution to enable this latest legislation to be introduced with as minimum an effect on businesses and cash reserves as possible.

The Panasonic renewal system allows good quality existing R22 pipe work to be re-used whilst installing new high efficiency R410A systems.

By bringing a simple solution to the problem Panasonic can renew all Split

Systems and VRF systems; and depending upon certain restrictions we don’t even limit the manufactures equipment we are replacing.

By installing a new high efficiency Panasonic R410A system you can benefit from around 30% running cost saving compared to the R22 system.

The installation can also qualify for the government’s ECA (Enhanced Capital

Allowance Scheme) which enables you to offset the cost against your

Capital Gains Tax.

Yes...

1. Check the capacity of the system you wish to replace

2. Select from the Panasonic range the best system to replace it with

3. Follow the procedure detailed in the brochure and technical data

Simple...

R22 - The reduction of Chlorine critical for a cleaner future

145

VRF RENEWAL

Panasonic’s Renewal system allows a completely new VRF system, indoor and outdoor units, to be installed using the existing systems pipe work.

Panasonic’s advanced technology enables the system to work with previously installed pipe work by managing the working pressure within the system down to R22 (33 bar) levels, this ensures the system works safely and efficiently without loss of capacity.

The new equipment can offer increased COP/EER by using state of the art inverter compressor and heat exchanger technology.

Having contacted your Panasonic supplier regarding pipe work restrictions and gained approval to use the Panasonic Renewal System there are three main tests that have to be carried out to ensure that the system can be used effectively.

Firstly a thorough inspection of the pipe work must be carried out and any damage must be repaired.

Secondly an oil test has to be carried out to ensure that the system has not been subject to a compressor burnout during its lifetime, Lastly a VRF

Renewal Kit (CZ-SLK2) has to be installed within the pipe work to ensure that the system is cleaned of any remnants of oil.

VRF Renewal Kit (CZ-SLK2) and Sight Glass

The following shows an overview of the VRF Renewal Kit (CZ-SLK2) that is required when existing tubing is reused. If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass in accordance with the figure below. It will be used for checking the amount of additional refrigerant charge.

VRF RENEWAL KIT: CZ-SLK2

Outdoor unit

B A

Filter Drier

445 (12, 14, 16 HP)

535 (4,5,6,8, 10 HP)

Charge Port

Indoor unit side

A B

Connecting tube dimensions (Inch mm)

A Ø 1/2 (12.7) (12, 14, 16 HP)

B Ø 3/8 (9.52) (4,5,6,8 10 HP)

Note: If the tube size does not match that of the existing tubing, use a reducer (field supply) to adjust the tube diameter.

Unit: mm

Possible to use on

R22 pipings

R22 RENEWAL

Sight glass (field supply)

If the exact tube length and tube size of the existing tubing are uncertain, attach a sight glass to the liquid tubing, and use it to check whether there is an appropriate amount of additional refrigerant charge.

Attaching the Filter Drier Kit and sight glass

· To adjust the limited pressure level into 3.3 MPa, special setting is necessary at site.

· A filter Drier shall be attached to the liquid tubing of each outdoor unit.

· High-Pressure switches shall be attached to both the liquid and the gas tubings of each outdoor unit.

· There is no need to remove the Filter Drier Kit after a test run is performed because normal operation continues while it is attached. (High pressure switch kit: CZ-PSWK2 (for 2-way and 3-way).

· When attaching the Filter Drier Kit, care shall be taken with reguards to the installation location and orientation of the filter drier and ball valve. If a mistake is made, the refrigerant is the system needs to be recovered when the filter drier is replaced, which will make maintenance difficult.

· Thermal insulation material (field supply: heat resistance of 80 °C or higher and thickness of 10 mm or greater) shall be applied to the Filter Drier Kit.

· The filter drier of the Filter Drier Kit may need to be replaced depending on the condition of the existing unit. Use a Danfoss DMB 164 as the replacement filter drier (field supply).

High-Pressure

S/W

Sight glass (field supply).

If the exact tube lenght and tube size of the existing tubing are uncertain, attach a sight glass to the liquid tubing, and use it to check whether there is an appropriate amount of aditional refrigerant charge.

Gas tubing

Balance tubing

Liquid tubing

VRF Renewal Kit (CZ-SLK2)

146

VRF SYSTEMS

PROCEDURE FOR VRF RENEWAL

Judgment 1 Is the existing pipe work reusable?

Judgment 2 Is the pipe work length and the installation height difference of the existing pipe work within the tolerance ranges of the new system?

Judgment 3 Is the existing pipe work within the ranges of reusable tube size?

Judgment 4 Is the additional refrigerant charge at or below the upper limit?

Judgment 5 Is there a problem with dirt inside the existing pipe work?

Judgments

1 to 4 all ok

Renewal fl ow

Can the existing pipe work be reused?

Yes

Can the existing unit perform cooling operation?

Yes

No

No

Perform cooling operation for at least 15 minutes, and then perform a pump down to recover refrigerant in the existing unit.

New pipe work needs to be installed.

Recover the refrigerant using a refrigerant recovery device.

Remove the existing indoor and outdoor units

Judgment 5

Is there a problem with dirt inside the existing pipe work?

No

Install the new indoor and outdoor units, and attach the VRF Renewal Kit (CZ-SLK2).

If the exact length of the pipe work is uncertain, attach a sight glass to aid charging.

If the gas pipe size of the main pipeing is three sizes larger, add oil. (Judgment 3 item)

Recheck

Recheck

If the existing pipe length and pipe size are uncertain, charge with the minimum amount of additional refrigerant that was calculated in

Judgment 4. Furthermore, determine whether the minimum amount of additional refrigerant charge resulted in an appropriate amount of refrigerant charge for the whole system by checking the system sight glass and system pressures during a cooling test run.

Is there any history of compressor failure in the existing unit?

No

Could the existing unit perform the cooling operation?

Yes

Yes

No

Perform a heating test run.

(1) Operate in heating test run mode for 30 minutes.

(2) Replace the filter driers of all outdoor units.

*Obtain replacement filter driers separately.

Perform a cooling test run.

If the minimum amount of additional refrigerant was added when the exact existing pipe lengths were uncertain, check the condition of flowing refrigerant through the sight glass attached to the liquid pipeing - add as required.

However, the amount of additional refrigerant charge should not exceed the maximum level.

147

BRANCHES AND HEADERS

Dimensions and Tube Sizes of Branches and Headers for 2-Pipe ECOi 6N Systems

Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure.

Outdoor unit side

Indoor unit side

COOLING CAPACITY AFTER DISTRIBUTION

68.0 kW or less

From 68.0 kW to 168.0 kW

22.4 kW or less

From 22.4 kW to 68.0 kW

From 68.0 kW 168.0 kW or less

REMARKS

CZ-P680PH2BM

CZ-P1350PH2BM

CZ-P224BK2BM

CZ-P680BK2BM

CZ-P1350BK2BM

Tubing size (with thermal insulation)

1. CZ-P680PH2BM

For outdoor unit side (Capacity after distribution joint is 68.0 kW or less.)

GAS TUBING

517

232 285

15 30 20 20 15

15 20 30

LIQUID TUBING

200

15 20 20 20 30

10

420

220

25 20 20 15

3

3

1

2 i 28,71 i 25,54 i 22,40 i 19,17

265

288

2. CZ-P1350PH2BM

For outdoor unit side (Capacity after distribution joint is greater than 68.0 kW and no more than 168.0 kW.)

GAS TUBING

20 35

245

500

15

255

35 25 25 20

LIQUID TUBING

200

15 20 20 20 30

10

420 i 16 i 12.81

i 9.64

220

25 20 20 15

1

2

Unit: mm

315

i 31,88

i 28,71

i 25,53

i 22,40

i 19,17

1

3

2

265 i 16 i 12.81

i 9.64

1

2

3

Unit: mm

148

VRF SYSTEMS

3. CZ-P224BK2BM

For indoor unit side (Capacity after distribution joint is 22.4 kW or less.)

GAS TUBING

420

3 4 5 6

6 5 4 3 2

100

5 4 3 2

LIQUID TUBING

1 2 3

4. CZ-P680BK2BM

For indoor unit side (Capacity after distribution joint is greater than 22.4 kW and no more than 68.0 kW.)

GAS TUBING

LIQUID TUBING

517 320

5 6 7 8

8 7 6 5 4 3

115

1 2 3 4

8 7 6 5 4 3

300

3 2 1

90

3 2 1

4 3 2 1

80

4 3 2 1

5. CZ-P1350BK2BM

For indoor unit side (Capacity after distribution joint is greater than 68.0 kW and no more than 168.0 kW.)

GAS TUBING LIQUID TUBING

500

7 8

1 2 3

Adat 4

11 9 8 7

120 3 4 5 6

Adat 69

7 8 9

8 9 11

7 6 5 4 3

Adat 25

420

Unit: mm

Unit: mm

6 5 4 3 2

100

5 4 3 2

Unit: mm

3

4

5

DIAMETERS

1

2

6.35 mm 1/4’’

9.52 mm 3/8’’

12.70 mm 1/2’’

15.88 mm 5/8’’

19.05 mm 3/4’’

8

9

10

DIAMETERS

6

7

22.40 mm 7/8’’

25.40 mm 1’’

28.57 mm 1’’ 1/8

31.75 mm 1’’ 1/4

34.92 mm 1’’3/8

DIAMETERS

11

12

13

14

38.10 mm 1’’1/2

41.28 mm 1’’5/8

44.45 mm 1’’3/4

50.80 mm 2’’

149

BRANCHES AND HEADERS

Dimensions and Tube Sizes of Branches and Headers for 3-Pipe ECOi 6N Systems (MF2)

Optional Distribution Joint Kits

See the installation instructions packaged with the distribution joint kit for the installation procedure.

MODEL NAME

For outdoor unit

For indoor unit

CAPACITY AFTER DISTRIBUTION JOINT

68.0 kW or less

REMARKS

CZ-P680PJ2BM greater than 68.0 kW and no more than 135.0 kW CZ-P1350PJ2BM

22.4 kW or less CZ-P224BH2BM greater than 22.4 kW and no more than 68.0 kW CZ-P680BH2BM greater than 68.0 kW and no more than 135.0 kW CZ-P1350BH2BM

1. CZ-P680PJ2BM

For outdoor unit side (Capacity after distribution joint is 68.0 kW or less.)

GAS TUBING

295

8 7 6 5

DISCHARGE TUBING

295

8

8

6

7

5

8

7 6 5 4

216

6 7 8

8

7

6

5

4

7

206

8

7

7

8

LIQUID TUBING

3

5

2

4

6

380

6 5 4 3 2

165

Unit: mm

2. CZ-P1350PJ2BM

For outdoor unit side (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW.)

SUCTION TUBING

375

8 7 6 5

DISCHARGE TUBING

330

8 8

LIQUID TUBING

210

9 11

11

8

7

6

5

9

308

100

8 9

9 11 8 7 6 5

7 8

8

7

6

5

8

242

9

260

9

165

3

5

380

2

4

6

6 5 4 3 2

Unit: mm

150

VRF SYSTEMS

3. CZ-P224BH2BM.

For outdoor unit side (Capacity after distribution joint is 22.4 kW or less.)

SUCTION TUBING DISCHARGE TUBING

290

210

4 5

5 4 3

142

4 3

5

4

3

LIQUID TUBING

3

4

3 4

107

2 3

2

3

235

3 2

68

Unit: mm

4. CZ-P680BH2BM.

For outdoor unit side (Capacity after distribution joint is greater than 22.4 kW and no more than 68.0 kW.)

SUCTION TUBING DISCHARGE TUBING LIQUID TUBING

408 388

8 7 6 5

2

3

4

5

6

5 6 7 8

266 266

8

5

4

7

6

7

6

5

4

3

380

6 5

4 3 2

165

Unit: mm

5. CZ-P1350BH2BM.

For outdoor unit side (Capacity after distribution joint is greater than 68.0 kW and no more than 135.0 kW.)

SUCTION TUBING

LIQUID TUBING

5

6

7

8

11

193

DISCHARGE TUBING

5

4 3

(quantity 2)

7

8

5

6

11

193

11 8 7 6 5

11 8 7 6 5

400

400

2

3

4

5

6

380

6 5

4 3 2

165

Unit: mm

3

4

5

DIAMETERS

1

2

6.35 mm 1/4’’

9.52 mm 3/8’’

12.70 mm 1/2’’

15.88 mm 5/8’’

19.05 mm 3/4’’

8

9

10

DIAMETERS

6

7

22.40 mm 7/8’’

25.40 mm 1’’

28.57 mm 1’’ 1/8

31.75 mm 1’’ 1/4

34.92 mm 1’’3/8

DIAMETERS

11

12

13

14

38.10 mm 1’’1/2

41.28 mm 1’’5/8

44.45 mm 1’’3/4

50.80 mm 2’’

151

Header pipe set for ECOi 6N 2-Pipe system

Header pipe models for 2-Pipe systems:

CZ-P4HP4C2BM

576

11 10 9

6 7 8 9

5

4

3

569

3 4 5

2

1

3 4 5

8

9

10

11

6

7

4

5

2

3

DIAMETERS

1 6.35 mm

9.52 mm

12.70 mm

15.88 mm

19.05 mm

22.40 mm

25.40 mm

28.57 mm

31.75 mm

34.92 mm

38.10 mm

1

2

Header pipe set for ECOi 6N 3-Pipe system

Header pipe model for 3-Pipe systems:

CZ-P4HP3C2BM

576

6 7 8 9

3

4

5

576

6 7 8 9

3

4

5

569

1/4’’

3/8’’

1/2’’

5/8’’

3/4’’

7/8’’

1’’

1’’ 1/8

1’’ 1/4

1’’3/8

1’’1/2

152

VRF SYSTEMS

CONTROL EQUIPMENT EXTERNAL DIMENSIONS

TIMER REMOTE CONTROLLER

(CZ-RTC2)

WIRELESS REMOTE CONTROLLER SEPARATE RECEIVER FOR

WIRELESS REMOTE CONTROLLER

4.4 x 9.4 slot

SIMPLIFIED REMOTE CONTROLLER

(CZ-RE2C2)

REMOTE SENSOR

(CZ-CSRC2)

SYSTEM CONTROLLER

(CZ-64ESMC2)

INTELLIGENT CONTROLLER

(CZ-256ESMC2)

4.4 x 9.4 slot

COMMUNICATION ADAPTER

(CZ-CFUNC2)

290

270 80

ON/OFF CONTROLLER

(CZ-ANC2)

¿22.2

SERI-PARA I/O UNIT FOR EACH INDOOR UNIT

(CZ-CAPBC2)

R 2.5

R 5

LONWORKS INTERFACE

(CZ-CLNC2)

Potbellied hole (4 locations)

3 - Ø 30 hole

4 - Ø 5 hole

Detail of the potbellied hole

SERI-PARA I /O UNIT FOR OUTDOOR UNIT

(CZ-CAPDC2)

Magnified view

153

VRF INDOOR UNITS DIMENSIONS

U1 TYPE // 4-WAY 90x90 CASSETTE

Type

1 Air intake grill

2 Air discharge outlet

3 Refrigerant piping (liquid pipes)

4 Refrigerant piping (gas pipes)

5 Drain outlet VP50

6 Power supply port

7 Discharge duct

8 Suspension bolt hole

9 Fresh air intake duct connection port

36-50

Ø6.35 (flared)

Ø12.7 (flared)

60-140

Ø9.52 (flared)

Ø15.88 (flared) outer Ø32

Ø150

4-12x30 slot

Ø100¹

1 Air inlet kit is necessary.

Flter size: 520 x 520 x 16

(ceiling opening dimension)

(suspension bolt pitch)

Type

A

B

36-71

256

124

100-140

319

187

X VIEW

Less than Less than

Burring hole Less than

Burring hole

Adjust the suspension bolt length so that the gap from the lower ceiling surface becomes 30 mm or more (18 mm or more from the lower surface of the body) as shown in the figure. When the suspension bolt length is long, it hits the ceiling panel and installation is not possible.

Y1 TYPE // 4-WAY 60x60 CASSETTE

1 Air intake

2 Discharge outlet

3 Refrigerant piping (liquid pipes)

Size 22 to 56: Ø 6.35 (flared)

4 Refrigerant piping (gas pipes)

Size 22 to 56: Ø 12.7 (flared)

5 Drain tube connection port VP20 (outer Ø 26)

6 Power supply port

7 Suspension bolt hole (4-12 x 30 hole)

8 Fresh air intake duct connection port (Ø 100)

(ceiling opening dimension)

(suspension bolt pitch)

Panel center

A view

Less than 25 Less than 25

The length of the suspension bolts should be selected so that there is a gap of 30 mm or the ceiling (17 mm or more below the lower surface of the main unit), as shown in the figure at right. If the suspension bolt is too long, it will contact the ceiling panel and the unit cannot be installed.

Dimensions: mm

154

VRF SYSTEMS

L1 TYPE // 2-WAY CASSETTE

1 Refrigerant liquid line (Ø 9.52)

2 Refrigerant gas line (Ø 15.88)

3 Drain connection (25 A. O.D. 32 mm)

4 Power supply entry

Inspection Panel

For Drain Pump

Panel Center

3

2

110

30 70

Inspection Panel

For Ecv, Drain Pan

1

4

40

70

20

80

70

5 9 0

1140

1320

1360

6 3 0

For Discharge Duct

(2-Ø 150 Hole)

Suspension Holes

Ceiling Opening (1320 X 640)

Fresh Air Intake

(For Ø 125 Duct Flange)

102

680

23

1360

Dimensions: mm

D1 TYPE // 1-WAY CASSETTE

1 Air intake grille

2 Air outlet

3 Refrigerant piping (liquid pipes)

Sizes 28 to 56: Ø 6.35 (flared)

Size 73: Ø 9.52 (flared)

4 Refrigerant piping (gas pipes)

Type 28 to 56: Ø 12.7 (flared)

Type 73: Ø 15.88 (flared)

5 Drain connection VP25 (outer Ø 32)

6 Power supply entry

7 Discharge duct connetcion port (for descending ceiling)

8 Wireless remote control receiver (option)

9 Suspension mounting (4-12 x 30 slot)

10 Fresh air intake (Ø 100)

(suspension bolt pitch)

(ceiling opening dimension)

Dimensions: mm

155

VRF INDOOR UNITS DIMENSIONS

F2 TYPE // VARIABLE STATIC PRESSURE HIDE AWAY

S-22MF2E5 // S-28MF2E5 // S-36MF2E5 // S-45MF2E5 // S-56MF2E5

Filter

1 Refrigerant tubing joint (liquid tube) Ø6.35 flare

2 Refrigerant tubing joint (gas tube) Ø12.7 flare

3 Upper drain port VP25 (O.D. Ø32 mm)

200 flexible hose supplied

4 Bottom drain port VP 25 (O.D. Ø32 mm

5 Suspension lug (4-12 x 30 mm)

6 Power supply outlet

7 Fresh air intake port (Ø150 mm)

8 Flange for flexible air outlet duct

9 Electrical component box

172

7

5

54

71

867

8

12 -

 3 holes

150 x 3 = 450

800

(Suspension bolt pitch)

71

592

(Flange O.D.)

154

33

(150)

(75)

Inspection acces

450 x 450

(Field supply)

6

35

3

9

26

4

89

1

23

27

130 70

140

186

290

23

2

S-60MF2E5 // S-73MF2E5 // S-90MF2E5

Filter

172

156

1 Refrigerant tubing joint (liquid tube) Ø9.52 flare

2 Refrigerant tubing joint (gas tube) Ø15.88 flare

3 Upper drain port VP25 (O.D. Ø32 mm)

200 flexible hose supplied

4 Bottom drain port VP 25 (O.D. Ø32 mm

5 Suspension lug (4-12 x 30 mm)

6 Power supply outlet

7 Fresh air intake port (Ø150 mm)

8 Flange for flexible air outlet duct

9 Electrical component box

7

5

21

54

8

16 -  3 holes

150 x 5 = 750

1000

1067

(Suspension bolt pitch)

792

(Flange O.D.)

150

21

154

33

(150)

(75)

Inspection acces

450 x 450

(Field supply)

6

35

3

9

26

4

89

1

23

27

130 70

140

186

290

23

2

Dimensions: mm

VRF SYSTEMS

F2 TYPE // VARIABLE STATIC PRESSURE HIDE AWAY

S-106MF2E5 // S-140MF2E5 // S-160MF2E5

Filter

172

7

1 Refrigerant tubing joint (liquid tube) Ø9.52 flare

2 Refrigerant tubing joint (gas tube) Ø15.88 flare

3 Upper drain port VP25 (O.D. Ø32 mm)

200 flexible hose supplied

4 Bottom drain port VP 25 (O.D. Ø32 mm

5 Suspension lug (4-12 x 30 mm)

6 Power supply outlet

7 Fresh air intake port (Ø150 mm)

8 Flange for flexible air outlet duct

9 Electrical component box

5

54

71

8

20 -

 3 holes

1467

150 x 7 = 1050

1400

(Suspension bolt pitch)

1192

(Flange O.D.)

150

71

33

(150)

154

(75)

Inspection acces

450 x 450

(Field supply)

6

35

3

9

26

4

89

1

23

27

130 70

140

186

290

23

2

Dimensions: mm

157

VRF INDOOR UNITS DIMENSIONS

M1 TYPE // SLIM VARIABLE STATIC PRESSURE HIDE AWAY

1 Refrigerant tubing joint (narrow tube)

2 Refrigerant tubing joint (wide tube)

3 Upper and bottom drain port (O.D. 26 mm)

4 Suspension lug

5 Power supply outlet (2- Ø 30)

6 Flange for air intake duct

7 Pl cover

8 Electrical component box

9 Frame filter

10 Signal output board (ACC-SG-AGB: optional)

Inspection access

Inspection access

(450 x 450)

Field supply

Hole

(suspension bolt pitch)

Inspection access panel

Ceiling

Hole

Hole

(air discharge spave)

View A. Frame Filter Uninstalled

E1 TYPE // HIGH STATIC PRESSURE HIDE AWAY

1 Refrigerant piping (liquid pipes) Ø 9.52

2 Refrigerant piping (gas pipes) Ø 22.22

3 Power supply outlet (Ø 25 grommet, rubber)

4 Power supply outlet (spare) (Ø 30 knock-out)

5 Drain port 25 A, male thread

6 Duct connection for suction

7 Duct connection for discharge or more (service space)

View in direction of arrow X holes (entire circumference)

Dimensions: mm

Inspection port pitch

(suspension bolt pitch) holes (entire circumference) holes (entire circumference)

Dimensions: mm

158

VRF SYSTEMS

T1 TYPE // CEILING

1 Drain port VP20 (inner Ø 26, hose accessory)

2 Drain for left piping

3 Upper piping outlet port (knock-out hole)

4 Right piping oulet port (knock-out hole)

5 Drain left piping outlet port (knock-out hole)

6 Power supply entry port (knock-out hole Ø 40)

7 Remote controller wiring inlet port

8 Wireless remote control receiver mounting part

36-56 type 73 type

A (body) 910

B (suspension bolt pitch) 855

1,180

1,125

9 Refrigerant gas piping

Type 36 to 56: Ø 12.7

Type 73 to 140: Ø 15.88

10 Refrigerant liquid piping

Type 36 to 56: Ø 6.35

Type 73 to 140: Ø 9.52

106-140 type

1,595

1,540

Air intake

Air outlet or more or more

(service space)

(suspension bolt pitch)

Front or more

(service space)

Dimensions: mm

159

VRF INDOOR UNITS DIMENSIONS

K2/K1 TYPE // WALL MOUNTED

Indoor unit:

S-22MK2E5 / S-28MK2E5 / S-36MK2E5

214

870

Indoor unit:

S-45MK1E5 / 56MK1E5 / 73MK1E5 / 106MK1E5

1065

1 Refrigerant tubing (liquid tube) 45-56 / 73-106 type Ø6.35 / Ø9.52 (flared)

2 Refrigerant tubing (gas tube) 45-56 / 73-106 type Ø12.7 / Ø15.88 (flared)

3 Drain hose VP13 (outer dia. Ø18)

4 Rear panel (PL BACK)

5 Tubing and wiring holes (Ø80)

160

11 67

5cm

67

86

7.5cm

Front view

5cm

230

60

(2.5)

197.4

2 Gas tube

1 Liquid tube

140

3 8 4 .

3

9 5

4 5 0

3 Drain hose

148.7

9 5

230.7

2 0 0

(Ø80)

158

415

439.8

496.8

(Ø80)

415

448.2

568.2

4

Rear panel

132

5

Tubing and wiring holes

Dimensions: mm

VRF SYSTEMS

P1 TYPE // FLOOR STANDING

1 4 x Ø 12 holes (for floor fixing)

2 Power supply outlet

3 Air filter

4 Refrigerant piping (liquid pipes)

5 Refrigerant piping (gas pipes)

6 Level adjustment bolt

7 Drain outlet VP20 (with vinyl hose)

8 Refrigerant piping connection port (bottom or rear)

9 Operation switch mounting part

10 Electric equipment box

11 Accessory copper pipe for gas pipe connection

Indoor unit A

22 to 36 type 1,065

45 type

56 type

71 type

1,380

B

665

980

C

632

947

Liquid pipes Gas pipes

Ø 6.35

Ø 9.52

Ø 12.7

Ø 15.88

R1 TYPE // CONCEALED FLOOR STANDING

1 4 x Ø 12 holes (for floor fixing)

2 Electric equipment box

3 Power supply outlet

4 Air filter

5 Discharge duct connection flange

6 Refrigerant connection outlet (liquid pipes)

7 Refrigerant connection outlet (gas pipes)

8 Drain filter

9 Drain pan

10 Level adjustment bolt

11 Drain outlet VP20 (with vinyl hose)

Indoor unit A B C D E F

22 to 36 type 904 692 672 665 500 86

45 type

56 type

71 type

1,219 1,007 1,002 980 900 51

Liquid pipes

Gas pipes

Ø 6.35 Ø 12.7

Ø 9.52 Ø 15.88

Knock-out hole

Dimensions: mm

(inner dimension)

(hole pitch=100)

(inner dimension)

Dimensions: mm

161

www.aircon.panasonic.eu

To find out how Panasonic cares for you, log on to: www.aircon.panasonic.eu

Contact Details:

Telephone: 01344 853182 www.panasonic.co.uk/aircon

Address: Panasonic Air Conditioning

Panasonic House

Willoughby Road

Bracknell

Berkshire

RG12 8FP