Safety information
MD0104E061201
INSTRUCTION MANUAL
We appreciate you for purchasing HanYoung NUX Co.,Ltd product.
Before using the product you have purchased, check to make sure that it
is exactly what you ordered. Then, please use it following the instructions
below.
Specification
MAIN PRODUCTS
- DIGITAL : Temperature Controller, Counter, Timer,Speedmeter,
Tachometer, Panel Meter, Recorder
- SENSOR : Proximity Sensor/Photo Electric Sensor,
Rotary Encoder, Optical Fiber Sensor,
Pressure Sensor
- ANALOG : Timer, Temperature Controller
Model
48(W)
48(H)
84(D)mm
Power
a.c
100 V-240 V d.c / a.c (50-60 Hz)
10
voltage
d.c
24 V - 60 V d.c / a.c (50-60 Hz)
10
Consumption a.c
power
d.c
HEAD OFFICE
1381-3, Juan-Dong, Nam-Gu Incheon, Korea
TEL: (82-32)876-4697 FAX : (82-32)876-4696
GE7-T
GE4-P
Appearance(mm)
Max. 13.5 V a.c
Max. 9 V A
Type
Preset
Display digit
Totalizer
6 Digits
P4 (P4 Digits)
FND height
PV : 11 mm, SV : 8 mm
Counting speed and input 1 cps / 30 cps / 1 K cps / 10 K cps Contact/Non-contact
Memory protection
20. The warranty period for this product including parts is one year if
this product is properly used.
21. When the power is on, the preparation period of contact output is
required. In case of use for signals of external interlock circuit, use
with a delay relay.
Safety information
Model and Suffix code
Description
Counter
input
Timer
Name of Each Section
①
(W)48
(H)48
(W)72
(H)36
(W)72
(H)72
Counter
ONE SHOT output
Timer
(Batch Counter)
PRESET BATCH
Type
TOTAL (Indicator)
4 : 9999 (4 digit)
Digit
6 : 999999 (6 digit)
1 stage
Stage
2 stage
0.01-99.99 s(OUT1, OUT2)
1 step 1c (OUT)
3 step NO contact: 250V a.c. 3A resistance load, NC contact: 250V a.c. 2A resistance load
1 step NPN 2 points
Power Supply
SOURCE
Shock
ms
ms
comparative cycle : Every 2ms, Repeat set error: Max. 5ms
Squard wave noise by noise simulator(l
pluse per each 16
Malfunction 10-55Hz Double amplitude width 0.5mm
Durability
10-55Hz Double amplitude width 0.75mm
Maifunction 100
Durability
300
Relay
Electrical
Min. 0.1millions (250 V a.c 2 A Resistance load)
Life
Mechanical Min. 10millions
Protection structure
The first 100 ms after power input and 200 ms after power opening is
the period designated for the ascent and descent of internal power and
external output power. Therefore, in order to prevent malfunction from
the incomplete output action of the external sensor, do not operate
during the unstable period.
IP65 (Front part)
Ambient temperature -20 ~ 65
Ambient humidity
-10 ~ 55
(Without icing)
, 35 ~ 85% R.H. (Without freezing and icing)
Max.133 g
Weight
Certificate
Max.102 g
CE
Supply signal only after 100ms following the power input.
Connection Diagram
Supply power only after 200 ms following the power shutdown.
GE4-P1(P41/P61)
GE4-P2(P42/P62)
[Unit]
48
84.7
64.3
5.3
Coefficient Indication Section (RED FND)
Indicates coefficient (counter), progression time value (timer), batch coefficient,
and setup items
Setup Indication Section (GREEN FND)
Displays setup value (counter), setup time (timer), batch setup value, instant
output setup (batch set at 0 at the timer) and setup details
SET1, SET2 (SET), BAT
Indicates the status of coefficient section and setup section
(BAT lamp corresponds to batch status.)
TIM (Timer)
This flashes when the timer progresses and remains lighted when the device
stops from inhibit input or reset.
(It is indicated in Change Mode of the device during TIM/TTWIN setup.)
CNT (Counter)
This is indicated during 1CNT/2CNT setup in Change Mode of the device.
OUT1, OUT2(OUT), BAT.O (Output Action Indication)
BAT.O lights up when the batch setup value is set. (OUT1 Output)
BAT.O lights up and outputs when the device operates with the instant output
where the batch setup value is 0 (timer).
CP1, CP2, RST. Verification of Input Status (Exclusively for TOTAL)
LOCK:Key Lock (KEY LOCK) Action IndicationThis lights up during Lock Setup.
This key is for function setup Mode Entry and Mode change. It can also be
used for ending after saving when changing the setup value
Setup value change Entry and Location shift
UP Key
RESET KEY
44.8
Maximum Coefficient Speed
GE4-P2(P42/P62)
45 +0.6
0
60
⑪
⑨
TOTAL Model does not have Setup Indication Section, SET1, SET2 and BAT
Lamp. OUT1, OUT2, BAT.O change their use as CP1, CP2, RST Input Status
Check Lamp.
Level 1 Setup Model does not have SET1 and OUT1 Lamp, and SET2 is
displayed as SET and OUT2 is displayed as OUT.
GE4-P1(P41/P61)
45
⑧
Batch and Operation Mode switchover key
15
NPN Input
60
⑪
3 step Open collector 30V d.c. 100mA Max.
ms) +/-2 (Power supply input terminal)
Vibration
⑧
⑦
⑥
⑩
④
⑤
2 step
Withstand noise
GE7 is only for 6 digits.
⑦
⑥
⑩
④
⑤
⑨
Setting time : 100ms from POWER ON.
Dielectrical strength 2000 V a.c 50 - 60 Hz for 1 minute
24 V-60V d.c
②
③
2 step 1a (OUT1), Ic (OUT2)
Timer operating
Twin timer
100 V-240 V a.c
Power supply
①
power
contact
Appearance
48
CAUTION
1. The contents of this manual may be changed without prior notification.
2. Before using the product you have purchased, check to make sure
that it is exactly what you ordered.
3. Check to make sure that there is no damage or abnormality of the
product during delivery.
4. Do not use this product at any place with corrosive(especially
noxious gas or ammonia) or flammable gas.
5. Do not use this product at any place with direct vibration or impact.
6. Do not use this product at any place with liquid, oil, medical
substances, dust, salt or iron contents. (Pollution level 1 or 2)
7. Do not polish this product with substances such as alcohol or benzene.
8. Do not use this product at any place with excessive induction
trouble, static electricity or magnetic noise.
9. Do not use this product at any place with possible thermal
accumulation due to direct sunlight or heat radiation.
10. Install this product at place under 2,000m in altitude.
11. When the product gets wet, the inspection is essential because
there is danger of an electric leakage or fire.
12. If there is excessive noise from the power supply, using insulating
transformer and noise filter is recommended. The noise filter must
be attached to a panel grounded, and the wire between the filter
output side and power supply terminal must be as short as possible.
13. If gauge cables are twisted closely, the effect on noise may occur.
14. Do not connect anything to the unused terminals.
15. After checking polarity of terminal, connect wires at the correct position.
16. When this product is connected to a panel, use a circuit breaker or
switch approved with IEC847-1 or IEC947-3.
17. Install the circuit breaker or switch at near place for convenient use.
18. For the continuous and safe use of this product, the periodical
maintenance is recommended.
19. Some parts of this product have limited life span, and others are
changed by their usage.
resistance connetion by NPN/PNP set (4.7
Min.
Non-contact
Model
WARNING
1. If there is a possibility of an accident caused by errors or
malfunctions of this product, install external protection circuit to
prevent the accident.
2. This product does not contain an electric switch or fuse, so the user
needs to install a separate electric switch or fuse externally. (Fuse
rating : 250 V 0.5 A)
3. To prevent defection or malfunction of this product, supply proper
power voltage in accordance with the rating.
4. To prevent electric shock or devise malfunction of this product, do
not supply the power until the wiring is completed.
5. Since this product is not designed with explosion-protective
structure, do not use it at any place with flammable or explosive gas.
6. Do not decompose, modify, revise or repair this product. This may
cause malfunction, electric shock or fire.
7. Reassemble this product while the power is off. Otherwise, it may
cause malfunction or electric shock.
8. It you use the product with methods other than specified by the
manufacturer, there may be bodily injuries or property damages.
9. Due to the danger of electric shock, use this product installed onto a
panel while an electric current is applied.
[H]level 4-30 V d.c, [L]level 0-2 V d.c, Pull-up / Pull-down
External output
DANGER
Do not touch or contact the input/output terminals because they may
cause electric shock.
10 years (Nonvolatile memory)
CP1, CP2, RESET, BATCH RESET (Preset type)
Input
Control output
Before you use, read safety precautions carefully, and use this product
properly. The precautions described in this manual contains important
contents related with safety; therefore, please follow the instructions
accordingly. The precautions are composed of DANGER, WARNING
and CAUTION.
for breakdown
Coefficient Input 1(CP1) / Inhibit Input (INHIBIT) Terminal
Counter during its use is used as coefficient input or inhibit input.
Timer during its use puts a hold on the processing time.
Coefficient Input 2(CP2) / Start (START) Terminal
l Counter during its use is used as coefficient input or inhibit input.
l Timer during its use can be used for Signal On Start or Signal One Start.
(Refer to Output Action Mode)
(SIGNAL ON START: Timer operates only with the continuous input.)
(SIGNAL ONE START: Timer operates only with the supply of Input 1 Pulse.)
BAT RESET
l This is used as batch reset during the use of counter/timer.
RESET
l This initializes the coefficient value and current time during the use of
counter/timer.
OUT2 (OUT): This is used as the counter/timer comparative output.
BAT.O: Batch Counter Output (Level 1 Setup Type)
(BAT.O): Select between Level 1 Setup Output and Batch Counter Output
(Level 2 Setup Type)
Maximum Coefficient Speed refers to the maximum response speed when duty
ratio (On, Off Ratio) of coefficient input signal is input as one to one ratio (1:1).
As for the input signal below the maximum coefficient speed, it is not counted if
either ‘On’ or ‘Off’ Time unilaterally falls below the standard value of minimum
signal width.
Minimum Input Time
Coefficient Speed Selection Minimum Input Signal
1 cps Mode
250 ms or more
+0.6
0
30 cps Mode
PNP Input
GE4-T6 : TOTAL does not possess transistor and relay output.
1 K cps Mode
10 K cps Mode
Minimum Signal Time refers
to ‘On’Time.
11 ms or more
0.3 ms or more
0.05 ms or more
Time
Counter Output Action Mode
Counter Input Action Mode
Counter Mode Setup Method
One Shot Output of OUT1 Output
Level 1 Setup Type
Operation Mode
‘A’ needs greater than minimum signal width and ‘Ø needs more than 1/2 of minimum signal width.
Inhibit Input / Individual Input / Command Input / Phase Difference Input
Level 2 Setup Type
Press Setup Mode Entry
for 2 seconds
Key
Operation Mode
Up - A Inhibit input
As for Level 1 Counter (Out), it is the same as
2ND Output (OUT2) Action.
Down - A Inhibit input
Select One Shot
Output between
0.01ms~99.99ms
One Shot Time Delay
Self-Maintenance Output Self-Maintenance Output
One Shot Output of OUT2 Output
Post Count Up Action
Device Change
Level 2 Output
Coefficient value indication is maintained. Hold (0)
setup on OUT2 leads to Self-Maintenance Output, and
when setting up time, OUT2 Output processes after
one shot delay set time. OUT1 and OUT2 are turned
off at Reset
Input and the device returns to START.
Level 1 Output
Coefficient value indication continues on. Hold (0)
setup on OUT2 leads to Self-Maintenance Output, and
when setting up time, OUT2 Output processes after
one shot delay set time. OUT1 and OUT2 are turned
off at Reset Input and the device returns to START.
Input Mode
Level 1 Output
Output Mode
Output Time
Up - B Inhibit input
Out2 Output time
Down - B Inhibit input
s
s
Level 2 Output
Out1 Output time
s
Coefficient value indication continues on during
START and OUT2 yields One Shot Output.
Self-Maintenance Output of OUT1 is turned off when
OUT2 is turned off. (Repetitive Action)
Batch Output Port Selection
Level 1 Output
Level 2 Output
Input Counting Speed
Coefficient value indication is maintained during One
Shot Time, and then resets. (Repetitive Action)
Decimal Point Setup
Up - AB Individual input
Down - AB Individual input
Level 1 Output
Level 2 Output
Prescale
Coefficient value indication continues on. OUT2 yields
One Shot Output. Self-Maintenance Output of OUT1
is turned off after One Shot Time of OUT2.
n
Reset Time
n-2
Level 1 Output
n-4
n-5
Power Cutoff
Level 2 Output
n-7
n-8
Input Logic Check
UP /Down - A Command input
Coefficient value returns to the initial status, and
coefficient value indication is maintained during One
Shot Time.
The processed coefficient value is indicated after One
Shot Time. (Repetitive Action)
UP/Down - D Command input
/
Level 1 Output
Key Lock
Counter Function Setup Mode
Setup Items
Mode
Level 2 Output
Coefficient value increases and OUT2 yields One
Shot Output. The device is reset after the One Shot
Output.
(Repetitive Action)
Convert Operation Mode to Function Mode
-> Press MD key for 2 seconds
Contents
1 level setup type
2 levels setup type
Level 1 Output
Level 2 Output
: 1 level setup counter
: 2 levels setup counter
CP1,CP2 Dual inputs UP mode operatio
: CP1,CP2 Dual inputs down mode operation
# Refer to Input operation Mode (Counter)
Input
Mode
UP /Down - B Individual input
UP/Down - E Individual input
Level 1 Output
Level 2 Output
# Refer to Output operation Mode (Counter)
1 level setup type : display as OUT One short delay time
(D setup is self-maintenance
OUT2 Output
output))
One short time setup
Output Mode
Output Time
BATCH Output
Counting speed
Input Connection
No display for level 1 product
Batch Set a BATCH output port (
or
Coefficient value is maintained and OUT2 yields One
Shot Output. OUT1 and OUT2 are independent from
one another.
# If OUT1 is the same as SET1 setup value, it leads to
One Shot Output or Self-Maintenance Output.
(In case of Level 1 Setup Type, OUT is the same as
OUT2.)
# Reset refers to OUT1 and OUT 2 being turned off
and coefficient value being initialized.
:Relay,
:Transistor)
NPN (Non-Voltage Input)
is set when contact is used with maxmum input speed
UP /Down - C Phase difference input
UP/Down - F Phase difference input
Deciaml point setup
PNP (Voltage Input)
Sensor
Sensor
PRESCALE
RESET TIME
Memory
Input Logic
Key Lock
Minimum signal width of external reset signal input
: Coefficient value is saved when power failure
: Coefficient value is initialized when power failure
Non-Contact Sensor
Connection Method
Convertible by dip switch
: Key Lock remove
: No use for all keys (
: No use for
,
,
: No use for
exception)
keys
Non-Contact Sensor
Connection Method
Contact Sensor
Connection Method
Input Logic Selection
Operate the Switchover Switch after confirming the NPN/PNP Indication displayed on the top
Counter Output Action of Exclusive Indication (GE-T)
UP
No display Output mode, OUT2 output time, OUT1 output time, and BATCH output setup items for
TOTAL product.
No display OUT1 output time and BATCH output setup for level 1 product.
Contact Sensor
Connection Method
DOWN
SET
-99999
UP/DOWN/A,B,C
During Down Mode, Set Value is first to decrease.
6 digits: When -999999(-999), it flashes and is
no longer counted.
During Up Mode, it increases to the maximum
indication value, initializes to 0 and then increases
again.
Input Method
PNP Setup
Setup
Voltage Input
O.C
Voltage Input
O.C
H
5-30 V d.c
5-30 V d.c
0-2V d.c
0 - 2V d.c
L
0-2 V d.c
OPEN
5-30 V d.c
OPEN
For receiving Open Collector Input, Input Logic (PNP/NPN) Switchover Switch is embedded internally to Pull up
/ Pull down the resistance of 4.7 . (NPN Setup during shipment)
NPN
Input Logic Setup Status can be
verified in Function Setup Mode.
PNP
Internal Impedance is 4.7 , and
switches over to Pull Up or Pull
Down from NPN/PNP Selection.
(Refer to Input Connection)
Indicated Time Range
Range Selection
To prevent chattering during the use of Contact Input Counter, setup the
coefficient speed at 1 or 30 cps in Function Setup Mode.
Timer Setup
Operation Mode
Twin Timer Setup
Press the Operation
for two seconds.
Sexagecimal
Decimal
Sexagecimal
System
System
System
System
99.99 s
59.99 s
9999.99 s
59 m 59.99 s
999.9 s
9 m 59.9 s
9999 s
9 m 59 s
999999 s
99 h 59 m 59 s
9999 m
99 h 59 m
999999 m
9999 h 59 m
9999 h
99 d 23 h
999999 h
9999 d 23 h
s : second m : minute.
Key Operation Mode
6 digits Time Range
4 digits Time Range
Decimal
Interval / Signal START
Signal START / ON delay
99999.9 s 9 h 59 m 59.9 s
h : hour
t
t
Runs when START (CP2) is ‘On’.
Runs when START (CP2) is’On’ from the initial setup value
Maintains indicated value and controls output when exceeds the set time
Output Connection
output is ‘Off’ when the set time elapses.
(One Shot Output for OUTT Setup)
Device Change
Flicker / Signal START
Example of Non-Contact Output
Connect surge observer (diode,
varistor) on the both ends of the load
when using inductive load (relay etc.),
and must use with GND since the
internal circuit and non-contact output
are isolated from one another.
Calculate power load and load to
prevent the non-contact output from
exceeding the maximum of 30V
100mA.
Scale Change
0
Time range
Operation Mode
ON
OFF
ON
OFF
ON
OFF
Signal RUN / ON delay
SET
0
ON
OFF
Example of Contact Output
Avoid the flow of excessive current
since it is AC250V NO 3A
(load resistance) NC 2A
(load resistance), and the connection
must correspond to standard
connection method.
Output Time
Input Time
Surge Observer
Relay Output
Resistance : 220 Ω
Condenser : 0.1㎌ Voltage : 630 V a.c
TIM(TIMER)Setup
Input Logic Check
Power ON RUN
/
Signal One RUN
Time
range
0.1sec~999999(9999)h
UP/DOWN selectable
In TIM(TIMER) setup
Operation Mode
CP1/INHIBIT function stops the time.
[S.---] is activated when CP2 (START) is ‘ON’
[S ---] is activated when CP2 is maintained ‘ON’, and resets when ‘ Off’.
[P ---] activates with ‘Power On’
Setup
as
in order to compensate for interruption of electric
power during ‘Power Off’
(Indicates the Memorized Value when electric power is inputted again.)
* One short or
self-maintenance for OUT2(OUT)
Memory
Input logic
[HOLD] Setup (when output time [OUTT] is set at 0{HOLD})
Setup Set Time in Run Mode
Maintains the indication of initial value when Power is ‘On’
Runs when becomes START (CP2).
On/Off Repetitious Action of control output after reaching the Set Time.
Initializes and stops when Reset is ‘On’
ONE SHOT TIME Setup (when output time [OUTT] is set at more than 1)
Setup Set2 Time in Run Mode.
Maintains the indication of initial value when Power is ‘On’
Runs when Power is ‘On’
One Shot Output after reaching the Set Time.
Initializes and stops when Reset is ‘On’
Signal Addition
When START (CP2) is °ÆOn°Ø, output is also °ÆOn°Ø and the time
indicates the initial value.
SET
The initial value is initialized and output is °ÆOff°Ø when the set time
elapses.
t
* Level 1 Setup Type Output is OUT.
* INHIBIT (CP1) temporarily stops the time.
* No display for Total and TWIN TIMER
mode
SAdd: Runs when START (CP2) maintains to be ‘On’and is put on Hold
when ‘Off’ (Cumulative Timer Function)
Current time and Batch count
value are saved when power failure
Remove a data when power failure
: NPN Input
: PNP Input
Power RUN - ON delay
Runs when Power is’On’
Convertible by dip switch It is not available
to change setup in power input menu.
Off Output for T1 Time / On for T2 Time. Repetition
Initializes and stops when Reset is ‘On’
: Key Lock
Key Lock
Key lock setup in operation
condition (4stages)
: No use for all keys (
: No use
No use
No display a output time setup in total product.
t
Interval / Signal RUN
Power RUN / ON delay
Minimum input time selection 1msec
/20msec (INHIBIT), (START), RESET
Input time
t
Time activates the initial value to run when START (CP2) is °ÆOff°Ø.
In Total(Display only)product
Output time
t
OFF delay
Twin timer
is not available with
level 1 output model.
Refer to output operation mode chart
In TTIM(TWIN TIMER) setup
t
ON delay
Signal One RUN
Signal Addition
10 (Decimal) / 60 (Sexagesimal) system
Scale
t
Signal One RUN
Interval (Signal One RUN)
: Twin Timer
Signal RUN / OFF delay
Power RUN
OFF delay
Flicker (Signal One RUN)
: Timer
For TOTAL Model
Power ON RUN
Signal OFF RUN
2 levels setup type
Runs when CP2 (START) is’On’from the initial setup value, and resets when
Signal RUN
ON delay
Signal ON RUN
Interval (Signal ON RUN)
Contents
1 level setup type
t
Shot Output for OUTT Setup)
TTIM(TWIN TIMER)Setup
Power ON RUN
Key Lock
Setup Item
t
Maintains indicated value and controls output when exceeds the set time (One
Timer Operation Mode
Device
Change
ON
OFF
‘Off’
Power Interruption Storage
Output is ‘On’ during the set time, and the indicated value is initialized and
,
,
keys
key exception)
keys
Power RUN - OFF delay
t
t
Runs when ‘Power On’
When Reset signal is authorized, process value initializes and runs.
Runs when Power is °ÆOn°Ø
Runs when START (CP2) is ‘On’ and resets when ‘Off’
Output is ‘On’during the set time, and the initial value is initialized and output is
‘Off’ when the set time elapses.
On Output for T1 Time / Off for T2 Time. Repetition
Initializes and stops when Reset is ‘On’
ON
OFF
ON
OFF
ON
OFF
0
ON
OFF
Signal START - ON delay
Maintains the indication of initial value when Power is ‘On’
Runs with the input of Start (CP2)
Batch Counting & Output Action
Batch counting value continues to increase until Batch Reset is authorized.
On Output for SET1 Time / Off for SET2 Time. Repetition
When the batch coefficient value exceeds 999999 (4 digits of 9999), maintain
Initializes and stops when Reset is ‘On’
and indicate as 999999.
In case of batch display state (BAT lamp is lighted), press the RST key on the
front section to reset the batch value.
Signal START - OFF delay
Even in the batch display state, counter/timer action operates normally.
Maintains the indication of initial value when Power is ‘On’
Batch coefficient increases at the output of OUT2 (OUT).
Runs with the input of Start (CP2)
Batch output is outputted as (BAT.O). (BAT.O lamp is lighted)
Off Output for SET1 Time / On for SET2 Time. Repetition
Initializes and stops when Reset is’On’
Instant Output Setup
Function switches over to instant output when the batch value is set at 0.
(BAT.O lamp is lighted)
Batch Counter setup Method
1. Press
+
Keys Simultaneously.
Enter as setup state and set 6 digits (4 digits) FND at ‘100’ by pressing the flashing
indication of
+
keys. (In case of setting the batch setup value as 100)
2. Press the
changes)
Key to complete the setup. (Press
3. Press the
turned off)
+
to exit without making any
key to restore to Operation Mode. (BAT lamp on the left is
Normal operation is possible under Batch Indication Mode.
Batch Switchover of Level 1 Setup Type
Press
Keys.
Timer Action of Exclusive Indication (GE-T)
Power RUN
SET display
BATCH display
Batch Switchover of Level 2 Setup Type
Press
Keys.
Runs after initializing the process value upon the authorization of Run Reset
Signal when Power is ‘On’ Set Time is first to be reduced during Down Mode
Setup.
GE7-P62
Signal RUN
SET1 display
Press
SET2 display
Keys.
Press
Runs when START (CP2) is ‘On’, and resets when START (CP2) is ‘Off’
Set Time is first to be reduced during Down Mode Setup.
BATCH display
Keys.
Was this manual useful for you? yes no