HI-E Dry Vehere Manual.qxp

Add to my manuals
10 Pages

advertisement

HI-E Dry Vehere Manual.qxp | Manualzz

HI-E DRY Vehere

Pool & Spa Humidity Controller

The HI-E DRY Vehere Pool & Spa Humidity Controller featuring FOCUS

TM

Technology is the industries most efficient, durable and economic product for controlling moisture related problems associated with indoor pools, whirlpools, hot tubs, and therapy/lap pools.

Vehere delivers comfort and solves:

• Chemical Odors

• Foggy Windows

• Condensate and Structural

Moisture Problems

• Mold & Mildew

• High Humidity Level

The Vehere with FOCUS

TM

Technology is... Performance, Reliability & Comfort

The Vehere utilizes FOCUS Technology, which dramatically improves performance, product reliability and comfort.

Performance - The Vehere’s FOCUS

Technology is an innovative heat transfer technology offering our customers...

“HI-Efficiency” - A dehumidifier resulting in a compact refrigeration system requiring less electric consumption. Vehere draws less than 12 amps of electricity.

“HI-Capacity” - Vehere’s passive heat transfer process allows the removal of over

192 pounds of water per day! (80°F, 60%

RH). That’s two- three times more water removal per kilowatt-hour of electricity than conventional dehumidifiers.

This ensures the use of a standard 15 Amp electrical outlet and LOW OPERATING COSTS!

Compact - The Vehere’s stainless steel enclosure is corrosion resistant with a built-in fan for low noise operation. The

Vehere features a cabinet mounted or remotely located control, easy-roll casters, and the highest dehumidification capacity available in it’s class.

Reliability

Our compact design uses less refrigerant, which reduces our cost and improves reliability. The Vehere’s HI-Efficiency operation can save thousands of dollars annually.

Comfort

The Vehere provides airflows up to 540

CFM (cubic feet/minute) of Dry Air. This airflow helps reduce foggy windows, mold, mildew and condensate... all reduced to increase indoor occupant comfort!

Figure 1: Features and Benefits

Manual P/N 4025281 | www.BreathePureAir.com | 1-877-688-2703

1

2

Table of Contents

I n

F

P r

1. Intended Application for Vehere

2 e e rt a

.

R o c t e d u a r u u e it c s o it o

& n s rt a n

B it o e n e f ti s

3. Specifications & Capacities

4 .

I

3

4

.

1 n s

.

1 g i s

V t a

L e o h e r e ll a c a it o n it n o s

D i a g r a m n

4.1A Improper Installation

4.1B In humid area, no ducting 3

4.1C In humid area, duct inlet and/or outlet 3

3

3

2

2

2

2

1

1

3

3

5

6

7

8

.

4.1D In remote area, duct inlet & outlet 3

4.2 Mounting the Humidity Sensor/Controller 4

4.3 Electrical Requirements

4.4 Condensate Removal

4

O

5 .

.

p

5

1

8 .

.

3

4

D

.

u

A

R e f o c

D it w ir g e n g u c e e r a

r R it n n g k e p l a ti

4.5B Ducting for Dehumidification e r

5 a

H u it m o n i d ti y C o n rt o l

5.2 Humidity Control Adjustment

5 .

3 F a n S w ti c h

5.4 Automatic Defrost Control

5.5 Automatic Low Pressure Control it o n

.

.

.

V e n t li a

6.1 Ventilation Recommendations

M

7 .

a

1

S e i n r v t

A i i c e n

r e

F i a n tl

8.1 Technical Description

2 T r o u b l c e e r s h o o

t C it n h g a r g i c e m e n g n t

9

1 0

.

8

8

8.5 Low Pressure Control

8

V

.

.

.

e

4

6 h

W a

B

R e r r l r e l e a y

A c c a n t y e s s o ir e s

11. Vehere Electrical Wiring Diagram

6

6

6

6

5

6

5

5

5

5

5

5

4

4

4

4

7

8

7

7

9

7

7

6

6

Read and Save These Instructions

IMPORTANT

Read these installation, operation and service instructions carefully before installing and using this unit. Proper adherence to these instructions is essential to obtain maximum benefit from your Vehere pool & spa humidity controller..

WARNING

• If used near a pool or spa, be certain there is NO chance the unit could roll into the water or be splashed and that it is plugged into a GROUND FAULT INTERRUPTER.

• DO NOT use the Vehere as a bench or table.

• Avoid discharging the exhaust directly at people or pets.

1 Intended Application for Vehere

The intended application for the Vehere is as a pool & spa area humidity sensing controller applied either as a free-standing device directly in the pool area or operated remotely to provide dehumidified air to the pool or spa area using optional ducting and remotely mounting the humidity controller. The Vehere high efficiency dehumidifier utilizes refrigeration to cool an incoming air stream below its dewpoint as it passes through an evaporator coil. This cooling results in the removal of moisture (latent heat). The cooled and dried air is used to pre-cool the incoming air stream resulting in up to a 200 percent increase in overall efficiency.

2 Registrations

The Vehere (P/N 4025276) conforms to UL STD 1995.

Certified to CAN/CSA STD C22.2 No. 236.

3 Specifications

Model: HI-E Dry Vehere (4025276)

Electrical: 110-120 VAC, 12.0 Amps, grounded

(7’ power cord included)

Compressor LRA: 64.5 Amps

Capacity: 184 pints/day @ 80°F, 60% RH

Air Flow: 540 CFM without external ducting

510 CFM @ .15 IWG external static

Refrigerant Charge: 2 lbs., 13 oz. R-22

Optional Duct connections: 12" round inlet & outlet

Size (w/o duct collars): 36.5" Long x 19" Wide x 40" High

Weight: 180 lbs.

Controller Accuracy: +/- 5% RH @ 72°F

Capacities

The Vehere is designed to control humidity for indoor pool (spa, hot tub) areas. It consists of a controller, dehumidifying cooling system, filter, fan and delivers the following dehumidification capacities:

Air Temp/Relative Humidity

80°F/80%RH

82°F/60%RH*

80°F/60%RH

60°F/80%RH

Air Temp/Relative Humidity

80°F/80%RH

82°F/60%RH*

80°F/60%RH

60°F/80%RH

Air Temp/Relative Humidity

80°F/80%RH

82°F/60%RH*

80°F/60%RH

60°F/80%RH

Lbs. Per Hour

10.34

8.336

8.04

7.17

Pints Per Hour

9.92

7.95

7.71

6.67

Lbs. Per Day

248

200

193

172

Pints Per Day

238

191

184

160

BTUs Per Hour KWH Per Day

(derived)

15313

13114

12680

10869

37.1

35.3

34.3

27.5

*ASHRAE Recommended Conditions

HI-E DRY Vehere Owners Manual

| www.BreathePureAir.com | 1-877-688-2703

3.1 Vehere Diagram (Fig. 2)

A - Air Intake B - Humidity Sensor/Control

C - Filters D - Air Exhaust E - Fan Switch

F - Power Cord G - Drain Hose

36.5”

A

C

C

B

4.1B In Humid Area, No Ducting (Fig. 4)

The simplest installation is to place the Vehere in the pool area with no ducting. The Vehere must be at least 3' from walls and other supply air obstructions. Additionally, the air inlet and outlet must be at least 3’ from any obstruction which blocks airflow.

Vehere

Pool & Spa

Humidity Controller

40”

D

E

G

Figure 2:

Vehere diagram.

F

19”

4 Installation Options

WARNING

WARNING: Do not use open combustion heating appliances

(unless equipped with power exhaust) in a pool room equipped with exhaust fans. Under certain conditions these exhaust fans may cause the backdrafting of toxic combustion by-products which are hazardous to human health and could cause death. We strongly recommend using only closed combustion heating appliances.

4.1 Location

The Vehere can be installed in a variety of locations to meet the owner's needs; other considerations include:

1) Providing access to a 115 VAC power outlet

(7’ power cord is provided).

2) Locating near a floor or other suitable drain

(4’ drain hose included).

4.1A Improper Installation (Fig. 3)

Do not install the Vehere with the exhaust of the unit within

3’ of a wall or obstruction. Do not place the unit near open water.

Figure 4: Installation in humid area with no ducting.

4.1C In Humid Area,

Duct Inlet and/or Outlet (Fig. 5)

If the pool room is very large or has high ceilings, dehumidification can be improved by adding an inlet and/or outlet duct to circulate and destratify stagnant areas. Add inlet or outlet ducting to create flow across the area's greatest length. For areas with ceilings higher than 12', use an inlet duct to draw warm, moist air from near the ceiling. See section 4.5 for attaching duct collars & ducting.

Quiet-Ven t

Quiet-Vent

Exhaust Ventilator

Low = 165 CFM high = 290 CFM for

Dehumidistats

Quiet-Vent remote

and

Vehere

Vehere

Pool & Spa

Humidity Controller

Figure 5: Installation in humid area with ducting.

Direct Warm & Dry Air

Toward Window Glass

3’ Minimum

Exhaust Clearance

Figure 3: Installation clearance requirements.

HI-E DRY Vehere Owners Manual | www.BreathePureAir.com | 1-877-688-2703 3

4.1D In Remote Area, Duct Inlet & Outlet (Fig. 6)

It is often desirable, especially in pool rooms and finished areas, to install the Vehere in an adjacent equipment room or unfinished area. Air is then transferred between the humid room and the unit via ducting. The factory mounted humidity control on the Vehere cabinet may not sense the humidity in the humid room accurately enough with this installation method. Remotely mount the Vehere humidity control in the humid room and wire to the Vehere. Local electrical codes must be followed when rewiring the control. Refer to the

“Mounting the Humidity Sensor/Controller” section which follows.

Direct Warm & Dry Air

Toward Window Glass

Optional Quiet-Vent

Exhaust Ventilator

Low = 165 CFM high = 290 CFM

Dehumidistats for Quiet-Vent and remote Vehere

Quiet-Ven

Vehere

Pool & Spa

Humidity Controller

Figure 6: Installation in remote area with ducting.

4.2 Mounting The Remote Humidity Sensor/Controller

If the Vehere is to be located in a remote location outside the pool or spa area, mounting of the humidity sensor in the space to be conditioned is necessary. If the humidity sensor is not located in the conditioned space, the Vehere will not operate properly.

IMPORTANT

Locate the humidity element on an inside wall, free from drafts, out of direct sunlight, and where the element is not exposed to excessive vibration. Be careful not to drop the unit. Mount the wall mount element at a height of 4 to 6 feet (1.2 to 1.8 m) above the floor.

To mount the HI-E DRY Vehere dehumidistat on a wall for remote application, first remove the cover from the controller by lifting the side of the controller cover over the catch tabs on both sides. The cover comes off easily.

Remove the humidity adjustment knob from the unit by pulling it straight off the control adjustment shaft. The knob is keyed so it only fits on the adjustment shaft one way.

Removing this knob for installation will not alter the calibration of the device. Hold the unit to the surface you would like to mount it on. You will need to mark the locations for two screw holes and one square knockout to accommodate wires and the devices wire guard. The wire-guard tabs fit inside the wall.

Once marked, drill a 1/8” hole for each mounting screw location and tap the provided anchor mount into the hole.

Use the provided screws to then mount the humidity control to the wall. Route the wiring through the hole you have created and connect wires according to the directions found in this manual. Replace humidity adjustment knob. Replace plastic housing.

4.3 Electrical Requirements

The Vehere can be plugged into any grounded 20 Amp circuit. At 80°F, 60% RH, it draws 11.6 Amps. A dedicated

20 Amp circuit is recommended. If an extension cord is required, it must have a minimum of 12 gauge conductors if less than 25 feet long, or 10 gauge conductors if greater than 25 feet long.

4.4 Condensate Removal

Condensate drains by gravity via the clear hose extending from the unit. Route the 4’ drain hose to a floor drain. Use care to keep the hose as flat to the floor as possible. Keep the hose away from walk ways if possible. Excessive humps or kinks will prevent proper drainage. If the Vehere is located too far from a floor drain for the attached hose to reach, inexpensive 1/2" PVC pipe can be used to extend it. It is commonly available in 10' lengths from building supply, plumbing and hardware stores. It will slide tightly inside the end of the drain hose. If more than one length of pipe is required, they can be joined with a short piece cut from the end of the drain hose.

4.5 Ducting

4.5A Ducting kit

The factory installation kit includes two twelve-inch collars to allow ducting to be attached to the inlet and outlet of the Vehere. The 12" collar with three tabs can be attached via the holes provided in the front of the unit, and the 12" flanged collar can be affixed to the top opening.

Figure 7: Mark mounting holes as indicated by arrows.

4

Figure 8: Control connection wires.

Figure 9: Tabbed duct collar is installed around the exhaust outlet.

The flanged duct collar is installed around the intake opening.

HI-E DRY Vehere Owners Manual

| www.BreathePureAir.com | 1-877-688-2703

4.5B Ducting for Dehumidification

Ducting the Vehere as mentioned requires consideration of the following points:

Duct Sizing: For total duct lengths up to 25', use a minimum 10" diameter round or equivalent rectangular.

For longer lengths, use a minimum 12" diameter or equivalent. Grills or diffusers on the duct ends must not excessively restrict airflow.

Isolated Areas: Effective dehumidification may require that ducting be branched to isolated, stagnant areas. Use

8" diameter branch ducting to each of two or three areas; for four or five areas use 6” diameter; or 4" to each of six or more areas.

Round flex duct can be purchased by ordering the following part numbers from the factory:

4020647 4” Flex Duct

4020128 6” Flex Duct

4” x 25’

6” x 25’

4020177 8” Flex Duct 8” x 25’

4022126 10” Flex Duct 10” x 25’

4024750 12” Flex Duct 12” x 25’

5 Operation

5.1 Humidity Sensor/Control (Fig. 10)

The control is an adjustable switch that closes when the relative humidity of the air it senses rises to the dial set point. It opens when the RH drops 4 to 6% below the set point.

5.2 Humidity Control Adjustment

The dehumidifier will run until the desired relative humidity

(RH) matches the control dial setting.

Figure 10:

Vehere humidity sensor/controller.

The humidity controller has been designed for simplicity of use. It is marked “Low”, “Normal” and “High.” These operational settings represent the amount of humidity in the air.

Setting the control to the “Low” setting will result in a lower relative humidity than the “High” setting. We recommend setting the controller at the “Normal” setting and then adjusting as you see fit, moving the controller toward “Low” to lower the humidity and toward “High” to increase the level of humidity in your pool or spa area.

Approximate Humidity Levels Per Setting

“Low”

“Normal” 45% to 55% Relative Humidity (Recommended)

“High”

35% to 45% Relative Humidity

55% to 65% Relative Humidity

A quality humidity meter is recommended to accurately monitor humidity levels. For a quote on a quality humidity meter, contact customer service at 1-800-533-7533.

5.3 Fan Switch

Turning the fan switch ON will cause the unit's internal blower to run continuously, whether the unit is dehumidifying or not.

This function is desirable if the unit is used for air circulation or fresh air ventilation, and to remove/diffuse pool based odors.

Figure 11:

Vehere fan switch.

5.4 Automatic Defrost Control

When the Vehere is used in a cool area, frost may form on the cooling coil as it dehumidifies. When frost forms, our automatic defrost thermostat will periodically turn off the compressor while allowing the blower to run. The blower draws air through the cooling coil and melts the frost. The defrost cycle is automatic and designed for optimum performance above 50°F.

5.5 Automatic Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the low pressure control opens and shuts off the compressor and blower. It is an automatic reset that will close when the pressure rises to 35 PSIG. This feature prevents damage to the compressor. It may also open if the unit is used in a cool area (below 50°F) or stored below 40°F and then started. Under these conditions, the unit will restart within several minutes.

HI-E DRY Vehere Owners Manual | www.BreathePureAir.com | 1-877-688-2703 5

6

6 Ventilation

6.1 Ventilation Recommendations

Ventilation is an important element of pool and spa dehumidification. A negative (exhaust) pressure ventilation system should be used. This ventilation system is operated and installed independently of the Vehere unit and keeps the concentrations of corrosive pool chemicals to a minimum and assists in keeping moisture from penetrating the rest of the structure.

7 Maintenance

7.1 Air Filter

The Vehere is equipped with two, 2” thick, pleated fabric air filters that must be checked regularly. Operating the unit with dirty filters will reduce the humidity controller’s capacity and efficiency and may cause the compressor to cycle off and on unnecessarily on the defrost control. The filters can generally be vacuumed clean several times before needing replacement.

Replacement filters can be ordered from the factory.

8 Service

WARNING

WARNING: Only qualified service people should service this unit. The Vehere has a high-pressure refrigerant system and high voltage circuitry. This could present a hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

8.1 Technical Description

The Vehere uses a refrigeration system to remove heat and moisture from incoming air, and add heat to the air it discharges. Hot, high-pressure refrigerant gas is routed from the compressor to the condenser coil. The refrigerant is cooled and condensed by giving up its heat to the air it discharges from the unit. The refrigerant liquid then passes through two capillary tubes, which cause the refrigerant pressure and temperature to drop. It next enters the evaporator coil where it absorbs heat from the incoming air and evaporates.

8.2 Troubleshooting

No dehumidification, neither blower nor compressor run with fan switch OFF.

1. Unit unplugged or no power to outlet.

2. Humidity control set too high or defective

3. Loose connection in internal wiring.

4. Open low pressure control

Dehumidification, blower runs continuously but compressor only runs sporadically with fan switch OFF.

1. Unit is in defrost cycle

2. Defrost thermostat defective or loose

3. Loose connection in compressor circuit

4. Defective compressor overload

5. Defective compressor

6. Defective relay

No dehumidification. Blower runs but compressor does not with fan switch OFF.

1. Bad connection in compressor circuit

2. Defective compressor capacitor

3. Defective compressor overload

4. Defective compressor

5. Defective relay

Blower does not run. Compressor runs briefly but cycles on & off.

1. Loose connection in blower circuit

2. Obstruction prevents impeller rotation

3. Defective blower

Unit removes some water but not as much as expected.

1. Air temperature and/or humidity have dropped.

2. Humidity meter and/or thermometer used are out of calibration.

3. Unit has entered defrost cycle

4. Air filter dirty

5. Defective defrost thermostat

6. Low refrigerant charge

7. Air leak such as loose cover.

8. Defective compressor

9. Restrictive ducting

Evaporator coil frosted continuously, low dehumidifying capacity.

1. Defrost thermostat loose or defective

2. Low refrigerant charge

3. Dirty air filters or airflow restricted.

The evaporator operates in a flooded condition, which means it should always be full of liquid refrigerant during normal operation. A flooded evaporator should maintain constant pressure and temperature across the entire coil, from inlet to outlet. A mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator prevents any liquid refrigerant from reaching the compressor.

The compressor removes the cool refrigerant gas from the accumulator and compresses it to a high pressure and temperature to repeat the process.

HI-E DRY Vehere Owners Manual

| www.BreathePureAir.com | 1-877-688-2703

8.3 Refrigerant Charging

WARNING

WARNING: Only qualified service people should service this unit. The Vehere has a high-pressure refrigerant system and high voltage circuitry. This could present a hazard which could result in death, serious bodily injury, and/or property damage. Only qualified service people should service this unit.

If the refrigerant charge is lost due to service or a leak, a new charge must be accurately weighed in. If any of the old charge is left in the system, it must be removed before weighing in the new charge. Refer to the unit nameplate for the correct charge weight and refrigerant type. Add the refrigerant through the low side service port.

8.6 Relay

The contacts of the single pole, single throw relay complete the power circuit to the compressor. The contacts are closed when power is provided to the relay coil via the control circuit. The control circuit includes the humidity control, low pressure control, defrost thermostat and timer.

9 Vehere Accessories

Part No.

4025283

4022646

4024934

4021749

4023539

4023603

Item

Vehere Remote Humidity Sensor/Control

Indoor/Outdoor Relative Humidity Meter

Deluxe Indoor Relative Humidity Meter

Filter (2 Filters Required)

Collar, Duct, 12”, Galv. (intake)

Collar Assy, Duct, 12”, Galv. (exhaust)

Optional Ventilator

4019663

4023348

Quiet-Vent Exhaust Ventilator

Quiet-Vent 3-Pickup Package

Includes 1 Each: Quiet-Vent, wall cap, boot and 6” x 25’ insulated flex duct. Plus three

4023349

Each: Register heads, grilles, timers and

4” foil flex duct.

Quiet-Vent 4-Pickup Package

Includes 1 Each: Quiet-Vent, wall cap, boot and 6” x 25’ insulated flex duct. Plus four

Each: Register heads, grilles, timers and

4” foil flex duct.

Figure 12:

Low side service port.

8.4 Blower Replacement

The blower has a PSC motor internal thermal overload protection.

If defective, the complete assembly must be replaced.

1. Unplug the power cord.

2. Remove the cabinet front.

3. If an outlet duct is connected to the unit, remove it.

4. Disconnect the blower leads: white from the compressor run capacitor, and black connected to the fan switch.

5. Remove the nuts & bolts holding the blower outlet flange to the cabinet end and remove the blower.

6. Reassembling with the new blower is the above procedure reversed.

8.5 Low Pressure Control

If the low side refrigerant pressure drops to 15 PSIG, the low pressure control opens and shuts off the compressor and blower. It is automatically reset. It will close when the refrigerant pressure rises to 35 PSIG. Its primary function is to prevent damage to the compressor if a leak develops in the refrigeration system. It may also open if the unit is

A) used in a cool area (below 50°F) and the defrost timer is not adjusted or B) stored where it is below 40°F and then started. Under these conditions, the unit will restart within several minutes. Until the unit warms up, it may cycle several times.

HI-E DRY Vehere Owners Manual | www.BreathePureAir.com | 1-877-688-2703 7

8

WARRANTOR:

HI-E DRY Vehere Dehumidifier Limited Warranty

Therma-Stor LLC

PO Box 8050

Madison, WI 53708. corrosion, freezing, tampering, modification, unauthorized or improper repair or installation, accident, acts of nature or any other cause beyond

Therma-Stor LLC's reasonable control.

Telephone: 1-800-533-7533

This warranty extends only to the original end-user of the Vehere, and may not be assigned or transferred.

If any Vehere part is repaired or replaced, the new part shall be warranted for the balance of original warranty (but all warranty periods will be extended by the period of time, if any, that the Vehere is out of service while awaiting covered warranty service).

WARRANTY: This warranty covers the Vehere.

Warranty service will be performed during normal working hours.

Year One - 100% parts and labor

(all components)

Year(s) Two through Five - The condenser, evaporator and compressor of the Vehere will operate free of any defects in material or will repair or replace the defective part(s).

If a defect in materials or workmanship occurs within the warranty period, Therma-Stor LLC will repair or replace the defect.

USER RESPONSIBILITIES: Warranty service must be performed by a servicer authorized by

Therma-Stor Products. To obtain warranty service you must obtain a return material authorization

(RMA). To obtain an RMA you must present proof of purchase or (lease), by use of a warranty card, original sales receipt or other reasonable and reliable means.

UPON THE EXPIRATION OF THE WRITTEN WARRANTY

APPLICABLE TO THE VEHERE OR ANY PART THERE-

OF, ALL OTHER WARRANTIES IMPLIED BY LAW,

INCLUDING MERCHANTABILITY AND FITNESS FOR

A PARTICULAR PURPOSE, SHALL ALSO EXPIRE. ALL

WARRANTIES MADE BY THERMA-STOR LLC ARE

SET FORTH HEREIN, AND NO CLAIM MAY BE MADE

AGAINST THERMA-STOR BASED ON ANY ORAL

WARRANTY. IN NO EVENT SHALL THERMA-STOR

LLC, IN CONNECTION WITH THE SALE, INSTALLA-

TION, USE, REPAIR OR REPLACEMENT OF ANY

VEHERE OR PART THEREOF BE LIABLE UNDER ANY

LEGAL THEORY FOR ANY SPECIAL, INDIRECT OR

CONSEQUENTIAL DAMAGES INCLUDING WITHOUT

LIMITATION WATER DAMAGE (THE END USER

SHOULD TAKE PRECAUTIONS AGAINST SAME),

LOST PROFITS, DELAY, OR LOSS OF USE OR DAM-

AGE TO ANY REAL OR PERSONAL PROPERTY.

To obtain an RMA call Therma-Stor LLC at the above number and ask for the Therma-Stor LLC

Service Department, which will then issue an

RMA# and arrange for, at our option, either repair or replacement.

Some states do not allow limitations on how long an implied warranty lasts, and some do not allow the exclusion or limitation of incidental or consequential damages, so one or both of these limitations may not apply to you.

FREIGHT: Freight to and from the servicer is the responsibility of the end-user. The end-user is responsible for normal care and proper return packaging.

LEGAL RIGHTS: This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

LIMITATIONS AND EXCLUSIONS: This warranty does not cover any defect, malfunction, etc. resulting from misuse, abuse, lack of normal care,

HI-E DRY Vehere Owners Manual

| www.BreathePureAir.com | 1-877-688-2703

11 Vehere Electrical Wiring

Figure 13: Vehere wiring diagram.

HI-E DRY Vehere Owners Manual | www.BreathePureAir.com | 1-877-688-2703 9

10

1236 Folly Road

Charleston, SC 29412

Phone: 1-877-688-2703

Fax: 1-843-795-5892

Web: www.BreathePureAir.com

Email: [email protected]

Information in this document is subject to change without notice.

No part of this document may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Therma-Stor LLC.

© 2004 Therma-Stor LLC. All rights reserved.

HI-E DRY Vehere Owners Manual

| www.BreathePureAir.com | 1-877-688-2703

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement