- No category
advertisement
BPS-602
NAC Power Extender
Installation Guide
(see Application Guide for additional information)
Rev. 042209
BPS-602 - NAC Power Extender
Overview:
The Mircom BPS-602 is an extremely cost effective 6.5 amp remote power supply/battery charger. It may be connected to any 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also provides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24 volt power to Class B, Style W, X, Y or Class A, Style Z
NAC loop circuits. Additionally, a separate 1.0A auxiliary output for four (4)-wire smoke detectors is available. The 6.5 amp max. alarm current can be divided between the four (4) outputs for powering NAC devices. Each output is rated at 2.5 amp max., and can be independently programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input to Output Follower Mode (output will follow input). An individual output of 4 amp is achieved by paralleling 2 outputs. In non-alarm condition independent loop supervision for Class A, Style Z and/or Class B, Style
W, X, Y FACP NAC circuits is provided. In the event of a loop trouble, the FACP will be notified via the steered input
(input 1 or input 2). In addition, there are common trouble output terminals (NC, C, NO) which are used to indicate general loop/system trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the
FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery to any combination of the four (4) outputs.
Specifications:
Agency Listings:
• UL Listed Control Units and Accessories for
Fire Systems (UL 864).
• MEA - NYC Department of Buildings Approved.
• CSFM - California State Fire Marshal Approved.
• FM - Factory Mutual Approved.
• NFPA 72 Compliant.
Input:
• Power input 120VAC 60 Hz, 4 amp.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, X, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• 24VDC @ 6.5 amp max total alarm current.
• 2.5 amp max current per output.
• Separate 1.0 amp auxiliary output.
• Two (2) outputs may be paralleled for more power on an
indicating circuit (see 02 Application Guide).
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, X, Y or Two (2) Class A,
Style Z or One (1) Class A, Style Z and Two (2) Class B,
Style W, X, Y (see 02 Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Charging voltage is 26.2-26.4VDC.
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switchover to stand-by battery when AC Fails.
• Zero voltage drop when switching over to battery backup.
Supervision:
• AC fail supervision (form “C” contact, 1 amp / 28VDC).
Factory set for 30 seconds with optional 2.5 to 3 hour
delay setting (field selectable).
Supervision (cont’d):
• Instant local AC trouble reporting relay
(form “C” contact, 1 amp / 28VDC).
• Battery presence and low battery supervision
(form “C” contact, 1 amp / 28VDC).
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
• Sync protocols include Potter/Amseco, Faraday,
Gentex
®
, System Sensor
®
, and CooperWheelock
®
.
• Temporal Code 3, Steady Mode, Input to Output
Follower Mode (maintains synchronization of
notification appliances circuit).
• Compatible with 12VDC or 24VDC fire panels.
• Output loop supervision steered to input 1 or input 2.
• Signal circuit trouble memory (helps identify
intermittent loop problems).
• Common trouble input and output for external trouble
signals tie-in.
• Ground fault detection.
• Unit includes power supply, red enclosure, cam lock,
and battery leads.
Enclosure Dimensions (approx. H x W x D):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
WARNING: To reduce the risk of fire or electric shock do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
- 2 - BPS-602
AC Input:
Power Supply Specifications:
120VAC 60Hz, 4 amp.
Output:
Four (4) regulated supervised NAC output circuits, 24VDC, 2.5 amp maximum current.
One (1) aux. special application 24VDC power output circuit 1 amp, non-supervised total output current must not exceed current 6.5 amp in Alarm Condition.
Battery
Use two (2) 12VDC / 7AH, two (2) 12VDC / 12AH or two (2) 12VDC / 40AH batteries connected in series.
Stand-by/Alarm Current
Consumption:
90mA/175mA
EOL Resistor (end of line):
2.2K (2200 ohm).
Ground fault maximum test impedance:
1000 ohm.
Stand-by Batteries
24VDC/7AH
24VDC/12AH
(use two (2) 12VDC batteries in series)
24VDC/40AH
Stand-by Specifications:
Stand-by Time Total Amp/Minutes Alarm Output Current Aux. Output
24 Hours
24 Hours
6.5 amp/5 minutes
6.5 amp/5 minutes
---
50mA
24 Hours 6.5 amp/5 minutes 1 amp
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” above for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor dry use only.
Carefully review:
ground
Application Guide for BPS-602, BPS-802, BPS-1002
Power Supply Specifications
Stand-by Specifications
Output Programming Selection Table
(pg. 3)
(pg. 3)
(pg. 4)
(pg. 4)
line
L N
neutral
Sync Mode Selection Table
Terminal Identification Table
LED Status Indication Table
(pgs. 5-6)
(pg. 6)
Fig. 1
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 12).
Secure enclosure to earth ground (Fig. 1, pg. 3). Small terminal block wire gauges range from
16 AWG to 24 AWG, all others range from 14 AWG to 24 AWG.
2. Connect the line (L) and neutral (N) terminals to a separate unswitched AC circuit (120VAC, 60Hz) dedicated to the Fire Alarm System.
3. Measure output voltage before connecting devices. This helps avoiding potential damage.
4. Connect battery to the terminals marked [+ BAT - ] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2] and desired output signal type (Output Programming Selection Table, pg. 4).
6. Connect FACP output to the desired AL800LGK9E logic board inputs, and notification appliances to the desired
AL800LGK9E logic board outputs (see 02 Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn/strobes, strobes with synchronization capability.
7. For connection of smoke detectors, digital dialer see Hookup Diagram, pg. 7.
BPS-602 - 3 -
Class A, Style Z Class B, Style W, X, Y, SW1 & SW2 Settings:
• For all Class B, Style W, X, Y, hookups SW1 & SW2 on the AL800LGK9E logic board must be open.
For all Class A, Style Z hookups SW1 & SW2 on the AL800LGK9E logic board must be closed.
Output Programming Selection Table:
Outputs must be programmed independently (OUT1 - OUT4)
Function
Switch Positions
ON OFF
Descriptions
Input to Output Follower
Mode
Temporal Code 3 Mode
1
3
2, 3
1, 2
Output follows signal it receives from the corresponding input
(i.e. FACP Sync module - maintains synchronization of notification appliance circuit).
Enables Temporal Code 3 signal generation output.
This mode will accept a steady or a pulsing input.
Steady Mode
For the above modes Dip Switch 4 determines which Input controls the corresponding output:
Switch 4 in the ON position causes output(s) to be controlled by Input 1.
Switch 4 in the OFF position causes output(s) to be controlled by Input 2.
(AL800LGK9E Board)
Output Dip Switches
INPUT SELECT
TEMPORAL
Note: It is required to control visual notification appliances (strobes) via Input 1 (IN1) and audible notification appliances (horns) via Input 2 (IN2). This allows audible
STROBE SYNC
IN>OUT SYNC notification appliances (horns) to be silenced while visual notification appliances (strobes) continue to operate. The
FACP must be capable of a visual annunciation to the silencing status of the output or zone(s) to which the
BPS-602 (NAC Power Extender) is connected.
Sync Mode Selection Table:
Function
Switch Positions
ON OFF
Descriptions
Amseco Sync
Mode*
1, 3,
4
2
This mode is designed to work with the Amseco series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/ strobe combination over a two-wire circuit while leaving strobes active.
Faraday
Sync Mode*
Gentex
®
Sync Mode*
Gentex is a registered trademark of Gentex Corporation.
System Sensor
®
Sync Mode*
System Sensor is a registered trademark of Honeywell.
CooperWheelock
®
Sync Mode*
CooperWheelock is a registered trademark of
Cooper Wheelock.
2, 4
1, 2,
3, 4
1, 2, 4
2, 3, 4
1, 3
3
1
This mode is designed to work with the Faraday series of horns, strobes, and horn/ strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the Gentex
®
series of horns, strobes, and horn/ strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the System Sensor
®
series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
This mode is designed to work with the CooperWheelock series of horns, strobes, and horn/strobes to provide a means of synchronizing the Temporal-coded horns, synchronizing the one-second flash timing of the strobe, and silencing the horns of the horn/strobe combination over a two-wire circuit while leaving strobes active.
- 4 - BPS-602
*Note: The BPS-602 will only synchronize horns, horn/strobes and strobes that contain synchronization capability.
Contact signal manufacturer for more detailed info (see Appendix A.4, pg. 12). The same synchronization mode must be
selected for all outputs
Amseco
Faraday
Gentex®
Amount of Notification Appliances per NAC:
27 per NAC*
39 per NAC*
32 per NAC*
*Not to exceed a maximum of 2.5 amp per NAC.
System Sensor®
CooperWheelock®
32 per NAC*
32 per NAC*
Terminal Identification Table:
AL800LGK9E Logic Board
Terminal
Legend
Function/Description
IN1+, IN1-
IN2+, IN2-
(Supervised)
RET1+, RET1-
RET2+, RET2-
(Supervised)
These terminals connect to the 24VDC FACP notification appliance circuit outputs.
(Class A, Style Z or Class B, Style W, X, Y) Input trigger voltage is 8-33VDC @ 5mA min.
Terminal polarity is shown in alarm condition. During an alarm condition these inputs will cause the selected outputs chosen to drive notification appliances. The designated outputs are set by output switches[OUT1 through OUT4] (Output Programming Selection Table, pg. 4). A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition will always override trouble to drive notification appliances.
For (Class A, Style Z hookups these terminal pairs return to FACP NAC1 and/or NAC2. For Class
B, Style W, X, Y hookups the FACP EOL resistor from the NAC1 and/or NAC2 outputs are terminated at these terminals.
C “DRY1” NC
C “DRY2” NC
(Dry input trigger)
An open across these inputs, will cause the selected outputs chosen to drive notification appliances.
The designated outputs are set by output switches [OUT1 through OUT4] (Output Programming
Selection Table, pg. 4). Note these inputs are unidirectional and will not report a trouble condition to the FACP.
+ OUT1 --
+ OUT2 --
+ OUT3 --
+ OUT4 --
(Supervised)
C “FAULT” NC
(Common
trouble input)
NC, C, NO
(Common
trouble output)
-- AUX+
+ DC --
Notification appliances are connected to these regulated outputs (see 02 Application Guide pg. 2-4).
Each power-limited output will supply 2.5 amp. Two (2) outputs may be connected in parallel for a maximum NAC output capability of 4 amp. Total supply current is 6.5 amp (see note below). Outputs are controlled by designated input 1 [IN1] or input 2 [IN2] (Output Programming Selection
An open circuit across this pair of terminals will cause [IN1 and IN2] to simultaneously signal a trouble condition back to the FACP (Typically used to report AC or BAT Fail). (form “C” contact 1 amp / 28VDC) (Fig. 2, pg. 7).
These are dry contact trouble outputs that follow any general loop/system trouble conditions.
(Typically used to trigger a digital communicator or other reporting device).
(form “C” contact 1 amp / 28VDC 0.35 Power Factor) (Fig. 2, pg. 7) .
This separate 1 amp max auxiliary Special Application Power output circuit is typically used to power 4-wire smoke detectors. See attached list of devices (Appendix A, pgs. 10-12).
24VDC from power supply.
Note: Unit is equipped with 1 amp max. auxiliary output: “AUX” will remain battery backed up during power outage. For loads connected to “AUX” please refer to battery “Stand-by Specifications” pg. 3 for ratings. When loads are connected to “AUX” output during alarm condition, the remaining outputs may not exceed 6.5 amp total alarm current (example: AUX = 1 amp, outputs up to 5.5 amp).
BPS-602 - 5 -
Power Supply Board*
Terminal
Legend
L, G, N
- DC +
Function/Description
AC FAIL
NO, C, NC
Terminal Identification Table:
Connect 120 VAC to these terminals: L to hot, N to neutral.
24VDC @ 6.5 amp in alarm non power-limited output.
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
AC LOCAL
NC, NO, C
BAT FAIL
NO, C, NC
+ BAT -
Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs terminals marked NO and C are closed, NC and C are open.
Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal conditions terminals marked NO and C are open, NC and C are closed. During a trouble condition terminals marked NO and C are closed, and NC and C are open (Fig. 2, pg. 7).
Stand-by battery input (leads provided) (Fig. 2, pg. 7).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut
jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power
Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).
A restored battery will report within 30 seconds.
LED Diagnostics:
Power Supply Board
Red (DC)
ON
ON
OFF
OFF
Green (AC) Power Supply Status
ON Normal operating condition.
OFF
ON
OFF
Loss of AC. Stand-by battery is supplying power.
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
AL800LGK9E - Logic Board
LED
ON
ON
OFF
OFF
Input 1
Input 2
Fault
OFF
Normal
Normal
Normal
Normal
Normal
Normal
Normal
ON
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
BLINK (LONG)*
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
---
BLINK (SHORT)**
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
---
---
---
* Indicates current trouble condition. When trouble (open, short or ground) occurs on a specific output, the corresponding red output LED, [OUT1-OUT4] will blink. The corresponding green input LED will blink as well. Loop trouble will report within 30 seconds.
** Indicates trouble condition memory. When a trouble condition restores, the units red output LED, [OUT1-OUT4] will blink with a shorter and distinctly a different duration. The green input LEDs will be off (normal condition).
To reset the memory depress the reset button (Fig. 2c, pg. 7). The LED(s) will extinguish.
Note: If indicating circuits have been restored, memory reset is not required for normal operation of the unit.
- 6 - BPS-602
Earth
Ground
EOL
Resistor from
FACP
Fire
Alarm
Control
Panel
(FACP)
Green Lead
Fig. 2
Fig. 2a
Hookup Diagram:
+
4-wire Smoke
Detector
--
+
4-wire Smoke
Detector
--
Fire
Alarm
Control
Panel
(FACP)
EOL Power
Supervision Relay
(Not Supplied) unswitched 120VAC power mains
(non-power limited)
5A
250V
line
AC Local
SW2
neutral
Non-Supervised
-- AUX +
Fire
Alarm
Control
Panel
(FACP)
Fuse
Cover
SW1
+ OUT1 --
+ OUT2 --
4-wire Smoke
Detector
--
10A
Use separate knockout. Keep 1/4" spacing from non power-limited wiring
Divider
Green Lead
RESET
+
-- DC +
OUT1 OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
unswitched 120VAC power mains
(non-power limited)
OUT4
TEMPORAL
5A
AC FAIL
line neutral
OUT1 OUT2 OUT3 OUT4
INP1 INP2
NO C NC NO C NC
BAT FAIL
DC
FAULT
J2
AC Local
Use separate knockout. Keep 1/4" spacing from non power-limited wiring
This connection is used to monitor AC and Bat Fail and will cause a simultaneous trouble condition to the FACP's IN1 and IN2
Divider
Green Lead
+ OUT3 -+ OUT4 --
Non-Supervised
-- AUX +
AC
-- DC +
15A
OUT1 OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
OUT2 OUT4
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
Green Lead
Non-Supervised
Common trouble output to
OUT1 OUT2 OUT3 OUT4
monitor AC and Bat Fail and
Local Annunciator Dry output Contact
(Form "C" contacts) (Non-Supervised)
Non-Supervised unswitched 120VAC power mains
(non-power limited)
+
4-wire Smoke
Detector
--
EOL
Resistor from
Green Lead
250V
4-wire Smoke
Regulated Power-Limited Outputs line ground neutral
+
2.5 amp max. per output in alarm
(total= 6.5 amp)
(Supervised)
EOL Power
Supervision Relay
-- DC +
RESET
IN1+ IN1--
RET1+RET1--
IN2+
IN2--
RET2+
C "DRY1" NC
RET2-C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
SW2 SW1
Supervised
+ BAT ---
+ OUT2 --
+ DC ---
Non-Supervised
Common trouble output to
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts) (Non-Supervised)
Use separate knockout.
Keep 1/4" spacing from non power limited wiring
2.5 amp max. per output in alarm
(total= 6.5 amp)
INPUT SELECT
Addressable
Control Module
Trigger Output
See Note 2
Trouble Memory
IN1+ IN1--
(Supervised)
OUT1 OUT3
INPUT SELECT
TEMPORAL
STROBE SYNC
IN > OUT SYNC
OUT1 OUT2 OUT3 OUT4
INP1 INP2
OUT2 OUT4
STROBE SYNC
IN > OUT SYNC
Reset Button
Fig. 2c
IN2+
RET1+RET1--
IN2--
RET2+
C "DRY1" NC
RET2-C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
Supervised Non-Supervised
FAULT
Addressable
Control Module
Trigger Output
Common trouble
Input/Output
These circuits are used to monitor AC and Bat Fail and
Fig. 2b
will cause a simultaneous trouble condition to the FACP's IN1 and IN2
+
4-wire Smoke
Detector
--
SW2 SW1
+ OUT1 --
+ OUT2 -+ OUT3 -+ OUT4 --
Digital Communicator or
Local Annunciator Dry output Contact
(Form "C" contacts)
EOL
Resistor from
FACP
EOL Power
Supervision Relay
(Not Supplied)
IN1+ IN1-IN2+
RET1+RET1-RET2+
IN2-C "DRY1" NC
RET2-C "DRY2" NC
UPPER TERMINALS
LOWER TERMINALS
Power Limited Outputs
2.5 amp per output in alarm
(total=10 amp)
Addressable
Control Module
Trigger Output
See Note 2
BPS-602 - 7 -
Optional Hookups:
1- Battery and AC monitoring: AC or Battery Fail condition will cause the common trouble input [C “FAULT” NC] to report back to the FACP via input 1 and input 2. The common trouble input may also be used for other optional supervisory monitoring. (see Power Board Parameter for use of AC Delay, pg. 6)
To report AC and Battery Trouble connect the battery and AC Fail relay output shown in (Fig. 2a) to the common trouble input.
2- Dry contact input (C “DRY1” NC) (C “DRY2” NC) can be used to alarm output from an addressable module (these inputs are unidirection and cannot report back to trigger module).
Connection to triggering devices must be made within 20ft of distance and using conduit for wiring.
3- Auxiliary output (-AUX+) 24VDC at 1 amp max.
4- AC Local [NC, NO, C] should connect to the host control panel for local annunciation of the trouble condition.
Note: If common trouble input, terminals marked [C “FAULT” NC] are not used, these terminals must be shorted (connect jumper) to remain inactive. For optional hookups see Fig. 2b.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level
(26.2-26.4VDC recommended range).
Battery Test: Under normal load conditions check that the battery is fully charged. Check specified voltage both at the battery terminal and at the board terminals marked [+ BAT - ] to ensure that there is no break in the battery connection wires.
Fuses: Check input fuse on the power supply board, replace if necessary. Input fuse rating is 5 amp @ 250V.
Note: Maximum charging current is 650mA.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
- 8 - BPS-602
A
Auxiliary Devices
Battery Calculation Worksheet
Device
Number of
Devices
Current per Device
For each device use this formula: This column x This column = Equals
BPS-602
(Current draw from battery)
1
Stand-by:
Alarm:
90mA
175mA
BPS-602 Current
Stand-by
Current
Alarm
Current
Current per number of devices.
90mA
175mA
90mA
Refer to device manual for current ratings.
175mA
Alarm/Stand-by
Alarm/Stand-by mA mA mA mA mA mA mA
B
Alarm/Stand-by mA
Auxiliary Devices Current (must not exceed 1 amp)
mA
Refer to device manual for current ratings.
Alarm:
Alarm: mA mA
0mA
0mA
Alarm:
Alarm: mA 0mA mA 0mA
C Notification Appliances Current must not exceed 6.5 amp (6500mA) 0mA mA mA mA mA mA
D Total alarm current mA mA
A E Total current ratings converted to amperes (line D x .001)
F Number of standby hours (24 for NFPA 72, Chapter 1, 1-5.2.5).
G Multiply lines E and F.
Total stand-by AH
A
H
AH
H
I Multiply lines E and H.
Total alarm AH
J Add lines G and I. Total stand-by and alarm AH
K
Multiply line J by 1.30.
(30% extra insurance to meet desired performance)
Total ampere - hours required
Units are capable of recharging 40AH battery max. If total ampere - hour required exceeds 40AH, decrease AUX current to provide enough stand-by time for the application.
AH
AH
AH
BPS-602 - 9 -
Appendix A - UL Listed Compatible Devices
A.1 Four (4) Wire Smoke Detectors
Table A-1 below lists four (4) wire smoke detectors compatible with BPS-602 AUX output.
Smoke Detector/Base
FenWal CPD-7021 (w/70-201000-005 Base)
FenWal PSD-7125
FenWal PSD-7125 (w/70-201000-005 Base)
Fire-Lite BLP-12-4W
Gentex 824
Gentex 824T
Gentex 824CP
Gentex 824CPT
Hochiki HSC-4R
Hochiki SPB-24
System Sensor B112LP
System Sensor B114LP
System Sensor B404B
System Sensor DH100ACDC
System Sensor DH100ACDCLP
System Sensor DH100ACDCLPW
System Sensor DH400ACDCI
System Sensor DH400ACDCP
System Sensor 1112/24/D
System Sensor 1424
System Sensor 1451 (w/B402B Base)
System Sensor 2112/24ATR
System Sensor 2112/24AITR
System Sensor 2112/24/D
System Sensor 2112/24R
System Sensor 2112/24TR
System Sensor 2112/24T/D
System Sensor 2112/24TSRB
System Sensor 2312/24TB
System Sensor 2412 (12 volt)
System Sensor 2412AT (12 volt)
System Sensor 2412TH (12 volt)
System Sensor 2424
System Sensor 2424TH
System Sensor 2451
System Sensor 2451TH (with/B402B Base)
System Sensor 2W-MOD
Detector Type
Ionization
Photoelectric
Photoelectric
Base
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Base
Projected Beam
Base
Base
Base
Photoelectric
Photoelectric
Photoelectric
Ionization Duct
Photoelectric Duct
Ionization
Ionization
Ionization
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric w/135 o
Thermal
Photoelectric w/135 o
Thermal Supervisory Relay
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Photoelectric
Loop Test/Maintenance
Mod.
Max Standby
Current (mA)
0.15
0.15
0.15
25
25
*
0.25
0.12
*
*
0.10
0.10
0.10
*
0.50
0.50
0.50
0.50
0.05
0.10
0.10
0.50
0.50
0.05
0.50
0.50
0.05
15
0.12
0.12
0.12
0.12
0.10
0.10
0.10
0.10
30
45
41
39
39
50
77
58
77
41
50
Alarm
Current (mA)
0.70
0.70
0.70
95
95
*
*
36
*
*
*
*
*
*
*
*
*
*
50
41
39
60/70
60/70
50
60/70
60/70
50
- 10 - BPS-602
A.1 Four (4) Wire Smoke Detectors (cont.)
Smoke Detector/Base
System Sensor 4W-B (12/24 volt)
System Sensor 4WT-B (12/24 volt)
System Sensor 4WTA-B (12/24 volt)
System Sensor 4WTR-B (12/24 volt)
System Sensor 4WTR-B (12/24 volt)
System Sensor 4WITAR-B (12/24 volt)
System Sensor 2W-MOD2
System Sensor RRS-MOD
System Sensor 6424
System Sensor Beam 1224(S)
* Contact manufacturer for current draws
Detector Type
Photoelectric I
3
Photoelectric I
3
w/Therm
I
3
Photo w/Therm/Sounder
I
3
Photo w/Therm/Relay
I
3
Photo w/Therm/
Sounder/Relay
I
3
Photo w/Isolated Therm/
Sounder/Relay
I
3
Loop Test/Maintenance
Mod.
I
3
Reversing Relay/Sync
Module
Projected Beam
Projected Beam
Max Standby
Current (mA)
.05
.05
.05
.05
.05
.05
.05
.05
10
17
Alarm
Current (mA)
23
23
35
35
50
50
*
*
28.4
38.5
A.2 Door Holders
Table A-2 below lists door holders compatible with BPS-602 AUX output.
Manufacturer
Edwards
Edwards
Edwards
Rixon Firemark
Rixon Firemark
Rixon Firemark
Model
DH150A
DH154A
DH158A
FM-980
FM-996
FM-998
Type
Floor Mount
Floor Mount
Surface Mount
Floor Mount, single
Surface Wiring
Concealed Wiring
A.3 Relays
Table A-3 below lists relays compatible with BPS-602 AUX output.
Manufacturer
Air Products &
Controls, LTD
Model
MR-101/C
MR-201/C
PAM-1
PAM-2
PAM-SD
A77-716B
Current (mA)
15
35
15
15
15
20
Manufacturer
System Sensor
Model
PR-1
PR-2
PR-3
EOLR-1
R-10T
R-14T
R-20T
R-24T
R-10E
R-14E
R-20E
R-24E
Current (mA)
96
96
96
68
68
68
Current (mA)
15
30
30
30
23
23
40
40
23
23
40
40
BPS-602 - 11 -
A.4 Strobes
Table A-4 below lists strobes compatible with BPS-602 NAC output.
Wheelock Devices:
Sychronizing Horns
AH-12
AH-12WP
HS-24
NH-12/24
ZNH
HNR
AH-24AH-24
AH-24WP
MIZ-24S
HNW
Sychronizing Horn Strobes
AS-121575W
AS-24MCW
AS-24MCWH
AS-2415C
AS-2475C
ASWP-2475W
NS4-121575W
HS4-241575W
HS4-24MCW
HS4-24MCWH
HS4-24185W
ZNS-MCW
ZNS-MCWH
HSR
AS-241575W
AS-24MCC
AS-24MCCH
AS-2430C
AS-24100C
NS-121575W
NS-2-41575W
NS-24MCW
HS4-24150C
HSW
Sychronizing Strobes
RSS-121575W
RSS-241575W
RSS-24MCW
RSS-24MCC
RSS-2415C
RSS-2430C
RSS-2475C
RSS-24100C
RSS-2415CR
RSS-2430CR
RSS-2475CR
RSS-24100CR
RSS-24150C
RSS-24177C
RSS-24150W
RSS-24177W
RSS-24185W
RSS-24150CR
RSS-24177CR
RSSWP-2475W
ZRS-MCW
ZRS-MCWH
STR
RSSP-121575W
RSSP-241575W
RSSP-24MCW
RSSP-24150W
RSSP-24177W
RSSP-24185W
STW
Appliances with Sychronizing Strobes
AMT-241575W
AMT-2475W
AMT-241575W-NYC
AMT-2475W-NYC
MT-12575W
MT-241575W
MTWP-2475W
CH70-24MCW
CH70-24MCC
CH70-2415C
CH70-2430C
CH70-2475C
CH70-24100C
CH70-24150C
CH70-24177C
CH70-24150W
CH70-24MCWH
CH70-24185W
E70-24MCW
E70-24MCC
E70-2415C
E70-2430C
E70-2475C
E70-24100C
E70-24150C
E70-24177C
E70-24150W
E70-24MCWH
E70-24185W
ET70-24MCW
ET70-24MCC
ET70-2415C
ET70-2430C
ET70-2475C
ET70-24100C
ET70-24150C
ET70-24177C
ET70-24150W
ET70-24MCWH
ET70-24185W
SA-70-24-SL
SA-70-24-SLM
AMT4-241575W
AMT4-2475W
AMT4-241575W-NYC
AMT4-2475W-NYC
MT-2475W
ET70WP-2475W
CH90-24MCW
CH90-24MCC
CH90-2415C
CH90-2430C
CH90-2475C
CH90-24100C
CH90-24150C
CH90-24177C
CH90-24150W
CH90-24MCCH
CH90-24185W
E90-24MCW
E90-24MCC
E90-2415C
E90-2430C
E90-2475C
E90-24100C
E90-24150C
E90-24177C
E90-24150W
E90-24MCCH
E90-24185W
ET90-24MCW
ET90-24MCC
ET90-2415C
ET90-2430C
SA-90-24-SL
SA-90-24-SLM
- 12 - BPS-602
A.4 Strobes (cont.)
Wheelock Devices:
Coded Audible Appliances
AMT - 12/24
AMT - 12/24-NYC
CH70
CSX10-24-DC
MT-12/24
AMT4 - 12/24
AMT4 - 12/24-NYC
CH90
CSXG10-24-DC
MT4-12/24
Non-Synchronizing Appliances
MB-G6-12
MB-G10-12
MIZ-TC12
MB-G6-24
MB-G10-24
MIZ-TC24
Gentex Devices:
Models
GE3 Series
GES/GEC Series GCS/
GCC Series
SSPK Wall and Ceiling Mount Series
GX93 Series
WGE and color lense units.
System Sensor Devices:
Wall Horn/Strobes
P2R
P2RH
P2RK
P2RHK
P2W
P2WH
P4R
P4RH
P4RK
P4RHK
P4W
P4WH
Wall Strobes
SR
SRH
SRK
SRHK
SW
SWH
Ceiling Horn/Strobes
PC2R
PC2RH
PC2RK
PC2RHK
PC2W
PC2WH
PC4R
PC4RH
PC4RK
PC4RHK
PC4W
PC4WH
Ceiling Strobes
SCR
SCRH
SCRK
SCRHK
SCW
SCWH
Horns
HR
HRK
HW
BPS-602 - 13 -
A.4 Strobes (cont.)
Amseco Devices:
Models
H24R
H24W
HP-25T
MH12/24
MH-120
RSD24-153075
RSD24W75110
SAD-24-153075
SAD2475110
SCM24C-177
SCM24W075110
SCM24W-153075
SCM24W3075110
SH24C-177
SH24C-3075110
SH24W-1530
SH24W3975110
SH24W-75110
Faraday Devices:
Models
HS-MC-R
HS-MC-W
HS-HMC-R
HS-HMC-W
HS-R
HS-W
NS-MC-CR
NS-MC-CW
NH-CR
NH-CW
SET-MC-R
SET-MC-W
SET-HMC-R
SET-HMC-W
SET-S17R-WP
SET-S17-W-WP
SET-S17-CW-WP
SET-MC-CW
SET-MC-CR
SET-HMC-CW
SET-HMC-CR
SET-177-CR-WP
SET-177-CW-WP
SET-185-R-WP
SET-185-W-WP
SEF-MC-R
SEF-MC-W
SEF-HMC-R
SEF-HMC-W
SEF-MC-CW
SEF-HMC-CW
ZH-MC-R
ZH-MC-W
ZH-HMC-R
ZH-HMC-W
ZH-R
ZH-W
ZH-MC-CR
ZH-MC-CW
ZH-HMC-CR
ZH-HMC-CW
ZR-MC-CW
ZR-MC-CW
ZR-HMC-CR
ZR-HMC-CW
ZBB-R
ZBB-W
MTH-R
MTH-W
MTH-MC-R
MTH-MC-W
MTH-75-R-WP
MTH-15-115-R-WP
MTH-HMC-CR-WP
MTH-HMC-R-WP
MTH-HMC-W-WP
SHB/SLB120-75
SHB/SLB24-75
SHB2475
SL24C-177
SL24C-3075110
SL24W-1530
SL24W-75110
SLB24-75
SE-MC-R
SE-MC-W
SE-HMC-R
SE-HMC-W
SE-CR
SE-CW
SE-MC-CR
SE-HMC-CW
SE-CR
SE-CW
SE-MC-CR
SE-MC-CW
SE-HMC-CR
SE-HMC-CR
AS-MC-R
AS-MC-W
AS-HMC-R
AS-HMC-W
AS-MC-CR
AS-MC-CW
AS-HMC-CR
AS-HMC-CW
AS-75-R-WP
AS-75-CR-WP
AH-R
AH-W
AH-WP
- 14 - BPS-602
Notes:
BPS-602 - 15 -
1.5”
(38.1mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
Enclosure Dimensions:
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
0.91”
(23.114mm)
1.1”
(27.94mm)
12.23”
(310.64mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
4.5”
(114.3mm)
1.25”
(31.75mm)
1.5”
(38.1mm)
2.0”
(50.8mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
1.25”
(31.75mm)
15.5”
(393.7mm)
1.1”
(27.94mm)
0.79”
(20.06mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1.25”
(31.75mm)
5.0”
(127.0mm)
Mircom is not responsible for any typographical errors
USA - 4575 Witmer Industrial Estates, Niagara Falls, NY 14305, Canada - 25 Interchange Way, Vaughan (Toronto), ON L4K5W3,
888-660-4655 • fax: 888-660-4113 web site: www.mircom.com
IIBPS-602 K23O
- 16 - BPS-602
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project