SP PRO AU Series
A smarter bi-directional inverter charger.
4 0 -AU on-grid and want
Whether youSPMC2
live off-grid,
SPMC2 4 1 -AU
to add storage,
or on-grid
SPMC4
8 1 -AU and want to move
SPMC4
-AU
off-grid, the SP
PRO8 2bi-directional
inverter
SPMC1 2 0 1
charger can control
and 2manage
every
NEW SPLC1
00
2 0 2energy needs.
aspectSPLC1
of your
By incorporating solar, wind, hydro or a
diesel generator with batteries, you can be
sure you will never be without power.
Product Highlights
• Australian designed and manufactured
• Off-grid and Solar Hybrid (grid backup and grid
feed), marine and mobile operation
• More features included as standard ‘inside the
box’ than any other inverter charger
• AC or DC coupling compatible
• Retrofit existing systems
• Easily configurable for domestic and
commercial applications
• Integrated generator controller to maximise
system efficiency
• AC continuous load power from 3 kW to 60 kW
• Single, dual or three phase
• 63A or 125A transfer contactor standard
• Comprehensive after-sales support
• Up to 10 year warranty*
* Conditions apply see website for details
SP PRO AU Series models
SPMC240-AU
SPMC241-AU
SPMC481-AU
SPMC482-AU
SPMC1201
SPLC1200
SPLC1202
Grid Independence | Outstanding Reliability | Ultimate Flexibility
+61 3 9727 6600 | www.selectronic.com.au | facebook.com/SelectronicAustralia
SP PRO AU Series Specifications
SPMC240-AU
SPMC241-AU
SPMC481-AU
SPMC482-AU
SPMC1201
SPLC1200
SPLC1202
7.5 kW
10.5 kW
12.0 kW
18.0 kW
18.0 kW
33.0 kW
38.0 kW
1 minute
5.4 kW
7.6 kW
8.7 kW
13.0 kW
13.0 kW
26.0 kW
35.0 kW
30 minutes
4.2 kW
6.75 kW
7.0 kW
11.25 kW
11.25 kW
23.0 kW
30.0 kW
60 minutes
3.2 kW
4.7 kW
5.3 kW
8.0 kW
8.0 kW
18.0 kW
24.0 kW
Continuous
3.0 kW
4.5 kW
5.0 kW
7.5 kW
7.5 kW
15.0 kW
AC OUTPUTS
Maximum Export Power
Maximum AC Load Power from batteries:
Continuous output (2 x continuous output for Selectronic Certified Managed AC Coupled)
30 seconds
Max total output to Load, AC source + inverter
Nominal voltage Off Grid
20.0 kW
30 kW 2
15 kW + inverter rating 2
240 V AC configurable 210 to 240 V AC
Total harmonic distortion Off Grid
<3% @ 0-200% rated load
Frequency Off Grid
50 or 60 Hz +/-0.005% No Grid
AC INPUTS
Nominal voltage
210 +/- 15% to 240 +/- 10% V AC
Nominal input frequency
50/60Hz configurable +/- 1% to 10%
63 A 3 / 15 kW
AC transfer current capacity
Max AC input source, (Generator or Grid)
125 A 3 / 30 kW
30 kW 4
15 kW 4
AC transfer time
typical < 1/2 cycle
Max charging from Grid or Generator
3.0 kW / 125 A
4.5 kW / 187 A
5.0 kW / 104 A
7.5 kW / 156 A
7.5 kW / 62 A
15.0 kW / 125 A
20.0 kW / 166 A
DC INPUTS
Rated DC input / DC voltage range (V DC)
24 V / 20 - 34
48 V / 40 - 68
Battery capacity (range)
120 V / 100 - 170
up to 10, 000 Ah
EFFICIENCY
Peak Efficiency
95%
95%
96%
96%
DC consumption: idle
97%
97.2 %
97.2%
6W
GENERAL
Disconnect time if Grid (AC source) fails
< 30 ms
DC Circuit Breakers internal
-
2 pole 250A
Operating Temperature Range
-10 ˚C to 60 ˚C
Inverter display indicators
charger status, charge source, usable battery capacity remaining, alarms, AC status.
Renewable charging source
Managed AC coupling with any Selectronic Certified single phase inverter, DC Renewable charge controller or generic AC coupled 1
Data logging storage
Up to 2.5 years
SP LINK configuration and monitoring software
Included as standard
Ambient temperature operating range
-10˚C to 60˚C
FEATURES
Generator Backup
Inbuilt for off-grid systems. Optional for on-grid systems using our Grid Fail Backup module.
Battery temperature / Mid point battery voltage
Inbuilt for off-grid systems
Yes / Yes
Battery Compatibility
Highly configurable battery charging set points allow integration with many battery chemistries including lithium.
Control Inputs
4 of, 12V to 60V True, < 3V False
Shunt Inputs
Two user definable: Suitable for 25 A - 1000 A current shunts at 25mV - 100mV
Analogue Inputs
2 general purpose logged 0-60V
-
Relay Control Outputs
Relay: 4 of 60 VDC, 500 mA / Digital: 3 of 60 VDC, 5 mA
Communication Port 1
USB (slave) or RS232 (adjustable baud rate of up to 115200)
Communication Port 2
RS485 or RS232 (adjustable baud rate of up to 115200)
Dual, Split & Three Phase compatible
Yes with an SP PRO AU on each phase
Warranty
3 - 10 years (conditions apply see website for details)
STANDARDS
Safety - Uninterruptible Power Supply (UPS)
IEC 62040-1-1:2002 / AS 62040-1-1:2003
Safety - Power converters used in PV Systems
IEC 62109-1 and IEC 62109-2
EMC (Domestic limits)
EN 61000.6.3:2007
EMC (Industrial limits)
-
EN 61000.6.4:2007
Grid Connect
AS4777.2:2015
Certification
Certificate of Suitability, Ctick
Protection
IP43
WEIGHTS & DIMENSIONS
Weight: Packed / Unpacked with wall mount
39 kg / 35 kg
Dimensions: Packed / Unpacked h x w x d (mm)
2
3
45 kg / 40 kg
54 kg / 42 kg
52 kg / 42 kg
810 x 500 x 350 / 690 x 375 x 220
Where AC rating of generic inverter does not exceed the Maximum AC Grid Feed Power of the SP PRO
60 kW with optional external contactor
250 A with optional external contactor
4
60 kW with optional external contactor
1
45 kg / 39 kg
160 kg / 113 kg
163 kg / 115 kg
1080 x 740 x 650 / 870 x 540 x 290
All specifications at 25˚C and rated DC input voltage except where otherwise stated.
Specifications may change without notice see website.
+61 3 9727 6600 | www.selectronic.com.au | facebook.com/SelectronicAustralia
Product: SP PRO AU Series | Document No: BR0007_08 SP PRO Series II Data Sheet | Nov 2016