Overview
The Relay Output Module converts a switch closure from a wireless transmitter into a switch closure for your controller. It
is available from BAPI with either normally open or normally closed contacts. The outputs default to normally open in a
fault condition or when power is removed.
All analog output modules are easily trained to a single transmitted variable with a pushbutton and LED.
Product Identification
Floating Contacts
Fig. 1: Relay Output Module
Tools and Materials
#2 Philips Screwdriver, 1/8” Screwdriver (BA/116W), Drill, Wire
Mounting and Termination
Relay output modules are surface, 2.75” snaptrack or 35mm din rail
mountable.
For mounting
y BAPI representative or our website www.bapihvac.
com on the bottom of the wireless receiver page.
Relay Output Module
Specifications subject to change without notice.
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
1 OF 2
Relay Output Module
Installation and Operating Instructions
18918_ins_RYOM
rev. 04/21/15
Diagnostics
Possible Problems:
Possible Solutions:
Relay contacts do not switch
- Check power to the receiver and output module.
- Retrain the modules as described in the 418MHz receiver Installation &
Operation sheet (17613_ins_wireless_418_rcvr.pdf) or the 900MHz receiver
Installation & Operation sheet (17614_ins_wireless_900_rcvr.pdf)
LED Blinks Rapidly
- Data not getting through from transmitter assigned to this output module. Check
transmitter to see if its LED flashes about every 20 seconds. If not replace the
batteries.
Specifications
Supply Power:9 to 30 VDC or 17 to 31 VAC
Power consumption: 15 mA max (relay on)
Relay Output:
40V(DC or AC peak)
150 mA Maximum
On state resistance 15Ω Maximum
Off state leakage current 1uA Maximum
Inputs: RS485
RS485 Cable Distance: 4,000 ft with shielded, twisted pair cable (Belden 9841, Belden 8132 or equivalent)
Environmental Operation Range:
Temp: 0° to 60°C
Humidity: 5% to 95% RH non-condensing
Material: ABS Plastic
Material Rating: UL94, V-0
Operation:
BA/RYOM
5 second momentary action from sensor override button
Used only with a BAPI Wireless Room Transmitter
BA/RYOL
Latching action following the digital input
Used only with a BAPI Wireless Digital Input Transmitter
Specifications subject to change without notice.
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:sales@bapihvac.com • Web:www.bapihvac.com
2 OF 2
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising