SINGLE-PHASE UPS from 1000 to 1500 VA
dhea
UPS
SINGLE-PHASE
from 1000
to 1500 VA
THE GLOBAL SPECIALIST
IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES
DHEA
ENERGY STATION
On‑Line double
conversion UPS that
can be extended with
stackable, automaticconnection units
conventional
single phase
UPS
The system comprises a UPS unit and battery packs
with automatic connections and a hot-swap system.
The compact size (depth: 185 mm) enables the UPS
to be installed in very small spaces.
The special sealed, fume-free batteries enable it to be used
in the home.
Load management
The 1500 VA model has 3 outputs, 2 of
which are timed, deactivating themselves
after a pre-set time, thus extending
the supply to the most important loads
according to the available backup time.
Plug-in connection with hot-swap system
The “standard” units with automatic connections make it very easy
for inexperienced users to install all the system’s components. With
the hot-swap system, battery packs can be added or replaced at any
time, without switching off the UPS.
2
DHEA
Conventional UPS - Single phase On-line double conversion VFI
Cat. Nos.
3 101 07
3 101 08
Nominal power (VA)
1000
1500
Active power (W)
700
1050
General characteristics
Technology
On-line double conversion
Waveform
Sinusoidal
Nominal input voltage
230 V
Input voltage range
184 V ÷ 265 V at 100% load
Minimum mains operating
voltage
184 V with nominal load/100 V at 50% of
nominal load
Input frequency
50/60 Hz ± 2% (± 14% in extended range)
3 101 08
› 0.99 at 20% load
Input power factor
Output voltage
230 V ± 1%
‹ 1%
Output voltage distortion
Output frequency (battery
operation)
50/60 Hz ± 1%
Batteries
3 107 73
Acoustic noise at 1 m (dBA)
- System can be combined with a genset to increase the backup time if there are
prolonged faults.
- Battery packs with integrated batteries and automatic connectors.
- Up to 10 battery packs can be added.
- UPS supply voltage only present when the pack is connected.
Cat. Nos.
4 (UPS) + 16 (battery pack)
Dimensions
(H x W x D) (mm)
309 x 450 x 170 (UPS) 125 x 450 x 170 (battery pack)
Regulations
Nominal power
VA
Active power
W
1000
1500
700
1050
BATTERIES
Description
3 107 73
Battery pack
EN 62040-1, EN 62040-2, EN 62040-3
1 x RS 232 + 3 contact outputs (2 poles) + EPO
Protection index
Energy stations
3 101 07
3 101 08
‹ 40
Net weight (kg)
External connections
Pack
2 x 36 V 7.2 Ah stacking battery packs
Output sockets
IP 21
1 line
3 lines
(2 of which are timed)
Backup time
No. of battery
packs
1000 VA
1
38’
22’
2
1h 24’
53’
3
2h 16’
1h 25’
4
3h 16’
1h 56’
5
4h 8’
2h 40’
6
5h 4’
3h 18’
7
5h 46’
3h 53’
8
6h 55’
4h 32’
9
8h 8’
5h 7’
10
9h 7’
5h 36’
1500 VA
NOTE: The backup times, expressed in minutes, are measured under optimum operating conditions.
3
WWW.UPS.LEGRAND.COM
AD-EXLG/UPS-DH12B/GB - 12/2012
World Headquarters and
International Department
87045 Limoges Cedex - France
☎ : + 33 (0) 5 55 06 87 87
Fax: + 33 (0) 5 55 06 74 55
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project