Hall-Effect Sensor Transducer Current Measure Split Solid Core

Hall-Effect Sensor Transducer Current Measure Split Solid Core
AC & DC Voltage & Current Monitor
ENVIROMUX®
AC & DC Voltage & Current Monitor
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
Reports AC voltage, AC current, DC voltage and DC current.
•• Current measurements require Hall-Effect transducers (sold
separately).
•• Polling rate: 1Sa/s.
Common applications include: electrical systems, power equipment,
battery monitoring, generators, remote sites, controlled environment
vaults (CEVs), building automation, data center, cabinets, telecom,
substations, storage power supplies, communication huts, indoor/
outdoor lighting, power distribution, and medical and test equipment.
AC voltage 2-pin terminal block
•• 0 to 240VAC 600V isolated
•• 0.25VAC resolution
•• Accuracy
ŠŠ 0 to 220VAC: 2.5VAC accuracy
ŠŠ 220 to 240VAC: 5.0VAC accuracy
DC voltage 2-pin terminal block
•• -60 to +60V DC non-isolated
•• 0.12VDC resolution
•• 1.2VDC accuracy
One rectifying Hall Effect 4-pin transducer interface for measuring AC
current
•• 0.2% resolution
•• Accuracy and range are transducer-dependent (sold separately).
One non-rectifying Hall Effect 4-pin transducer interface for measuring
DC current
•• 0.2% resolution
•• Accuracy and range are transducer-dependent (sold separately).
Supports CAT5/5e/6 cable up to 1,000 ft (305 m).
Dimensions WxDxH (in): 6.2x2.3x1.6 (158x58x41 mm).
Powered by ENVIROMUX-2D/5D/16D.
Regulatory approvals: CE, RoHS.
Compatible with ENVIROMUX-FSC Fiber Converter/Extender.
•• Use to extend the monitor up to 1.2 miles (2km) from the
ENVIROMUX unit.
ENVIROMUX-ACDCLM
The AC & DC Voltage & Current Monitor measures and reports AC and DC
voltage, and reports AC and DC current measured with attached Hall-Effect
transducers (sold separately) to the ENVIROMUX-2D/5D/16D unit.
AC & DC Voltage & Current Monitor
R
1
NTI Part #
ENVIROMUX-ACDCLM
NETWORK
TECHNOLOGIES
INCORPORATED
Description
AC & DC Voltage & Current Monitor
1.800.RGB.TECH (800.742.8324)
To l l F r e e : U S & C a n a d a
330.562.7070
International calls
© 2015, 2016 NTI. All rights reserved.
330.562.1999
Worldwide fax
sales@ntigo.com
www.networktechinc.com
AC & DC Voltage & Current Monitor
ENVIROMUX®
Hall-Effect Current Sensors, Solid-Core,
6.5mm Loop Diameter
Hall-Effect Current Sensors, Split-Core,
12mm Loop Diameter
ENVIROMUX-AMPxx-SC12
ENVIROMUX-AMPxx-6-5
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
Measures both AC and DC currents using a solid-core system.
•• Available rated currents: 10A, 20A, and 50A.
ŠŠ Contact an NTI product consultant for other available ratings
between 10A and 50A.
Common applications include: monitoring AC variable speed drives,
static converters for DC motor drives, battery supplied applications,
uninterruptible power supplies (UPS), switched mode power
supplies (SMPS), electrochemical systems, and power supplies for
welding applications.
Includes a 7ft 4-wire cable for connecting to the
ENVIROMUX-ACDCLM.
•• To extend the distance between the hall-effect sensor and
the ENVIROMUX-ACDCLM, simply connect longer wires
(22AWG) using the included splices.
ŠŠ It is recommended to place the ENVIROMUX-ACDCLM
as close to the hall-effect sensor as possible. The
ENVIROMUX-ACDCLM can be placed up to 1000 ft away
from the ENVIROMUX-2D/5D/16D unit using CAT5/5e/6
cable.
Loop diameter: 0.26” (6.5mm).
Response time: ≤1µS @ 50A/µ S, 10%-90%.
Galvanic isolation: 2.5KV @ 50Hz, AC, 1min.
Supply voltage: ±12V, ±15V.
Output voltage: ±4V.
Power consumption: ≤25mA.
Comes with two 0.08” (2mm) diameter mounting holes.
Dimensions WxDxH (in): 0.98x1.26x0.98 (25x32x25mm).
Operating temperature: -40 to 185°F (-40 to 85°C).
Storage temperature: -40 to 257°F (-40 to 125°C).
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
Hall-Effect Current Sensors, Solid-Core,
6.5mm Loop Diameter
NTI Part #
Hall-Effect Current Sensors, Split-Core,
12mm Loop Diameter
Rated Current
Loop Diameter
10A
20A
50A
0.26” (6.5mm)
0.26” (6.5mm)
0.26” (6.5mm)
ENVIROMUX-AMP10-6-5
ENVIROMUX-AMP20-6-5
ENVIROMUX-AMP50-6-5
Measures AC and DC currents using a split-core system.
•• Available rated currents: 50A, 100A, 200A, 300A, 400A.
ŠŠ Contact an NTI product consultant for other available ratings
between 50A and 400A.
Common applications include: monitoring AC variable speed drives,
static converters for DC motor drives, battery supplied applications,
uninterruptible power supplies (UPS), switched mode power supplies
(SMPS), electrochemical systems, and power supplies for welding
applications.
Includes a 7ft 4-wire cable for connecting to the ENVIROMUXACDCLM or ENVIROMUX-DCLM-6.
•• To extend the distance between the hall-effect sensor and the
ENVIROMUX-ACDCLM or ENVIROMUX-DCLM-6, simply
connect longer wires (22AWG) using the included splices.
ŠŠ It is recommended to place the ENVIROMUX-ACDCLM or
ENVIROMUX-DCLM-6 as close to the hall-effect sensor as
possible. The ENVIROMUX-ACDCLM and ENVIROMUXDCLM-6 can be placed up to 1000 ft away from the
ENVIROMUX-2D/5D/16D unit using CAT5/5e/6 cable.
Loop diameter: 0.47” (12mm)..
Response time: ≤7µS @ 50A/µ S, 10%-90%.
Galvanic isolation: 2.5KV @ 50Hz, AC, 1min.
Supply voltage: ±12V, ±15V.
Output voltage: ±4V.
Current consumption: ≤25mA.
Dimensions WxDxH (in): 1.81x0.63x1.46 (46x16x37mm).
Operating temperature: -13 to 185°F (-25 to 85°C).
Storage temperature: -40 to 212°F (-40 to 100°C).
NTI Part #
Rated Current
Loop Diameter
50A
100A
200A
300A
400A
0.47” (12mm)
0.47” (12mm)
0.47” (12mm)
0.47” (12mm)
0.47” (12mm)
ENVIROMUX-AMP50-SC12
ENVIROMUX-AMP100-SC12
ENVIROMUX-AMP200-SC12
ENVIROMUX-AMP300-SC12
ENVIROMUX-AMP400-SC12
Note: Contact an NTI product consultant for hall-effect sensors in other sizes and ratings.
R
NETWORK
TECHNOLOGIES
INCORPORATED
1.800.RGB.TECH (800.742.8324)
To l l F r e e : U S & C a n a d a
330.562.7070
International calls
© 2015, 2016 NTI. All rights reserved.
330.562.1999
Worldwide fax
sales@ntigo.com
www.networktechinc.com
2
AC & DC Voltage & Current Monitor
ENVIROMUX®
Hall-Effect Current Sensors, Split-Core,
21mm Loop Diameter
ENVIROMUX-AMPxx-SC21
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
„„
Measures both AC and DC currents using a split-core system.
•• Available rated currents: 30A, 50A, 100A, 200A, and 500A.
ŠŠ Contact an NTI product consultant for other available ratings
between 30A and 500A.
Common applications include: monitoring AC variable speed drives,
static converters for DC motor drives, battery supplied applications,
uninterruptible power supplies (UPS), switched mode power supplies
(SMPS), electrochemical systems, and power supplies for welding
applications.
Includes a 7ft 4-wire cable for connecting to the
ENVIROMUX-ACDCLM.
•• To extend the distance between the hall-effect sensor and
the ENVIROMUX-ACDCLM, simply connect longer wires
(22AWG) using the included splices.
ŠŠ It is recommended to place the ENVIROMUX-ACDCLM
as close to the hall-effect sensor as possible. The
ENVIROMUX-ACDCLM can be placed up to 1000 ft away
from the ENVIROMUX-2D/5D/16D unit using CAT5/5e/6
cable.
Loop diameter: 0.83” (21mm).
Response time: ≤5µS @ 50A/µ S, 10%-90%.
Galvanic isolation: 2.5KV @ 50Hz, AC, 1min.
Supply voltage: ±12V, ±15V.
Output voltage: ±4V.
Power consumption: ≤25mA .
Comes with two 0.2” (5mm) diameter open-slotted mounting holes.
Dimensions WxDxH (in): 2.36x0.63x2.40 (60x16x61mm).
Operating temperature: -40 to 185°F (-40 to 85°C).
Storage temperature: -40 to 257°F (-40 to 125°C).
Hall-Effect Current Sensors, Split-Core,
21mm Loop Diameter
NTI Part #
Rated Current
Loop Diameter
30A
50A
100A
200A
500A
0.83” (21mm)
0.83” (21mm)
0.83” (21mm)
0.83” (21mm)
0.83” (21mm)
ENVIROMUX-AMP30-SC21
ENVIROMUX-AMP50-SC21
ENVIROMUX-AMP100-SC21
ENVIROMUX-AMP200-SC21
ENVIROMUX-AMP500-SC21
Note: Contact an NTI product consultant for hall-effect sensors in other sizes and ratings.
R
3
NETWORK
TECHNOLOGIES
INCORPORATED
1.800.RGB.TECH (800.742.8324)
To l l F r e e : U S & C a n a d a
330.562.7070
International calls
© 2015, 2016 NTI. All rights reserved.
330.562.1999
Worldwide fax
sales@ntigo.com
www.networktechinc.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising