Generator Sets
Generator
Sets
3600 Family
1845-7670 hp
1375-5720 kW
CATERPILLAR® ENGINE SPECIFICATIONS
Bore — mm (in) . . . . . . . . . . . . . . . . . . . . . . . . 280 (11.0)
Stroke — mm (in) . . . . . . . . . . . . . . . . . . . . . . . 300 (11.8)
Displacement — L (cu in) . . . . . . . . . . . . . . . 18.5 (1127)
Aspiration . . . . . . . . . . . . . . Turbocharged-Aftercooled
Compression ratio . . . . . . . . . . . . . . . . . . . . . . . . . . . 13:1
Rotation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ccw or cw
Low Idle Speed — rpm . . . . . . . . . . . . . . . . . . . . 300-400
Rated Speed — rpm . . . . . . . . . . . . . . . . . . . . . 720-1000
Avg. Piston Speed — m/s (ft/s) . . . . 7.2-10.0 (23.6-32.8)
BMEP — bar (psi)
Continuous . . . . . . . . . . . . . . . . . . 20.0-21.7 (290-314)
Prime. . . . . . . . . . . . . . . . . . . . . . . . 22.0-23.9 (319-347)
Standby . . . . . . . . . . . . . . . . . . . . . 24.2-26.3 (351-382)
BSFC (with pumps) — g/kW-h (lb/hp-h)
Continuous . . . . . . . . . . . . . . . . . . 187-199 (.307-.327)
Prime. . . . . . . . . . . . . . . . . . . . . . . . 186-199 (.306-.327)
Standby . . . . . . . . . . . . . . . . . . . . . 186-199 (.306-.327)
Description – Caterpillar® 3600 Generator Sets are designed to provide reliable and durable service with a
wide variety of blended and bunker fuels up to 700 cSt at 50° C.
PERFORMANCE DATA
All Industry Voltages are Available
Generator Set Displacement kW at 720 rpm/60Hz kW at 750 rpm/50 Hz kW at 900 rpm/60 Hz kW at 1000 rpm/50Hz
Engine Model
Liters
(cu. in.)
Cont. Prime Stdby Cont. Prime Stdby Cont. Prime Stdby Cont. Prime Stdby
3606
6 In-line
110.8
6,764
1375
1525
1680
1420
1570
1730
1650
1820
2000
1760
1940
2150
3608
8 In-line
147.8
9,018
1830
2020
2220
1890
2080
2290
2200
2420
2660
2350
2600
2860
3612
12 Vee
221.7
13,527
2750
3050
3360
2840
3140
3460
3300
3640
4000
3520
3880
4300
3616
16 Vee
295.6
18,036
3660
4040
4440
3780
4160
4580
4400
4840
5320
4700
5200
5720
RATING CONDITIONS
Ratings – Generator Set ratings are in electrical
kilowatts, operating on distillate fuel.
Continuous – Power and speed capabilities of the
engine which can be used without interruption
of load — capable of 10% overload.
Prime – For electrical service with variable loads —
capable of 10% overload.
Standby – for electrical service during interruption of
normal power.
Power – ±5% power tolerance applicable for
overload/fuel stop power.
Fuel consumption – is based on ISO3046/1 with +5%
tolerance for distillate fuel having an LHV of
42 780 kJ/kg (18,390 BTU/lb) and density or 838.9 g/liter
(7.001 lbs/U.S. gal.). Including all associated pumps.
Heavy Fuel continuous ratings are 9% less than
distillate fuel. Prime and standby ratings are not
available. Fuel viscosity and contaminant capability is
CIMAC Class K55 (700 cSt at 50° C) at 720-1000 rpm.
3600
FAMILY GENERATOR SETS
STANDARD EQUIPMENT
Engine
Accessory module with coolant expansion tank
Base mounting
Base, with lifting provisions and vibration
isolators
Breather, crankcase
Circuit cooling system, combined or separate
Cooler, lubricating oil
Duplex filters, right/left hand
fuel, full flow
lubricating oil, full flow
Engine running relay signal
Governor, Electronic 2301A
Instrument panel, includes:
differential pressure gauges – oil filter, fuel filter,
and inlet air restriction
digital tachometer
pressure gauges – oil, fuel
temperature gauges – engine coolant,
lubricating oil, exhaust stack, and air manifold
Manifold, exhaust, dry shielded
Oil filters, centrifugal
Pumps, gear driven
aftercooler & oil cooler
fuel transfer
jacket water
lubricating oil
Shutoff, electrical 24 VDC, for:
crankcase pressure
high oil temperature
high water temperature
low oil pressure (high & low idle)
overspeed
Single or separate circuit cooling system
Starting, air
Generator
Electrical
3 phase, six leads, WYE
Class “F” insulation
Maximum voltage harmonic – not to exceed 5%
total with no single voltage harmonic above 3%
NEMA MG1-22, IEC 34-1
Overload capability 110% for two hours on prime .
and continuous ratings
Short circuit capability: 300% overcurrent for 10
seconds
Voltage waveform – less than 5% deviation
Mechanical
Bearing, two sleeve, self-lubricating
Enclosure – open drip-proof – guarded (IP23)
Mechanical balance, NEMA
Overspeed: 125% per IEC 34-1 and NEMA MG-1
Package
Performance test to ISO8528
Standard Accessories
Bearing temperature detectors
Space heaters, single phase
Stator temperature detectors
Terminal box for connections
Voltage Regulation: ±1/2% no load to full load
Paralleling capability
Power isolation transformers and/or permanent
magnet excitation
Static regulator, 1 or 3 phase sensing
DIMENSIONAL DATA
No radiator is included in table below.
Gen Set
3606
3608
3612
3616
WT
L
kg
lb
mm
34,070 74,970 7950
41,390 91,050 9240
51,230 112,690 8970
64,470 141,840 10,260
H
in
313
364
353
404
mm
3330
3330
3710
3790
W
in
131
131
146
149
mm
2425
2425
2515
2515
in
96
96
99
99
All data is for reference only. Data is subject to change without
notice. Check TMI or contact factory for confirmation.
Materials and specifications are subject to change without notice.
LEHX5459 (9-95)
Supersedes LEHX5051
The International System of Units (SI) is used in this publication.
© 1995 Caterpillar Inc.
Printed in U.S.A.
Was this manual useful for you? yes no