Basic Rack PDU AP7557 - Overview and Specifications
Basic Rack PDU
Overview
The American Power Conversion (APC™) Basic Rack
Power Distribution Unit (PDU) distributes power to
devices in the rack.
Outlets. The Rack PDU has thirty-six (36)
IEC-309-C13 outlets and six (6) IEC-309-C19 outlets.
Power cord. The 0.91-m (3-ft) power cord
terminates with an IEC-309 16 A connector.
pdu0373a
AP7557
Specifications
Electrical
Input connector
IEC-309, 16 A
Nominal output voltage
220–240 VAC
Output connectors
(36) IEC-309-C13
(6) IEC-309-C19
Cord length
0.91 m (3.00 ft)
Max output current (outlet)
10 A–IEC-309-C13
16 A–IEC-309-C19
Max output current (phase)
16 A
Max input current (phase)
16 A
Nominal input voltage
230/400 VAC, 3-phase
Acceptable input voltage
±10% of normal voltage
Input frequency
50/60 Hz
Physical
Dimensions
(H x W x D)
177.80 x 5.56 x 4.39 cm
(70.00 x 2.19 x 1.73 in)
Shipping dimensions
(H x W x D)
213.36 x 15.24 x 12.7 cm
(84.00 x 6.00 x 5.00 in)
Weight
5.4 kg (12 lb)
Shipping weight
8.8 kg (19.5 lb)
Environmental
Maximum elevation
(above MSL)
Operating
Storage
3000 m (10,000 ft)
15 000 m (50,000 ft)
Temperature
Operating
Storage
–5 to 45°C (23 to 115°F)
–25 to 65°C (–13 to 149°F)
Humidity
Operating
Storage
5–95% RH, non-condensing
5–95% RH, non-condensing
Compliance
Safety verification
VDE, CE Mark, Queensland,
CCC, GOST
Customer support and warranty information is available at the APC Web site,
www.apc.com.
© 2011 APC by Schneider Electric. All trademarks are owned by Schneider
Electric Industries S.A.S., American Power Conversion Corporation, or their
affiliated companies.
990-3084A-001