Description Specifications Installation CAUTION Maintenance

Description Specifications Installation CAUTION Maintenance
Installation and Maintenance Instructions for the
Catalog 53D-GW AdaptaBeacon® Signal
Cheshire, CT 06410 203-699-3300 (Ph)
203-699-3365 (Cust. Serv. Fax)
203-699-3078 (Tech. Serv. Fax)
Description
The catalog number 53D-GW AdaptaBeacon signal is an
in-rush current limited, DC-operated, rotating light. The
signal may be either conduit mounted or direct surface
mounted and is suitable for indoor installation. A hardware kit is included with the signal for direct mounting
applications.
Specifications
Catalog
Number
53DA-GW
53DB-GW
53DC-GW
53DG-GW
53DM-GW
53DR-GW
Voltage
24
24
24
24
24
24
-
28V
28V
28V
28V
28V
28V
DC
DC
DC
DC
DC
DC
Current
Dome
Replacement
1.0A
1.0A
1.0A
1.0A
1.0A
1.0A
52-LA
52-LB
52-LC
52-LG
52-LM
52-LR
Lamp
Replacement
Cat.
Cat.
Cat.
Cat.
Cat.
Cat.
No.
No.
No.
No.
No.
No.
1638
1638
1638
1638
1638
1638
Installation
CAUTION
Ensure that power is disconnected before installing the
signal.
1. Remove the screw in the clamp ring, remove the ring
and lift off the dome (Figure 1).
2. Install the base using one of the following applicable
procedures.
Conduit Mounting
a. Route the wiring from the required power source
for the signal (refer to the signal's label for voltage
rating) through a 1/2" NPT conduit (not supplied)
and through the conduit entrance hole in the base.
b. Install the base on the conduit.
Direct Surface Mounting
a. Remove the two knockouts for the mounting
screws from the bottom of the base. See Figure 1
for the location of the knockouts.
b. Place the gasket provided in the hardware kit on
the mounting surface and mark the center of the
three holes in the gasket on the surface. Remove
the gasket and drill a 3/8" hole at each of the
marked positions.
c.
Install the two rubber expansion plugs provided
in the hardware kit into the two outer holes in
the mounting surface as indicated in Figure 2.
d. Route the wiring from the required power source
for the signal (refer to the signal's label for the
voltage rating) through the center holes in the
mounting surface, gasket and base.
e. Align the holes in the gasket with the holes in the
base. Insert the two screws with lockwashers
provided in the hardware kit through the
mounting holes inside the base and align the
screws with the rubber expansion plugs as shown
in Figure 2. Press the base firmly against the
mounting surface and tighten the screws.
3. Using wire nuts (not supplied), connect one of the
signal's red wire leads to the incoming positive (+)
power source lead and the other to the outgoing
positive (+) power source for the next unit or an endof-line resistor. Connect one of the signals' white wire
leads to the incoming negative (-) power source lead
and the other to the outgoing negative (-) power source
for the next unit or an end-of-line resistor.
NOTE: Wire run must be broken at each unit for
electrical supervision.
Maintenance
CAUTION
Always disconnect power before disassembling the
signal.
Lamp Replacement
1. Replace the lamp as follows (Refer to Specifications
for the required lamp.):
a. Disconnect power.
b. Remove the screw in the clamp ring and remove
the ring.
c.
Lift the dome off the signal.
d. Replace the lamp.
CAUTION
Do NOT use abrasive materials or cleaners to clean the
dome.
Cleaning
The dome should be periodically cleaned to maintain light
visibility. The dome may be cleaned with a soft cloth or
sponge using a mild detergent. Dry the dome thoroughly
before replacing.
P/N 3100633 ISSUE 2 © 2004
Figure 1. Catalog 53D-GW Rotating Light
P/N 3100633 ISSUE 2
Figure 2. Direct Surface Mounting of Signal
Was this manual useful for you? yes no