INSTALLATION
Model 634
VOLTAGE REGULATOR
GENERAL INFORMATION
The VR634B-A Voltage Regulator is built for use on 50/60 Hz brushless alternators. This AVR includes frequency compensation, over voltage shutdown, an automatic exciter circuit, and an EMI filter.
ELECTRICAL SPECIFICATIONS
Dc Output Power:
4 Adc at 63 Vdc continuous,
7 Adc at 100 Vdc (700W) forcing one minute
(at 240 Vac input).
Exciter Field Dc Resistance:
15 to 100 Ohms
Sensing Input:
220v Position: 190-240 Vac, Single phase, 50/60 Hz ±5%
110v Position: 100-120 Vac, Single phase, 50/60 Hz ±5%
Voltage Adjust Range:
220v Position: 170-265 Vac
120v Position: 90-132 Vac.
Regulation Accuracy:
Better than ± 1.0% no load to full load.
Response Time:
Less than 1.5 cycles for ± 5% change in sensing voltage.
EMI Suppression:
Internal EMI filter
Overexcitation Shutdown:
Power to fields STOPS when exciter voltage greater than 100 Vdc
Voltage Build-up:
Automatic voltage build-up with 5 Vac minimum residual
Operating Temperature:
-40° C to + 80°C
MOUNTING
The regulator may be mounted in any position. Use the Voltage Regulator itself as a template
Weight:
15 oz. (0.45 kg) Net.
FUSE
The fuse is part of the Voltage regulator
Use Bussman Model T5AH250
FIELD FLASHING
WARNINGS
Only qualified personal should install & service this AVR.
The resistance of the exciter must be from 15 to 100 Ohms.
Do not use Meggers they damage the AVR.
When a new regulator is installed for the first time, the polarity of residual magnetism may be incorrect or the magnitude low. If the generator does not build-up voltage after startup, shut down the engine and do the following:
OVER EXCITATION SHUTDOWN a.
With the engine STOPPED, apply a dc voltage of not more than 12Vdc, for 3 sec. to terminals F- & F+ in series with a current limiting resistor
If the exciter field voltage exceeds 100
Vdc, the regulator removes the field current of 3-5 ohms & 100 Watts on the fields.
after a time delay. At 135 Vdc, the field voltage is totally removed within 0.2
c.
Start the engine and measure voltage at regulator leads 3 and 4 if is greater seconds.
than 6 volts, voltage build-up should be successful.
Repeat procedure
After shutdown, reset the regulator by stopping and restarting the engine.
if less than 6 Volts is measured.
VOLTAGE ADJUST RHEOSTAT (VAR)
Adjust with a screwdriver potentiometer on AVR to change generator output voltage.
moving rheostat CW increases generator voltage.
d.
If repeating steps 1 and 2 does not result in generator voltage build-up, replace the voltage regulator.
When using remote voltage adjust rheostat
(VAR), the VAR wire on the regulator should be cut and the rheostat connected to wire ends. A 1 k ohm 1/2 watt rheostat is adequate for most applications.
See connection Diagrams
Volt selector
Switch
PRELIMINARY SET-UP
To prevent damage to the regulator, complete the following steps before proceeding with system start-up: a. Verify that the voltage regulator conforms with the generator system requirements.
b.
Ensure that the regulator is correctly connected to the generator.
See connection Diagrams c.
Set the regulator VAR fully CCW before
starting
SYSTEM START-UP a.
Start the prime mover and bring up to rated speed. Voltage should buildup. If a minimum of 5 Vac residual is not present, you must flash the fields.
Fuse
Stab.
Adjust
Voltage
Adjust b.
Adjust internal VAR rheostat on AVR for normal generator output voltage.
EXCITER FIELD POWER CIRCUIT (regulator wires F+ & F-).
Connect the regulator wire F+ to the exciter field F+ terminal, and regulator wire F- to exciter field F- terminal.
Generator
120 V
L1
L2
Generator
L1
L2
L3
POWER & SENSING INPUT (regulator wires 3
& 4)
15 to 100 Ohms
15 to 100 Ohms
Connect as shown in side diagrams.
Power for the exciter field and regulator
HZ HZ F+ F3 4 VAR VAR circuitry is taken from the generator output.
Input Voltage
120 VOLTS on 120 v Position
1 K Ohm 1/2 W external VAR
If Used
HZ HZ F+ F3 4
Input Voltage
200 to 277 volts
FREQUENCY ROLL OFF
Hz & Hz Together For
50 HZ USE
At 60 Hz ROLL OFF FREQUENCY starts 55 Hz.
At 50 Hz ROLL OFF FREQUENCY starts 45 Hz.
The Regulator comes factory set for 60 Hz use.
Short wires marked Hz. for 50 Hz use.
Hz & Hz Together For
50 HZ USE
Be sure to insulate the connection. Dist. by Flight Systems Inc. www.flightsystems.com
VAR VAR
1 K Ohm 1/2 W external VAR
If Used